Function Manual Basic Positioner en-US
Function Manual Basic Positioner en-US
Introduction 1
___________________
Basic positioner 2
___________________
Appendix A
SINAMICS
SINAMICS G120
Function Manual Basic Positioner
Function Manual
06/2013, FW V4.6
A5E31759509B AB
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
1 Introduction ................................................................................................................................................ 7
2 Basic positioner ......................................................................................................................................... 9
2.1 Basic positioner and position control .............................................................................................9
2.2 Permissible encoder combinations in the "Vector" control mode ................................................10
2.3 Permissible encoders in the "Servo" control mode ......................................................................12
2.4 PROFIdrive interfaces..................................................................................................................13
2.4.1 Control and status word 1 ............................................................................................................15
2.4.2 Control and status word 2 ............................................................................................................17
2.4.3 Control and status word for the positioner ...................................................................................18
2.4.4 Control and status word 1 for the positioner ................................................................................20
2.4.5 Control and status word 2 for the positioner ................................................................................22
2.4.6 Control word block selection ........................................................................................................24
2.4.7 Control word MDI mode ...............................................................................................................25
2.4.8 Status word messages.................................................................................................................26
2.4.9 Function block FB283 ..................................................................................................................27
2.5 Commissioning.............................................................................................................................28
2.5.1 Commissioning sequence ............................................................................................................28
2.5.2 Normalizing the encoder signal....................................................................................................29
2.5.2.1 Define the resolution ....................................................................................................................29
2.5.2.2 Modulo range setting ...................................................................................................................31
2.5.2.3 Checking the actual position value ..............................................................................................33
2.5.2.4 Setting the backlash .....................................................................................................................34
2.5.3 Limiting the positioning range ......................................................................................................36
2.5.4 Setting the position controller.......................................................................................................38
2.5.4.1 Precontrol and gain ......................................................................................................................38
2.5.4.2 Optimizing the position controller .................................................................................................39
2.5.4.3 Limiting the traversing profile .......................................................................................................42
2.5.5 Setting the monitoring functions...................................................................................................44
2.5.5.1 Standstill and positioning monitoring ...........................................................................................44
2.5.5.2 Following error monitoring ...........................................................................................................46
2.5.5.3 Cam sequencer ............................................................................................................................48
2.5.6 Referencing ..................................................................................................................................49
2.5.6.1 Referencing methods ...................................................................................................................49
2.5.6.2 Setting the reference point approach ...........................................................................................51
2.5.6.3 Setting the flying referencing .......................................................................................................57
2.5.6.4 Set reference point .......................................................................................................................62
2.5.6.5 Absolute encoder adjustment ......................................................................................................64
2.5.7 Jogging.........................................................................................................................................66
2.5.7.1 Jog velocity ..................................................................................................................................66
2.5.7.2 Incremental jogging ......................................................................................................................67
2.5.7.3 Setting jogging .............................................................................................................................67
2.5.8 Traversing blocks .........................................................................................................................69
2.5.8.1 Travel to fixed stop .......................................................................................................................76
2.5.8.2 Examples..................................................................................................................................... 80
2.5.9 Direct setpoint input (MDI) .......................................................................................................... 82
A Appendix.................................................................................................................................................. 87
A.1 Additional information on the converter ...................................................................................... 87
A.1.1 Manuals for your converter ......................................................................................................... 87
A.1.2 Configuring support ..................................................................................................................... 88
A.1.3 Product Support .......................................................................................................................... 88
Index ........................................................................................................................................................ 89
Overview
Position control means controlling the position of an axis. An "axis" is a machine or system
component that comprises the inverter with active position control and the driven mechanical
system.
The basic positioner (EPos) calculates the traversing profile for the time-optimized traversing
of the axis to the target position.
Overview
In the "Vector" control mode you are allowed to use two encoders per inverter. The encoder
for the speed controller must be mounted on the motor shaft.
HTL or SSI Resolver HTL Connection via Sensor Module SMC or SME DRIVE-
TTL encoder encoder HTL or SSI Resolver Endat sin/cos CLiQ
encoder TTL encoder 2.1 encoder encoder
encoder
Encoderless ② ② ② ② ② ② ② ② ② ②
HTL or TTL ① --- --- ③ ③ ③ ③ ③ ③ ③
encoder
Resolver --- --- ① --- --- --- --- --- --- ---
② The position controller evaluates an encoder on the motor shaft or on the load side.
The speed controller operates without an encoder.
Advantages:
• You can use an encoder that is
already present on the load
side, e.g. an SSI encoder, for
position control.
• Favorably-priced solution
Disadvantages:
• Restrictions regarding the
accuracy and dynamic
performance of the position
control
• Not suitable for the position
control of hoisting gear
• The "Travel to fixed stop" EPos
function is not possible.
