100% found this document useful (1 vote)
323 views

CPP Control Room False Floor Details

The document provides details for a false flooring panel system made of medium density fiber board. The main components include: 1) A 100mm x 100mm x 2mm thick aluminum jackhead in the center to lift the panels, connected to a 15mm diameter steel pipe stud. 2) A cross-shaped steel frame underneath made of 18.5mm x 18.5mm x 2mm channels to provide structure and support. 3) 15mm thick medium density fiber board panels that sit within the frame and lift in and out using the central jackhead. Additional channels are included for extra support.

Uploaded by

saha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
323 views

CPP Control Room False Floor Details

The document provides details for a false flooring panel system made of medium density fiber board. The main components include: 1) A 100mm x 100mm x 2mm thick aluminum jackhead in the center to lift the panels, connected to a 15mm diameter steel pipe stud. 2) A cross-shaped steel frame underneath made of 18.5mm x 18.5mm x 2mm channels to provide structure and support. 3) 15mm thick medium density fiber board panels that sit within the frame and lift in and out using the central jackhead. Additional channels are included for extra support.

Uploaded by

saha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

15 MM TH.

MEDIUM DENSITY FIBER BOARD


(EXTERIOR GRADES PER IS:12406) PANEL FACED ON TOP WITH
ANTISTATIC P.V.C TILES AND M.S. TRAYAT BOTTOM 100
MAIN CHANNEL 16 I.D. 2MM THK.
18.5X18.5X2MM TH.

100
MS PIPE STUD
6 DIA HOLES FOR
CROSS CHANNEL
DASH FASTENERS
PRESSURE DIE CAST ALIMINIUM 18.5X18.5X2MM TH.
ALLOY JACKHEAD 2.5MM TH. 100MM DIA
CHANNEL SHAPED
PROJECTION IN JACKHEAD
STIFFENING FOLDS
PART VIEW OF PANEL
M.S. CHECK NUTS
ADDITIONAL CHANNEL
16DIA FULLY THREADED BRIGHT
ROD WELDED TO JACKHEAD
SECTION PLAN AT A-A
15 LD. 2MM TH. M.S. PIPE STUD
100X100X3MM TH. M.S. BASE PLATE
A A FIXED TO CEMENT CONCRETE FLOOR BY
6DIA 40MM LONG DASH FASTENERS
CONTROL
PANEL

25MM THK. CEM. CONC. FLOORING TREATED WITH INTEGRAL

FALSE FLOORING
WATER PROOFING COMPOUND AND PAINTED
ON TOP WITH POLYURETHANE FLOOR COATING
610 610

600
610
610
CONCRETE FLOORING ADDITIONAL PEDESTAL FOR
BASE CONC. FLOOR
SUPPORTING CONTROL PANEL

SECTION AT XX

PART GRID PLAN


600
MDF BOARD FALSE FLOOR PANEL CONTROL
PANEL
ADDITIONAL CHANNEL FIXED TO
MAIN CHANNEL AS PER DET (Z)

600
ANGLE CLEATS 6DIA M.S. COUNTER SUNK
SCREWS 8 NOS FOR FIXING
M.D.F. BOARD TO M.S. BOTTOM SHEET

DETAILS 'Y'

PLAN OF FLOOR PANEL

12MM TH. PARTICLE


BOARD PANEL

ADDITIONAL CHANNEL
2MM TH. PVC SHEET
PVC EDGING 75
C

MAIN CHANNEL O/o THE TECHNICAL SECTION, NRL,


5X6.2X2 MM TH.
GOLAGHAT, ASSAM
50

CHANNEL SHAPED PROJECTION TOP CHECKED BY :- CHECKED BY :- APPROVED BY :-


CROSS CHANNEL
50 B
1.2MM TH. M.S. B
100

PROJECT :-
BOTTOM SHEET
CPP CONTROL ROOM EXTENSION
M.S. CHANNEL SHAPED AT NRL,GOLAGHAT
5MM DIA 5MM HIGH PINS
SECTION 50X42X75X2MM TH. JOB :- STRUCTURAL DRAWING.
C

TITLE :- FALSE FLOORING DETAILS


DETAILS AT JUNCTION WITH WALL
STIFFENER BELOW 20X20X2 MM THK MS ANGLE CLEATS
DRAFTED BY: DESIGNED BY:
DRG. NO. :- 200-01-D001
FOR FIXING ADDITIONAL CHANNEL SHEET
NO.- D.BORO S.A.BARBHUIYA

TO MAIN GRID CHANNEL CAD. NO. :- 200-01-D001 9 DATED- 27-08-2018 P - A3 REV.-00


PLAN OF JACKHEAD M/S. MJ CONSULTANCY
G:\CONSULTANCY WORK\Logo1.jpg
D:\CONSULTANCY Office Address: Zoo road, Maniknagar,Guwahati-05,Assam
Email ID: [email protected]
DETAILS 'Z' Ph. M: 9435993044