Power Monitoring Control
Power Monitoring Control
Section 4
Power Monitoring and Control
Table 4.1:
Data Presentment & Management Data Acquisition, Alarms & Monitoring
Online Energy Supervisory Control & Power Monitoring
Enterprise Tenant Submetering
Analysis Data Acquisition System
Data Centers; Water/Wastewater, Industrial, large Commercial Buildings,
Industrial Buildings, Heavy Process commercial buildings, Government
Utilities Buildings,
Property Management, Industry, Data Centers, Military Bases, Military Bases
Utilities Critical Power Healthcare
For products see DIGEST section: 4-6 4-17 4-5 4-4 thru 4-12 4-13 thru 4-16
For services see DIGEST section: 4-20 4-20 4-21 4-21 4-22
Meter Application
Automatic Meter Reading • •••• ••
Revenue Metering • •••• ••
WAGES Utility Pulses •••
Sub-billing ••• ••• ••••
Measurement & Verification •••• •• •••
Cost Allocation & Utility Billing
Energy Usage Analysis •••• ••• • •• •
Reduce Energy Costs &
Energy Efficiency Procurement Optimization •• ••• • •
Allocate Energy Costs • •
Interval Benchmarking & Profiling •••• ••• • ••
Total Load Aggregation ••••
Energy Efficiency
Emissions Tracking •• •••
Power Factor Correction • • •••
Peak Demand Reduction •• • ••• •••
Demand Response & Curtailment ••• •••
Improve Maintenance Practices
Commissioning & Troubleshooting ••• ••••
Equipment Monitoring: transformers, MCCs,
switchgear, switchboards, circuit breaker status, ••• ••••
protective equipment, capacitors, generators,
panelboards, PDU, UPS, etc.
Facility Planning
Optimize Equipment
Utilization Identify Equipment Capacity •••
Determine Transformer Stress •••
Equipment Asset Optimization •• •• •••
Improve Efficiency
Balance Circuit Loading •••
Balance Generator Usage •••
Optimize Chiller & Mechanical Equipment •
System Monitoring & Analysis
Transient Voltage Detection ••••
Sag/Swell Disturbance Monitoring ••••
Power Quality & Harmonic Analysis ••••
Improve Reliability & Power Quality Compliance •••• • •••
Safety
Alarm & System Diagnositics
Electrical Distribution Alarm & Event Analysis • ••• ••••
Waveform capture viewing ••••
Remote alarm notification •••• •••
Energy Services
System Mgr. Device Limited (1 web-enabled client, 16 devices, up to 32 devices with SMSDL32U, Interactive Graphics) SMSDL 4150.00
System Mgr. Standard Ed. (1 web-enabled client, MSDE or SQL Personal Edition with Interactive Graphics) SMSSE 12750.00
System Mgr. Professional Edition (10 web-enabled clients, SQL Server, Advanced Reports, Interactive Graphics) SMSPE 19950.00
Add On Modules
CONTROL
PowerLogic SCADA
PowerLogic® SCADA software was created to meet the requirement for real-time monitoring and control of electrical
distribution systems, including fast response times and high reliability through redundancy. PowerLogic SCADA is
powered by Citect® SCADA technology but is specifically designed for electrical power systems applications. The
complete PowerLogic supervisory control and data acquisition (SCADA) solution includes a dynamic graphical user
interface, enhanced alarm management, one second response times for control operation and status, transparent
redundancy, and reliable communications (through hardware components and network topology). The system also
features Sequence of Events Recorder (SER) logs with time stamps of 1ms resolution. PowerLogic SCADA software
includes a web-based client for remote viewing capability. The graphical user interface consists of animated objects
which change according to status information. The flexible graphics editor includes both ANSI and IEC electrical
symbols to facilitate easy one-line diagram creation. Real-time and historical trending is also supported.
PowerLogic® Powerview™ Software
PowerLogic Powerview is an entry level software designed for monitoring power consumption, allocating cost and
performing maintenance of small system applications. With Powerview software, system and device configuration is
simple and easy through its automatic device detect and connect feature. The software provides pre-configuration real-
time and historical data displays that retrieve onboard data logs from connected devices and performs PC-based
logging for devies without onboard memory. The software also features time of use capabilities for reporting energy
and demand values over user-specified time periods to satisfy special billing requirements and predefined reports for
analysis of energy usage, peak demand power, and more. Custom reports are available too for easy viewing, analysis,
sharing with other stakeholders or integrating into existing business platforms.
Table 4.4:
Description Catalog No. $ Price
Powerview Power Monitoring Software PLVENGUS 2850.00
Typical applications
• Manage all utilities (electricity, gas, water, etc.) and emissions through a single, unified interface
• Benchmark facility performance across an entire enterprise to identify energy inefficiencies
• Measure and verify savings from energy conservation projects or performance contracts
• Reduce operational costs, improve processes, and prolong asset life
• Meet corporate environmental stewardship goals or mandated impact targets
• Manage demand control schemes, load shedding, peak shaving, base loading or on-site generation
• Enable participation in real-time pricing and load curtailment programs
• Optimize procurement by forecasting and budgeting for energy needs and comparing utility rates
Use advanced billing
• Identify utility billing errors and validate contract compliance
functions to support energy
• Allocate and recover utilities costs from tenants, departments, processes, etc.
procurement and manage • Maximize the use of existing infrastructure capacity and avoid overbuilding
load or generation assets in • Identify and reduce risks to uptime
response to curtailment or Data presentment tier
pricing signals.
Web portal delivers enterprise-wide access
through personalized dashboards, reports,
detailed analytics, and integration of views
from third-party systems. Information and
alerts via cell phone, PDA, pager and more.
