03 Definition - Classification of Power System Stability IEEE-CIGRE Joint Task Force On Stability Terms and Definitions
03 Definition - Classification of Power System Stability IEEE-CIGRE Joint Task Force On Stability Terms and Definitions
yste,ms
315
316 Excitation Systems Chap. 8
Generator considerations
The basic requirement is that the excitation system supply and automatically
adjust the field current of the synchronous generator to maintain the terminal voltage
as the output varies within the continuous capability of the generator. This
requirement can be visualized from the generator V-curves, such as those shown in
Figure 5.19 of Chapter 5. Margins for temperature variations, component failures )
emergency overrating, etc., must be factored in when the steady-state power rating is
determined. Normally, the exciter rating varies from 2.0 to 3.5 kW/MV A generator
rating.
In addition, the excitation system must be able to respond to transient
disturbances with field forcing consistent with the generator instantaneous and shor],
term capabilities. The generator capabilities in this regard are limited by severa]
factors: rotor insulation failure due to high field voltage, rotor heating due to high
field current, stator heating due to high armature current loading, core end heating
during underexcited operation, and heating dueto excess flux (volts/Hz). The thermal limits
have time-dependent characteristics, and the short-term overload capability of the
generators may extend from 15 to 60 seconds. To ensure the best utilization of the
excitation system, it should be capable of meeting the system needs by taking full
advantage of the generator's short-term capabilities without exceeding their limits.
From the power system viewpoint, the excitation system should contribute to
effective control of voltage and enhancement of system stability. It should be capable
of responding rapidly to a disturbance so as to enhance transient stability, and of
modulating the generator field so as to enhance small-signal stability.
Historically, the role of the excitation system in enhancing power system
performance has been growing continually. Early excitation systems were controlled
manually to maintain the desired generator términal voltage and reactive power
loading. When the voltage control was first automated, it was very slow, basically
filling the role of an alert operator. In the early l 920s, the potential for enhancing
small-signal and transient stability through use of continuous and fast-acting regulators
was recognized. Greater interest in the design of excitation systems developed, and
exciters and voltage regulators with faster response were soon introduced to the
industry. Excitation systems have since undergone continuous evolution. In the early l
960s, the role of the excitation system was expanded by using auxiliary stabilizing
signals, in addition to the terminal voltage error signal, to control the fíeld voltage to
damp system oscillations. This part of excitation control is referred to as the power
system stabilizer. Modern excitation systems are capable of providing practically
instantaneous response with high ceiling voltages. The combination of high field-
forcing capability and the use of auxiliary stabilizing signals contributes to substantial
enhancement of the overall system dynamic performance. This will be discussed in
detail in Chapters 12, 13, and 17.
. sec. s.z Elements of an Excitation System 317
To fulfill the above roles satisfactorily, the excitation system must satisfy the
following requirements:
Figure 8.1 shows the functional block diagram of a typical excitation control
system for a large synchronous generator. The following is a brief description of the
various subsystems identified in the figure.
Limiters and
protective circuits -
®
Terminal voltage
transducer and
load compensator
-
~
@ CD
- To power
Ref.
-
Regulator - Exciter -....- Generator system
r ©
Power system
stabilizer -
Figure 8.1 Functional block diagram of a synchronous
generator excitation control system
318 Excitation Systems Chap. 8
(2) Regulator. Processes and amplifies input control signals to a level and fonn.
appropriate for control of the exciter. This includes both regulating and
excitation system stabilizing functions (rate feedback or lead-lag
compensation).
(3) Terminal voltage transducer and load compensator. Senses generator terminal
voltage, rectifies and filters it to de quantity, and compares it with a reference
which represents the desired terminal voltage. In addition, load (or line-drop,
or reactive) compensation may be provided, if it is desired to hold constant
voltage at sorne point electrically remote from the generator terminal (for
example, partway through the step-up transformer).
(4) Power system stabilizer. Provides an additional input signa! to the regulator to
damp power system oscillations. Sorne commonly used input signals are rotor
speed deviation, accelerating power, and frequency deviation.
( 5) Limiters and protective circuits. These include a wide array of control and
protective functions which ensure that the capability limits of the exciter and
synchronous generator are not exceeded. Sorne of the commonly used
functions are the field-current limiter, maximum excitation limiter, terminal
voltage limiter, volts-per-Hertz regulator and protection, and underexcitation
limiter. These are normally distinct circuits and their output signals may be
applied to the excitation system at various locations as a summing input or a
gated input. For convenience, they have been grouped and shown in Figure 8.1
as a single block.
Excitation systems have taken many forms over the years of their evolution.
They may be classified into the following three broad categories based on the
excitation power source used [4,8]:
• DC excitation systems
• AC excitation systems
• Static excitation systems
':
1
Exc. field
! 1 rheostat
L------ ---------1
Voltage
regulator
With stationary rectifiers, the de output is fed to the field winding of the main
generator through slip rings.
When non-controlled rectifiers are used, the regulator controls the field of the
ac exciter, which in turn controls the exciter output voltage. A simplified one-line
diagram of such a field controlled alternator rectifier excitation system is shown in
Figure 8.3. In the system shown, which is representative of the General Electric
ALTERREX1 excitation system [14], the alternator exciter is driven from the main
enerator rotor. The exciter is self-excited with its field power derived through
~yristor rectifiers. The voltage regulator derives its power from the exciter output
voltage.
An alternative form of field-controlled alternator rectifier system uses a pilot
exciter as the source of exciter field power.
When controlled rectifiers (thyristors) are used, the regulator directly controls
the de output voltage of the exciter. Figure 8.4 shows the schematic diagram of such
an alternator supplied controlled-rectifier system, representative of the General
Electric ALTHYREX 1 System [17]. The voltage regulator controls the firing of the
thyristors. The exciter altemator is self-excited and uses an independent static voltage
regulatorto maintain its output voltage. Since the thyristors directly control the exciter
output, this system inherently provides high initial response (small response time).
As shown in Figures 8.3 and 8.4, two independent modes of regulation are
provided: (1) ac regulator to automatically maintain the main generator stator terminal
voltage at a desired value corresponding to the ac reference; and (2) de regulator to
maintain constant generator field voltage as determined by the de reference. The de
regulator or manual control mode caters to situations where the ac regulator is faulty
or needs to be disabled. The input signals to the ac regulator include auxiliary inputs
which provide additional control and protective functions which will be described in
Section 8.5.
