td2014p 000736 PDF
td2014p 000736 PDF
Transformer Condition
Failure Rate
0 10 20 time / a
Classical 5a
Diagnostics
Temporary
3a
Monitoring
Permanent
Monitoring
without
A layers
Emax= low
with layers
A
Failure Mechanisms and Diagnostics
• Voids, cracks
– Partial discharges
– Capacitance
• Ageing by-products, moisture
– Dissipation factor / power factor
Im
CR CX, IR IX
IR IX
u0(t)
d
UR(t) Z1 Z2 UX(t)
j
Uo
L1
L3 L2
from 2011-02-13 to 2011-02-15
Systematic error
0.65 %
plus instrument
inaccuracy 0.5 %
Capacitance?
DF impossible!
1,0
Systematic error
0,8
DF (%)
0,6
0,4 typ: 0,35
typ: 0,25
0,2 RIP
OIP
0,0
[P. Picher “Integration of New Transformer Monitoring Technologies ...”
TechCon Asia-Pazific 2011]
•PAGE 12
Connection Diagram VT Reference
UVT+ IB
90°
Bushing
VT
Comparison to accurate
off-line tests:
DF 2.701 E-3
C (pF) 467.1
C/DF Measurement over 1.75 Years
1,0
0,8 0.7 % IEC Warning
DF (%)
0,6
0,4 typ: 0,25 0,27 +/- 0,05 %
0,2 RIP Measurement
OIP
0,0
500
Capacitance (pF)
478 pF Warning
467 +/- 2 pF
Measurement
400
DF Temperature Correction
Reasons
• Failures of design or during manufacturing process
• Aging of equipment
– Electrical stress
– Thermal stress
– Mechanical stress
Effects of PDs:
• Heating
• Creeping destruction of the insulation material
• Treeing, chain reaction
• Insulation breakdown, short circuit
Treeing in polyethylene
PD Activity
over 4 Days
10
L1
Q in nC
L2
1 L3
0.1
0.01
00:00:00 01:00:00 02:00:00 03:00:00 04:00:00 05:00:00
t in dd:hh:min
Fighting PD Noise: UHF Gating
Corona
Electr. PD
Internal
PD
UHF PD
EM Field
Combination of the Methods
IEC
UHF
IEC PD Measurement
& UHF PD Measurement
3 Internal
2 PD
EM Field
3PARD and Back Transformation
3FREQ: PD Discrimination by Spectrum
Corona
A
0.5M
0.5M 2M 8M f
MPD1
8M Internal
2M PD
EM Field
PD Risk Assessment
-200
0 40 80 17 24
t in ms t in ms
200
Voltage in kV
-200
0 50 t in ms 100 15 t in ms 29
Case Study: Combined Generator and
Transformer Monitoring
Generator GSU
900 MW 1100 MVA Transmission line Substation Grid
21 kV 400 kV 400 kV
6 km
UMTS
Voltag Transformers
OMS843
Generator - C/DF
(Reference)
PDM600
OMS843 OMS843
- PD - PD
- Transients - Transients
- C/DF - C/DF
ca. 10 m
Transformer 1 Transformer 2
0,6% OMS843
Generator
DF / %
- C/DF
(Reference)
0,4%
PDM600
0,2%
10
QIEC in nC
0,0%
1 11-20-2012 11-25-2012 11-30-2012
0.1
OMS843 OMS843
- PD - PD
0.01 - -60
Transients - Transients
0 10 t in ms 20 - C/DF - C/DF
P in dBm
ca. 10 m
100
Transformer 1 Transformer 2
1
U in µV
UHF620 + UVS
-100 UHF620 + UVS
-120
0.9
35
0.8
IEC60137 max: 0,7 % 30
0.7
dissipation factor in %
temperature in C°
25
0.6
0.5 20
0.4
15
U-phase
0.3 W-phase
10
0.2
V-phase
5
0.1
0 0
0 5 10 15
time / days
Transient Over-Voltages
C Phase BAT20
> Oszillation frequency 10 kHz, 400
Voltage in kV
> Several times a day
Generator GSU
0
900 MW 1100 MVA Transmission line Substation Grid B Phase
21 kV 400 kV 400 kV
6 km
-200 A Phase
G
-400
0 6 12 t in ms 18
BAT10 BAT10
400
Voltage in kV
200
-200
-400
0 6 12 0 6 12 t in ms 18
t in ms
Agenda
Thomas Prevost