Business applications tier
Standard and optional modules tailor
functionality to specific needs. Advanced
4
Table 4.5: Typical PowerLogic ION8600 Power and Energy Meter Ordering Configurations
Description Catalog No. $ Price
ION8600, feature set A, 9S socket base, 5A nominal current inputs, auxiliary power pigtail: 65-120Vac/80-160Vdc, 60 Hz, communications card with: 10baseT Ethernet S8600A0C0H6E0A0A 6252.00
— RS-232/485 — Optical, RS-485
ION8600, feature set B, 9S socket base, 5A nominal current inputs, auxiliary power pigtail 65-120Vac/80-160Vdc, 60 Hz, communications card with: 10base T Ethernet S8600B0C0H6E0A0A 4700.00
— Optical, RS-485
ION8600, feature set C, 9S socket base, 5A nominal current inputs, auxiliary power pigtail 65-120Vdc/80-160Vac, 60 Hz, communications card with: RS-232/485. S8600C0C0H6A0A0A 2609.00
RS-485, Optical port, standard I/O
Table 4.6: Typical PowerLogic ION7550/7650 Power and Energy Meter Ordering Configurations
Description Catalog No. $ Price
POWER MONITORING AND
S7550A0C0B6A0A0A 5589.00
optical port), standard I/O
Typical PowerLogic ION7650 Power and Energy Meter Ordering Configurations
Integrated display, with 1024 samples/cycle, 10 MB logging memory, 5A inputs, standard power supply, standard comms. (1 RS232/RS485 port, 1 RS485, 1 Type 2 S7650B1C0B6E0A0E 9279.00
optical port) plus Ethernet, standard I/O, EN50160 compliance monitoring
Integrated display, with 512 samples/cycle, 5 MB logging memory, 5A inputs, standard power supply, standard comms. (1 RS232/RS485 port, 1 RS485, 1 Type 2 S7650A0C0B6E0A0A 7869.00
optical port) plus Ethernet, standard I/O
Integrated display, with 512 samples/cycle, 5 MB logging memory, 5A inputs, standard power supply, standard comms. (1 RS232/RS485 port, 1 RS485, 1 Type 2 S7650A0C0B6C1A0A 8409.00
optical port) plus Ethernet, standard I/O
Integrated display, with 512 samples/cycle, 5 MB logging memory, 5A inputs, standard power supply, standard comms. (1 RS232/RS485 port, 1 RS485, 1 Type 2 S7650A0C0B6A0A0A 7140.00
optical port) plus modem, standard I/O
Integrated display, with 1024 samples/cycle, 10 MB logging memory, 5A inputs, standard power supply, standard comms. (1 RS232/RS485 port, 1 RS485, 1 Type S7650B1C0B6E0A0A 9279.00
2 optical port) plus Ethernet, standard I/O
Note: Please refer to powerlogic.com for the most complete and up-to-date list of feature availability. Some features are optional.
4
Used in diverse applications such as feeder monitoring and sub-metering, the PowerLogic ION7300 series meters are also
suitable for high-accuracy power and energy metering, bill verification, cost allocation and billing, demand and power factor
control, load studies, circuit optimization, equipment monitoring and control and preventative maintenance. They are ideal
replacements for analog meters, with a multitude of power and energy measurements, analog and digital I/O,
communication ports and industry-standard protocols. The ION7330 meter adds on-board data storage, emails of logged
data and an optional modem. The ION7350 meter is further augmented by more sophisticated power quality analysis,
alarms and a call-back-on-alarm feature. They are compatible with PowerLogic ION EEM enterprise energy management
software, PowerLogic ION Enterprise operations software or can be integrated with other energy management or building
control systems through multiple communication channels and protocols.
PowerLogic ION7350, ION7330 and ION7300 Power and Energy Meter Features
The PowerLogic ION7300 includes:
The ION7330 adds the following features:
• Multiple form factors: transducer integrated and • Time of use - multi-year scheduling, hourly activity profiles
remote display models, GE S1 or ABB FT21 • 4 digital inputs for status monitoring and pulse counting
switchboard forms • Communications: a second RS-485 port, internal modem, DNP 3.0
• True RMS 3-phase voltage, current, and power that through serial, modem and I/R ports, EtherGate and ModemGate,
meets stringent ANSI C12.16, Class 10 data/alarms via e-mail and MV-90 on serial and Ethernet ports
• Power quality: harmonics - individual, even, odd, total • 12, one second setpoints for single, multi-condition alarms, plus math,
to the 15th, maximum 32 samples/cycle logic, trig, log, and linearization formulas
• Communications: 1 RS-485 port, 1 optional Ethernet • Non-volatile onboard memory capacity of 300kb, min/max logging,
port, 1 ANSI Type 2 infrared optical port, 1 PROFIBUS min/max logging, up to 32 channels of historical logs, timestamp
DP port (ION7300 only), onboard web server resolution to 0.001 seconds
• Supported protocols include : ION, Modbus RTU slave The ION7350 includes the following additional features:
on serial, modem, I/R ports, Modbus TCP through
• Power Quality: sag/swell, individual, even, odd, total harmonics up to
Ethernet
31st , maximum 64 samples/cycle
• Extensive standard I/O includes: 4 analog inputs,
• Up to 96 channels of logs and up to 48 cycles of waveform logs
4 analog outputs, 4 digital relay outputs
• Alarm notifications via e-mail
• Minimum/maximum recording
- -
Table 4.7: Typical PowerLogic ION7350/7330/7300 Power and Energy Ordering Configurations
Description Catalog No. $ Price
Typical PowerLogic ION7350 Power and Energy Meter Ordering Configurations
Integrated display with optical port, 5A inputs, standard power supply, standard comms, (two RS-485 ports) plus 10BaseT S7350A0B0B0E0A0A 3567.00
Ethernet
Integrated display with optical port, 5A inputs, standard power supply, standard comms, (two RS-485 ports) S7350A0B0B0A0A0A 2906.00
Typical PowerLogic ION7330 Power and Energy Meter Ordering Configurations
Integrated display with optical port, 5A inputs, standard power supply, standard comms, (two RS-485 ports) plus 10BaseT S7330A0B0B0E0A0A 2800.00
Ethernet
Integrated display with optical port, 5A inputs, standard power supply, standard comms, (two RS-485 ports) S7330A0B0B0A0A0A 2159.00
Typical PowerLogic ION7300 Power and Energy Meter Ordering Configurations
Integrated display with optical port, 5A inputs, standard power supply, standard comms, (one RS-485 port) S7300A0B0B0A0A0A 1436.00
The modular PowerLogic ION6200 is a low-cost, ultra-compact meter that offers outstanding versatility and
functionality. It is simple to use, and has a big, bright LED display. It offers four-quadrant power, demand, energy,
power factor and frequency measurements, and is available in a variety of flexible configurations. It is available as a
low-cost base model to which enhanced functionality can be added over the long term. The PowerLogic ION6200 is
ideal for customers who need revenue-accurate and/or certified measurements and want easy integration with power
distribution assemblies and building automation systems. A Megawatt version is available for applications requiring
readings in megawatts and kilovolts. It is well suited for sub-metering, energy cost tracking load profiling, and
substation panel metering and is an ideal replacement for analog meters. It can be used for stand-alone metering in
custom panels, switchboards, switchgear, gensets, motor control centers and UPS systems.
The meter consists of a base unit with options card and a power supply pack, with a remote display being optional.
