7-5-2. Operation from the indoor remote controller is not accepted,
and a check code is displayed on the 7-segment display of the
interface PC board of the header unit.
Indoor remote Header unit
controller 7-segment Cause Countermeasures
status display
Line addresses and indoor addresses of all the connected Set up addresses.
L08 indoor units are not set.
There is no header unit of group control. Set up a group address.
Indoor unit power is not turned on. Turn on the power again. (In the order:
indoor outdoor)
Indoor/outdoor communication line is not correctly connected Correct wiring
to the U1/U2 terminal of the header unit ( Fig. 1). (Indoor/
E19 -00 outdoor cannot communicate before address setup.)
Alternate
blinking There is no of outdoor terminator resistor, or there ON Check SW30 bit 2 of the header unit.
are two or more resistances (before address setup). 1 2 No connection between multiple refrigerant
lines: SW30 bit 2 is on.
No response
SW30 Connection between multiple refrigerant
lines: SW30 bit 2 of the connected header
unit is turned on only for one line.
When connecting an indoor/outdoor communication line Correct wiring
E19 -02 between outdoor units under the condition of a connected
Alternate communication line between outdoor units ( Fig. 2).
blinking
SW08 setup trouble T u r n a l l SW 0 8 s w i tch es t o “ of f. ”
Address setup is performed with connecting an indoor/ Correct wiring
E20 -01 outdoor communication line between outdoor units ( Fig. 3).
Alternate
blinking Address setup is performed under the condition of Correct wiring
connecting multiple refrigerant lines ( Fig. 3).
- 102 -
7-5-4. In checking the number of connected outdoor units and
connected indoor units after address setup, a lower number of
connected units is displayed. (There are outdoor/indoor units
that do not operate in a test operation.)
Status Cause Countermeasures
The number of Miswiring of communication lines between outdoor units After improvement of wiring, set up the addresses again
connected or an unconnected wire ( Fig. 4). (Address setup and check the number of connected outdoor units.
outdoor units is operation finished without recognizing a miswired
too few. follower unit.)
Miswiring of communication lines between indoor units After modification of wiring, set up the addresses again and
The number of or an unconnected wire ( Fig. 5). (Address setup check the number of connected indoor units.
connected indoor
units is too few. operation finished without recognizing a miswired indoor
unit.)
The indoor remote controller is not connected with wire. Using the main indoor remote controller connected to a group,
Miswiring of the indoor remote controller start a test operation, specify the unit that is not operating (the
The number of unit not connected to the group), and then check the wiring.
indoor units
connected to a Indoor remote controller communication circuit trouble Using the main indoor remote controller connected to a group,
group is too few in If 220-240 V is incorrectly applied to the remote controller start a test operation and then specify the unit that is not
group operation terminal, the remote controller communication circuit operating (the unit not connected to the group). Remove the
from an indoor
remote controller. fails. quick connect terminal connected to remote controller
terminals A/B, and check the voltage. If voltage is not applied
(normally 15 to18 V), replace the PC board.
- 103 -
Miswiring example
Remote Header unit
Figure controller 7-segment Miswiring example
status display
U3 U4 U5 U6
No
Fig. 1 E19-00
response
U1 U2 U1 U2 U1 U2 U1 U2
U1 U2 U5 U6 U1 U2 U5 U6
No
Fig. 2 E19-02
response
U1 U2 U1 U2
Header unit Follower unit Header unit Follower unit Header unit Follower unit
[Line 1] [Line 2]
U1 U2 U1 U2 U1 U2 U5 U6 U1 U2 U1 U2
No
Fig. 3 E20-01
response
U1 U2 U1 U2 U1 U2 U1 U2 U1U2 U1 U2
U1 U2 U3 U4 U1 U2 U3 U4 U1 U2 U5 U6
Fig. 4
U1 U2 U1 U2
or or
U3 U4 U3 U4
or
U1 U2 U1 U2 U1 U2 U1 U2 U1 U2 U1 U2
U5 U6
U1 U2 U1 U2
Fig. 5
Wiring forgotten
U1 U2 A B U1 U2 U1 U2
- 104 -
7-6. Test Operation Check
7-6-1. Fan Check
START
Check code
appears
Push the Start/Stop button on the remote controller. When a check code has been
displayed on the remote
controller, remove the cause
of the trouble, referring to
Check code "Check code and check
appears position displayed on remote
Select the " Fan" operating mode. controller and outdoor unit."
Is air discharged from the discharge port of NO Check the indoor fan, fan
the indoor unit? motor, and fan circuit.
YES
YES
Normal
- 105 -
7-6-2. Cooling Test Operation Check
The cooling test operation check can be performed on both the indoor remote controller and the
outdoor header unit interface PC board.
(1) Test operation start/stop operation
Test operation from the indoor remote controller
• Wired remote controller: Refer to the items below in “Test operation” of the wired remote controller.
• Wireless remote controller: Refer to the items below in “Test operation” of the wireless remote controller.
• Lite-Vision plus remote controller : Refer to the installation manual of RBC-AMS51E
Wired remote controller Wireless remote controller (Except the 4-
way Cassette type and the Ceiling type)
Procedure Operation content
When the Test button is pushed for 4 seconds or Test run (Forced cooling operation)
more, “TEST” is displayed in the display section,
and the unit enters test operating mode. Requirement:
• Finish the forced cooling operation in a short
1 time because it applies excessive strength to the
air conditioner.
How to perform forced cooling operation
1. When TEMPORARY button is pushed for 10
seconds or more, “Pi!” sound is heard and the
2 Push the button. operation changes to a forced cooling operation.
After approx. 3 minutes, a cooling operation starts
Using the Select Mode button, select the
“ COOL” operating mode. forcedly.
• Do not use an operating mode other than Check cool air starts blowing. If the operation does
“ COOL” not start, check wiring again.
• Temperature adjustment is unavailable during
test operation.
2. To stop a test operation, push TEMPORARY
3 • Check code is detected as usual. button once again (Approx. 1 second).
• Check wiring / piping of the indoor and outdoor
units after forced cooling operation.
2, 4
3
1, 5
- 106 -
Wireless remote controller Wireless remote controller
(4-way Cassette type) (Ceiling type)
Test run (Forced cooling operation) Test run (Forced cooling operation)
Requirement: Requirement:
• Finish the forced cooling operation in a short • Finish the forced cooling operation in a short
time because it applies excessive strength to the time because it applies excessive strength to the
air conditioner. air conditioner.
How to perform forced cooling operation How to perform forced cooling operation
1. When TEMPORARY button is pushed for 10 1. When TEMPORARY button is pushed for 10
seconds or more, “Pi!” sound is heard and the seconds or more, “Pi!” sound is heard and the
operation changes to a forced cooling operation. operation changes to a forced cooling operation.