Example
HTL or SSI Resolver HTL Connection via Sensor Module SMC or SME DRIVE-
TTL encoder encoder HTL or SSI Resolver Endat 2.1 sin/cos CLiQ
encoder TTL encoder encoder encoder
encoder
Figure 2-2 Position controllers and speed controllers evaluate the same encoder
Abbreviation Significance
STW1 Control word 1
ZSW1 Status word 1 see Control and status word 1 (Page 15)
STW2 Control word 2
ZSW2 Status word 2 see Control and status word 2 (Page 17)
SATZANW Selection of traversing block see Control word block selection (Page 24)
AKTSATZ Currently selected traversing block
MDI_TARPOS Position setpoint for direct setpoint input (MDI)
XIST_A Actual position value (32 bits)
OVERRIDE Speed setpoint
MELDW Status word for messages see Status word messages (Page 26)
NIST_B Actual speed value (32 bits)
frei Freely interconnectable
MDI_VELOCITY MDI velocity
MDI_ACC MDI acceleration
MDI_DEC MDI deceleration
MDI_MOD Selection of positioning mode with direct setpoint input (MDI) see Control word MDI mode (Page 25)
POS_STW Control word for basic positioner
POS_ZSW Status word for basic positioner see Control and status word for the positioner (Page 18)
POS_STW1 Control word 1 for basic positioner
POS_ZSW1 Status word 1 for basic positioner see Control and status word 1 for the positioner (Page 20)
POS_STW2 Control word 2 for basic positioner
POS_ZSW2 Status word 2 for basic positioner see Control and status word 2 for the positioner (Page 22)
WARN_CODE Number of the actual alarm
FAULT_CODE Number of the actual fault
4 0 = Reject traversing job Axis brakes down to standstill with the maximum p2641 =
deceleration. Converter rejects the actual traversing block. r2090.4
1 = Do not reject traversing task Axis can be started or travel to position setpoint.
5 0 = Intermediate stop Axis brakes down to standstill with the specified deceleration p2640 =
override. Converter remains in the actual traversing block. r2090.5
1 = No intermediate stop Axis can be started or continue to travel to position setpoint.
6 0 → 1: Activate traversing job The converter starts axis travel to the setpoint position. p2631 =
r2090.6
0 → 1: Setpoint transfer MDI p2650 =
r2090.6
7 0 → 1: = Acknowledge faults Acknowledge fault in the converter. If the ON command is p2103[0] =
still active, the converter switches to "closing lockout" state. r2090.7
8 1 = jogging bit 0 Jogging 1 p2589 =
r2090.7
9 1 = jogging bit 1 Jogging 2 p2590 =
r2090.7
10 0 = No control via PLC Converter ignores the process data from the fieldbus. p0854[0] =
1 = Control via PLC Control via fieldbus, converter accepts the process data from r2090.10
the fieldbus.
11 0 = Stop referencing --- p2595 =
1 = Start referencing The converter does not start referencing. r2090.11
12 Reserved
13 0 → 1: External block change The axis goes to the next traversing block. p2633 =
r2090.13
14, 15 Reserved
6 1 = Software limit switch, minus actuated The load is outside the permitted traversing range. p2084[6] =
r2683.6
7 1 = Software limit switch, plus actuated p2084[7] =
r2683.7
8 1 = Position actual value ≤ cam switching Feedback of the software cams in the converter. p2084[8] =
position 1 r2683.8
0 = Cam switching position 1 passed
9 1 = Position actual value ≤ cam switching p2084[9] =
position 2 r2683.9
0 = Cam switching position 2 passed
10 1 = Direct output 1 active The converter sets these signals in the actual traversing p2084[10] =
block. r2683.10
11 1 = Direct output 2 active See also Section: Traversing blocks (Page 69) p2084[11] =
r2683.11
12 1 = Fixed stop reached The axis is at the fixed stop p2084[12] =
r2683.12
13 1 = Fixed stop clamping torque reached The axis is at the fixed stop and has reached the p2084[13] =
clamping torque. r2683.13
14 1 = Travel to fixed stop active The converter moves the axis to a fixed stop. p2084[14] =
r2683.14
15 Reserved --- ---
6 1 = Software limit switch, minus actuated The axis is outside the permitted traversing range. p2084[6] =
r2683.6
7 1 = Software limit switch, plus actuated p2084[7] =
r2683.7
8 1 = Position actual value ≤ cam switching Feedback of the cam sequencer in the converter. p2084[8] =
position 1 r2683.8
0 = Cam switching position 1 passed
9 1 = Position actual value ≤ cam switching p2084[9] =
position 2 r2683.9
0 = Cam switching position 2 passed
10 1 = Direct output 1 active The converter sets these signals in the actual traversing p2084[10] =
block. r2683.10
11 1 = Direct output 2 active See also paragraph: Traversing blocks (Page 69) p2084[11] =
r2683.11
12 1 = Fixed stop reached The axis is at the fixed stop p2084[12] =
r2683.12
13 1 = Fixed stop clamping torque reached The axis is at the fixed stop and has reached the p2084[13] =
clamping torque. r2683.13
14 1 = Travel to fixed stop active The converter moves the axis to a fixed stop. p2084[14] =
r2683.14
15 1 = Traversing command active Feedback signal indicating as to whether the converter p2084[15] =
0 = Axis stationary is currently moving the axis. r2684.15
Block selection
4…14 Reserved
15 0 = Deactivate MDI Switching from traversing blocks to direct setpoint p2647 = r2091.15
1 = Activate MDI input.
MDI mode
Table 2- 17 Selection of the MDI mode and interconnection with parameters in the converter
Table 2- 18 Status word for messages and interconnection with parameters in the converter
Overview
The function block FB283 is an interface block that connects an inverter with basic positioner
to a SIMATIC S7 controller via PROFIBUS/PROFINET.
The block FB283 transfers all of the required process data to and from the drive. It is suitable
for both controlling the basic positioner and for a pure speed-controlled drive.
The FB283 additionally provides the following functions:
● Reading and writing parameters in the inverter.
● Reading out the fault buffer of the inverter.
● Transferring up to 16 traversing blocks when a function is initiated.
● Reading or writing a maximum of any 10 parameters with one job, e.g. for product
adaptation.