DC
C'-o-nt_ro_l_le_d , +<}-
.
f---
,,.....--' 1
1
DC
regulator
ref
1
rectifier 1
1
1
1
¡
AC
~
1
1
1
ref.
AC
regulator
----- Aux. inputs
1
ALTHYREX is a trademark of General Electric Co.
322 Excitation Systems Chap.a
e¡ '-,,-'
TPT
DC
DC ref.
regulator
J\C
Exc. ref.
reg. J\C
With rotating rectifiers, the need for slip rings and brushes is eliminated, and
the de output is directly fed to the main generator field. As shown in Figure 8.5, the
armature of the ac exciter and the diode rectifiers rotate with the main generator field.
A small ac pilot exciter, with a permanent magnet rotor (shown as NS in the figure),
rotates with the exciter armature and the diode rectifiers. The rectified output of the
pilot exciter stator energizes the stationary field of the ac exciter. The voltage
regulator controls the ac exciter field, which in turn controls the field of the main
generator.
Such a system is referred to as a brushless excitatign system. It was developed
to avoid problems with the use ofbrushes that were perceived to exist when supplying
the high field currents of very large generators; for example, the power supplied to
the field of a 600 MW generator is on the order of 1 MW. However, with well-
maintained brushes and slip rings, these perceived problems <lid not actually develop.
AC excitation systems with and without brushes have performed equally well.
High initial-response performance of brushless excitation can be achieved by
special design of the ac exciter and high voltage forcing of the exciter stationary field
winding. An example of such a system is the Westinghouse high initial response
brushless excitation system [13].
Brushless excitation systems do not allow direct measurement of generator
field current or voltage. Manual control of main generator voltage is provided by an
adjustable de input setting to the thyristor gating circuits. For the sake of simplicity, ,
the functions of the control circuitry are not shown in detail in Figure 8.5.
sec. 8.3 Types of Excitation Systems 323
~-_, -et
1
1
f---CX ¡
1
=
]1
Three- Field
phase ac
In this system, the excitation power is supplied through a transfonner from the
generator terminals or the station auxiliary bus, and is regulated by a controlled
rectifier (see Figure 8.6). This type of excitation system is also commonly known as a
bus-fed or transformer-fed static system.
This system has a very small inherent time constant. The maximum exciter
output voltage (ceiling voltage) is, however, dependent on the input ac voltage. Hence,
during system-fault conditions causing depressed generator terminal voltage, the
· available exciter ceiling voltage is reduced, This limitation of the excitation system
is, to a large extent, offset by its virtually instantaneous response and high post-fault
field-forcing capability [18, 19]. In addition, it is inexpensive and easily maintainable.
For generators connected to large power systems such excitation systems perform
· satisfactorily [18]. Compounding ancillaries, such as those described below, are not
normallyjustified; they are likely important for generators feeding power directly into
small industrial networks with slow fault-clearing. -
324 Excitation Systems Chap. 8
Three-
phase ac*
Field
DC DC ref.
regulator
* Altematively, from
auxiliary bus AC ref
AC
regulator Aux. inputs
The power to the excitation system in this case is formed by utilizing the
current as well as the voltage of the main generator. This may be achieved by means
of a power potential transformer (PPT) and a saturable-current transformer (SCT) as
illustrated in Figure 8.7. Altematively, the voltage and current sources may be
combined by utilizing a single excitation transformer, referred to as a saturable-current
potential transformer (SCPT). ·
The regulator controls the exciter output through controlled saturation of the
excitation transformer. When the generator is not supplying a load, the armature
current is zero and the potential source supplies the entire excitation power. Under
loaded conditions, part of the excitation power is derived from the generator current.
During a system-fault condition, with severely depressed generator terminal voltage,
the current input enables the exciter to provide high field-forcing capability.
Examples of this type of excitation system are General Electric SCT-PPT and
SCPT static excitation systems.
sec. s.s Types of Excitation Svsterns 325
Saturable Armature
current transformer
Linear reactor
Regulator
---- Aux. inputs
This system utilizes controlled rectifiers in the exciter output circuits and the
compounding of voltage and current-derived sources within the generator stator to
provide excitation power. The result is a high initial-response static excitation system
with full "fault-on" forcing capability.
An example of this type of system is the compound power-source
GENERREX1 excitation system [15,16]. Figure 8.8 shows an elementary single-line
diagram of the system. The voltage source is formed by a set of three-phase windings
placed in three slots in the generator stator and a series linear reactor. The current
source is obtained from current transformers mounted in the neutral end of the stator
windings. These sources are combined through transformer action and the resultant
ac output is rectified by stationary power semiconductors. The means of control is
provided by a combination of diodes and thyristors connected to form a shunt bridge.
A static ac voltage regulator controls the firing circuits of the thyristors and thus
regulates the excitation to the generator field.
The excitation transformer consists of three single-phase units with three
windings: current (C) and potential (P) primary windings, and a secondary output
winding (F). Under fault conditions, the fault current flowing through the excitation
transformer "C" windings provides the field-forcing capability when the generator
voltage is depressed.
i1
:"C''
'P"::
11
::
CTT TPT
1 11 '----.,-'
i
---------
"F" ----------
¡¡
1
Field
~------ !
Rectifier
with shunt
thyristor DC A_ux. inputs
control regulator
DC ref. AC ref.
Since the source of power to a static excitation system is the main generator,
it is in effect self-excited. The generator cannot produce any voltage until there ÍS'
sorne field current. It is therefore necessary to have another source of power for a few
seconds to initially provide the field current and energize the generator. This process
of build-up of generator field flux is called field flashing. The usual field-flashing
source is a station battery.
The advances in excitation control systems over the last 20 years have been
influenced by developments in solid-state electronics. Developments in analog-
integrated circuitry have made it possible to easily implement complex control
strategies.
sec. a.4 Dynamic Performance. Measures 327
The latest development in excitation systems has been the introduction of
digital technology. T?yristors. continue to be use? for the power. s~áge. The co~trol,
rotection, and logic functions have been implemented digitally, essentially
~uplicating the functions previously provided by analog circuitry.
The digital controls are likely to be used extensively in the future as they
rovide a cheaper and possibly more reliable alternative to analog circuitry. They have
~e added advantage of being more flexible, allowing easy implementation of more
cornplexcontrol strategies, and interfacing with other generator control and protective
[unctions.