PowerLogic ION6200 Power and Energy Meter Features
• Only two inches deep, and fits a standard The standard ION6200 is available with the following parameters:
ANSI four-inch switchboard cutout, or as a
Voltage L-N average and per phase, Voltage L-L average and per phase,
TRAN model with no display and can be
Current average and per phase
fastened to a flat surface with a 4” (10cm)
ANSI bolt pattern or mounted to a DIN rail. Option EP#1, includes the standard measurements and provides the
A remote display module (RMD) can be following additional parameters:
ordered for the TRAN and mounted through I4, kW/mW total, kWh/mWh total, kW/mW peak, Current demand
an ANSI 4” (10cm) and DIN 96 cutout. average and per phase, Current peak demand average and per phase,
• LED display with twelve 3/4” (19mm) high Power factor total
4
• Communications: optional RS-485 port with per phase, kWh/mWh and del/rec per phase, kVARh/mVARh total and
Modbus RTU and ION compatible del/rec per phase, kVAh/mVAh total and per phase, kW/mW demand,
• 64 samples per cycle true RMS kVAR/mVAR demand and peak, kVA/mVA demand and peak, Power
• 3-phase voltage and current inputs Factor per phase, Voltage THD per phase, Current THD per phase
CONTROL
- -
Table 4.8: Typical PowerLogic ION6200 Power and Energy Meter Ordering Configurations
Description Catalog No. $ Price
Integrated display, 10A inputs, standard 100-240 Vac power supply, RS485 port (Modbus RTU), Enhanced Package #2 S6200A0A0B0A0A0R 943.00
TRAN Model, with remote display, 10A inputs, standard 100-240 Vac power supply, RS485 port (Modbus RTU), Enhanced S6200R1A0B0A0A0R 977.00
Package #2
TRAN Model, (no display), 10A inputs, standard 100-240 Vac power supply, RS485 port (Modbus RTU), Enhanced Package #2 S6200T1A0B0A0A0R 753.00
Note: Please refer to powerlogic.com for the most complete and up-to-date list of feature availability. Some features are optional.
Table 4.11:
Description Catalog No. $ Price
Series 800 Power Meters
PM820 Power Meter with integrated display, THD, Alarming, 80kb Logging PM820 2390.00
PM850 Power Meter with integrated display, THD, Alarming, 800kb Logging, Waveform Capture PM850 3889.00
PM870 Power Meter with integrated display, THD, Alarming, 800 kb Logging, configurable Waveform Capture, Sag/Swell Detection PM870 4799.00
PM820 Meter unit only without display PM820U 2050.00
PM850 Meter unit only without display PM850U 3529.00
PM870 Meter unit only without display PM870U 4460.00
Series 800 Power Meter Accessories
PM800 Display for integrated meter unit PM8D 443.00
PM800 Module, 2 digital outputs, 2 digital inputs PM8M22 635.00
PM800 Module, 2 digital outputs (relays), 6 digital inputs PM8M26 635.00
PM800 Module, 2 digital out, 2 digital in, 2 analog out, 2 analog in PM8M2222 856.00
PM800 Mounting adapter for CM2000 PM8MA 267.00
PM8ECC Ethernet PM8ECC Ethernet Communications Card; 10/100 Base T Ethernet port and 1 RS-485 master port PM8ECC 1150.00
Communications Card
PowerLogic Series 3000 Circuit Monitor
The PowerLogic Series 3000 Circuit Monitor is designed for industrial, commercial and OEM users and is the ideal
monitoring device for electrical mains, branch feeders, as well as OEM applications, such as computer power. It
provides instant access to real time web pages without installing or learning special software.
CM3000 can serve up instantaneous readings, energy usage cost, power quality and disturbance analysis or even
customized web pages. Web-access summary data transparently from other devices connected downstream.
4
• Comes with 8Mb of standard memory allowing for more data • Built-in Trending and Forecasting functionality allows you to
logging than any other meter in its class forecast energy usage up to 4 days in advance
• 128 samples/cycle allow for zero blind metering • Custom web pages with optional Ethernet Communications
POWER MONITORING AND
Table 4.12:
Description Catalog No. $ Price
Series 3000 Circuit Monitors
Instrumentation, On-board Data Logging Waveform Capture, Disturbance Waveform Capture, Configurable I/O, 0.15% Accuracy CM3250 3944.00
Same as CM3250 plus Sag/Swell Disturbance Detection and 100 ms RMS Event Recording CM3350 5121.00
NOTE: See page 4-11 for Series 3000 Accessories
Series 3000 Power Meter
• Waveform capture with up to 512 samples/cycle • Extended waveform capture (up to 110 seconds)
• Built-in Trending and Forecasting functionality allows you to • Field installable Digital/Analog I/O cards and flexible I/O
CM4000T with VFD Display forecast energy usage up to 4 days in advance extender modules
• Sag/Swell disturbance monitoring • Harmonic powerflows up to the 40th harmonic
• Two option card slots for field installable cards • Standard KYZ pulse output
• Optional field installable Ethernet communications card with • Standard 32 MB of non-volatile memory
standard and custom web pages • Integrated power quality standards including EN50160,
• Alarm Setpoint Learning feature allowing optimum threshold setting IEC 61000-4-15 (Flicker)
(patent pending) • Sequence of events recording using GPS synchronization
• Multiple alarms including standard, digital, Boolean, high-speed, technology
and disturbance alarms • Oscillatory transient detection and recording
• Waveshape alarm monitoring • Extended range current/voltage module(CVMXR) for
• High speed transient voltage detection at 5 MHz per channel with higher inrush currents available, field installable
field installable CVMT current/voltage module • UL Listed, CSA Approved, CE Marking, NOM Approved,
PCM4000 • True RMS Metering through the 255th harmonic FCC compliant
• Also available in a rugged sealed case as a Portable Circuit Monitor
PowerLogic Satellite Time System, Circuit Monitor and SEPAM GPS Time Synchronization, 100 microsecond accuracy STS3000 5348.00
Satellite Time Reference Module STRM 2827.00
Smart Antenna Module SAM 2292.00
Smart Antenna Module Interface Cable - 200 FT SAIF200 611.00
CONTROL
PowerLogic Submetering
In today's increasingly competitive commercial property market, attracting and retaining
high-quality, long-term tenants by offering exceptional value is the primary goal. Balancing
these premium services and reliable infrastructure vs. the financial exposure to volatile
utility costs is the challenge.
Minimizing energy costs requires information on how energy usage translates into money
spent. PowerLogic energy sub-metering systems are specifically engineered to address the
measurement, verification and billing needs of multi-tenant properties.