After approx. 3 minutes, a cooling operation starts After approx. 3 minutes, a cooling operation starts
forcedly. forcedly.
Check cool air starts blowing. If the operation does Check cool air starts blowing. If the operation does
not start, check wiring again. not start, check wiring again.
2. To stop a test operation, push TEMPORARY 2. To stop a test operation, push TEMPORARY
button once again (Approx. 1 second). button once again (Approx. 1 second).
• Check wiring / piping of the indoor and outdoor • Check wiring / piping of the indoor and outdoor
units in forced cooling operation. units in forced cooling operation.
TEMPORARY button
TEMPORARY
button
- 107 -
(2) Test operation
START
Test operation for every indoor unit in turn
NO
Is air circulation sufficient? Check the direction of the louver.
YES
Note 1
Is there adequate temperature difference NO
between suction and discharge?
YES
Note 2
NO • Check the temperature load of the
Is the operating current normal?
indoor/outdoor units.
• Check the pipe length and refrigerant
YES amount.
Note 3
NO • Check the operating Hz of the
Is the operating pressure normal? compressor.
• Check the operation of the outdoor
fans.
• Check for abnormal sound in the
outdoor unit.
(Abnormal sound, etc. of the
YES compressor and other components)
Normal
Notes 1-3 are on the next page.
- 108 -
7-7. Service Support Function
7-7-1. Check Function for Connecting of Refrigerant and Control Lines
This function is provided to check misconnection of the refrigerant pipes and the control transmission line (Wiring
over lines) between indoor unit and outdoor unit by using the switch on the interface P.C. board of the header unit.
However, be sure to check the following items prior to executing this check function.
1 This check function does not work when a group operation by remote controller is performed and
it is used over outdoor units.
2 When using this check system, be sure to check for each 1 line in the unit of outdoor unit. If
checking the multiple lines at the same time, misjudgment may be caused.
(Check procedure)
Check No. of indoor units/No. of units with cooling thermostat (7-segment display)
ON
[A] [B]
Set the rotary switches SW01/SW02/SW03 on the interface
P.C. board of the header unit to [1/4/3]. Then No. of indoor [ .] [C ]
units connected to the system is displayed on 7-segment
display [A]. Check that this display surely matches with the No. of No. of units
expected No. of indoor units. connected with cooling
outdoor thermostat ON
units
- 109 -
Note 1: Criteria for the difference between suction and discharge temperatures
(1) Cooling operation
After operating for a minimum of 30 minutes in “COOL” mode, if the T dry bulb temperature difference between
suction and discharge air of the indoor unit is 8°C or more, it is normal.
* This compressor is driven with a 4-pole motor. The value of the compressor frequency (rps) measured with a clamp meter at the compressor
lead line is two times the rotation count (rps) of the compressor.
* Each compressor may have a different frequency as a measure against resonance.
* The temperature of the indoor heat exchanger (TC) indicates TCJ sensor temperature when cooling.
- 110 -
(3) On rotations of outdoor fans
Outdoor fans may rotate slowly to control pressure when cooling with low outer air temperature. For control
content, also refer to items in Section 5, “Control Outline: Outdoor Unit, Outdoor Fan Control.”
SW04 SW05
- 111 -
7-7-2. Function to Start/Stop (ON/OFF) Indoor Unit from Outdoor Unit
The following functions of the indoor unit can start or stop by the switches on the interface P.C. board of the header unit.
No Function Outline Setup/Release 7-segment display
Cooling test Changes the mode of all the [Setup] Section A Section B
operation connected indoor units collectively Set SW01/SW02/SW03 to [2/5/1], and [C. ] [ – C]
to cooling test operation. press SW04 for 2 seconds or more.
1 Note) [Release]
Control operation same as usual Return SW01/SW02/SW03 to [1/1/1].
test operation from remote
control is performed.
2 Fan test Changes operation mode of all the [Setup] Section A Section B
operation connected indoor units collectively Set SW01/SW02/SW03 to [2/9/1], and [F. ] [ – F]
to test operation mode. push SW04 for 2 seconds or more.
Note) Control operation same as [Release]
usual test operation from remote Return SW01/SW02/SW03 to [1/1/1].
control is performed.
Batch start Starts all the connected indoor [Setup] Section A Section B
units collectively. Set SW01/SW02/SW03 to [2/7/1], and [C.H] [ 11]
Note) press SW04 for 2 seconds or more.
[ 00] is displayed on Section B for 5
The contents follow to the setup [Release]
seconds.
of remote controller. Return SW01/SW02/SW03 to [1].
3
Batch stop Stops all the connected indoor [Setup] Section A Section B
units collectively. Set SW01/SW02/SW03 to [2/7/1], and [C.H] [ 00]
press SW05 for 2 seconds or more.
[ 00] is displayed on Section B for 5
[Release]
seconds.
Return SW01/SW02/SW03 to [1].
Individual Starts the specified indoor unit. [Setup] Section A Section B
start Notes) Set SW01 to [16], set SW02 and SW03 [ ] [ ]
• The contents follow to the to address No. (1 to 64) to be started,
Section A: Displays the
setup of remote controller. and press SW04 for 2 seconds or more.
corresponding indoor address.
• The other indoor units keep [Release]
Section B: Displays [ 11] for 5
the status as they are. Return SW01/SW02/SW03 to [1/1/1].
seconds from operation-ON.
Individual Stops the specified indoor unit. [Setup] Section A Section B
stop Note) Set SW01 to [16], set SW02 and SW03 [ ] [ ]
The other indoor units keep the to address No. (1 to 64) to be stopped,
4 status as they are. and press SW05 for 2 seconds or more.
Section A: Displays the
corresponding indoor address.
[Release]
Section B: Displays [ 00] for 5
Return SW01/SW02/SW03 to [1/1/1].
seconds from operation-OFF.
Individual Operates the specified indoor unit. [Setup] Section A Section B
test Note) Set SW01 to [16], set SW02 and SW03 [ ] [ ]
operation The other indoor units keep the to address No. to be operated, and
Section A: Displays the
status as they are. press SW04 for 10 seconds or more.
corresponding indoor address.
[Release]
Section B: Displays [ FF] for 5
Return SW01/SW02/SW03 to [1/1/1].
seconds from test operation-ON.
NOTE 1) This start/stop function only sends the signals from the outdoor unit to the indoor unit, such as start, stop,
operation mode, etc. It does not resend the signals even if the indoor unit does not follow the sent signals.
NOTE 2) The above controls are not used during abnormal stop.
SW04 SW05
- 112 -
(1) Cooling test operation function
This function is provided to change collectively the mode of all the indoor units connected to the same system for
the cooling test operation mode, by using switches on the interface board of the header unit.