A configuration example and a description of the FB283 can be found on the Internet: FB283
(http://support.automation.siemens.com/WW/view/en/25166781).
2.5 Commissioning
Distance unit (LU): the resolution of the position actual value in the converter
The converter calculates the position actual value of the axis using the neutral position unit
LU (Length Unit). The distance unit LU is independent of whether the converter controls e.g.
the position of an elevating platform or the angle of rotary table.
Firstly, for your application define the required resolution. In other words: Which distance or
angle corresponds to the length unit (LU)?
The following rules apply when selecting the distance unit LU:
1. The higher the resolution of the distance unit LU, the higher the accuracy of the position
control.
2. If you select a resolution that is too high, then the converter cannot represent the position
actual value over the complete axis traversing range. The converter responds with a fault
in the case of an overflow when representing the number.
3. The resolution of the distance unit LU should be less than the maximum resolution that is
obtained from the resolution of the distance-encoder.
Preconditions
● You are online with the STARTER .
● You have selected the "Mechanical system" screen.
● You have defined the required resolution for your particular application (e.g. 1 LU ≙ 1 µm
or 1 LU ≙ 1/1,000° (1 millidegree).
Procedure
To normalize the encoder signal, proceed as follows:
1. Enable the settings so they can be edited.
2. Enter the gear ratio of the axis. Load revolutions.
3. Motor revolutions
Unknown gear ratio
If you do not know the gear ratio, then you must measure the ratio, for example by
manually rotating the motor and counting the load revolutions.
Example: After 5 motor revolutions, the load has turned through 37 °. The ratio is
therefore 37 ° / (5 × 360 °). You must then enter the following values into STARTER:
– ② 37 [load revolution]
– ③ 1800 [motor revolution]
Parameter Meaning
p2502 Encoder assignment
0 No encoder
1 Encoder 1
2 Encoder 2
p2503 Length unit LU per 10 mm
p2504 Motor/load motor revolutions
p2505 Motor/load load revolutions
p2506 Length unit LU per load revolution
Description
Linear axis
A linear axis is an axis whose traversing range is limited in both motor directions of rotation
by the mechanical system of the machine, e.g.:
• Stacker crane
• Elevating platform
• Tilting station
• Gate/door drive
Modulo axis
A modulo axis is an axis with an infinite traversing range, e.g.:
• Rotary table
• Conveyor belt
• Roller conveyor
Preconditions
● You are online with the STARTER .
● You have selected the "Mechanical system" screen.
Procedure
To set the modulo range, proceed as follows:
1. Enable the modulo correction.
2. Define the modulo range.
Example 1: In the case of a rotary table, one load revolution corresponds to 3600 LU. In
this case, the modulo correction is also 3600.
Example 2: For a roller conveyor, 100 motor revolutions corresponds to one production
cycle. For a resolution of 3600 LU per motor revolution, the modulo range is 360000 LU.
Parameter Meaning
p2576 Modulo offset, modulo range
p2577 Modulo correction activation (signal = 1)
r2685 Offset value
Preconditions
● You are online with the STARTER .
● You have selected the screen for "Actual value processing".
Procedure
To ensure that the converter calculates the actual position value correctly, you must check
the following:
● There must be no overflow of the actual position value in the entire traverse range. The
converter can show as a maximum the value range of -2147483648 … 2147483647. If
this maximum value is exceeded, the converter reports fault F07493.
● If you have defined a modulo range, the converter resets the actual position value after
passing through the range.
You have now checked the calculation for the actual position value.
Parameter Meaning
r2521[0] Position actual value for position control
Description
Backlash (also called play, dead travel on reversing etc.) is the distance or the angle that a
motor must travel through when the direction of rotation reverses until the axis actually
moves in the other direction.
With the appropriate setting, the converter corrects the positioning error caused by the
backlash when reversing.
The converter corrects the backlash under the following condition:
● For an incremental encoder, the axis must be referenced.
See also section: Referencing (Page 49).
● For an absolute encoder, the axis must be adjusted.
See also section: Absolute encoder adjustment (Page 64).
Measuring backlash
Procedure
To measure the backlash, proceed as follows:
1. Move the axis to position A in the machine. Mark this position in the machine and note
down the actual position value in the converter, see also Section: Checking the actual
position value (Page 33).
2. Move the axis a little bit more in the same direction.
3. Move the axis in the opposite direction until the actual position value in the converter
shows the same value as at position A. Due to the backlash when reversing, the axis is
now at position B.
Correcting backlash
Requirements
You have selected the "Mechanical system" screen.
Procedure
To correct the measured backlash, set the following:
● If the axis has not traveled far enough, then set a positive backlash.
● If the axis has traveled too far, then set a negative backlash.
Parameter Meaning
p2583 Backlash compensation
r2685 Offset value
Description
In addition, using its digital inputs, the converter evaluates signals from stop cams. When
passing a STOP cam, the converter responds – depending on the setting – either with a fault
or an alarm.
Fault as response
When passing the STOP cam, the inverter brakes the axis with the OFF3 ramp-down time,
switches the motor off, and reports the fault F07491 or. F07492. To switch the motor on
again, you must do the following:
● Switch the motor off (OFF1).
● Acknowledge the fault.
● Move the axis away from the STOP cam, e.g. using the jogging function.
Alarm as response
When passing the STOP cam, the converter brakes the axis with the maximum deceleration
(see Section: Limiting the traversing profile (Page 42)), maintains the axis in closed-loop
control and outputs alarm A07491 or A07492. In order to bring the axis back into the valid
traversing range, you must move the axis from the STOP cam, e.g. using the jogging
function.