Power Plant
.
Controller VR amplifier Efd
(generator and Et
~ (regulator)
- (exciter) power system)
ve
Feedback
elements
Figure 8.9 Excitation control system in the classical feedback control form
(a) Excitation system ceiling voltage: The maximum direct voltage that the excitation
system is able to supply from its terminals under specified conditions (7,20].
Ceiling voltage is indicative of the field-forcing capability of the excitation
system; higher ceiling voltages tend to improve transient stability.
For potential source and compound source static excitation systems, whose
supply depends on the generator voltage and current, the ceíling voltage is defined at
specified supply voltage and current. For excitation systems with rotating exciters, the
ceiling voltage is determined at rated speed.
(b) Excitation system ceiling current: The maximum direct current that the excitation
system is able to supply from its terminals for a specified time [7,20].
When prolonged disturbances are a concern, the ceiling current may be based
on the excitation system thermal duty.
(e) Excitation system voltage time response: The excitation system output voltage
expressed as a function of time under specified conditions [7,20].
(d) Excitation system voltage response time: The time in seconds for the excitation
voltage to attain 95% of the difference between the ceiling voltage and rated load-
field voltage under specified conditions [7,20].
The rated load field voltage is the generator field voltage under rated
continuous load conditions with the field winding at (i) 75ºC for windings designed
to operate at rating with a temperature rise of 60ºC or less; or (ii) 1 OOºC for windings
designed to operate at rating with a temperature rise greater than 60ºC.
(/) Excitation system nominal response 1: The rate of increase of the excitation
system output voltage determined from the excitation system voltage response curve,
divided by the rated field voltage. This rate, if maintained constant, would develop the
same voltage-time area as obtained from the actual curve over the first half-second
interval (unless a different time interval is specified) [7,20].
1 Historically, the excitation system nominal response has been referred to as the exatation
system response ratio (see 1978 version of [7], and [20]).
sec- 8.4 Dynamic Performance Measures 329
...... r
...... 1 Actual response
_,~' 1
...... 1
..,. ... .,,. 1
-~----------------------------~d
,,.,. ...... -- 1
a Rated load field voltage
1
'1
1
1
1
1
1
1
1
1
r
1
1
1
1
1
1
Time in seconds
Ü'-------------------------------------
e
not adequate to cover many of the modem excitation systems. In particular, it is not
a good figure of merit for excitation systems supplied from the generator or the power
system, due to the reduced capability of such systems during a system fault.
For high initial-response excitation systems, the nominal response merely
establishes the required ceiling voltage. The ceiling voltage and voltage response time
are more meaningful parameters for such systems.
- ~l~ ~ -~ ~- - - - - - - - - -
Specified band
for settling time
Peak
val u e
0.1
Initial value
Delay time Time
Time to reach
peak value
Sett 1.in time
Figure 8.11 Typical time response to step input. ©IEEE 1990 [7]
sec. 8.4 Dynamic Performance Measures 331
40 Asymptotic o
approximation -40 dB/dec
r/'J
(1)
(1)
of gain 6h
(1)
20 -50 "O
~ ·-
t::
,-..,
-e-
....
i::::
o 1 -100 '-'
o
i::::
·~
1
1 <Pe ~
--- -- -G-m---~----------
o
-20
~
:
1
1 <Pm
-150
~
ª
!l.)
..d
e : 180º ~
Excitation Synchronous
--- - -----------
-40 system machine -200
VR
+ VE Vr
G2
-60 -250
M
o -------------~Al 50
V)
Bandwidth t P (l)
(l.)
-3 ~
OS)
<P lú)M
o (1.)
-5 "O
o:¡
·-
i:::::
"O ~
-e-
·-
i:::
-1 o -50 '--'
·ti-
(l)
e:: ~
c.tj
§
(l)
-15 -100 V)
c.tj
.r:::
e,
Excitation Synchronous
-20 machine -150
VT
VR G2
-25 -200
The indices of interest associated with the closed-loop frequency response are
the bandwidth ro 8 and peak value MP.
A high value of MP (> 1.6) is indicative of an oscillatory system exhibiting
large overshoot in its transient response. In general, a value of MP between 1.1 and
1. 5 is considered a good design practice.
Bandwidth is an important closed-loop frequency response index. Larger values
indicate faster response. It approximately describes filtering or noise-rejection
characteristics of the system.
Generally accepted values of performance indices characterizing good feedback
control system performance are:
Gain margin ¿ 6 dB
Phase margin ¿ 40°
Overshoot = 5-15%
MP = 1.1-1.6
Control and Protective Functions 333
sec. 8.5
It is not possible to define such generally acceptable ranges of values for other
all-signal performance indices: rise time, settling time, and bandwidth. These
~rnd. ces are a measure of the relative speed of the control action. They are primarily
dinetterrninedby t he synchr?º~us m~chine dynarm·c e ha~acten·st1·cs.
The performance indices grven above are applicable to any feedback control
stem having a single majar feedback loop, i.e., a single controlled-output variable.
itierefore, they are applicable to an excitation control system with the synchronous
achine on open circuit or feeding an isolated load. Stable operation of the excitation
~ntrol system with the generator off-line is ensured based on these performance
~ndices and associated analytical techniques [3]. On the other hand, synchronous
~achines connected to a power system form a complex multiloop, multivariable, high-
order control system. Por such a system, the performance indices identified above are
not applicable. The state-space approach using eigenvalue techniques is an effective
method of assessing the performance of such complex systems. This is covered in
detail in Chapter 12.
~
-- DC
regulator 11
1
1
1
DC voltage 1 Field *
1
1 Exciter ~ Generator
adjust 1
1 shorting
1
AC 11Y
11'1
~ regulator
AC voltage ~ r Exc. sys.
adjust
stab. circuits
Overexc. ***
limiter
Underexc.
limiter
V/Hz limiter
and protection
and reactive power excursions in the event the ac regulator is removed from service
abruptly. Care must be taken to ensure that a trip of the unit operating on manual
control <loes not leave the generator in an overexcited condition.
Compensation
sKF
I+sTF
The power system stabilizer uses auxiliary stabilizing signals to control the
excitation system so as to improve power system dynamic performance. Commonly
used input signals to the power system stabilizer are shaft speed, terminal frequency
and power. Power system dynamic performance is improved by the damping of
system oscillations. This is a very effective method of enhancing small-signal stability
performance.
