Controller SR609C
Controller SR609C
Content
1. Safety information ............................................................................................3
1.1 Installation and commissioning .......................................................................3
1.2 Liability waiver ...................................................................................................3
1.3 Signal description ..............................................................................................4
2. Installation .............................................................................................................4
2.1 Mounting controller ...........................................................................................4
2.2 Power connection..............................................................................................5
2.3 Terminal connection ..........................................................................................6
3. System diagram ...................................................................................................8
4. Functions operation.............................................................................................9
4.1 Signals on display and function code ............................................................9
4.2 Button Description ...........................................................................................10
4.3 Menu structure ................................................................................................. 11
4.4 Menu description .............................................................................................12
4.5 Setting time ......................................................................................................13
4.6 THEH Timing heating .....................................................................................13
4.7 TCYC Setting the running time/ temperature of DHW pump...................15
4.8 AHO Automatically thermostat function .......................................................19
4.9 OTF Three time sections set (Timer function) ............................................21
4.10 PHTC Time controlled pipe heating protection ........................................22
4.11 TDIS Thermal disinfection ...........................................................................24
4.12 CFR Tank anti-freezing protection .............................................................25
4.13 UNIT Celsius degree and Fahrenheit unit switch ....................................27
4.14 BEEP Beeper error warning ........................................................................27
4.15 RST Reset function.......................................................................................27
4.16 M.H manual heating .....................................................................................28
4.17 Intelligent heating mode...............................................................................28
-1-
SR609C Operation manual
-2-
SR609C Operation manual
1. Safety information
We have carefully checked the text and pictures of this manual and provided the
best of our knowledge and ideas, however inevitable errors maybe exist. Please
note that we cannot guarantee that this manual is given in the integrity of image
and text, incorrect, incomplete and erroneous information and the resulting
damage we do not take responsibility.
-3-
SR609C Operation manual
2. Installation
-5-
SR609C Operation manual
Notes: the flexible wire must be fastened to the case using the strain-relief
clamps provided.
③ ③ ④ ④
Power terminal N, L: 20A, for power connection, L: live wire, N: zero wire,
protective wire, please is sure to connect to ground.
Output ports
H1: Designed for electrical heater, electromagnetic relay, max. power is
3000W,
R1: Designed for anti-freezing heating cables, Electromagnetic relay, max.
power is 500W
3. System diagram
LCD display
Code Description Code/Signal Lighting Code/Signal Blink
Economic mode
-9-
SR609C Operation manual
4.2 Button Description
Layout of button
Button description
“CLOCK” button: current time setting
“M.H” button: manual heating switch on/off
“SET” button: confirm the setting or activate the setting program
“ESC” button: exit or return to the previous menu
“ ” button: increase adjustable value or upwards menu
“ " button: decrease adjustable value or downwards menu
- 10 -
SR609C Operation manual
Main menu
Submenu
Note: R1 output port is designed for one of functions from TCYC, AH, OTF,
PHTC, if one of these functions is selected to be activated, and then the others
should be deactivated in the menu.
- 12 -
SR609C Operation manual
4.5 Setting time
►Press “Clock” button, time displays on the
screen, hour “00” blinks on the screen.
►Press “▲▼” button to set hour of clock
►Repress “Clock”, minute “00”blinks
► Press “▲▼” button to set minute of clock.
► Press “Clock” to exit program, or waiting for 20 seconds, controller exits
automatically, the set parameter is saved automatically.
Note: at the case that power is switched-off, time can be kept for
36hours.
Description:
Electrical heater can be integrated into solar system used as back-up
heating of system, and it can be triggered automatically at preset time by
preset temperature. Within a preset time section, when the temperature
(T1) of tank drops below the preset switching-on temperature of this function,
electrical heating (H1) starts to work, when T1 rises up to the preset turning
off temperature, electrical heating (H1) is stopped.
Within 24 hours, three time sections can be set with this controller.
Factory set:
The first time section: electrical heating function starts at 4:00 and ends at
5:00 am. Within this time section, switch-on temperature is 40℃,
switch-off temperature is 50℃.
The second time section: from 10:00 to 10:00 am, it means there is no
electrical heating in this time.
The third time section: electrical heating function starts at 17:00 and ends at
22:00 pm. Within this time section, the switch-on temperature is 50℃,
- 13 -
SR609C Operation manual
If you want to shut off one timing heating, then you can set the turning on
time and turning off time same value (for example, the second time section
no this function, then you can set turning on/off time is 10:00 ~ 10:00)
When time is outside of the preset time section, electrical heating doesn’t
work automatically even when the tank temperature reaches the switch –on
temperature of heating.
Setup steps:
►Press “SET” button for 6 seconds, to access the
main menu and select menu “THET”.
►Press “SET” button again to access the program.
►Press “SET” button again, the first switch-on time
and temperature parameters “th1O 04:00 ”displays
and blinks on the screen.
►Press “SET” button, hour “04” blinks on the screen.
►Press “▲▼” button, to set hour of the switch-on
time of heating
►Press “SET” button, minute “00” blinks on the screen.
►Press “▲▼” button, to set minute of the switch-on time of heating
►Press “SET” button, temperature “40” blinks on the screen.
►Press “▲▼” button, to set the switch-on temperature of heating.
►Press “SET” or “ESC” button to confirm.