Precondition
You have selected the "Limit" screen.
Procedure
To set the limits of the positioning range, proceed as follows:
1. Enable the software limit switch.
2. Move the axis to the positive limit position in your machine. Set the position of the
software limit switches to the actual position value.
3. Move the axis to the negative limit position in your machine. Set the position of the
software limit switches to the actual position value.
4. Enable the STOP cams.
5. Interconnect the signal of the STOP cam minus with the corresponding signal of your
machine.
Signal = 0 means an active STOP cam.
6. Interconnect the signal of the STOP cam plus with the corresponding signal of your
machine.
Parameter Meaning
p2568 STOP cam activation
p2569 STOP cam, minus
p2570 STOP cam, plus
p2578 Software limit switch, minus signal source
p2579 Software limit switch, plus signal source
p2580 Software limit switch, minus
p2581 Software limit switch, plus
p2582 Software limit switch activation
r2683.6 Software limit switch, minus actuated
r2683.7 Software limit switch, plus actuated
r2684.13 STOP cam minus active
r2684.14 STOP cam plus active
Description
If the speed control of the converter has an encoder to feedback the actual speed, then
deactivate the integral component TN of the position controller.
If you use the position control together with the encoderless vector control (SLVC,
SensorLess Vector Control), the positioning accuracy may be inadequate. With active
integral time, positioning accuracy improves.
Procedure
To optimize the position controller, proceed as follows:
1. In the control panel, select the operating mode "Basic positioner".
2. Click the "Jog" button.
3. Enter a speed setpoint.
6. Following controller optimization, set the precontrol of the position controller to 100%.
Parameter Meaning
p2534 Speed precontrol factor
p2538 Proportional gain / Kp
p2539 Integral time / Tn
p2731 Signal = 0: activate position controller
Advanced settings
If you permanently activate the integral time of the position controller, the characteristics of
the position control change as follows:
● The following error while positioning goes to zero.
● When positioning the axis, it tends to overshoot; this means that the axis briefly moves
beyond the target position.
Description
The converter calculates the traversing profile when positioning from specified values for
velocity, acceleration and jerk (= acceleration change with respect to time).
If the axis must traverse more slowly or must accelerate at a lower rate or "softly", then you
must set the relevant limits to lower values. The lower that one of the limits is, the longer the
converter needs to position the axis.
Precondition
You have selected the "Limit" screen and the "Traversing profile limitation" tab.
Procedure
To set the limitation of the traversing profile, proceed as follows:
1. Set the maximum velocity with which the converter may position the axis.
2. Set the maximum acceleration.
3. Set the maximum delay.
The "override" in the traversing blocks or for the direct setpoint input refers to the values
② and ③.
4. Reduce the maximum jerk, if you require softer acceleration and braking.
5. For permanent jerk limiting, set this signal to 1.
Parameter Meaning
p2571 Maximum velocity
p2572 Maximum acceleration
p2573 Maximum deceleration
p2574 Jerk limiting
p2575 Activating jerk limiting
1 signal: Jerk limiting is active
Description
As soon as the setpoint for the position within a positioning operation no longer changes,
then the converter sets the "Setpoint stationary" signal to 1. With this signal, the converter
starts to monitor the position actual value:
● As soon as the axis has reached the positioning window, the converter signals that the
target has been reached, and maintains the axis in closed-loop control.
● If the axis does not come to a standstill within the standstill monitoring time, the converter
reports fault F07450.
● If the axis does not enter the positioning window within the positioning monitoring time,
the converter reports fault F07451.
Precondition
You have selected the "Monitoring" screen and the "Position monitoring" tab.
Procedure
To set the standstill and positioning monitoring, proceed as follows:
1. Set the required positioning accuracy.
2. Set the time within which the axis must be positioned.
Parameter Meaning
p2542 Standstill window (target position ±p2542)
p2543 Standstill monitoring time
p2544 Positioning window (target position ±p2544)
p2545 Positioning monitoring time
Description
The following error is the deviation between the position setpoint and the position actual
value while the converter is positioning the axis.
The converter reports fault F07452 if the following error is too high. If you set the tolerance
to 0, monitoring is deactivated.
Precondition
You have selected the "Monitoring" screen and the "Following error monitoring" tab.
Procedure
To set the monitoring of the following error, proceed as follows:
1. Set the monitoring window.
Start with the factory setting value.
Test your setting by positioning the axis at maximum velocity, e.g. from the control panel.
If the converter stops the travel with fault F07452 , you will need to either increase the
monitoring window or increase the dynamics of the position controller.
2. If you want to evaluate the message in your higher-level control, interconnect this signal
with, for example, a status bit in the fieldbus telegram.
Parameter Meaning
p2546 Dynamic following error monitoring tolerance
r2563 Following error, dynamic model
Description
The converter compares the position actual value with two different positions and therefore
simulates two independent cam switching signals.
If you need this function, set the cam switching position to match your particular application
and appropriately interconnect the cam switching signal.
Parameter Meaning
p2547 Cam switching position 1
p2548 Cam switching position 2
r2683.8 Position actual value <= cam switching position 1
r2683.9 Position actual value <= cam switching position 2
2.5.6 Referencing
Overview
If you are using an incremental encoder for the position actual value, after the supply voltage
is switched off, the converter loses its valid position actual value. After the supply voltage is
switched on again, the converter no longer knows the reference of the axis position to the
machine.
Referencing re-establishes the reference between the zero point of the position calculated in
the converter and the machine zero point.