The principie of operation of power system stabilizers and their structure and
tuning are discussed in detail in Chapters 12 and 1 7.
The automatic voltage regulator (AVR) normally controls the generator stator
terminal voltage. Sometimes, load compensation is used to control a voltage which
is representative of the voltage at a point either within or external to the generator.
This is achieved by building additional circuitry into the AVR loop as shown in
Figure 8.16. The compensator has adjustable resistance (Re) and inductive reactance
(Xc) that simulate the impedance between the generator terminals and the point at
which the voltage is being effectively controlled. Using this impedance and the
measured armature current, a voltage drop is computed and added to or subtracted
336 Excitation Systems~ Chap. 8
Generator Step-up
Field
Annaru~t---+-~-t---~--- .......... ----tr-~~sfu~~~er----------~j~H-T_b_u_s ...._
º ~
PT
CT '~
Load compensator
Topo~
system
Voltage
Exciter
regulator
from the terminal voltage. The magnitude of the resulting compensated voltage (Ve),
which is fed to the AVR, is given by
(8.1)
With Re and Xc positive in Equation 8 .1, the voltage drop across the compensator is
added to the terminal voltage. The compensator regulates the voltage at a point within
the generator and thus provides voltage droop. This is used to ensure proper sharing
of reactive power between generators bussed together at their terminals, sharing a
common step-up transformer. Such an arrangement is commonly used with hydro
electric generating units and cross-compound thermal units. The compensator
functions as a reactive-current compensator by creating an artificial coupling between
the generators. Without this provision, one of the generators would try to control the
terminal voltage slightly higher than the other; hence, one generator would tend to
supply all of the required reactive power while the other would absorb reactive power
to the extent allowed by underexcited limits.
With Re and Xc negative, the compensator regulates the voltage at a point
beyond the machine terminals. This form of compensation is used to compensate for
the voltage drop across the step-up transformer, when two or more units are connected
through individual transformers. Typically, 50% to 80% ofthe transformer impedance
is compensated, ensuring voltage droop at the paralleling point so that generators can
operate in parallel satisfactorily. This device is commonly referred to as a line-drop
compensator although it is practically always used to compensate only for transformer
drop. The nomenclature appears to have been derived from a similar compensator
used on distribution system voltage regulators (see Chapter 11, Section 11.2).
sec. 8.5 Control and Protective Functions 337
~
~
> o>
~ PinMW
...i..:.:. o
~
'"O
.E
......
u
X
(l.)
¡....;
Q)
'"O
~
:::i
Small-signal stability limit
Loss-of-excitation relay
Figure 8.17 Coordination between UEL, LOE relay and stability limit
120
\
90
B\
]
tfl
\
o
<)
(1.)
tfl
\
...i.:.:.
(1.)
60 \
......s .\ Field thermal capability
~ ·~
-.
30
<.
Overexcitation limiting '-.......'-.......
o "--y;--_._~~_._~------~--'-~~_._~---........._
Exciters with very high ceiling voltages may be provided with an additional
jield current limiter, which acts instantaneously through the ac regulator and limits the
field current to the short time limit (typically 160% of rated value).
These are used to protect the generator and step-up transformer from damage
due to excessive magnetic flux resulting from low frequency and/or overvoltage.
Excessive magnetic flux, if sustained, can cause serious overheating and may result
in damage to the unit transformer and to the generator core.
The ratio of per unit voltage to per unit frequency, referred to as volts per
hertz (V/Hz), is a readily measurable quantity that is proportional to magnetic flux.
Typical V/Hz limitations for generators (GEN) and step-up transformers (XFMR) are
shown in the following table.
Since rectifiers cannot conduct in the reverse direction, the exciter curreni
cannot be negative in the case of ac and static exciters. Under conditions of pole
slipping and system short circuits, the induced current in the generator field winding
may be negative. If a path is not provided for this negative current to flow, very high
voltages may result across the field circuit. Therefore, special circuitry is usually
provided to bypass the exciter to allow negative field current to flow. This takes the
form of either a field-shorting circuit, commonly referred to as crowbar, ora varistor
[8,30].
A crowbar consists of a thyristor and a field discharge resistor (FDR)
connected across the generator field as shown in Figure 8.19. The thyristor is gated
in response to an overvoltage condition that is created by the induced current not
initially having a path in which to flow. The thyristor so gated conducts induced field
current through the field discharge resistor.
Generator
Field
From exciter
FDR
Generator
Field
Varistor Armature
In sorne cases, no special field shorting circuits are provided. The amortisseurs
associated with the solid rotor iron provide paths for the induced rotor currents. This
is sufficient to limit the induced voltage to a level that is below the withstand
capabilities of the generator field and the exciter. Since the field is not shorted, it
carries no current in the negative direction.
In choosing the per unit system for exciter output voltage and current, there
are severa! options.
First, the per unit system used for the main synchronous machine field circuí¡
would appear to be the obvious choice. While this system was chosen to simplify the
synchronous machine equations (see Chapter 3, Section 3.4), it is not considered
suitable for expressing the exciter output quantities. This is because, for normal
operating conditions, the per unit exciter output voltage would be very small, being
on the arder of 0.001.
Second, for excitation system specification purposes it has become standard
practice to use the rated-load field voltage as 1.0 per unit. However, this is not
convenient for use in the formulation of synchronous machine and excitation system
equations for system studies.
The third choice is to have 1.0 per unit exciter output voltage equal to the field
voltage required to produce rated synchronous machine armature terminal voltage on
the air-gap line; 1.0 per unit exciter output current is the corresponding synchronous
machine field current. This per unit system is universally used in power system
stability studies as it offers considerable simplicity. Here, we refer to this system as
the non-reciproca! per unit system to distinguish it from the reciproca! per unit system
used for modelling synchronous machines.
Excitation system models must interface with the synchronous machine model
at both the field terminals and armature terminals. The input control signals to the
excitation system are the synchronous machine stator quantities and rotor speed. The
per unit systems used for expressing these input variables are the same as those used
for modelling the synchronous machine. Thus, a change of per unit system is required
only for those related to the field circuit.