• Residential high-rise and low-rise
• Campuses
• Shopping centers
• Malls / food courts
• Offices
• Commercial buildings
PowerLogic energy management
and metering systems are ideal
for multi-tenant buildings
providing:
• Metering & Verification tools to
assure compliance to Energy
Policy Act 2005
• Integrated approach from simple
energy allocation requirements to
high-end power quality
• Monitor energy usage and
efficiency to accurately recover
the costs while providing tenants
with energy and a reliable
infrastructure
• Implement energy efficiency
initiatives essential to obtaining
LEED certification
Table 4.16:
Description Catalog No. $ Price
PowerLogic Tenant Metering Commercial Edition Software TMSCE 5880.00
The PowerLogic E4000 series multi-circuit energy meters combine accurate electricity sub-
16 meter configuration metering with advanced communications technology. They are ideal for multi-tenant or
departmental metering applications within office towers, condominiums, apartment
buildings, shopping centers and other multi-point environments, metering up to 24
individual circuits from the same meter. The E4800 series has a system accuracy of 0.5%
for power and energy, including the metering class CTs. Each meter is available separately
or as part of a Scquare D integrated power center (IPC) for use in building retrofits or new
construction.
Table 4.19:
Description Catalog No. $ Price
4
4-14 Discount
© 2009 Schneider Electric All Rights Reserved PL1 Schedule
PowerLogic® Submetering
PowerLogic Split Core Current Transformers-Instrument Grade 5 Amp Split-Core Current Transformers
The 3090 SCCT series of split-core current transformers provide secondary amperage proportional to the primary (sensed)
current. For use with Circuit Monitors, Power Meters, data loggers, chart recorders and other instruments the 3090 SCCT
CONTROL
series provides a cost-effective means to transform electrical service amperages to a 0-5A level compatible with monitoring
equipment.
Table 4.27: Note: Max. Voltage without additional insulation 600Vac. Do
SA Split-Core Current not apply 600V Class current transformers to circuits having a
Transformers Catalog No. Description $ Price phase-to-phase voltage greater than 600V, unless adequate
3090SCCT022 Split Core CT - 200A (sz.2): 1.25" x 1.51 120.00 additional insulation is applied between the primary conductor
3090SCCT032 Split Core CT - 300A (sz.2): 1.25" x 1.51 120.00 and the current transformers. Square D assumes no
3090SCCT043 Split Core CT - 400A (sz.3): 2.45" x 2.89 129.00
3090SCCT063 Split Core CT - 600A (sz.3): 2.45" x 2.89 129.00 responsibility for damage of equipment or personal injury
3090SCCT083 Split Core CT - 800A (sz.3): 2.45" x 2.89 129.00 caused by transformers operated on circuits above their
3090SCCT084 Split Core CT - 800A (sz.4): 2.45" x 5.05 137.00 published ratings.
3090SCCT124 Split Core CT - 1200A (sz.4): 2.45" x 5.50 160.00
4
Table 4.28:
Catalog No. Description $ Price
BCPMA042D 42 circuit power and energy meter. Includes 2 CT strips, 21 CTs per strip, 3/4” CT spacing. 3569.00
BCPMB042D 42 circuit meter, measures power and energy on the mains, current per circuit. Includes 2 CT strips, 21 CTs per strip, 3/4” CT spacing. 2901.00
BCPMC042D 42 circuit current meter. Includes 2 CT strips, 21 CTs per strip, 3/4” CT spacing. 2331.00
BCPMA142D 42 circuit power and energy meter. Includes 2 CT strips, 21 CTs per strip, 1” CT spacing. 3569.00
BCPMB142D 42 circuit meter, measures power and energy on the mains, current per circuit. Includes 2 CT strips, 21 CTs per strip, 1” CT spacing. 2901.00
BCPMC142D 42 circuit current meter. Includes 2 CT strips, 21 CTs per strip, 1” CT spacing. 2331.00
BCPMA084D 84 circuit power and energy meter. Includes 4 CT strips, 21 CTs per strip, 3/4” CT spacing. 5748.00
BCPMB084D 84 circuit meter, measures power and energy on the mains, current per circuit. Includes 4 CT strips, 21 CTs per strip, 3/4” CT spacing. 4627.00
BCPMC084D 84 circuit current meter. Includes 4 CT strips, 21 CTs per strip, 3/4” CT spacing. 3495.00
BCPMA184D 84 circuit power and energy meter. Includes 4 CT strips, 21 CTs per strip, 1” CT spacing. 5748.00
BCPMB184D 84 circuit meter, measures power and energy on the mains, current per circuit. Includes 4 CT strips, 21 CTs per strip, 1” CT spacing. 4627.00
BCPMC184D 84 circuit current meter. Includes 4 CT strips, 21 CTs per strip, 1” CT spacing. 3495.00
PowerLogic Branch Current Monitor
BCM42 The Branch Current Monitor reports the current level of each of the breakers of a panelboard to provide timely circuit
loading information. In addition, as the circuit load approaches one of two user set levels, an alarm can be generated
back to the monitoring software such as PowerLogic System Manager Software. Four models of the Branch Current
Monitor are available. The BCM42 consists of rail mounted solid-core CTs intended for mounting inside new
panelboards or complete panel retrofits. The BCM42SR is designed to fit into a column width panel design. The
BCMSC model is made up of split-core CTs that are an ideal solution for retrofit applications in existing panelboards.
The BCMSC_ _ H is a 100 Amp version of the split core design.
Table 4.29:
Catalog No. Description $ Price
BCM42 Branch Circuit Monitor 42 circuits, 3/4” center line CT spacing, 10–50 Amp range, configurable 2350.00
BCM42C1 Branch Circuit Monitor 42 circuits, 1” center line CT spacing, 10–50 Amp range, configurable 2350.00
BCM42SR Branch Circuit Monitor, single row, 3/4” on center CTs 2950.00
BCM42SRC1 Branch Circuit Monitor, single row 1” on center CTs 2950.00
BCMSC12 Branch Circuit Monitor, split core, 12 CTs 1975.00
BCMSC18 Branch Circuit Monitor, split core, 18 CTs 1975.00
BCMSC24 Branch Circuit Monitor, split core, 24 CTs 2350.00
BCMSC30 Branch Circuit Monitor, split core, 30 CTs 2750.00
BCMSC42 Branch Circuit Monitor, split core, 42 CTs 3250.00
BCMSC12H Branch Circuit Monitor, 100A split core 12 CTs 2225.00
BCMSC24H Branch Circuit Monitor, 100A split core, 24 CTs 3300.00
BCMSC42H Branch Circuit Monitor, 100 split core, 42 CTs 4950.00
Note: CT hole size accommodates up to #6 THHN insulated conductor.