Absolute encoders retain their position information, even after the supply has been switched
off.
The converter offers various ways of referencing the axis:
● Reference point approach - only with incremental encoders
● Flying referencing - with all encoder types
● Set reference point - with all encoder types
● Absolute encoder adjustment - with absolute encoders
Flying referencing
The converter corrects its position actual value while traversing and reduces errors, e.g.
caused by wheel slip or a gear ratio that has not been precisely set.
Example: A pallet on a roller conveyor must be stopped at a specific position. However, the
exact position of the pallet on the conveyor is only known when a sensor is passed.
Description
A reference point approach generally consists of the following three steps:
1. Travel to reference cam.
When it receives a signal, the axis searches in a specified direction for the reference
cam.
2. Travel to zero mark.
After reaching the reference cam, the axis changes the traversing direction and evaluates
the zero mark of the encoder.
3. Travel to reference point.
After the zero mark is reached, the axis traverses to the reference point and synchronizes
the actual position value in the converter with the machine.
Under one of the following conditions, the converter skips the first step and starts with step 2:
● The axis is already at the reference cam.
● There is no reference cam available.
• Reference cam available: When the converter reaches the reference cam, the
axis accelerates in the opposite direction to the start
direction , to the "approach velocity zero mark".
• No reference cam is available: The converter accelerates the axis in the start
direction to the "approach velocity zero mark".
Figure 2-14 Travel to the zero mark if a reference cam is not available
After the load has reached the reference point coordinate, the converter sets its position
setpoint and actual value to this value.
Preconditions
1. You have selected the "Homing" screen.
2. You have come to the settings via the button on the screen.
3. You have selected "Active homing".
Procedure
To set the reference point approach, proceed as follows:
1. You specify the referencing mode:
– Only using the encoder zero mark
– With external zero mark
– With reference cam and encoder zero mark
2. Specify the start direction.
3. Set the approach velocity to the reference cam.
4. Set the approach velocity to the reference point.
5. Set the approach velocity to the zero mark.
Procedure
To define the digital signals for controlling, proceed as follows:
1. This signal starts the reference point approach.
2. This signal must be 0 for the reference point approach.
3. Interconnect the signal of the reference cam with the corresponding signal of your
machine.
4. If you use the reversing cam minus, interconnect the reversing cam with the
corresponding signal, e.g. with the fieldbus.
0 = Reversing cams active.
5. If you use the reversing cam plus, interconnect the reversing cam with the corresponding
signal, e.g. with the fieldbus.
0 = Reversing cams active.
Procedure
To define the analog signals for controlling, proceed as follows:
1. Define the signal source for the velocity override.
See also section: Direct setpoint input (MDI) (Page 82).
2. Change the source for the reference point coordinate, if necessary.
Parameter Meaning
p2595 Start referencing
p2598 Reference point coordinate, signal source
p2599 Reference point coordinate value
p2600 Reference point approach, reference point offset
p2604 Reference point approach, start direction
p2605 Reference point approach, approach velocity, reference cam
p2606 Reference point approach reference cam, maximum distance
p2607 Reference point approach reference cam available
p2608 Reference point approach, approach velocity, zero mark
p2609 Reference point approach, max distance reference cam and zero mark
p2610 Reference point approach, tolerance band for the distance to the zero mark
p2611 Reference point approach, approach velocity, reference point
p2612 Reference point approach, reference cam
p2613 Reference point approach reversing cam, minus
p2614 Reference point approach reversing cam, plus
r2684.0 Reference point approach active
r2684.11 Reference point set
Description
During motion, the load passes a reference cam. The converter evaluates the reference cam
signal via a suitable fast digital input, and corrects its calculated position during travel. The
fast digital inputs of the converter used for flying referencing are also called probe inputs.
For flying referencing, the converter corrects the position setpoint and actual value
simultaneously.
If the position actual value correction means that the axis has already passed the point
where it should start braking, then the axis travels beyond the target and approaches the
target from the opposite direction.
The converter sets the "Reference point set" signal back to zero after its supply voltage is
switched off and switched on again. The converter only corrects its position actual value for a
1 signal from "Start referencing". In this way, you can define, for example, the direction of
travel when the converter is referencing.
Precondition
1. You have selected the "Homing" screen.
2. You have come to the settings via the button on the screen.
3. You have selected "Passive homing".
Procedure
To set the flying referencing, proceed as follows:
1. Set with which edge of the reference cam signal the converter references its position
actual value:
0: Rising edge
1: Falling edge
2. Interconnect the switchover of reference cams 1 and 2 with a signal of your choice.
3. Select the digital input with which reference cam 1 is interconnected.
4. Select the digital input with which reference cam 2 is interconnected.
Several reference points:
If you require several reference points for an axis, then you must do the following:
– Assign the corresponding digital input to the respective reference point.
– Change the reference point coordinate during operation, e.g. using the non-cyclic
communication of the fieldbus.
5. Set the inner window for referencing. You deactivate the inner window with the value 0.
6. Set the outer window for referencing. You deactivate the outer window with the value 0.
Referencing can be suppressed depending on the deviation of the actual position value:
Inner window: For excessively small deviations, the converter does not correct its position
actual value.
Outer window: The converter signals an excessive deviation, but does not correct its
position actual value.
– Not taking into account the correction in the traversing distance: The converter
corrects both the actual position as well as the setpoint. The relative travel distance
remains unchanged.
Example: 500 LU is the axis start position. The axis should travel relatively through
1000 LU. The converter corrects the reference point during travel by 2 LU, however,
moves to the old target position 1500 LU.