<Operation procedure>
SW04 SW05
- 113 -
(2) Fan test operation function
This function is provided to change collectively the mode of all the indoor units connected to the same
system for the fan test operation mode by using switches on the interface P.C. board of the header unit.
<Operation procedure>
Power ON Be sure to turn on power of the indoor unit
and then turn on power supplies at outdoor unit side.
Push the push switch SW4 for 2 seconds or more on the P.C. board. Operation
SW04 SW05
NOTE) The test operation ends after 60 minutes and the operation returns to normal status.
- 114 -
(3) Batch start/stop (ON/OFF) function
This function is provided to start/stop collectively all the indoor units connected to the same system by using
switches on the interface board of the header unit.
<Operation procedure>
0
Set up the operation mode of the remote controller. The unit which is not given with priority by cooling
(If it is not set up, the operation continues with the current mode.) priority control and selection of cooling mode is not
(FAN/COOL) operated.
In this case, " operation ready" or " operation
mode controlled" is displayed on the remote controller.
SW04 SW05
- 115 -
(4) Individual start/stop (ON/OFF) individual test operation function
This function is provided to start/stop (ON/OFF) individually each indoor unit connected to the same system by
using switches on the interface board of the header unit.
Set SW01 [16] and set SW02, SW03 to indoor address No. (1 to 64) to be started (Refer to the following table*) -
only the setup indoor unit starts operation.
(In the rotary switches of the indoor unit which operates in a group by the remote controller, the follower unit cannot
be individually started or stopped. In this case, [ - - ] is displayed on 7-segment display [B] on the interface P.C.
board of the header unit.)
<Operation procedure>
0
Press the push-switch SW04 on the same board for 2 (7-segment display)
seconds or more. [A] [B]
(If pressed continuously for 10 seconds or more, the [ ] [ ] Start
operation changes to the individual test operation.)
Address display [ 11] is displayed for 5 seconds after operation-ON.
of corresponding (For individual test operation, [ FF] is displayed.)
indoor unit
*
Press the push-switch SW05 (7-segment display) SW01 SW02 SW03 Units to be operated
on the interface P.C. board of [A] [B] Address 1 to
the header unit for 2 seconds [ ] [ ] 16 1~16 1 Address 16 } In individual
or more. individually start/stop
Address display [ 00] is displayed
of corresponding for 5 seconds after Address 17 to
indoor unit operation-ON. 16 1~16 2 Address 32 }
individually
Address 33 to
16 1~16 3 Address 48 }
After test operation, return the display select switches individually
SW01/SW02/SW03 on the interface P.C. board of the End
Address 49 to
header unit to [1/1/1].
16 1~16 4 Address 64 }
individually
NOTE) The individual test operation returns to the normal operation after 60 minutes.
- 116 -
7-7-3. Check code Clearing Function
(1)Clearing from the main remote controller
Check code clearing in outdoor unit
Check code of the outdoor unit currently detected is cleared by the unit of one refrigerant circuit system to which
the indoor units operated by the remote controller is connected. (Check code of the indoor unit is not cleared.)
For clearing check codes, the service monitor function of the remote controller is used.
<Method>
1 Change the mode to service monitor mode by pushing + buttons simultaneously for 4
seconds or more.
2 Using buttons, set CODE No. to “FF”.
3 The display in Section A in the following figure is counted with interval of 5 seconds as
“0005” --> “0004” --> “0003” --> “0002” --> “0001” --> “0000”.
When the count arrives “0000”, the check code is cleared.
*However, counting from “0005” is repeated on the display.
4 When button is pushed, the status returns to the normal status.
3 Section A
TEMP. ON / OFF
FILTER
RESET TEST SET CL SWING/FIX UNIT LOUVER
4 1
Check code clearing in indoor unit
Check code in the indoor unit is cleared by button on the remote controller.
(Only check code of the indoor unit connected with operating remote controller is cleared.)
- 117 -
(2)Clearing check code by using switches on the interface board of the header unit
Using the switches on the interface P.C. board of the header unit, this function is to clear the currently
detected check code for each refrigerant circuit system without resetting the power supply.
Check codes in both outdoor and indoor units are once cleared, and check code detection is performed again.
Set the rotary switches on the interface P.C. board of 7-segment display
the header unit as follows. [A] [B]
Set SW01/SW02/SW03 to [2/16/1] [ E r ][ ]
SW04 SW05
NOTE) After power reset, it requires usually 3 minutes to power-on due to the initial communication of the
system. In some cases, it requires max. 10 minutes.
- 118 -
7-7-4. Remote Controller Distinction Function
This function is provided to distinguish the remote controller connected to the indoor unit from the outdoor unit for
a refrigerant circuit system by using switches on the interface P.C. board of the header unit.
<Distinction procedure>
SW04 SW05
- 119 -
7-7-5. Pulse Motor Valve (PMV) Forced Open/Close Function in Indoor
Unit
This function is provided to open or close forcedly PMV for 2 minutes in all the indoor units by the switch operation
on the interface P.C. board of the header unit.
This function is also used to open PMV fully when turning off the power and executing an operation.
<Operation>
[Open fully]
Set the switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [2/3/1], and press SW04 for
2 seconds or more.
(Display appears on 7-segment display for 2 minutes as follows.) [P ] [ FF]
[Close fully]
Set the switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [2/3/1], and press SW05 for
2 seconds or more.
(Display appears on 7-segment display for one minute as follows.) [P ] [ 00]
[Clear]
After 2 minutes (1 minutes for “Close fully”) after setting up, the opening automatically returns to the normal
opening.
[Clear]
For both open fully and close fully, after 2 minutes, the opening returns to the normal opening.
Be sure to remove the cord used for short-circuit after confirmation, and set the DIP switch [SW12·bit1] to
[OFF] and [SW12·bit2] to [OFF].
- 120 -
7-7-7. Solenoid Valve Forced Open/Close Function in Outdoor Unit
This function is provided to forcedly open each solenoid valve mounted in the outdoor unit by the switch operation
on the interface P.C. board in the outdoor unit. Use this function to check there is no refrigerant clogging with ON/
OFF operation of the solenoid valve.
[Operation]
(1) Set the switches SW01/SW02/SW03 on the interface P.C. board of the outdoor unit to [2/1/3].
(2) When [H. r] is displayed in 7-segment display [A], keep pressing the switch SW04 for 2 seconds or more.
(3) From when [ 2 ] is displayed in 7-segment display [B], SV2 is turned on.
(4) After then, ON and OFF of each solenoid valve are exchanged by changing the setup number of the switch
SW02.
(ON/OFF output pattern of each solenoid valve is as shown below.)
NOTE 1) Display in 7-segment display [B] is exchanged just when the number of SW02 has been changed; on the
other hand, the solenoid valve output is exchanged when SW02 has been kept with the same number for
5 seconds or more.