We now develop the relationship between the per unit values of the exciter
output voltage/current expressed in the non-reciproca! system and the synchronous
machine field voltage/current expressed in the Laábase reciproca! system (see Section
3.4). Forthe synchronous machine, under open-circuit conditions, id=iq=O. Substituting
in Equations 3.139, 3.140, 3.142 and 3.143 yields
(8.2)
(8.3)
sec. 8.6 Modelling of Excitation Systems 343
l/Ladu
1.0
Referring to Figure 8.21, the field current required to produce 1.0 per unit
stator terminal voltage on the air-gap line (slope = Ladu) is determined by
(8.4)
Therefore, in the reciproca! per unit system, the field current i¡d required to generate
rated stator terminal voltage on the air-gap line is given by
=
R~d
J' pu
Ladu
By definition, the corresponding value of exciter output current l¡dis equal to 1.0 per
unit. Therefore,
344 Excitation Systems Chap. 8
(8.5)
(8.6)
Physically, exciter output voltage/current and generator field voltage/current are the
same; distinction is made only in their per unit values to allow independent selection
of the per unit systems for modelling excitation systems and synchronous machines.
This is illustrated in Figure 8.22.
Under steady-state conditions, the per unit values of E¡d and l¡d are equal.
During a transient condition, however, E¡d and l¡d differ; E¡d is determined by the
excitation system and l¡d is determined by the dynamics of the field circuits.
A few interesting observations regarding the above per unit conversion are
appropriate at this time:
l. The factor Lad)R¡d in Equation 8.6 is the steady-state value of G(s) (see
Chapter 4, Equations 4.14 and 4.17), in the absence of saturation.
-
The steady-state value of G(s) is equal to 1.0. There is thus a one to one
relationship between ~d and E¡d·
sec- 8.6 Modelling of Excitation Systems 345
With amortisseurs neglected, Equation 8. 7A becomes
1
A lJr j.s) = áE1d (8.7B)
1 +sT/Jo
3. From the steady equations developed in Section 3.6.3, with the generator on
open circuit, we have
A. 1'il'rd = A.e q = .6.Et
1
= (8.7C)
l+sT~
Example 8.1
The following are the parameters in per unit on machine rating of the 555 MVA, 0.9
p.f., 24 kV turbine generator considered in Examples 3 .1, 3 .2 and 3 .3 of Chapter 3:
Ladu = 1.66 Laqu = L61 L1=0.15
L¡d = 0.165 R¡d = 0.0006 Rª = 0.003
(a) The field current required to generate rated stator voltage E1 on the air-gap
line is 1300 A and the corresponding field voltage is 92.95 V. Determine the
base values of E¡d and l¡d in the non-reciproca! per unit system and the base
values of e¡d and i¡d in the reciproca! per unit system.
(b) Compute the per unit values of E¡d and I1d,when the generator is delivering
rated MVA at rated power factor and terminal voltage. Assume that the
corresponding values of the saturation factors Ksd and Ksq are equal to 0.835.
Solution
(a) By definítiori, the base values of E¡d and l¡d are respectively equal to the field
vo1tage and field current required to produce rated air-gap line voltage. Hence,
From Equations 8.5 and 8.6, the base values of e¡d and i¡d are
1¡d base == L cui1.l¡d base
= l.66xl300 == 2158 A
346 Excitation Systems Chap, 8
The above base values of e¡d and i¡d, as expected, agree with the values computed in
Example 3.1.
(b) From the results of Example 3.2, at the rated output conditions,
e¡d = 0.000939 pu
͡d = 1.565 pu
E¡d = (LadjR¡d)e¡d
= (1.66/0.0006)0.000939 = 2.598 pu
l¡d =
=
L adu͡d
1.66x 1.565 = 2.598 pu •
Specification o/ temperature
The base exciter output voltage depends on the synchronous machine field
resistance, which in turn depends on the field temperature. The standard temperatures
used for calculating the base exciter output voltage are 1 OOºC for thermal units
(operating temperature rise greater than 60ºC) and 75ºC for hydraulic units (operating
temperature rise 60ºC or less) [5]. However, care should be exercised in using these
temperatures for modelling of excitation systems.
The value of the field resistance used should correspond to the resistance under
the actual operating conditions being simulated, as closely as possible. The value of
TJ0 should be consistent with this value of field resistance.
The field resistance corrected to a specified operating temperature may be
calculated as follows [31]:
t 8-
R=R- +k) (8.8)
s t ( tt +k
where
ts = specified operating temperature, ºC
E:xaJJlple 8.2
The per unit R¡d of a steam-turbine-driven generator is 0.00063 at 75ºC and the
corresponding value of T~ is 7.6125 s. The base exciter output voltage at the standard
temperature of lOOºC is 105.575 V. If the generator is operating ata temperature of
60ºC, find consistent values of R¡d, T~' and base E¡d at this temperature. Assume that
the constant k of the field winding material is 234.5.
Solution
234.5+60
Base E¡d60 = base E¡d roo ( 234.5+100
l
= 105.575x0.8804 = 92.95 V
•
8.6.2 Modelling of Excitation System Components
The basic elements which form different types of excitation systems are the
de exciters (self or · separately excited); ac exciters; rectifiers (controlled or non-
controlled); magnetic, rotating, or electronic amplifiers; excitation system stabilizing
feedback circuits; signal sensing and processing circuits. We describe here models for
these individual elements. In the next section we will consider modelling of complete
· excitation systems.
1eJ
Eef i; Ex
(8.1 O)
where Kx depends on the speed and winding configuration of the exciter armature.
The output voltage Ex is a nonlinear function of the exciter field current le¡ due
to magnetic saturation. The voltage Ex is also affected by the load on the exciter. The
common practice [1,4] in de exciter modelling is to account for saturation and load
regulation approximately by combining the two effects and using the constant-
resistance load-saturation curve, as shown in Figure 8.24.