8. Set the reference point coordinate p2599 via the expert list in the STARTER.
9. Close the screen form.
Procedure
To define the digital signals for controlling, proceed as follows:
1. This signal starts flying referencing.
2. For flying referencing, this signal must be 1.
The other signals are of no significance for flying referencing.
Procedure
To define the analog signals for controlling, proceed as follows:
1. Define the signal source for the velocity override.
See also section: Direct setpoint input (MDI) (Page 82).
2. Change the source for the reference point coordinate, if necessary.
Parameter Meaning
p2595 Start referencing
p2598 Reference point coordinate, signal source
p2599 Reference point coordinate value
p2601 Flying referencing, inner window
p2602 Flying referencing, outer window
p2603 Flying referencing, relative positioning mode
p2612 Reference point approach, reference cam
r2684.11 Reference point set
p2660 Measured value referencing
Description
Position the load, e.g. using the "jog" function, at the reference position in the machine.
Precondition
You have selected the "Homing" screen.
Procedure
To activate 'set home position', proceed as follows:
1. Interconnect this bit with the corresponding signal of your machine.
If the axis is stationary, with the signal change 0 → 1, the inverter sets its actual position
value to the reference point coordinate.
For this function, all of the other signals are of no significance.
2. In STARTER, proceed in the expert list and set p2599 to the reference point coordinate.
Parameter Meaning
p2596 Set reference point
p2598 Reference point coordinate, signal source
p2599 Reference point coordinate value
r2684.11 Reference point set
Precondition
1. You have positioned the axis (e.g. using the "jog" function) to the reference position in the
machine.
2. You have selected the "Homing" screen.
3. You have come to the settings via the button on the screen.
4. You have selected "Absolute encoder adjustment".
Procedure
To adjust the absolute encoder, proceed as follows:
1. Specify the reference point coordinate.
2. Accept the reference point coordinate in the position actual value.
Parameter Meaning
p2598 Reference point coordinate, signal source
p2599 Reference point coordinate value
p2507 Absolute encoder adjustment status
0 Error has occurred in the adjustment
1 Absolute encoder was not adjusted
2 Absolute encoder was not adjusted and encoder adjustment was initiated
3 Absolute encoder adjusted
2.5.7 Jogging
Description
Only input a setpoint velocity for the converter for velocity jog. With the signal "Jogging 1" or
"Jogging 2", the converter accelerates the axis to the relevant setpoint velocity. The
converter stops the axis when the respective "Jog" signal returns to zero.
Description
In the case of incremental jogging, input a relative traversing distance and a velocity setpoint
into the converter. With the signals "Jogging 1" or "Jogging 2" the converter positions the
axis by the respective travel path.
Precondition
You have selected the "Jog" screen.
Procedure
To set the "jog" function, proceed as follows:
1. Interconnect the signal that defines the mode for the "jog" function.
0: Velocity jogging
1: Incremental jogging
2. Interconnect the signal for jogging 1.
3. Interconnect the signal for jogging 2.
4. Select the button for the other settings.
5. Set the velocities for the "jogging 1" function.
6. Set the velocities for the "jogging 2" function.
7. If you use the incremental jog, set the relative position setpoint for the "jogging 1"
function.
This value has no significance for velocity jogging.
8. If you use the incremental jog, set the relative position setpoint for the "jogging 2"
function.
This value has no significance for velocity jogging.
Parameter Meaning
p2585 Jogging 1 setpoint velocity
p2586 Jogging 2 setpoint velocity
p2587 Jogging 1 traversing distance
p2588 Jogging 2 traversing distance
p2589 Jogging 1 signal source
p2590 Jogging 2 signal source
p2591 Incremental jogging
Description
A traversing block describes a positioning instruction for the drive.
The converter saves 16 different traversing blocks, which it normally executes one after the
other. However, you can also directly select a specific traversing block or skip traversing
blocks.
Element Meaning
Number With this number in the range 0 to 15, every traversing block can be selected
using binary-coded control signals.
Job Positioning command: You can give the converter various commands. For some
Parameter jobs, you must also specify a parameter. See the table below.
Mode Positioning mode: Positioning relative to the start position or absolute to the
machine zero point.
Position Target position
Velocity v Setpoints for the traversing profile.
Acceleration a
Braking -a
Advance Jump condition to the next traversing block. See the table below.
Precondition
1. You have selected the "Traversing blocks" screen.
2. You select the "Program traversing blocks" button.
Procedure
To program the traversing blocks, proceed as follows:
1. Assign a unique number for each traversing block.
2. Define the command and the corresponding parameters.
3. Set the job-specific values.
4. Define the step enabling condition for the next job.
5. If you travel to a fixed stop, a button appears to make additional settings for this function.
See also section: Travel to fixed stop (Page 76).
6. Click this button to interconnect the status signals of the traversing blocks, for example,
with bit 10 and 11 of the positioner status word with the fieldbus.
7. When you have programmed all traversing blocks, close the screen.
Procedure
To define the digital signals for controlling the traversing blocks, proceed as follows:
1. Define the signal for the start of the traversing block.
The signal change 0 → 1 starts the currently selected traversing block.
2. In the factory setting, this signal is interconnected with the appropriate internal signals of
the converter. We recommend that you do not change this setting.
3. See ②.
4. See ②.
5. Define the signal for the settings for the intermediate stop.
The axis temporarily stops for the "intermediate stop" = 0 signal. The axis continues its
travel with "intermediate stop" = 1. The same traversing block as before the stop is active.
See also section: Examples (Page 80).