NOTE 2) The mark [O] in the table indicates that the corresponding solenoid valve is forcedly turned on.
NOTE 3) The mark [-] in the table indicates that ON/OFF of the solenoid valve is controlled based upon the
specifications of the air conditioner.
NOTE 4) The mark [×] in the table indicates that the corresponding solenoid valve is forcedly turned off with this
operation.
[Clear]
Return switches SW01/SW02/SW03 on the interface P.C. board to [1/1/1].
NOTE) As this function is not based on the specified general control, be sure to release this mode after checking.
- 121 -
7-7-8. Fan Operation Check in Outdoor Unit
This function is provided to check the fan operation of the outdoor unit by using switches on the interface P.C. board
in the outdoor unit. The frequency of the fan speed can be controlled by setting of the switches. Use this function
to check the operation or abnormal sound in the fan system. And, use this function while the system is stopped.
NOTE) Do not use this function during operation of the compressor. It may damage the compressor.
Two fans move synchronously in two fan model (MMY-MAP2207* and MAP2407*).
[Operation]
(1) Set the switches SW01/SW02/SW03 on the interface P.C. board of the outdoor unit to [2/1/4].
(2) When [F. d] is displayed in 7-segment display [A], keep pressing the switch SW04 for 2 seconds or more.
(3) When [ 63 ] is displayed in 7-segment display [B], the fan starts operation. (Max. mode operation)
(4) After that, by changing the setup number of the switches SW02 and SW03, 7-segment display [B] and the fan
mode are changed.
(Mode output pattern of the fan is as follows.)
SW02 SW03 7-segment display [B] Fan mode SW02 SW03 7-segment display [B] Fan mode
1 [ 63 ] 63 1 [ 31 ] 31
2 [ 62 ] 62 2 [ 30 ] 30
3 [ 61 ] 61 3 [ 29 ] 29
4 [ 60 ] 60 4 [ 28 ] 28
5 [ 59 ] 59 5 [ 27 ] 27
6 [ 58 ] 58 6 [ 26 ] 26
7 [ 57 ] 57 7 [ 25 ] 25
8 [ 56 ] 56 8 [ 24 ] 24
4 6
9 [ 55 ] 55 9 [ 23 ] 23
10 [ 54 ] 54 10 [ 22 ] 22
11 [ 53 ] 53 11 [ 21 ] 21
12 [ 52 ] 52 12 [ 20 ] 20
13 [ 51 ] 51 13 [ 19 ] 19
14 [ 50 ] 50 14 [ 18 ] 18
15 [ 49 ] 49 15 [ 17 ] 17
16 [ 48 ] 48 16 [ 16 ] 16
1 [ 47 ] 47 1 [ 15 ] 15
2 [ 46 ] 46 2 [ 14 ] 14
3 [ 45 ] 45 3 [ 13 ] 13
4 [ 44 ] 44 4 [ 12 ] 12
5 [ 43 ] 43 5 [ 11 ] 11
6 [ 42 ] 42 6 [ 10 ] 10
7 [ 41 ] 41 7 [ 9] 9
8 [ 40 ] 40 8 [ 8] 8
5 7
9 [ 39 ] 39 9 [ 7] 7
10 [ 38 ] 38 10 [ 6] 6
11 [ 37 ] 37 11 [ 5] 5
12 [ 36 ] 36 12 [ 4] 4
13 [ 35 ] 35 13 [ 3] 3
14 [ 34 ] 34 14 [ 2] 2
15 [ 33 ] 33 15 [ 1] 1
16 [ 32 ] 32 16 [ 0] 0
[Clear]
This function is cleared by one of the following operations.
(1) When SW01 setting number was changed to other number.
(2) Press-switch SW05 was pressed for 2 seconds or more.
- 122 -
7-7-9. Abnormal Outdoor Unit Discrimination Method By Fan
Operating Function
This function is provided to forcedly operate the fan of the outdoor unit in which a check code occurred or the
fan of the normal outdoor unit by the switch operation on the interface P.C. board in the header unit.
To specify which one of the follower units connected to the system had problem, use this function for the system
stop due to a follower unit problem (Check code [E28]).
[Operation]
<In case to operate the fan in the erroneous outdoor unit only>
(1) Check that the switches SW01/SW02/SW03 on the interface P.C. board in the header unit are set to [1/1/1].
7-segment display
[A] [B]
<In case to operate the fans in all the normal outdoor units>
(1) Check that the switches SW01/SW02/SW03 on the interface P.C. board in the header unit are set to [1/1/1].
(2) Press the push-switches SW04 and SW05 at the same time for 2 seconds or more.
(3) [E 0] is displayed on 7-segment display [A].
(4) The fans of all the normal outdoor units start operation with the Max. fan speed within approx. 10 seconds after
[E 0] was displayed.
[Release]
Press the push-switch SW05 on the interface P.C. board in the header unit for 2 seconds or more.
The outdoor fan which was operated stops.
* Check that [U. 1] is displayed on 7-segment display [A], and then finish the work.
- 123 -
7-7-10. Manual Adjustment Function of Outside Temperature (TO)
Sensor
This function is provided to fix TO sensor value manually by the switch operation on the interface P.C. board in the
outdoor unit. When the unit stops abnormally due to TO sensor failure, etc, an emergent operation is available by
setting up the value manually to position near the current outside temperature.
[Operation]
(1) Set the rotary switches on the interface P.C. board to numbers as follows:
• SW01/SW02/SW03 to [2/1/15]
• 7-segment display: [ t o ]
(2) Keep pressing the push-switch SW04 on the interface P.C. board for 1 second or more. The mode changes to
the TO sensor value fix manual mode.
(3) As shown in the following table, TO sensor value can be fixed by setting the rotary switch SW02 on the interface
P.C. board.
[Clear]
Return SW01/SW02/SW03 on the interface P.C. board in the outdoor unit to [1/1/1].
SW02 7-segment display [B] TO sensor value
1 [ 10 ] 10°C
2 [ 15 ] 15°C
3 [ 20 ] 20°C
4 [ 25 ] 25°C
5 [ 30 ] 30°C
6 [ 35 ] 35°C
7 [ 40 ] 40°C
8 [ 43 ] 43°C
9 [ 45 ] 45°C
10 [ –15 ] -15°C
11 [ –10 ] -10°C
12 [– 5] -5°C
13 [ 0] 0°C
14 [ 2] 2°C
15 [ 5] 5°C
16 [ 7] 7°C
NOTE) If operated with TO sensor fixed by this function, the system control operation of the air conditioner may
not be based on the specification of the product. Therefore an emergent operation should be restricted
to a day or so.