PowerLogic Multi-Circuit Meter
Typical BCMSC Designed for OEM style placement in electrical distribution equipment the MCM8364 is configurable to meter 1 or 3
panelboard installation phases of up to eight individual loads, six loads if neutral monitoring is required. The MCM will monitor up to 10,000
amps per service using standard 5 Amp CTs. All of the metered circuits must share a common voltage source. The
MCM8364 is a great solution for monitoring critical power distribution equipment and provides 24 different electrical
metering quantities plus an additional nine Modbus register alarms.
With one RS-485 connection, the multi-circuit meter provides Modbus RTU communications output that communicates
to each individual metered circuit. Up to 30 multi-circuit meters can be addressed on the same Modbus network. The
multi-circuit meter can provide warnings to the central monitoring computer via its Modbus output using the MNode
software provided or can be integrated into PowerLogic SMS software. The MCM also works with the submeter display
as shown below.
Electrical Data:
Energy Consumption (kWHr), Real Power (kW), Reactive Power (kVAR), Apparent Power (kVA), Power Factor Total,
Voltage, L-L, avg. of 3 phases, Voltage, L-N, avg. of 3 phases, Current, average of 3 phases, Real Power (kW) phase
A, B, & C, Power Factor, phase A, B,&C, Line to Line Voltage, phase A-B, B-C, A-C, Line to Neutral Voltage, phase
A-N, B-N, C-N, Current, phase A, B, & C, Frequency (measured from phase A) (Hz).
4
3-phase, 4-wire
(with neutral current wiring)
Modbus Alarms:
Over Voltage, Under Voltage, Over Current, Under Current, Over kVA, Under kVA, Phase Loss A, Phase Loss B,
Phase Loss C
POWER MONITORING AND
Table 4.30:
Catalog No. Description $ Price
MCM8364 Multi-Circuit Meter 8364 1863.00
PowerLogic Submeter Display
CONTROL
The PowerLogic Submeter Display (SMD) is a comprehensive electrical submetering display that provides a view of
electrical parameters from multiple metering products with one networked LCD. In addition to viewing system data on
the display itself, you can also view data on a remote PC via a network connection. Touch pad buttons provide a
convenient way to view downstream devices on the power-monitoring network. The display is RS-485 Modbus RTU
compatible. It has additional RS-485 and RS-232 Modbus ports for networking to additional displays or to a master PC.
The submeter display is compatible with the following metering devices: BCM, MCM, & Enercept® meters.
Table 4.31:
Catalog No. Description $ Price
SMD Submeter display mounted in enclosure 725.00
Submeter Display SMD OEM OEM style submeter display, no enclosure 595.00
For the utility, EPO provides an intuitive, easy-to-maintain tool for better understanding
customer usage patterns and meeting customers’ growing need for information. It also
provides a convenient platform from which to administer real-time pricing (RTP) or load
Bill estimates provide valuable information for budgeting curtailment programs. EPO's instinctive online functionality gives first-time users an
and forecasting extremely short learning curve, while its powerful configuration options address the needs
of more sophisticated users. The service is available to users at their convenience, 24/7,
and regular updates ensure that customers get the most current information.
Key features: Applications:
• Data access and analysis • Energy load analysis
• Automated reporting • Energy budgeting and bill forecasting
• Estimated bills and rate comparisons • Demand response and load curtailment
• Demand response and curtailment programs program management
• RTP programs • Real-time pricing program management
• Alarming • EPO's Real-Time Pricing module lets users
• Administration tool see interval data for accounts with future
pricing information, and multiply that data
against a price stream.
- -
Comparison statistics display For price & ordering information, contact your local PowerLogic Sales Specialist or
PowerLogic Inside Sales at 1-866-466-7627.
Advantages
• Easy to setup—No special software required. Configuration via Microsoft Internet Explorer or
Hyperterminal.
• Easy to troubleshoot—Detailed diagnostics for communication ports through a
Web interface.
• Easy to maintain—Field upgradable firmware lets you add new features while reducing costly
downtime.
• Secure-Customizable, password-protected access to configuration.
• Cost-effective, high-speed communications—Use existing LAN infrastructure to reduce
communications wiring and network management costs.
EGX100 lets the Administrator assign access to • Open platform provides broad connectivity—Modbus TCP/IP over Ethernet allows transparent
setup pages by user groups access via intranet/internet. Each gateway supports up to 32 Modbus or PowerLogic protocol
devices.
• Subnet initiated communications—The gateway supports a slave mode for connecting a serial-line
based system to Ethernet. For example, a building management system with a Modbus serial
interface can route to 16 remote Modbus TCP/IP interfaces supporting up to 128 serial-line devices.
• Extended temperature range— -25 to 70°C enables operation in harsh environments.
Table 4.32:
Built in tabs provide easy EGX100 EGX400
DIN rail mounting solution. Type $ Price
950.00 2460.00
Control Power
24Vdc control power (from external source) x x
Power Over Ethernet x
Protocols
Ethernet: HTTP, FTP, Modbus TCP/IP, SMTP, SNMP (MIB2), SNTP, TCP, UDP, ICMP, ARP x x
Serial: Modbus RTU, Modbus ASCII (EGX100 only), JBUS, PowerLogic (SY/MAX) x x
Ports
Serial: RS485 1
Serial: RS232/485 configurable 1 1
Ethernet UTP (10/100) 1 1
Fiber (100Mb) 1
Integral web server
Web page generation tool x
Maintenance/diagnostics x x
Gateway administration setup x x
Comprehensive meter reading x
Interval logging/trends 32 devices
User defined custom pages x
Historical Data Logging
Interval data x
File transfer on scheduled basis email
Export to Excel via web query x
EGX400 Ethernet Gateway offers you a “window” into your Manual FTP x
power equipment
PowerLogic WebPageGenerator
POWER MONITORING AND
gateway in this wizard-based software utility. The utility takes care of the rest. This utility is
available for download from www.powerlogic.com.
4
Square D professional engineers - safety trained and equipped - will listen to your concerns and goals, define the
problem or enhancement, and engineer the solution that best satisfies your needs.
For additional information on power system engineering services and pricing, contact your nearest
POWER MONITORING AND
long-term, comprehensive, “Energy Action Plan”, that serves as the blueprint for energy savings. Unlike performance
contracts or one-time energy audits, the Total Energy ControlSM program offers a strategic partnership for energy-
intensive industrials who want to improve energy efficiency.
• Total Energy Control – Comprehensive integration of all three areas affecting energy efficiency
— Procurement (electricity and gas)
— Demand management
— Optimization of process and plant utilities
• Program deliverables:
— Long-term Energy Action Plan
— Energy efficiency projects
— Ongoing accountability for results
Engineered Solutions
Schneider Electric provides an engineered solution approach to your specific power system
applications. Our total solutions for power monitoring and power system controls allow
greater safety, reliability, and energy efficiency of your power systems. As a long standing
industry leader in Power Monitoring and Control Systems, we understand your power
system requirements and needs.