The air-gap line is tangent to the lower linear portian of the open circuit
saturation curve. Let Rg be the slope of the air-gap line and Me¡ denote . the departure
of the load saturation curve from the air-gap line. From Figure 8.24, we write
Ex (8.11)
I ef = -+d.I
R ef
g
(8.12)
Air-gap line
»->: Open circuit curve
,..,... ,..,,../ -- Constant-resistance
- 1 6.1e ¡ i1-
1 1
1 1
1 1
1 1
r 1
(8.13)
The above equation gives the relationship between the output Ex and the input voltage
Eef A convenient per unit system for this equation is one with base values of Ex and
le¡ chosen to be equal to those values required to give rated synchronous rnachine
voltage on the air-gap line. Thus,
EX base = Efdbase
/e/base = Efdbasef Rg
(8.14)
Rgbase =R g
--'-E
ef_ = _R!f_ EX +R S (E ) EX +--1 d( EX l
EXbase Rg EXbase ef e x E Xbase K X dt EXbase
350 Excitation Systems Chap.8
In per unit f orm, we have
-
- Re¡- - - 1 dEx
E =-E [l+S (E)]+--- (8.15)
ef R X e X K dt
g X
In the above equation, Se(Ex) is the per unit saturation function defined as follow~:
(8.16)
From Figure 8.25, with Ex and le¡ expressed in per unit, the per unit saturation
function is given by [4]
A-B (8.17)
B
-
Ex R Ex
K = - = ---
g
X 1jT L J-
e/ e/
Constant-resistance
load-saturation curve
(8.19)
where
(8.20)
Equation 8.19 represents the input-output relationship of the exciter. For a separately
excited exciter, the input voltage Eef is the regulator output VR. The output voltage Ex
of a de exciter is directly applied to the field of the synchronous machine. Therefore,
the exciter may be represented in block diagram form as shown in Figure 8.26. In the
diagram, ali variables are in per unit; however, the superbar notation denoting this
has been dropped.
VX
(8.21)
The block diagram of Figure 8.26 provides a convenient means of representing the
de exeiter in stability studies. However, the effective gain and time eonstant of the
exciter are not readily apparent from it. These are more evident when the block
diagram is reduced to the standard form by considering small-signal response:
For any operating point with Ex=EFD;;;:,EFDO' the effective gain K and time
constant of the exciter for small perturbations are
1
K=----- (8.22)
BEx SE(Epoo) +KE
T =
TE (8.23)
For this exciter, the regulator output VR is in series with the exciter shunt field.
Tberefore, the per unit voltage across the exciter field (without the explicit per unit
notation) is
(8.24)
jhe relationship between the per unit values of Ee¡ and Ex developed for the
separately exci.ted exci:er also applies in this case. Substituting for Ee¡ given by
Equation 8.24 m Equation 8.15, we have
R 1 dE
= _!f_E [l +S(E )] +---x
R X e X K dt
g X
This reduces to
(8.25)
where
TE = (8.26)
R
SE= se (E)~
X R
g
The block diagram of Figure 8.26 also applies to the self-excited de exciter. The value
of KE, however, is now equal to Re/Rg-1 as compared to Re/Rg for the separately
excited case.
The station operators usually track the voltage regulator by periodically
adjusting the rheostat setpoint so as to make the voltage regulator output zero. This
is accounted for by selecting the value of KE so that the initial value of VR is equal
to zero. The parameter KE is therefore not fixed, but varies with the operating
condition.
+ 1
[ - .
~ sTE
vx = VE·SE(VE)
+
vx
E + KE
+
KD IFD
The general structure of the model is similar to that of the de exciter. However, in
this case the load regulation due to the armature reaction effect is accounted for
distinctly, and the no-load saturation curve is used to define the saturation function
SE. The exciter internal voltage VE is the no-load voltage as determined by the
saturation function. The main generator field current I FD represents the exciter load
current, and the negative feedback of KDIFD accounts for the armature reaction
demagnetizing effect. The constant KD depends on the ac exciter synchronous and
transient reactances [32]. Figure 8.29 illustrates the calculation of the saturation
function SE for a specified value of VE.
The per unit saturation function is
S (V) = A-B (8.27)
E E B
decrease in the average output voltage of the rectifier as its load current increases.
Reference 33 shows that a three-phase full-wave bridge rectifier circuit operates in
one of three distinct modes as the rectifier load current varies from no load to the
short circuit level. The mode of operation depends on the commutating voltage drop
(equal to the product of commutating reactance and load current).
The equations defining the rectifier regulation as a function of commutation
voltage drop may be expressed as follows [8,34]:
where
FEX = f(IN) (8.29)
and
IN =
KCIFD (8.30)
VE
The constant Kc depends on the commutating reactance. The expressions for the
functionf(JN) characterizing the three modes of rectifier circuit operation are
356 Excitation Systems Chap. 8
Now IN should not be greater than 1.0, but if for sorne reason it is, FEx should be set
to zero [8].
The rectifier regulation effects identified above may be depicted in the block
diagram form as shown in Figure 8.30.
Referring to Figures 8.28 and 8.29, the exciter output voltage Epn is simulated as
the ac exciter interna! voltage VE reduced by the armature reaction (Ipnf(n) and
rectifier regulation (FEx).
(d) Amplifiers
VRMAX
~---
Figure 8.31 Amplifier model
The output limits of sorne amplifiers having power supplies from generator or
uxiliarY bus voltage vary with generator terminal voltage. In such cases, VRMAX and
~ vary directly with generator terminal voltage s,
RMIN The transfer function of an amplidyne is derived in reference 12 and has the
general form shown in Figure 8.32.
There are severa! ways of physically realizing the stabilizing function identified
in Figure 8.15. Sorne excitation systems use series transformers as shown in Figure
S.33.
The transformer equations in Laplace notation are
(8.32)
where subscripts 1 and 2 denote primary and secondary quantities; R, L, and M denote
resistance, leakage inductance and mutual inductance, respectively.
Exciter
Field Armature
~-~-----~+
)Ex
Amplifier _ Stabilizing
---¡- transformer
+ 2
+
~--,o+
verr
~--~-----------0-
(8.33)
Thus
-----
(8.34)
1
Representation: U---i
s
dv
S ystem equation: = u
dt
Limiting action:
If LN<v<Lx, then y = v
If v ~ Lx, then y = Lx
If v:::;,LN, then y = LN
1
Representation: u y
s
LN
system equation: dy
= u
dt
Limítingaction:
If LN<y<Lx, then dy = u
dt
If y z Lx and dy >O, then set dy =o y= Lx
dt dt '
dy dy
If y~LN and -<O, then set = o, y= LN
dt dt
With windup limits the variable v is not limited. Therefore, the output variable y
cannot come off a limit until v comes within the limit. With non-windup limits, the
output variable y is Iimited; it comes off the limit as soon as the input u changes sign.