When the outside temperature is 45ºC or more, set to 45ºC (SW02="9")
- 124 -
<Service support function list>
SW01 SW02 SW03 7-segment display [A] Function contents
Refrigerant circuit and control communication line check function (Cooling
1 [J . C]
operation)
3 [P . ] Indoor PMV forced full open function
5HIULJHUDQWoverchargeGHWHFWLRQ
The refrigerant overcharge can be confirmed by using the switches on lnterface PCB of the outdoor unit.
If refrigerant overcharge detection worked, first check the following.
• Occlusion of outdoor heat exchanger
• Outdoor fan trouble
• Outdoor service valve, check valve in discharge pipe, check valve in liquid pipe clogging
• Ventilation resistance of outdoor fan
• Short-circuiting of outdoor suction/discharge air flows
If these conditions are not abnormal, there is a possibility that the refrigerant charging amount is excessive.
Refill the refrigerant to its standard volume.
Refrigerant overcharge can be detected by comparing the Actual PD with the Calculated PD during the
operation.
* Calculated PD: Calculated from suction saturation temperature, compressor frequency, outdoor
temperature.
[Operation]
• Confirming the refrigerant overcharge
Set SW01 to 03 as shown in the following table to confirm whether the overcharge is being detected.
(It also can be confirmed by remote control monitor function. Refer to 7-7-13.Monitor Function of
Remote Controller Switch.)
• Refrigerant overcharge detection data is automatically cleared when it is not the detection conditions.
- 125 -
25HIULJHUDQWOHDNDJHGHWHFWLRQ
The refrigerant leakage can be confirmed by using the switches on Interface PCB of
the outdoor unit.
If there is a leak, the location must be found in order to recover the refrigerant.
After that, implement appropriate countermeasure and refill the refrigerant to its
standard volume.
Refrigerant leaks can be detected by comparing the Actual opening of PMV with the Calculated
opening of PMV* during the operation.
* Calculated opening of PMV: calculated from the initial value(C.i), the pressure sensor value, the
compressor’s URWDWLRQVSHHG, and the opening of PMV. The initial values are automatically saved
when the specified conditions are met.
(A leak can be detected only when C.i = 1)
[Operation]
(1) Confirming the refrigerant leakage
Set SW01 to 03 as shown in the following table to confirm whether the leaks are being detected.
(It also can be confirmed by remote control monitor function. Refer to 7-7-12. Monitor function of remote
controller switch.)
(2) Clearing the initial value
If the system is changed (e.g. indoor units are increased/replaced, outdoor units are moved, or refrigerant is
refilled/increased) it is necessary to clear the initial value that had been saved.
Make sure that the compressor has stopped, and then press and hold SW04 for at least 5 seconds.
[Clear]
Return SW01/SW02/SW03 on the Interface PCB in the outdoor unit to [1/1/1] .
NOTE)
(a) During the operation, the slow leaks can be detected.
However, if the air-conditioner cannot cooling down / make an unusual stop, the slow leaks might not be
detectable. The fast leaks always cannot be detected.
(b) Poor refrigerant circulation may be detected as a refrigerant leaks.
(e.g. plugged strainers / capillaries, malfunction / clogging of the PMV / 2-way valve)
(c) Due to the outside temperature, the initial value may not be recorded, or it may be impossible to determine
the leakage.
(d) The initial value cannot be saved until the accumulated operating time has reached at least 20 hours.
(e) The initial value cannot be saved if the indoor unit’s operating ratio is low.
(f) If the following inGRRU units are connected, leakage determination is not possible.
・Air to air heat exchanger with DX coil unit
- 126 -
7-7-13. Monitor Function of Remote Controller Switch
When using a remote controller with the model name RBC-AMT32E, the following
monitor functions can be used.
Switching to the service monitor mode
<Content>
The sensor temperature or operation status of the remote controller, indoor unit, or the outdoor unit can be
known by switching to the service monitor mode from the remote controller.
[Procedure]
1 Push + buttons simultaneously for 4 seconds or more
to call up the service monitor mode.
The service monitor goes on, and temperature of the CODE No. 00
is firstly displayed.
- 127 -
C O D E N o. Da t a n a m e Display format Unit Remote controller display example
00 Room temperature (Use to control) ×1 °C
01 Room temperature (Remote controller) ×1 °C
Indoor unit data *2
CODE No.
Data name Display format Unit Remote controller display example
U1 U2 U3
10 20 30 High-pressure sensor detention pressure (PD) ×100 MPa
*3
[0123] = 1.23MPa
Outdoor unit individual data 1
CODE No.
Data name Display format Unit Remote controller display example
U1 U2 U3
CODE No. Data name Display format Unit Remote controller display example
0: Normal [0001]=Cooling recovery controlled
90 Cooling recovery controlled
individual data 3 *5
1: Recovery controlled
Outdoor unit
*1 Only a part of indoor unit types is installed with the discharge air temperature sensor. This temperature is not displayed for other types.
*2 When the units are connected to a group, data of the header indoor unit only can be displayed.
*3 The first digit of an CODE No. indicates the outdoor unit number.
*4 The upper digit of an CODE No. -4 indicates the outdoor unit number.
1 , 5 ... U1 outdoor unit (Header unit)
2 , 6 ... U2 outdoor unit (Follower unit 1)
3 , 7 ... U3 outdoor unit (Follower unit 2)
*5 Only the CODE No. 9* of U1 outdoor unit (Header unit) is displayed.
- 128 -
7-8. SMMS WAVE TOOL FOR SMARTPHONE
The NFC TAG DEVICE of the Outdoor unit communicates with SMARTPHONE that simplifies the install, the test
operation and the maintenance of the SMMS-7. *NFC (Near Field Communication)
As for the details, refer to the Operation Manual of "SMMS WAVE TOOL FOR SMARTPHONE"
●You can download the Application and the Operating Manual from the below URL or QR code.
SMARTPHONE
QR code
URL:http://www.toshiba-carrier.co.jp/global/appli/smms_wave_tool/
(Default setting)
After the power input,
:below 48 hours
(1) 2 1 14 - [ nF] [ c.00 ]
[NFC operation permit]
:more than 48 hours
[NFC operation prohibit]
Press for more NFC operation
(2) 2 1 14 [ nF] [ c.01 ]
than 5 secs all time prohibition
- 129 -
How to set the NFC operation all time permission
Follow the below procedure.
(Default setting)
After the power input,
:below 48 hours
2 1 14 - [ nF] [ c.00 ]
[NFC operation permit]
(1) :more than 48 hours
[NFC operation prohibit]
NFC operation
2 1 14 (Press 5 secs) [ nF] [ c.01 ]
all time prohibition
Press for more NFC operation
(2) 2 1 14 [ nF] [ c.02 ]
than 10 secs all time permission
Trademark
Android is a trademark or registered trademark of Google Inc.