6. Define the signal for "reject signaling task".
For the signal "reject traversing task" = 0, the converter stops the axis with the maximum
deceleration (p2573). If you start the axis again with "Activate traversing request" = 0 → 1,
the converter starts again with the currently selected traversing block.
You have now defined the digital signals for controlling the traversing blocks.
Procedure
To define the analog signals for controlling the traversing blocks, proceed as follows:
1. Change the signal source for the velocity override, if required.
The velocity override refers to the velocity values you have set in the screen for
programming the traversing blocks.
You have now defined the analog signals for controlling the traversing blocks.
Precondition
You have selected the "External block change" button.
Procedure
To define an external signal for the block change, proceed as follows:
1. Specify whether the external signal is received via a fast digital input (probe) or from
another source, e.g. via the fieldbus.
2. To initiate a block change via the machine control system, you must interconnect this
signal with a signal of your choice.
3. Select the input with which cam signal 1 is interconnected.
4. Select the input with which cam signal 2 is interconnected.
5. Specify the edge with which the inverter jumps to the next traversing block:
0: Rising edge
1: Falling edge
You have now defined an external signal for the block change.
Parameter Meaning
p0488 Probe 1, input terminal
p0489 Probe 2, input terminal
p0581 Probe edge
0 Positive edge 0 → 1
1 Negative edge 1 → 0
p2615 Maximum number of traversing blocks
p2616[0…n] Traversing block, block number
p2617[0…n] Traversing block, position
p2618[0…n] Traversing block, velocity
p2619[0…n] Traversing block, acceleration override
p2620[0…n] Traversing block, deceleration override
p2621[0…n] Traversing block, job
1 POSITIONING 6 GOTO
2 FIXED STOP 7 SET_O
3 ENDLESS_POS 8 RESET_O
4 ENDLESS_NEG 9 JERK
5 WAIT
p2622[0…n] Traversing block, job parameter
Parameter Meaning
p2623[0…n] Traversing block, job mode
Value = 0000 cccc bbbb aaaa
cccc = 0000 Positioning Absolute
cccc = 0001 mode Relative
cccc = 0010 Absolute positive (only for rotary axis with modulo
correction)
cccc = 0011 Absolute negative (only for rotary axis with modulo
correction)
bbbb = 0000 Advance End
bbbb = 0001 condition Continue with stop
bbbb = 0010 Continue flying
bbbb = 0011 Continue external
bbbb = 0100 Continue external wait
bbbb = 0101 Continue external alarm
aaaa = 0001 Identifiers: Skip block
p2624 Sort traversing block
To sort the traversing blocks according to their block number: p2624 = 0 → 1.
p2625 Traversing block selection, bit 0
p2626 Traversing block selection, bit 1
p2627 Traversing block selection, bit 2
p2628 Traversing block selection, bit 3
p2631 Activate traversing block (0 → 1)
p2632 External block change evaluation
0 External block change via probe
1 External block change via BI: p2633
p2633 External block change (0 → 1)
p2640 Intermediate stop (0 signal)
p2641 Reject traversing job (0 signal)
p2646 Velocity override
Preconditions
The "Travel to fixed stop" function is only possible with the control type vector control with
encoder (VC):
"Travel to fixed stop" is not possible with the following types of control:
● V/f control
● Vector control without encoder (SLVC)
Description
With this function, the converter positions a machine part to another machine part with force
locking – and presses both machine parts together with an adjustable force.
Examples:
1. A door is pressed against a frame so that it is reliably closed.
2. A rotary table is pressed against a mechanical fixed stop, in order to secure a specific
alignment.
• If the start of braking point is located in front of the mechanical fixed stop, the converter
cancels the travel and outputs fault F07485.
• Before starting the travel, the converter calculates the traversing profile for accelerating
and braking the axis. The selected torque limit for the fixed stop has no influence on this
calculation. However, the torque limit for the fixed stop reduces the available drive torque
for the complete traversing distance. If the torque available for the predicted acceleration
is not sufficient, then the following error is higher.
If the following error monitoring for travel to fixed stop responds, then you must reduce
the acceleration override.
Figure 2-21 Converter detects the fixed stop using the following error
Precondition
1. You have programmed "Travel to fixed stop" as traversing block.
See also section: Traversing blocks (Page 69).
2. If you select the "Programming traversing blocks" button, the "Configuration of fixed stop"
button appears.
After the fixed stop is detected, the inverter monitors the actual position of the axis. If the
position actual value changes by more than this distance, then the converter stops the
axis and outputs fault F07484. Therefore, the converter detects that the fixed stop has
"broken away"
You have now set "Travel to fixed stop" using an external signal.
You have now set "Travel to fixed stop" using maximum following error.
Parameter Meaning
p2634 Fixed stop, maximum following error
p2635 Fixed stop, monitoring window
p2637 Fixed stop reached
0 Fixed stop has not been reached.
1 Fixed stop has been reached.
p2638 Fixed stop outside the monitoring window
p2639 Torque limit reached
0 Torque limit has not been reached.
1 Torque limit has been reached.
2.5.8.2 Examples
1. Example
2. Example
The converter only goes to the next traversing block for the 0 → 1 change of the "External
block selection" signal.
Description
For direct setpoint input (MDI, Manual Data Input), a higher-level control provides the
converter with the position setpoint and traversing profile.
Example 1
The higher-level control specifies the value of the setpoint either as a relative or an absolute
position setpoint:
Example 2
The higher-level control selects the mode "Set-up":
Precondition
You have selected the "Direct setpoint input (MDI)" screen.