Figures 8.35(a) and (b) show the difference between the two types of lirnits
when applied to a single time constant block. The significance of the two types of
limits is similar to that for an integrator. With a .windup limit, the output y cannot
come off a limit until v comes within the limit. With a non-windup limit, however,
the output y comes off the limit as soon as the input u re-enters the range within
limits.
1
Representation: U---
l+sT
dv u-v
System equation: =
dt T
Limitingaction:
If LN<v<Lx, then y = v
If v '2:. Lx, then y = L:x
If v~LN, then y = LN
Figure 8.35 (a) Single time constant block with windup limits
360 Excitation Systems Chap. 8
1
Representation: U---i i---- y
l+sT
u-y
System equation: f=
T
Limiting action:
If LN<y<Lx, then dy = f
dt
If y c.Lx and f>O, then set dy = O, y = Lx
di.
If y -:;,LN and f <O, then set d; = O, y = LN
Figure 8.35 (b) Single time constant block with non-windup limits
LX
l+sTA
Representation: u y
l+sT8
LN TA<TB
Physical realization:
Lx
+ TA
u y
TB
Lirniting action:
If LNs,.v ::;.Lx, then y = v
If v>Lx, then y = i;
If v<LN , then y = LN
u LV y u HV y
V gate V gate
If u s v, y=u If u z v, y=u
If u>v, y=v If u<v, y=v
Et--•
It ,
......_
_ °V"Cl 1
.
1
l+TR
1
Figure 8.39 depicts the general structure of a detailed excitation system model
having a one-to-one correspondence with the physical equipment. While this niodel
structure has the advantage of retaining a direct relationship between model
parameters and physical parameters, such detail is considered too great for general
system studies. Therefore, model reduction techniques are used to simplify and obtain a
practica} model appropriate for the type of study for which it is intended.
The parameters of the reduced model are selected such that the gain and phase
characteristics of the reduced model match those of the detailed model over the
frequency range of O to 3 Hz. In addition, all significant nonlinearities that impact on
system stability are accounted for. With a reduced model, however, direct
correspondence between the model parameters and the actual system parameters is
generally lost.
The appropriate structure for the reduced model depends on the type of
excitation system. The IEEE has standardized 12 model structures in block diagram
form for representing the wide variety of excitation systems currently in use [8].,
Other
signals
These are intended for use in transient stability and small-signal stability studies. For
urposes of illustration, we will consider five of these models. These are shown in
~·gures 8.40 to 8.44, with slight modification of the block diagram conventions to
~nform to the recommendations made in reference 35. The figures include a brief
º!
~escription the key features an~ samp~e.data. The suffix "A" acco~panying the
designationsis for the purpose of differentiating these models developed m 1992 from
5
irnilar models developed previously in 1981 [4].
The principal input signal to each of the excitation systems is the output Ve
ofthe voltage transducer shown in Figure 8.38. At the first summing point, the signal
V. is subtracted from the voltage regulator reference Vref and the output V8 of the
p¿wer system stabilizer, if used, is added to produce the actuating signal which
controls the excitation system. Additional signals, such as the underexcitation Iimiter
output (VUEL), come into play only during extreme or unusual conditions. Under
steady state, V8=0 and Vref takes on a value unique to the synchronous machine
loading condition so that the error signal results in the required field voltage E¡d· This
is illustrated in Example 8.3.
l+sTc HV
Ve l+sTB gate
vref
+
Figure 8.40 IEEE type DClA excitation system model. ©IEEE 1992 [8]
Self-excited de exciter:
I+sTc
l+sT8
o
~MIN
sKp
l+sTp
Figure 8.41 IEEE type AClA excitation system model. © IEEE 1992 [8]
Sample data
+
l+sTc HV
l+sTs gate
vref
Figure 8.42 IEEE type AC4A excitation system model. © IEEE 1992 [8]
Sample data
HV (1 +sTJ(l +sTc1) KA HV LV
gate (1 +sT~(l +sTBI) l+sTA gate gate
VaEL
V¡,.
sKF
l+sTF
Figure 8.43 IEEE type STlA excitation system model. © IEEE 1992 [8]
Sample data
Sample data
KA=120.0 TA =0.15 KE=l.0 TE=0.5 Kc=0.65
KF=0.02 TF=0.56 VRMAx=l.2 VRMIN=-1.2 EFDMAX=3.55
Kp=l.19 K1=1.62
sec. 8.6 Modelling of Excitation Systems 367
Vs *
V uEL
VRMAN
VuEL
HV KA
Ve gate l+s7A
Vs
V,.ej VF o
VRMIN
sKp
l+sTF
-
Vr---
+
~ "E =I x,Vr+i K1lr1
Ir---~---~-----'
Example 8.3
(a) If it is equipped with a type AC4A excítation system represented by the block
diagram of Figure 8.42, determine the value of vref"
The parameters of the excitation systems are the same as for the sample data provided
with the figures.
Solution
VR=E¡iKA
2·598
= =0.013 pu
200.0
Under steady-state operation, V1= VR and V8=0. Since the generator is operating under
normal conditions, VUEL =O. Therefore, from Figure 8.42 we see that
Vre/ = Ve+ V1
In this case, KE takes a value such that VR =0. With E¡dat a steady-state value and
VR=O, VFE=O. Hence,
KEEfd = -Vx
= -0.7852
Therefore,
K = _ 0.7852
E 2.598
= -0.3022
•
Modelling of limiters
VKMX
K¡ VuMX
1 +sT1 Vu
KP VUEL
(1 +sT2) (l +sT3)
1
s VuMN
ILIM
Sample data:
An example of the V/Hz limiter model is shown in Figure 8.46. The operation
of the limiter is quite straightforward. When the per unit V/Hz value exceeds the
limiting value of VzLM' a strong negative signal drives the excitation down. The VZL
limit is set typically at 1.07 to 1.09 pu. M
AVR summing
Et (pu) VzLM function
1.0 Ve
f (pu)---4 E/f
+ L ~~ 1
s
Kz2 Vz ~ L r----
+
o
Sample data:
o o AVR summing
1 function
l¡d s +
VFJ High-low
LM2 select switch
K4 @ ---'1'"~~~--=--=...J
1--~~...;::_~~~~~~
CD Normally at
high setting
Sample data:
]FLMl= l.6xfull load l¡d IFLM2 = l.05xfull load l¡d
K1 = 150 K2 = 0.248 K3 = 12.6
K4 = 140 LMI = -0.085 LM2 = -3.85
º T 30 s Time
Although most of the data related to excitation system models cari be obtainect
from factory tests, such data can only be considered as typical. The actual settings are
usually determined on site during installation and commissioning of the equipment.