QR code is a trademark or registered trademark of DENSO WAVE Inc.
- 130 -
8 TROUBLESHOOTING
8-1. Overview
(1) Before engaging in troubleshooting
(a) Applicable models
All Super Module Multi System (SMMS-7) models.
(Indoor units: MM*-AP*** , Outdoor units: MMY-MAP***7*)
(b) Tools and measuring devices required
(c) Screwdrivers (Philips, flat head), spanners, long-nose pliers, nipper, pin to push reset switch, etc.
(d) Multimeter, thermometer, pressure gauge, etc.
(b) Things to check prior to troubleshooting (behaviors listed below are normal)
NO. Behavior Possible cause
A compressor would not start • Could it just be the 3-minute delay period (3 minutes after compressor
shutdown)?
1 • Could it just be the air conditioner having gone thermostats OFF?
• Could it just be the air conditioner operating in fan mode or put on the timer?
• Could it just be the system going through initial communication?
An outdoor fan would not start or would • Could it just be cooling operation under low outside temperature
2 change speed for no reason conditions?
The air conditioner would not respond to a • Could it just be the air conditioner operation under external or remote
3
start/stop command from a remote controller control?
CAUTION
The cooling performance may decling considerably when total operating capacity of cooling indoor units is
less than 4 HP WHILE AMBIENT TEMPERATURE IS BELOW 0°C.
NOTE
Rather than a product trouble (see the List of Check Codes below), the problem could have been caused by
a microprocessor malfunction attributable to a poor quality of the power source or an external noise. Check
for possible noise sources, and shield the remote controller wiring and signal wires as necessary.
- 131 -
8-2. Troubleshooting Method
The remote controllers (main remote controller and central control remote controller) and the interface P.C. board
of an outdoor unit are provided with an LCD display (remote controller) or a 7-segment display (outdoor interface
P.C. board) to display operational status. Using this self-diagnosis feature, the problem site/problem part may be
identified in the event of a problem by following the method described below.
The list below summarizes check codes detected by various devices. Analyze the check code according to where it is displayed and work out
the nature of the problem in consultation with the list.
• When investigating a problem on the basis of a display provided on the indoor remote controller or TCC-LINK central control remote controller -
See the “TCC-LINK remote control or main remote controller display” section of the list.
• When investigating a problem on the basis of a display provided on an outdoor unit - See the “Outdoor 7-segment display” section of the list.
• When investigating a problem on the basis of a wireless remote controller-controlled indoor unit - See the “Light sensor indicator light block”
section of the list.
List of Check Codes (Indoor Unit) IPDU: Intelligent Power Drive Unit (Inverter P.C. board)
: Lighting, : Flashing, : Goes off
(Check code detected by indoor unit)
ALT.: Flashing is alternately when there are two flashing LED
SIM: Simultaneous flashing when there are two flashing LED
Check code Display of receiving unit
TCC-LINK central Outdoor 7-segment display Indicator light block
control or main Typical problem site Description of Check code
remote controller Operation Timer Ready
Sub-code Flash
display
Communication from remote controller or network
Indoor-remote controller periodic
E03 – – adaptor has been lost (so has central control
communication trouble
communication).
Indoor-outdoor periodic
E04 – – Signals are not being received from outdoor unit.
communication trouble
E08 E08 Duplicated indoor address Duplicated indoor address Indoor unit detects address identical to its own.
Indoor inter-MCU communication MCU communication between main controller and
E10 – –
trouble motor microcontroller is troubled.
Trouble in periodic
Periodic communication between indoor header
E18 – – communication between indoor
and follower units cannot be maintained.
header and follower unit
Indoor heat exchanger Heat exchanger temperature sensor (TCJ) has
F01 – – ALT
temperature sensor (TCJ) trouble been open/short-circuited.
Indoor heat exchanger Heat exchanger temperature sensor (TC2) has
F02 – – ALT
temperature sensor (TC2) trouble been open/short-circuited.
Indoor heat exchanger Heat exchanger temperature sensor (TC1) has
F03 – – ALT
temperature sensor (TC1) trouble been open/short-circuited.
Room air temperature Room air temperature sensor (TA) has been
F10 – – ALT sensor (TA/TSA) trouble
open/short-circuited.
Discharge air temperature Discharge air temperature sensor (TF) has been
F11 – – ALT
sensor (TF/TFA) trouble open/short-circuited.
Outside air suction temperature Open/Short of outside air suction temperature
F17 – – ALT
sensor (TOA) trouble sensor (TOA) was detected.
Indoor air suction temperature Discharge air temperature sensor (TF) has been
F18 – – ALT
sensor (TRA) trouble open/short-circuited.
Open/Short of indoor air suction temperature
F29 – – SIM P.C. board or other indoor trouble
sensor (TRA) was detected.
Duplicated indoor group header
L03 – – SIM There is more than one header unit in group.
unit
Connection of group control cable There is at least one stand-alone indoor unit to
L07 – – SIM
to stand-alone indoor unit which group control cable is connected.
Address setting has not been performed for one or
L08 L08 – SIM Indoor group address not set more indoor units (also detected at outdoor unit
end).
Capacity setting has not been performed for indoor
L09 – – SIM Indoor capacity not set
unit.
There is duplication in central control address
L20 – – SIM Duplicated central control address
setting.
Indoor external trouble input Unit shutdown has been caused by external
L30 L30 Detected indoor unit No. SIM
(interlock) trouble input (CN80).
Indoor AC fan trouble is detected (activation of
P01 – – ALT Indoor AC fan trouble
fan motor thermal relay).
P10 P10 Detected indoor unit No. ALT Indoor overflow trouble Float switch has been activated.
- 132 -
(Check code detected by main remote controller)
Check code Display of receiving unit
Outdoor 7-segment display Indicator light block
Main remote Typical problem site Description of check code
controller Operation Timer Ready
Sub-code Flash
Note: The same trouble, e.g. a communication trouble, may result in the display of different check codes depending on the device that detects it.
Moreover, check codes detected by the main remote controller/central control device do not necessarily have a direct impact on air
conditioner operation.
- 133 -
List of Check Codes (Outdoor Unit)
(Check code detected by SMMS-7 outdoor interface - typical examples)
If "HELLO" is displayed on the oudoor 7-segment for 1 minute or
more, turn off the power supply once and then turn on the power IPDU: Intelligent Power Drive Unit (Inverter P.C. board)
supply again after passage of 30 seconds or more. When the : Lighting, : Flashing, : Goes off
same symptom appears, it is considered there is a possibility of ALT.: Flashing is alternately when there are two flashing LED
I/F board trouble. SIM: Simultaneous flashing when there are two flashing LED
Outdoor discharge
Outdoor discharge temperature sensor (TD1) has
F04 – F04 ALT temperature sensor
been open/short-circuited.
