Example Storage Tank Concrete
Example Storage Tank Concrete
General Input :-
tr= 0.20 m
Seismic Force
Direction of
L= 9.30 m tw= 0.30 m HL= 2.20 m Hw= 2.95 m
γL= 10.0 KN/m3
B= 9.30 m
Rectangular Tank Plan Rectangular Tank Elevation
2-Calculation the Height of center of gravity for impulsive hi & convective hc components:
3-Calculation the fundamental period of oscillation of the tank for impulsive Ti & convective Tc components:
= ,∴ =( ∗ = 289.7 KN/m
= 2.2 KN/m2
7- Load Cominations:
Note that, the Calculated Seismic Force E above is based on Strength-level Forces (ultimate loads).
For allowable stresses Design (ASD) Method (service loads), the design seismic forces shall be reduced by a factor of 1.4
ACI 350.3-06, Appendix B, Clause B.5
For Ultimate Strength Design method (factored loads), follow ACI 350-06, Clause 9.2.1 load combinations.