It is therefore desirable to determine the model parameters by performing tests on the
actual equipment on site.
The nature of the tests required will depend on the type of excitation systern
being tested. A general procedure for model verification and development is as
follows:
1. Obtain circuit diagrams, block diagrams, nominal settings and setting ranges ..
Construct a detailed block diagram of the complete excitation system }
3. Perform frequency response and time-response tests with the generator running at
rated speed and producing rated voltage on open-circuit, Measure the overall
linear response and responses at various points of the system to a step change
in terminal voltage. Perform additional tests with the generator operating near
rated load. Validate the detailed rnodel of the complete system by comparison
with the measured responses.
4. Reduce the detailed model to fit the standard model applicable to the specific
type of excitation systern using techniques of classical control theory. Validate
the responses of the reduced rnodel against the measured responses.
The above procedure is quite involved and time-consuming for the older slow-
response exciter. For a high-response excitation system, frequency response tests are
usually not required as the nurnber of time constants within the major feedback loop
is small. For static excitation systems, model parameters can usually be obtained from
design data; field tests are required only for verification.
Techniques for field testing, performance verification and model development
of excitation systems are described in references 3, 7, and 36.
References 373
REFERENCES
[4] IEEE Committee Report, "Excitation System Models for Power System
Stability Studies," IEEE Trans., Vol. PAS-100, pp. 494-509, February 1981.
[5] IEEE Standard Definitions for Excitation Systems for Synchronous Machines,
IEEE Standard 421.1-1986.
[6] IEEE Guide for the Preparation of Excitation System Specifications, IEEE
Standard 421.4-1987.
[7] IEEE Guide for Identifzcation, Testing and Evaluation of the Dynamic
Performance of Excitation Control Systems, IEEE Standard 421.2-1990
(revision to IEEE Standard 421A-l978).
[8] IEEE Recommended Practice for Excitation System Models for Power System
Stability Studies, IEEE Standard 421.5-1992.
[11] E.W. Kimbark, Power System Stability, Vol. JI!: Synchronous Machines, John
Wiley & Sons, 1956.
[13] T.L. Dillman, J.W. Skooglund, F.W. Keay, W.H. South, and C. Raczkowski,
"A High Initial Response Brushless Excitation System," IEEE Trans., Vol.
374 Excitation Systems Chap. 8
PAS-90, pp. 2089-2094, September/October 1971.
[14] J.S. Bishop, D.H. Miller, and A.C. Shartrand, "Experience with ALTERREx
Excitation for Large Turbine-Generators," Paper presented at the Joint
IEEE/ASME Power Conference, Miami Beach, September 15-19, 1974.
[15] R.K. Gerlitz, R.E. Gorman, and M. Temoshok, "The GENERREX Excitation
System for Large Steam Turbine-Generators," Paper GE3-3003, Pacific Coast
Electric Association Engineering and Operation Conference, Culver City~
Calif., March 20-21, 1975.
[16] P.H. Beagles, K. Carlsen, M.L. Crenshaw, and M. Temoshok, "Generator and
Power System Performance with the GENERREX Excitation System," IEEE
Trans., Vol. PAS-95, pp. 489-493, March/April 1976.
[17] H.M. Rustebakke (editor), Electric Utility Systems and Practices, John Wiley
& Sons, 1983.
[18] F. Peneder and R. Bertschi, "Static Excitation Systems with and without a
Compounding Ancíllary," Brown Boveri Review 7-85, pp. 343-348.
[19] D.C. Lee and P. Kundur, "Advanced Excitation Controls for Power System
Stability Enhancement," CIGRE Paper 38-01, Paris, France, 1986.
[20] IEEE Standard Dictionary of Electrical and Electronics Terms (ANSI), IEEE
Standard 100-1988.
[21] P. Kundur, M. Klein, G.J. Rogers, and M.S. Zywno, "Application of Power
System Stabilizers for Enhancement of Overall System Stability," IEEE Trans.,
Vol. PWRS-4, No. 2, pp. 614-626, May 1989.
[22] A.S. Rubenstein and W.W. Walkley, "Control of Reactive kVA with Modern
Amplidyne Voltage Regulators," AJEE Trans., Part III, pp. 961-970, December
1957.
[23] A.S. Rubenstein and M. Temoshok, "Underexcited Reactive Ampere Limit for
Modern Amplidyne Voltage Regulator," AJEE Trans., Vol. PAS-73, pp.
1433-1438, December 1954.
[24] J.T. Carleton, P.O. Bobo, and D.A. Burt, "Minimum Excitation Limit for
Magnetic Amplifier Regulating System," AJEE Trans., Vol. PAS-73, pp.
869-874, August 1954.
[27] Discussion of reference 26 by D.C. Lee, R.E. Beaulieu, P. Kundur, and G.J.
Rogers.
[28] M.S. Baldwin and D.P. McFadden, "Power Systems Performance as Affected
by Turbine-Generator Controls Response during Frequency Disturbances,"
IEEE Trans., Vol. PAS-100, pp. 2486-2494, May 1981.
[31] IEEE Guide: Test Procedures for Synchronous Machines, IEEE Standard 115-
1983.
[32] R.W. Ferguson, H. Herbst, and R.W. Miller, "Analytical Studies of the
Brushless Excitation System," AJEE Trans., Part III, pp. 961-970, 1957.
[33] R.L. Witzke, J.V. Kresser, and J.K. Dillard, "Influence of AC Reactance on
Voltage Regulation of 6-Phase Rectifiers," AJEE Trans., Vol. 72, pp. 244-253,
July 1953.
[34] L.L. Freris, "Analysis of a Hybrid Bridge Rectifier," Direct Current, pp.
22-23, February 1966.
[35] IEEE Task Force, "Conventions for Block Diagram Representations,'' IEEE
Trans., Vol. PWRS-1, No. 3, pp. 95-100, August 1986.
[36] IEEE Tutorial Course Text, "Power System Stabilization via Excitation
Control - Chapter IV: Field Testing Techniques," Publication 81 EHO 175-0
PWR.