Procedure
Interconnect the signals to control the direct setpoint input using the appropriate signals from
your machine control.
① Enables MDI. This bit must be = 1 if you control the converter using MDI.
② Specifies the MDI mode:
0: Positioning: Traverse the axis with position control using the target position.
1: Set up: Traverse the axis position-controlled using velocity input
While operational, the axis operating mode can be switched over from "Set up" to
"Positioning".
If "Set up" is active, then the two bits ⑥ and ⑦ define the direction of travel.
③ Intermediate stop:
0: The converter stops the axis and maintains the axis in position after standstill. The
actual traversing block still remains valid.
1: The axis continues the interrupted traversing block.
④ Reject traversing block:
0: The converter stops the axis and maintains the axis in position after standstill. The
converter can no longer continue the actual traversing block.
1: Axis waits for a new start command.
⑤ Positioning mode: These signals are only effective
0: Relative (see also bit ⑨). if, in the interface for analog
1: Absolute (the axis must be referenced). signals, the value ⑥ is not
⑥ Direction selection for "Set up" (Bit ② = 1): interconnected. See also the
table below.
⑦ Bit ⑥ = 1: Positive direction.
Bit ⑦ = 1: Negative direction.
If both bits are the same, the axis stops.
⑧ Accept setpoint:
0 → 1: Start axis
Is only active, if bit ⑨ = 0.
⑨ 1: Continuous mode:
The converter continually accepts changes to the position setpoint. In this mode, relative
positioning is not permitted (see bit ⑤).
0: The converter starts using bit ⑧.
You have now interconnected the digital signals for controlling the direct setpoint input.
Precondition
You have selected the "Direct setpoint input (MDI)" screen.
Procedure
Interconnect the signals to control the direct setpoint input using the appropriate signals from
your machine control:
Procedure
To set the fixed setpoints, proceed as follows:
1. Select the button for configuring the fixed setpoint:
Parameter Meaning
p2640 Intermediate stop (0 signal)
p2641 Reject traversing job (0 signal)
p2642 Direct setpoint input/MDI, position setpoint
p2643 Direct setpoint input/MDI, velocity setpoint
p2644 Direct setpoint input/MDI, acceleration override
p2645 Direct setpoint input/MDI, deceleration override
p2646 Velocity override
p2647 Direct setpoint input/MDI selection
p2648 Direct setpoint input/MDI, positioning type
0 Absolute positioning is selected
1 Relative positioning is selected
p2649 Direct setpoint input/MDI, acceptance method selection
0 Values are accepted when p2650 = 0 → 1
1 Continuous acceptance of values
p2650 Direct setpoint input/MDI, setpoint acceptance, signal edge
p2650 = 0 → 1 and p2649 = 0 signal
p2651 Direct setpoint input/MDI, positive direction selection
p2652 Direct setpoint input/MDI, negative direction selection
p2653 Direct setpoint input/MDI, set up selection
Signal = 1: Set up is selected.
p2654 Direct setpoint input/MDI, mode adaptation
p2690 Position fixed setpoint
Interconnect fixed setpoint: p2642 = 2690
p2691 Velocity fixed setpoint
Interconnect fixed setpoint: p2643 = 2691
p2692 Acceleration override fixed setpoint
Interconnect fixed setpoint: p2644 = 2692
p2693 Deceleration override fixed setpoint
Interconnect fixed setpoint: p2645 = 2693
J
D Jerk limiting, 42
DRIVE-CLiQ, 12 Jog velocity, 66
Dynamic response, 38 Jogging, 22, 39
Jogging (EPos), 9
E
L
Elevating platform, 29, 31
Encoder zero mark, 53 Limit switch (software), 36
Encoderless speed control, 12, 38 Limit switches, 36
Endat 2.1, 10 Linear axis, 31
EPos (basic positioner), 9 List Manual,
LU (Length Unit), 29
F
M
FB283, 27
Fixed stop, 9, 76 Machine zero point, 49
Fixed stop reached, 19 Manual Collection,
S
P Sensorless Vector Control (SLVC), 38
POS_STW (positioning control word), 18 Set reference point, 22
POS_STW1 (positioning control word 1), 20 Set up, 9, 20, 21, 83
POS_STW2 (positioning control word 2), 22 sin/cos encoder, 10
POS_ZSW (positioning status word), 19 SIZER, 88
POS_ZSW1 (positioning status word 1), 21 Software limit switch, 19, 22
POS_ZSW2 (positioning status word 2), 23 SSI encoder, 10
Position actual value, value range, 33 Stacker crane, 31
Position control, 9 Standstill monitoring, 44
Position controller, 38 Status word 1, 16
Position setpoint reached, 19, 45 Status word 2, 17
Positioning control word, 18 Status word messages, 26
Positioning control word 1, 20 STOP cam, 21, 22, 36
Positioning control word2, 22 STW1 (control word 1), 15
Positioning monitoring, 44 STW2 (control word 2), 17
Positioning status word, SUB-D connector, 12
Positioning status word 1, Support, 88
Positioning status word 2, Symbols, 7
Positioning window, 44
Precontrol, 38
Probe, 22, 57 T
Procedure, 7
Target position reached, 45
Proportional controller, 38
Terminal strip, 12
Proportional gain, 39
Tilting station, 31
Traversing block, 9, 21, 69
Traversing block selection, 20
Traversing profile, 42
V
Value range, position actual value, 33
Z
Zero mark, 51
ZSW1 (status word 1), 16
ZSW2 (status word 2), 17