All of our Engineered Solutions are tailored to your specific system requirements. Schneider
Electric is your total Solution provider.
Power Monitoring Applications
Increased Reliability and Energy Efficiency
Increased Reliability and Energy Efficiency are key results produced from our Power
Monitoring Applications. Schneider Electric power monitoring applications provide detailed
reporting, testing and analysis capabilities for your systems and related components.
• EPSS Emergency Power Supply Systems – The PowerLogic EPSS Test Report provides
information regarding the health and status of the emergency power supply system, including
automatic transfer switches and generators.
• SER Sequence of Events Recording – The PowerLogic Sequence of Events Recorder (SER)
Module is a root-cause analysis tool for rapid response for problem resolution that is ideal for
pinpointing the cause of a service disruption in very large complex power systems.
• WAGES Water, Air Gas, Electric, Steam – PowerLogic energy and power management systems
can provide instantaneous readings, alarm notifications, and graphical diagrams for monitoring
electrical and piped utilities (Water, Air, Gas, Electric, Steam).
• APM Active Pager Module – The PowerLogic Active Pager Module allows automatic paging to
alphanumeric pagers, cell phones and PCs.
System Integration
System Design and Engineering
Our Square D Engineering Services solution specialists can work with you to design or
upgrade your existing system to best achieve your energy and power management
objectives and informational needs. With expertise in electrical systems, communications,
and automatic control systems, we can integrate, install, and commission your system for
optimal performance.
• System Design and Bill of Material Recommendations
• Power Monitoring and Control
• WAGES (Water, Air, Gas, Electric, Steam)
• Enterprise web-based monitoring
• Specification development, drawings, documentation
• Enclosure panel design and build
• Metering Connection Verification/Testing
• Power distribution automation
PowerLogic Engineers specialize in the • On-Site Installation Assistance, Component Configuration & Startup
design and setup of Emergency Power • Turn-key project management
Supply Systems (EPSS). • Third Party Device and communication interfaces
• Configured Workstations, User Software Interfaces
• Interactive Graphic Design to mimic facility layout, one-lines, equipment status
• Custom Software, Reports & Applications – Billing and Paging
POWER MONITORING AND
For additional information, contact your nearest Square D / Schneider Electric office.
CONTROL
Service Entrance/Utility Socket Enclosure Type 3R, UL & CUL 508A Listed
• Available for ION8600 only, with up to 3 Digital Inputs and 4 Digital Outputs
• Supports Single Voltage Source only for Indoor & Outdoor (Type 3R) applications.
• Units are Ring Type with removable cover.
• Available with 1 meter per panel. Serial & Ethernet Communications options available.
• Supports Form 9S, 35S, 36S, 39S and 76S configurations.
• Options available for remote mounted CTs
• Options available for integrated, bar type CTs
• Optional Test Switch.
• Designed to fit any environment – Indoor (Type 1 & 12) & Outdoor (Type 3R & 4) applications
For additional information and pricing please contact your local PowerLogic sales
specialist or PowerLogic Inside Sales Support at 1-866-466-7627. Enclosure pricing
CONTROL
Capacitor Bank
Feeder or main
• Includes all Series 20 and Series 40 features
(Substation)
Transformer
Generator
Motor
Bus
Sepam Series 40 Relay Features
• Compact standard footprint (< 4”deep) for enhanced
Criteria Selection protection of Mains/Feeders, Transformer, Motor, Generator
Radial Applications
S23 T23 M20 G40 B80 C86
(51, 51N, 46) • Directional overcurrent protection for dual mains and ties and
Long feeders (67N) S41 M41 closed loop feeders
Network Closed loop
(67N, 67) S42 • Current and voltage inputs I, V, E, P, PF
structure
Parallel mains [transf]
• Setting software with Boolean logic equation assistance
[sources] (67N, 67) S42 T42 G82 • CT/VT and Trip Circuit supervision
Series 40 Sync-check required S82 T82 G82 B80 • Sixteen seconds of fault recording, last 5 trip reports, and last
(25)(67N, 67) 200 time-tagged alarms
Advanced Display
Solid or low/high
(A Suffix)
Grounding impedance (51N) S23 T23 M20 G40 • Rear communication port for interface to optional
system Ungrounded or communications modules
S41 T42 M41 G82
compensated (67N/NC) • Includes all Series 20 features
Basic Feeder
[Transf][Motor] S23 T23 M20 G40
Voltage/frequency S40 T40 M41 G40 B21 Sepam Series 20 Relay Features
(27/59/81)
ROCOF (81R) S84 B22 • Backlit LCD graphic bitmap display
Advanced Fdr/Main[Transf] S41 T82 M81 G82 B83
• Compact standard footprint (< 4”deep) for basic protection of
[Motor][Gen] Mains/Feeders, Transformer, Motor, Bus (Voltage)
Protection Thermal overload (49)- S81 Applications
cable
Thermal O/L
• 16 inverse time overcurrent characteristic curves
(49)- capacitor bank C86 • Setting software with offline file creation and
Differential (87T) T87 download to relay
Machine M87 G87
• Two 86 cycle records of fault recording, last trip fault values,
differential (87M) and last 64 time-tagged alarms retained
Machine-
transformer unit differential M88 G88 • Provides trip diagnostic information for analysis of faults
• Self-test diagnostic ensures correct operation of relay and
I S23 T23 M20 integrity of protection
V, f B21 • Wide range of control power inputs
Metering
I, V, f, P, E S40 T40 M41 G40 B80 • Display operation minimal training required for operation.
Series 20 I, V, V, f, P, E B83 • Application specific design for Main/Feeder, Transformer,
Advanced Display I, I, V, F, P, E T87 M87 G87 Motor, Bus (Voltage) zones
(A Suffix) THD-I, THD-V S80 T81 M81 G82 B80 • Zone selective interlocking (ZSI) improved protection
<8 RTDs of same type T23 M20 G40 coordination
Temperature > 8 RTDs (< 16) or 2 types
of RTDs T40 M41 G40 • Rear communication port for interface to optional Modbus
< 10 I / 8 O S23 T23 M20 G40 B21
communications modules, plus dual port module, optional
I/Os protocols DNP3 and IEC60870-5-103, and also fiber optics
> 10 I / 8 O and < 42 I / 23 O S80 T81 M81 G82 B80
Control matrix S23 T23 M20 G40 B21
• Modular architecture
Program logic Logic equation editor S40 T40 M41 G40 B80 • Breaker diagnostics
customization
Ladder-logic software S80 T81 M81 G82 B80 • Two groups of current protection settings (logic input
4
1 Modbus port S23 T23 M20 G40 B21 selectable) to allow reduced arc-flash hazard during
Modbus
communication 2 Modbus ports S80 T81 M81 G82 B80
maintenance operation
Note: Units in table depict least complex device types compliant with
POWER MONITORING AND
criterion.