- 14 -
SR609C Operation manual
- 15 -
SR609C Operation manual
DHW pump running at below 2 modes:
Running controlled by time within the three time sections
If sensor T2 is not connected to the controller, then time controlled mode is
selected automatically, within a running time section, as default set, pump runs
for 3 minutes and then ceases for 15 minutes, same process repeated within
the running time section. Running time can be adjusted from 1-30Min; Stop time
can be adjusted from 0-60Min.
If the stop time ( CYCF) is set to 0 minute, then
within the time section, DHW pump keeps running
without any intervals.
Default time sections:
The first time section starts at 05.00 am, closes at
7:00am.
The second time section starts at 11.00 am, and closes at 13:00pm.
The third time section starts at 17.00 pm, and closes at 22:00pm.
Note:
STAT not available on the time controlled mode.
Note:
DHW pump temperature controlled mode is prior to time controlled mode.
When sensor T2 is connected to the controller, then time controlled mode is
switched -off automatically, and switched to temperature controlled mode.
If sensor T2 should be installed, in order to avoid measuring error, please
ensure a safety distance of 1.5m to tank.
The setting steps for time controlled mode and temperature controlled mode is
same.
- 17 -
SR609C Operation manual
►Press “▲” button, to the first time section setting, “tC 1F 07:00”displays
(switch –off time of the first time section of DHW
pump)
►Press “SET” button again, hour “07” blinks on the
screen.
►Press “▲▼” button, to adjust hour of the switch-off time
►Press “SET” button again, minute“00” blinks on the screen.
►Press “▲▼” button, to adjust minute of the switch-off time
- 18 -
SR609C Operation manual
If it is needed to close one time section, just set the start time and stop time at a
same value (e.g. 10:00 starts, 10:00 stops)
- 19 -
SR609C Operation manual
When the signal of thermostat “AH” is blinks on the screen, it indicates that the
thermostat function is activated.
Setup steps:
►Select OTF DHW circulation main menu.
►Press “SET” button, “OFF” displays on the screen.
►Press“ ”button to activate the function
►Press “SET” or “ESC” to confirm
►Press“ ”button to access the setting program to
set the timer, “t1O 00:00”displays on the screen, it is
ready for setting the start time of the first time
section.
►Press “SET” button, hour“00”blinks
►Press“ ”button to adjust hour of the start time
►Press “SET” button, minute“00”blinks,
►Press“ ”button to adjust minute of the start
time
- 21 -
SR609C Operation manual
Setup steps:
►Select menu PHTC pipe heating function.
►Press “SET” button, “OFF” blinks on the screen
►Press“ ”button to activate this function
- 22 -
SR609C Operation manual
- 23 -
SR609C Operation manual
When the timer signal blinks on the screen, it indicates that the timer
function is activated.。
Note: if the interval time PHET is set with 0 minute, then within the time
section, pipe heating will run without stop.
Setup steps:
►Select TDIS thermal disinfection main menu
►Press “SET” button, “OFF” blinks
►Press“ ”button, to activate this function
►Press “SET” or “ESC” to confirm
►Press“ ”button, to set the days of a thermal
disinfection period, “PDIS 07”displays on the screen.
- 24 -
SR609C Operation manual
- 25 -
SR609C Operation manual
Setup steps:
►Select main menu CFR tank anti-freezing
protection function
►Press “SET” button, “OFF” blinks
►Press “ ”button to activate the function
- 26 -
SR609C Operation manual
4.13 UNIT Celsius degree and Fahrenheit unit switch
Setup steps:
►Select this function menu UNIT,
- 27 -
SR609C Operation manual
4.16 M.H manual heating
Description:
You can trigger back-up electrical heater by this controller to adjust the tank
temperature. When controller measures the temperature T1 is below the
desired temperature, it will trigger the electrical heater until the tank temperature
(T1) rises up to the desired temperature.
Note: manual heating can heat tank only for one time, when manual
heating function is activated, tank is heated until its temperature reaches to the
desired value, and then manual heating is deactivated automatically.
When intelligent heating signal blinks on the screen, it indicates this function
is working.
Note: if the timing heating function is needed to be used, then the eco
mode should be deactivated.
- 29 -
SR609C Operation manual
5. Protection function
6. Quality Guarantee
The warrantee expires within 12 months after the date of purchasing the
controller.
- 30 -
SR609C Operation manual
7. Technical specification
Power supply:AC230V ±10%,50Hz
Power consumption:< 3W
Accuracy of temperature measuring: ± 2oC
Range of tank temperature measuring: 0 ~100 oC
Suitable power of electrical heater: ≤ 1.5KW or ≤ 3KW (optional)
Inputs:T1: NTC10K, B3950 sensor (≤ 135oC) for tank, (PVC cable ≤105oC),
T2: temperature sensor, optional
Outputs:H1 for electrical heater, R1: Relay.
Ambient temperature :-10oC ~ 50oC.
Water proof grade:IP40.
Note:
If power supply:AC110V±10%,60Hz:
Suitable power of electrical heater: ≤ 0.75KW or ≤ 1.5KW (optional)
Suitable power of R1: ≤ 0.25KW
8. Delivery list
Controller 1 piece
Power cable 10A ( for controller of 3000W, plug not provided) 1 piece
Customer manual 1 piece
NTC10K sensor(size: φ6*50mm,cable length20 m) 1 piece
Accessories 1 bag
- 31 -