r48 2000e User Manual
r48 2000e User Manual
Rectifier Module
DANGER! Warns of a hazard the reader will be exposed to that will likely result
in death or serious injury if not avoided. (ANSI, OSHA)
WARNING! Warns of a potential hazard the reader may be exposed to that could result in
death or serious injury if not avoided. This admonition is not used for situations that pose a
risk only to equipment, software, data, or service. (ANSI)
CAUTION! Warns of a potential hazard the reader may be exposed to that could
result in minor or moderate injury if not avoided. (ANSI, OSHA) This admonition is not
used for situations that pose a risk only to equipment, data, or service, even if such use
appears to be permitted in some of the applicable standards. (OSHA)
ALERT! Alerts the reader to an action that must be avoided in order to protect
equipment, software, data, or service. (ISO)
ALERT! Alerts the reader to an action that must be performed in order to prevent
equipment damage, software corruption, data loss, or service interruption. (ISO)
FIRE SAFETY! Informs the reader of fire safety information, reminders, precautions,
or policies, or of the locations of fire-fighting and fire-safety equipment. (ISO)
Voltages
AC Input Voltages
DANGER! This system operates from AC input voltage capable of producing fatal electrical shock.
Hazardous Voltage
DANGER! HAZARD OF ELECTRICAL SHOCK.
More than one disconnect may be required to de-energize the system before servicing.
Specifications
NOTE! A current limitation can be set by the User and the output voltage level is set through the
controller.
DC Output Ratings
• Voltage: Nominal -48.0 VDC, Positive Ground.
a) Adjustment Range: The output voltage can be set within the range of -42V to -58V, adjustable via
the controller.
• Output Power and Current:
2000W (41.7A) @ 208/240VAC Input and -48VDC Output.
1262W (26.3A) @ 120VAC Input and -48VDC Output.
• Output Characteristics:
a) Refer to Figure 1 for a graph of output voltage vs. output current for the R48-2000e rectifier.
b) Refer to Figure 2 for a graph of output voltage vs. output current for the R48-2000 and R48-2000H
rectifier.
Figure 2: Output Voltage vs. Output Current [R48-2000 (1R482000) and R48-2000H (1R482000H)]
• Power Derating Based on Input Voltage: The rectifier power varies with changes in input voltage and
output voltage. It uses an advanced power limitation method. The lower input threshold is 85 VAC. The
rectifier can provide its maximum rated power (2000W) as long as the input voltage is within the range
of 176 to 300 VAC. Below 176 VAC, and down to 85 VAC, the rectifier will continue to operate normally
but will be in a power derating mode. The relationship between the output power and input voltage is
illustrated in Figure 3 and Figure 4.
• Power Derating Based on Temperature: The rectifier delivers full power when operating at an ambient
temperature of +45°C (+113°F) or below (1R482000 and 1R2000H) or +55°C (+131°F) or below
(1R482000e). Each rectifier continuously monitors the ambient temperature surrounding the power
conversion circuit. If this temperature for any reason (such as a high ambient temperature or failed fan)
increases above approximately +45°C (+113°F) (R48-2000 and R48-2000H) or +55°C (+131°F) (R48-
2000e), the rectifier will not shut down. Rather, the rectifier limits its maximum output power to
maintain the temperature of the power conversion circuit within design parameters. Operation between
+45°C (+113°F) (R48-2000 and R48-2000H) or +55°C (+131°F) (R48-2000e) and +80°C (+176°F) will
result in output power being decreased. Full power capability is restored when the temperature
decreases to below approximately +45°C (+113°F) (R48-2000 and R48-2000H) or +55°C (+131°F) (R48-
2000e). Refer to Figure 5 and Figure 6 to view the relationship between the output power and the
ambient temperature.
Other power rating values are as follows:
a) 1R482000 and 1R2000H:
1. At an ambient temperature of +65°C (+149°F), the power delivered by the rectifier is 1600W.
2. At an ambient temperature of +75°C (+158°F), the power delivered by the rectifier is 800W.
Figure 5: Power Derating Based on Temperature [R48-2000 (1R482000) and R48-2000H (1R482000H)]
NOTE! System output is initially adjusted to 54.48 volts DC as measured at the system sense point at
50% of full load and nominal input. “Percent of Full Load” refers to percent of 34.5 amperes.
NOTE! At 100% of full load with output adjusted to 58 volts DC as measured at the shelf output
terminals.
NOTE! System output is initially adjusted to 54.48 volts DC as measured at the system sense point at
50% of full load and nominal input. “Percent of Full Load” refers to percent of 34.5 amperes.
NOTE! At 100% of full load with output adjusted to 58 volts DC as measured at the shelf output
terminals.
NOTE! System output is initially adjusted to 54.48 volts DC as measured at the system sense point at
50% of full load and nominal input. “Percent of Full Load” refers to percent of 34.5 amperes.
NOTE! At 100% of full load with output adjusted to 58 volts DC as measured at the shelf output
terminals.
NOTE! System output is initially adjusted to 54.48 volts DC as measured at the system sense point at
50% of full load and nominal input. “Percent of Full Load” refers to percent of 34.5 amperes.