CONTROL
Undervoltage 27/27S 2 2 2 2 2 2 2
Overvoltage 59 2 2 2 2 2 2 2 2 2
Neutral voltage displacement 59N 2 2 2 2 2 2 2 2 2
Negative sequence overvoltage 47 1 1 1 1 1 1 1
CONTROL
Overfrequency 81H 2 2 2 2 2 2 2 1 1
Underfrequency 81L 4 4 4 4 4 4 4 2 2
Rate of change of frequency 81R 1
Recloser (4 cycles) 79 e e e e
Temperature monitoring (8 or 16 RTDs)a 38/49T e e e e e e
Thermostat / Buchholzb 26/63 e e e
Note: Numerals in table indicate number of protection setpoints
a Protection functions with 2 groups of settings
b Requires MES120 I/O module
c Requires MET1482 RTD Input module
d Requires MCS025 synch check module
e Option
4
Series 80
[2] Spare by application Memory module 0 MMS020xxx Spare memory module 0.00
[3] Select from Table 4.36 (as required) Digital I/O 1 MES120 14 inputs + 6 outputs / 24-250Vdc 770.00
[4] Select from Table 4.36 (as required) Communication module 1 ACE959 RS485 4-wire Interface Module l 398.00
[5] Select from Table 4.36 (as required) RTD Input 1 MET1482 8 temperature sensor input module 695.00
CONTROL
[6] Select from Table 4.36 (as required) Analog output 0 MSA141 Analog output module (1 channel) 0.00
[7] Select from Table 4.36 (as required) Sync check (25) module 1 MCS025 Synch check module (includes cable CCA785) 1410.00
[8] Select from Table 4.36 (as required) Config S/W 1 SFT2841KIT Setting / operating software kit 543.00
[9] Select from Table 4.36 (as required) Cable for RTD I/F Modulle 1 CCA772 2m cable from remote display to base unit 51.00
4
Application Note: Capacitors are a low impedance path for the harmonic currents and voltages in the electrical network. This amplification can cause
produced by variable frequency drives, motor soft starters, welders, computers, nuisance fuse operation and/or damage to electrical equipment
PLCs, robotics and other electronic equipment. These harmonic currents can be including capacitors and other electronic devices. If power factor
drawn into the capacitor causing it to overheat, shortening its life. Furthermore, the correction in the presence of harmonics is required, please contact
resonant circuit formed by shunt capacitors coupled with system inductances your nearest Square D/Schneider Electric sales office for
(motors and transformers) can amplify harmonic currents assistance.
Table 4.41: Unfused 480V 3 phase/60 Hz Unit
Recommended copper Recommended circuit protection device
Kvar rating Regular duty Indoor NEMA 1 unit Rated Current wire sized ratinga
at 480V Catalog number $ Price Enclosurebc at 480V AWG Fuse Circuit breaker
6 PFCD4006 929.00 1 7.2 14 15 15
8.5 PFCD4008 1022.00 1 10.2 12 20 15
10 PFCD4010 1077.00 1 12 12 25 20
12.5 PFCD4012 1215.00 1 15 10 30 25
15 PFCD4015 1329.00 1 18 10 40 25
16.5 PFCD4017 1374.00 1 19.8 8 40 30
20 PFCD4020 1479.00 1 24 8 50 35
25 PFCD4025 1655.00 1 30 6 60 45
27.5 PFCD4027 1754.00 1 33 6 70 50
30 PFCD4030 1851.00 1 36 6 75 50
33 PFCD4033 1953.00 1 39.6 6 80 60
35 PFCD4035 2102.00 2 42 4 90 60
40 PFCD4040 2358.00 2 48 4 100 70
45 PFCD4045 2519.00 2 54 4 110 75
50 PFCD4050 2676.00 2 60 3 125 90
60 PFCD4060 3975.00 2 72 2 150 100
65 PFCD4065 4200.00 2 78 1 175 110
70 PFCD4070 4280.00 3 84 1 175 125
75 PFCD4075 4434.00 3 90 1/0 200 125
80 PFCD4080 4695.00 3 96 1/0 200 150
90 PFCD4090 5217.00 3 108 2/0 225 150
100 PFCD4100 5738.00 3 120 2/0 250 175
125 PFCD4125 7148.00 4 150 250 300 225
150 PFCD4150 8556.00 5 180 300 400 250
175 PFCD4175 9561.00 5 210 400 450 300
200 PFCD4200 10565.00 5 240 500 500 350
The AV4000 and AV5000 standard automatic power • Modular construction; free standing QED switchboard
factor correction banks are designed for centralized power enclosures contain up to 500 kVAR per section and allow for
factor correction to supply varying amounts of reactive easy future expansion
power required to compensate for changing load • Standard offering available up to 400 Kvar at 208/240 Vac,
conditions. The AV4000 and AV5000 banks are ideally 1000 kVAR at 480 or 600 Vac
suited for facility electrical distribution systems with TDD • Main lugs or main breaker section at your choice
(total harmonic current distortion) < = 5% and THD(V) • Dry capacitor element design eliminates risk of fluid leakage,
(total harmonic voltage distortion) < = 3%. An advanced environmental hazard and drip pans
microprocessor-based recative power controller measures • Capacitor rated contactors are designed specifically for the
plant power factor via a single remote CT. Plus, it switches switching of capacitive currents and feature a patented
capacitor modules in and out of service to maintain a user- capacitor precharge circuit that exceeds air-core reactor
selected target power factor. transient dampening
Application Assistance: • Three different microprocessor controller options provide a
The AV4000 and AV5000 are choice in functionality and control sophistication
suitable for use where The Schneider Electric Power Quality Correction Experts
harmonic generating loads provide engineering assistance for the application of • Backlit display on controller displays actual PF, alarms,
number of steps energized and much more
are less than 15% of the total capacitors in harmonic rich environments. Specialists at
connected load (AV5000 Schneider Electric can assess the likelihood of application • Rugged design — units are constructed with removable steel
problems and arrange for more detailed study if required. panels over heavy gauge steel frame
shown here).
Solutions can include computer modeling and system • Available in Type NEMA 1 indoor enclosures
simulation. Our application engineers can make all the • Indoor units are finished with ASA 49 grey textured paint
arrangements for system studies, custom engineering, finish
installation and commissioning, as required by the • For application up to 200 kVAR max., 480 V (main lugs, top
application. Contact Schneider Electric sale office for entry only), the AV4000 offers compact and cost effective
detail equipment quotation assistance. alternative.