(TD1) trouble
Outdoor discharge
Outdoor discharge temperature sensor (TD2) has
F05 – F05 ALT temperature sensor
been open/short-circuited.
(TD2) trouble
Outdoor heat exchanger Outdoor heat exchanger liquid side
01: TE1
F06 F06 ALT liquid side temperature temperature sensors (TE1) have been open/
sensor (TE1) trouble short-circuited.
01: TL1
F07 – F07 ALT Outdoor liquid temperature Outdoor liquid temperature sensor (TL1,TL3) has
03: TL3 sensor (TL1,TL3) trouble been open/short-circuited.
- 134 -
Check code Display of receiving unit
Outdoor 7-segment display TCC-LINK Indicator light block
central control Typical problem site Description of check code
or main remote Operation Timer Ready
Sub-code controller Flash
display
Outdoor suction
01: TS1 Outdoor suction temperature sensor
F12 F12 ALT temperature sensor
03: TS3 (TS1,TS3) has been open/short-circuited.
(TS1,TS3) trouble
04: TS3 TS3 sensor position trouble
Outdoor temperature
Wiring trouble in outdoor temperature sensors
F15 – F15 ALT sensor (TE1,TL1)
(TE1,TL1) has been detected.
wiring trouble
Outdoor pressure sensor Wiring trouble in outdoor pressure sensors
F16 – F16 ALT
(PD, PS) wiring trouble (PD, PS) has been detected.
Low pressure sensor
F23 – F23 ALT Output voltage of low pressure sensor (PS) is zero.
(PS) trouble
Output voltage of high pressure sensor (PD) is
High pressure sensor
F24 – F24 ALT zero or provides abnormal readings when
(PD) trouble
compressors have been turned off.
Outdoor EEPROM is troubled (alarm and
F31 – F31 SIM Outdoor EEPROM trouble shutdown for header unit and continued operation
for follower unit)
Outdoor discharge Wiring/installation trouble or detachment of
H05 – H05 temperature sensor outdoor discharge temperature sensor (TD1)
(TD1) wiring trouble has been detected.
Activation of low-pressure Low pressure (PS) sensor detects abnormally
H06 – H06
protection low operating pressure.
Temperature sensor for oil level detection
H07 – H07 Low oil level protection
(TK1,TK2) detects abnormally low oil level.
Trouble in temperature
Temperature sensor for oil level detection
H08 01: TK1 sensor trouble
H08 sensor for oil level
(TK1,TK2) has been open/short-circuited.
02: TK2 sensor trouble detection
(TK1,TK2)
Outdoor discharge Wiring/installation trouble or detachment of
H15 – H15 temperature sensor outdoor discharge temperature sensor (TD2)
(TD2) wiring trouble has been detected.
Too many outdoor units More than three outdoor units have been
L28 – L28 SIM
connected connected.
- 135 -
Check code Display of receiving unit
Outdoor 7-segment display TCC-LINK Indicator light block
central control Typical problem site Description of check code
or main remote Operation Timer Ready
Sub-code controller Flash
display
01: Compressor 1 Heat sink overheating Temperature sensor built into IPM (TH) detects
P07 P07 ALT
02: Compressor 2 trouble overheating.
- 136 -
(Check code detected by IPDU featuring in SMMS-7 outdoor unit - typical examples)
Check code Display of receiving unit
Outdoor 7-segment display TCC-LINK Indicator light block
central control Typical problem site Description of check code
or main remote Operation Timer Ready
Sub-code controller Flash
display
Trouble in temperature
01: Compressor 1 Temperature sensor built into indoor IPM (TH)
F13 F13 ALT sensor built into indoor
02: Compressor 2 has been open/short-circuited.
IPM (TH)
01: Compressor 1 Heat sink Temperature sensor built into IPM (TH) detects
P07 P07 ALT
02: Compressor 2 overheating trouble overheating or has been short-circuited.
Note: The above check codes are examples only, and different check codes may be displayed depending on the outdoor unit configuration
- 137 -
8-3. Troubleshooting Based on Information Displayed on
Remote Controller
Using main remote controller (RBC-AMT32E)
(1) Checking and testing
When a problem occurs to an air conditioner, a check
code and indoor unit No. are displayed on the
display window of the remote controller.
Check codes are only displayed while the air
conditioner is in operation.
If the display has already disappeared, access
check code history by following the procedure Check code
Indoor unit No. in which
described below. check code has occurred
2 To check other check code history items, press the 2 TIMER SET FAN MODE
FILTER
Check code “01” (latest) Check code “04” (oldest) RESET TEST SET CL SWING/FIX UNIT LOUVER
1 2 3
REQUIREMENT
Do not push the button as it would erase the whole check code history of the indoor unit.
- 138 -
Using TCC-LINK central remote controller (BMS-CM1280TLE)
(1) Checking and testing
When a problem occurs to an air conditioner,
Display of Unit No. Display of check code
the bar under the group number display flashes.
When a group in the alarm issuance with the UNIT No.
(GROUP) buttons, Unit number and the TEST
latest check code are alternately displayed. Alternate blinking
*If you select a group not issuing an alarm, the
check code will not be displayed even if another No.
air condifioner is issuing an alarm.
4 To check other check code history items, push the button to select another check code (01-04.).
5 To check check code relating to another group, push (ZONE) and (GROUP) buttons to select
a group No.
Do not push the button as it would erase the whole check code history of the selected group.
6 To finish off the service check, push the button.
- 139 -
Using indoor unit indicators (receiving unit light block) (wireless type)
To identify the check code, check the 7-segment display on the header unit. To check for check codes not
displayed on the 7-segment display, consult the “List of Check Codes (Indoor Unit)” in “8-2. Troubleshooting
Method”.