NOTE! At 100% of full load with output adjusted to 58 volts DC as measured at the shelf output
terminals.
NOTE! System output is initially adjusted to 54.48 volts DC as measured at the system sense point at
50% of full load and nominal input. “Percent of Full Load” refers to percent of 34.5 amperes.
NOTE! At 100% of full load with output adjusted to 58 volts DC as measured at the shelf output
terminals.
NOTE! System output is initially adjusted to 54.48 volts DC as measured at the system sense point at
50% of full load and nominal input. “Percent of Full Load” refers to percent of 34.5 amperes.
NOTE! At 100% of full load with output adjusted to 58 volts DC as measured at the shelf output
terminals.
Environmental Ratings:
• Operating Ambient Temperature Range:
a) -40°C (-40°F) to +80°C (+176°F) with derating output.
b) 1R482000 and 1R2000H: -40°C (-40°F) to +45°C (+113°F) with full power performance.
c) 1R482000e: -40°C (-40°F) to +55°C (+131°F) with full power performance.
d) Temperature Coefficient: 0.01% per degrees Celsius.
• Storage Ambient Temperature Range: -40°C (-40°F) to +80°C (+176°F).
• Relative Humidity: This rectifier is capable of operating in an ambient relative humidity range of 0% to
95%, non-condensing.
• Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
• Surge Protection: Compliance with EN61000-4-5 (2kV Line to Line, 2kV Line to Earth). Capable of
withstanding surges per ANSI/IEEE C 62.41 1980 Category B3 across the input terminals.
NOTE! This level of protection is a widely used standard for telecommunications power equipment. As
with all such equipment, it is the end user's responsibility to provide an adequately sized Surge
Suppression Device at the commercial power service entrance of the building that reduces all incoming
surges to levels below the classes/categories stated for the equipment.
• Ventilation Requirements: The rectifiers are fan cooled and utilize front to back forced ventilation. A
rectifier must be mounted so ventilating openings are not blocked and temperature of the air entering
the rectifier does not exceed the Operating Ambient Temperature Range stated above.
• Single Rectifier Audible Noise:
a) R48-2000e: At 25°C ≤ 50dB(A) with fan in high speed. Measurement made at 0.6m distance in
front of rectifier and at same horizontal line of the middle of rectifier.
• External Control Circuits: Provided via the associated controller. Refer to the separate Power System
documentation for a complete description of available external control circuits.
• External Alarm Circuits: Provided via the associated controller. Refer to the separate Power System
documentation for a description of available external alarms.
Mechanical Specifications
• Dimensions:
a) Millimeters: 86.0 (Height) X 84.5 (Width) X 272.0 (Depth)
b) Inches: 3.4 (Height) X 3.3 (Width) X 10.7 (Depth)
• Weight: 2.4 kg (5.3 lbs).
OPERATION
AC Input Protection Device Requirements/Recommendations
Refer to the system documentation supplied with the system the rectifier is installed in.
Local Indicators
Location and Identification: Refer to Figure 10.
Description: There are three (3) indicators located on the rectifier’s front panel. The functions of these
indicators are as shown in Table 14.
NOTE! DC voltage must be present at the rectifier output terminals (from battery or an operating
rectifier) or AC voltage at the input terminals.
Installing Rectifiers
The rectifier is hot swappable. It can be installed with the system operating.
WARNING! To prevent damage to the latching mechanism, ensure the handle is in the open position
when installing or removing a rectifier. NEVER hold the handle in the closed position when installing a
rectifier into a shelf.
Procedure
NOTE! Refer to Figure 11 as this procedure is performed.
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable
these alarms. If these alarms cannot be easily disabled, notify the appropriate personnel to disregard
any alarms associated with this system while this procedure is performed.
2. On the rectifier to be removed, loosen the captive fastener securing the top of the latch mechanism to
the front of the rectifier. Pull the top of the latch mechanism away from the rectifier (this will retract the
latch mechanism located on the underside of the rectifier). This unlocks the rectifier from the shelf.
Refer to Figure 11 for latch mechanism illustration.
3. Slide the rectifier out by pulling forwards.
4. Place the replacement rectifier into the mounting position without sliding it in completely.
5. On the replacement rectifier, loosen the captive fastener securing the top of the latch mechanism to the
front of the rectifier. Pull the top of the latch mechanism away from the rectifier (this will retract the
latch mechanism located on the underside of the rectifier). See Figure 11.
6. Push the rectifier completely into the shelf.
7. Push the top of the latch mechanism into the front panel of the rectifier, and secure by tightening the
captive fastener. This locks the rectifier securely to the shelf.
8. Certain functions (i.e. rectifier current limit, rectifier addressing) may require adjustment when adding or
replacing a rectifier. Refer to the Power System documentation for instructions.
9. After the rectifiers are physically installed in the mounting shelf(s), they are ready for operation
immediately after power is supplied to them. Verify that the rectifiers are operating normally.
10. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
11. Ensure that there are no local or remote alarms active on the system.