This document summarizes the calculation of seismic loads on a rectangular reinforced concrete liquid storage tank according to ACI 350.3-06. It provides details on determining the equivalent seismic weights, heights of mass centers, fundamental periods of vibration, lateral forces, base shear, and dynamic force distributions for the impulsive and convective components in both plan and elevation. The total seismic force is then calculated and adjusted based on the design method before concluding.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
159 views

Example Storage Tank Concrete

This document summarizes the calculation of seismic loads on a rectangular reinforced concrete liquid storage tank according to ACI 350.3-06. It provides details on determining the equivalent seismic weights, heights of mass centers, fundamental periods of vibration, lateral forces, base shear, and dynamic force distributions for the impulsive and convective components in both plan and elevation. The total seismic force is then calculated and adjusted based on the design method before concluding.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Seismic Loads for Liquid-Containing Rectangular RC Tank, According ACI 350.

3-06 , Appendix B Method


Based on 1997 Uniform Building Code Rev1.1

Project :- Project Designed by:- M. Abu Shady


Building :- Building Checked by:- M. Abu Shady
Element:- Element Date:- 14-Oct-18
Location:- Location M.A.S.

General Input :-
tr= 0.20 m

Seismic Force
Direction of
L= 9.30 m tw= 0.30 m HL= 2.20 m Hw= 2.95 m
γL= 10.0 KN/m3

B= 9.30 m
Rectangular Tank Plan Rectangular Tank Elevation

γc= 24.0 KN/m3


fc= 35.0 N/mm2 Ec= 27805.6 N/mm2 ACI318-08, Clause 8.5.1
g= 9.81 m/sec2

Importance factor I = 1.00 ACI 350.3-06, Table 4.1.1(a)


Rc = 1.00 ACI 350.3-06, Table 4.1.1(b)
Ri = 2.00 ACI 350.3-06, Table 4.1.1(b)
SEISMIC ZONE 2B
Z factor 0.2 UBC 97, TABLE 16-I
Soil Profile Very Dense
Soil Profile Type SC UBC 97, TABLE 16-J
Na For Zone 4 only 1 UBC 97, TABLE 16-S
Nv For Zone 4 only 1 UBC 97, TABLE 16-T
Ca 0.240 UBC 97, TABLE 16-Q
Cv 0.320 UBC 97, TABLE 16-R
Ts =0.40Cv/Ca 0.533 sec UBC 97, FIGURE 16-3

1-Calculation the Equivalent Weight for impulsive Wi & convective Wc component:

WL = 1902.8 KN , L / HL = 4.23 ,Ww = 815.6 KN ,Wr = 442.4 KN

= 0.27 WL = 519.1 KN ACI 350.3-06, Eq 9-1 ,Ww perp = 407.8 KN

= 0.71 WL = 1345.6 KN ACI 350.3-06, Eq 9-2

2-Calculation the Height of center of gravity for impulsive hi & convective hc components:

= 0.825 m ACI 350.3-06, Eq 9-3 & Eq 9-4

= 1.149 m ACI 350.3-06, Eq 9-5

3-Calculation the fundamental period of oscillation of the tank for impulsive Ti & convective Tc components:

= 1777.1 KN = 1.48 m = 3.05 m


, ,

= 1.22 m , = 102802.2 KN/m ACI 350.3-06, R9.2.4

= 0.26 sec ACI 350.3-06, Eq 9-11

= 4.43 = 4.32 sec ACI 350.3-06, Eq 9-13,14

= ,∴ =( ∗ = 289.7 KN/m

Seismic Loads for Liquid-Containing Rectangular RC Tank Page 1 of 2 M.A.S ______


Seismic Loads for Liquid-Containing Rectangular RC Tank, According ACI 350.3-06 , Appendix B Method
Based on 1997 Uniform Building Code Rev1.1
Project :- Project Designed by:- M. Abu Shady
Building :- Building Checked by:- M. Abu Shady
Element:- Element Date:- 14-Oct-18
Location:- Location M.A.S.

4-Calculation the total lateral impulsive force Pi & convective force Pc :

= 0.600 ACI 350.3-06, Appendix B, Eq B-1,2,3

= 0.077 ACI 350.3-06, Appendix B, Eq B-4,5

= 122.3 KN = 132.7 KN ACI 350.3-06, Appendix B, Eq B-6,7

= 155.7 KN = 103.7 KN ACI 350.3-06, Appendix B, Eq B-8,9

5-Calculation the total Base Shaer V:


= 423.7 KN ACI 350.3-06, Appendix B & Eq 4-5
6-Dynamic force distribution above base per Wall perpendicular to ground motion:

Pi Top = 1.0 KN/m2

Pi Bottom = 6.7 KN/m2

Pc Top = 2.9 KN/m2 ACI 350.3-06, R5.3.1

Pc Bottom = 2.2 KN/m2

= 2.2 KN/m2

= 2.2 KN/m2 = 2.2 KN/m2


= 1.0 KN/m2 = 2.9 KN/m2 = 6.0 KN/m2

= 6.7 KN/m2 = 2.2 KN/m2 = 11.0 KN/m2


Wall Inertia Force Pw Impulsive Force Pi ConvectiveForce Pc Total Seismic Force E per Wall
perpendicular to ground motion
Dynamic force distribution above base per Wall perpendicular to ground motion

7- Load Cominations:
Note that, the Calculated Seismic Force E above is based on Strength-level Forces (ultimate loads).
For allowable stresses Design (ASD) Method (service loads), the design seismic forces shall be reduced by a factor of 1.4
ACI 350.3-06, Appendix B, Clause B.5
For Ultimate Strength Design method (factored loads), follow ACI 350-06, Clause 9.2.1 load combinations.

Seismic Loads for Liquid-Containing Rectangular RC Tank Page 2 of 2 M.A.S ______