For dimension reference, see page 4-33.
Equipment specification:
Voltage: 240, 480, 600 Vac standard, 208, 380, 415 Vac available
Kvar rating: up to 1000 Kvar (depending on voltage rating)
Ambient temperature: -5°C to 40°C
Average temperature limit: <40°C within 24 hours, <30°C over 1 year
Elevation: <=1800 meter
Humidity: 0-95% non-condensing
Overvoltage limit: 110% maximum
Dielectric withstand test level: 2.15 times rated voltage or 1000 V, whichever is higher for 10s
Overcurrent limit: 130% maximum
Incoming: Top (standard), bottom, side.
Main lug: Mechanical standard, compression optional
Main breaker: PowerPact® with Micrologic® trip unit. LI standard, LSI available
Enclosure rating: NEMA 1 standard
Color: ANSI 49 standard, ANSI 61, ANSI 70 optional
Table 4.46:
CT Selection Guide for Class 5830, 5860, 5870
4
Ratio XXXX/5
Diagram 1. The CT should be sized for the maximum load 500 0500 07 11
current. The CT should be installed upstream of the 600 0600 07 11
capicator bank and plant loads to measure the combined 750 0750 07 11
current. 800 0800 07 11
1000 1000 07 11
CONTROL
Application Assistance
The Schneider Electric Power Quality Correction Experts provide engineering assistance for the application of
capacitors in harmonic rich environments. Specialists at Schneider Electric can assess the likelihood of application
problems and arrange for more detailed study if required. Solutions can include computer modeling and system
simulation. Depending on the network, the solution may include de-tuned banks (AV6000) or fully filtered banks
(AV7000). Our application engineers can make all the arrangements for system studies, custom engineering,
installation and commissioning, as required by the application. Contact Schneider Electric sales office for detail
equipment quotation assistance.
For dimension reference, see page 4-33.
Equipment specification:
Main breaker: PowerPact® with Micrologic® trip unit. LI standard, LSI available
Enclosure rating: NEMA 1 standard
Color: ANSI 49 standard, ANSI 61, ANSI 70 optional
4
Application Assistance
The Schneider Electric Power Quality Correction Group provides engineering assistance for
the application of capacitors in harmonic rich environments. Specialists at Square D can
assess the likelihood of application problems and arrange for more detailed study if
required. Solutions can include computer modeling and system simulation. Our application
engineers can make all the arrangements for system studies, custom engineering,
installation and commissioning, as required by the application. Contact Schneider Electric
sales office for detail equipment quotation assistance.
TOP VIEW
44.28
REMOVABLE
LIFTING
LUGS 36 MIN. CLEARANCE
AIR
FLOW
62.42
23.50 21.43
TOP VIEW
60.00 60.00
SUPPLIED BUT
FIELD FITTED SUPPLIED BUT
CABLE ENTRY 36. MIN. CLEARANCE 36. MIN. CLEARANCE
FIELD FITTED
BOX C/W CABLE ENTRY
REMOVABLE BOX C/W
CABLE ENTRY REMOVABLE
PLATE QTY (1) CABLE ENTRY
PLATE QTY (1)
18.00 REMOVABLE 18.00 REMOVABLE
LIFTING LUGS LIFTING LUGS
AIR FLOW
AIR
FLOW
93.50
91.50 91.50
CONTROL
66.26
Features:
• Fused and unfused applications
• Standard rating up to 600 kVAR, 4800 V (for specials, consult factory)
• Metallized polypropylene film capacitors for low dielectric loss
• Internally mounted discharge resistors
• Operating temperature range of –25°C to +45°C
• Built to applicable NEMA, IEEE, and IEC standards
• Available in indoor (Type 1/12) and outdoor (Type 3R) enclosures
• Painted ASA 61 gray
MVC systems are suitable for Lead time: 12–14 weeks typical (consult factory for committed delivery)
power factor correction of steady
harmonic-free motor loads. Prices & assistance: Call PQc Group at (905) 678-6699 or email
[email protected]
Features:
• Standard metal enclosures available up to 20,000 kVAR, 5/15 kV, 50/60 Hz
• The Square D HVL load interrupter switch (fused or unfused)
• Externally fused Merlin Gerin PROPIVAR (or equivalent) or Cooper capacitors with excellent life due
to high temperature withstand, small temperature rise, chemical stability, overvoltage and
overcurrent withstand. (Internally fused capacitor available upon request)
• Three-bushing capacitor cells connected in delta available up to 5 kV. Two-bushing capacitor cells
connected in ungrounded wye for higher voltages
• Current limiting capacitor fuses with blown fuse pop-up indicators
• current limiting reactors in multistage-step MV5000 standard systems to limit high capacitor inrush
MV5000 systems are suitable for use where currents
harmonic generating loads are less than 15% of • Iron core reactors in MV6000 de-tune banks to prevent parallel resonance
the total connected load. • Heavy-duty iron core reactors in MV7000 filtered banks for effective 5th harmonic filtering.
MV6000 systems are suitable for use where • Available in Type 1 indoor and 3R outdoor enclosure types
harmonic generating loads are less than 50% of • Key interlocking system forces sequential operation of the controls, non-load break switch (or circuit
the total connected load. breaker) and ground switches
MV7000 systems are suitable for use where • Superior Square D Varlogic™ microprocessor based power factor controller
harmonic generating loads exceed 50% of the • The Merlin Gerin SEPAM protective relaying.
total connected load.
Lead time: 16–20 weeks typical (consult factory for committed delivery)
MVHVC High-Speed compensation systems are
designed for compensation of rapidly Prices & assistance: Call PQc Group at (905) 678-6699 or email
fluctuating loads [email protected]
4
POWER MONITORING AND
CONTROL
The problem:
High levels of harmonics generated by non-linear loads can have significant negative
impact in the facility electrical system. It can cause malfunction of the equipment, disrupt
plant operation, thus, resulting in loss of productivity.
Harmonic filtering:
The AccuSine Power Correction System (PCS) is an Active Harmonic Filter (AHF) that
actively injects opposite harmonics current on the source side of the load and it:
• Decreases harmonic related overheating of cables, switchgear and transformers
• Reduces downtime caused by nuisance thermal tripping of protective devices
• Increases electrical network reliability and reduces operating costs
• Corrects to the 50th harmonic, reduce harmonics level to meet IEEE 519, IEC 61000 3-4, and
UK G5/4-1 standards.
• Compensates entire network or specific loads depending on installation point