: Goes off : Lighting : Blinking (0.5 seconds)
Light block Check code Cause of check code
- 140 -
Light block Check code Cause of check code
F01 Heat exchanger temperature sensor (TCJ) trouble
Operation Timer Ready
F02 Heat exchanger temperature sensor (TC2) trouble
Indoor unit temperature sensor
F03 Heat exchanger temperature sensor (TC1) trouble
troubles
Alternate blinking F10 Ambient temperature sensor (TA/TSA) trouble
F11 Discharge temperature sensor (TF) trouble
F04 Discharge temperature sensor (TD1) trouble
Operation Timer Ready
F05 Discharge temperature sensor (TD2) trouble
F06 Heat exchanger temperature sensor (TE1) trouble
Outdoor unit temperature
F07 Liquid temperature sensor (TL1,TL3) trouble
Alternate blinking sensor troubles
F08 Outside air temperature sensor (TO) trouble
F12 Suction temperature sensor (TS1,TS3) trouble
F13 Heat sink sensor (TH) trouble
Wiring trouble in heat exchanger sensor (TE1) and liquid temperature sensor (TL1)
F15
Outdoor unit temperature sensor wiring/installation trouble
Wiring trouble in outdoor high pressure sensor (PD) and low pressure sensor (PS)
F16
Outdoor pressure sensor wiring trouble
F17 Outside air suction temperature sensor (TOA) trouble
F18 Indoor air suction temperature sensor (TRA) trouble
F23 Low pressure sensor (PS) trouble Outdoor unit pressure sensor
F24 High pressure sensor (PD) trouble troubles
Synchronized blinking
H08 Trouble in temperature sensor for oil level detection circuit (TK1 or TK2)
H15 Wiring/installation trouble or detachment of outdoor discharge temperature sensor (TD2)
H16 Oil level detection circuit trouble - Trouble in outdoor unit TK1 or TK2 circuit
L02 Outdoor unit model unmatched trouble
L03 Duplicated indoor group header unit
Operation Timer Ready
L05 Duplicated priority indoor unit (as displayed on priority indoor unit)
L06 Duplicated priority indoor unit (as displayed on indoor unit other than priority indoor unit)
L07 Connection of group control cable to stand-alone indoor unit
Synchronized blinking
L08 Indoor group address not set
L09 Indoor capacity not set
L04 Duplicated outdoor refrigerant line address
Operation Timer Ready
L10 Outdoor capacity not set
L17 Outdoor model incompatibility trouble
L20 Duplicated central control address
Synchronized blinking
L23 SW setting mistake
L28 Too many outdoor units connected
L29 Trouble in number of IPDUs
L30 Indoor external interlock trouble
- 141 -
Light block Check code Cause of check code
Synchronized blinking
Synchronized blinking
- 142 -
8-4. Check Codes Displayed on Remote Controller and
SMMS-7 Outdoor Unit (7-Segment Display on I/F
Board) and Locations to be Checked
For other types of outdoor units, refer to their own service manuals.
Check code
Location
Outdoor 7-segment display Check code detection
Main of Description System status Check items (locations)
remote detection condition(s)
Check
controller
code
Sub-code
- 143 -
Check code
Location
Main
Outdoor 7-segment display of Description System status Check code detection Check items (locations)
condition(s)
remote
Check detection
controller
code
Sub-code
No. of indoor Indoor Indoor-outdoor All stop Condition 1 • Check power supply to
units from unit communication One indoor unit or more indoor unit.
which signal is circuit trouble initially communicating (Is power turned on?)
received (E04) normally fails to return signal • Check indoor-outdoor
normally for specified length of time. power-on sequence.
• Check indoor address
Condition 2 setting
Outdoor I / F board • Check wiring of Indoor-
SW09, Bit 4: ON outdoor communication
(To switch the check code wires
detection condition.) • Check outdoor terminator
resistor setting (SW30,
SW09
ON
Bit 2).
I/F Indoor-outdoor All stop Signal cannot be transmitted • Check outdoor terminator
communication from outdoor to indoor units resistor setting (SW30,
circuit trouble for 30 seconds continuously. Bit 2).
– E07 –
(detected at • Check connection of
outdoor end) indoor-outdoor
communication circuit.
Duplicated indoor address Indoor Duplicated All stop More than one indoor unit • Check indoor addresses.
unit indoor address are assigned same address. • Check for any change
I/F made to remote controller
E08 E08
connection (group/
individual) since indoor
address setting.
Remote Duplicated Stop of In two remote controller • Check remote controller
controller master remote corresponding configuration (including settings.
controller unit wireless), both controllers are • Check remote controller
E09 – – set up as master. (Header P.C. boards.
indoor unit is shut down with
alarm, while follower indoor
units continue operating.)
Indoor Indoor inter- Stop of Communication cannot be • Check for trouble in indoor
unit MCU corresponding established/maintained upon P.C. board
E10 – –
communication unit turning on of power or during
trouble communication.
01: I/F Automatic All stop • Indoor automatic address • Perform automatic address
Indoor-outdoor address starting setting is started while setting again after
communication trouble automatic address setting disconnecting
02: for equipment in other communication cable to
Outdoor-outdoor refrigerant line is in that refrigerant line.
E12 E12 communication progress.
• Outdoor automatic
address setting is started
while automatic address
setting for indoor units is in
progress.
- 144 -
Check code
Location Check code detection
Main
Outdoor 7-segment display of Description System status Check items (locations)
condition(s)
remote
Check detection
controller
code
Sub-code
I/F Indoor unit not All stop Indoor unit cannot be • Check connection of
found during detected after indoor indoor-outdoor
automatic automatic address setting is communication line.
address setting started. • Check for trouble in indoor
power supply system.
E15 E15 –
• Check for noise from other
devices.
• Check for power failure.
• Check for trouble in indoor
P.C. board.
00: I/F Too many All stop • Combined capacity of • Check capacities of indoor
Overloading indoor units indoor units is too large. units connected.
01-: connected • Check combined HP
No. of units connected capacities of indoor units.
Note: • Check HP capacity settings
If this code comes up of outdoor units.
after backup setting for • Check No. of indoor units
outdoor unit failure is connected.
performed, perform “No • Check for trouble in outdoor
E16 E16 P.C. board (I/F).
overloading detected”
setting.
<“No overloading detected”
setting method>
Turn on SW09/Bit 2 on I/F
P.C. board of outdoor header
unit.
For Cooling Only model,
this check code is not
displayed even if it exceeds
the combined capacity of
indoor units.
• More than 64 indoor units
are connected.
- 145 -
Check code
Location
Main
Outdoor 7-segment display of Description System status Check code detection Check items (locations)
condition(s)
remote
Check detection
controller
code
Sub-code
- 146 -
Check code
Location
Main
Outdoor 7-segment display of Description
System Check code detection Check items (locations)
status condition(s)
remote
Check detection
controller
code
Sub-code
Indoor Indoor TCJ Stop of Sensor resistance is infinity • Check connection of TCJ
unit sensor trouble corresponding or zero (open/short circuit). sensor connector and
unit wiring.
• Check resistance
F01 – –
characteristics of TCJ
sensor.
• Check for trouble in indoor
P.C. board.
Indoor Indoor TC2 Stop of Sensor resistance is infinity • Check connection of TC2
unit sensor trouble corresponding or zero (open/short circuit). sensor connector and
unit wiring.
• Check resistance
F02 – –
characteristics of TC2
sensor.
• Check for trouble in indoor
P.C. board.
Indoor Indoor TC1 Stop of Sensor resistance is infinity • Check connection of TC1
unit sensor trouble corresponding or zero (open/short circuit). sensor connector and
unit wiring.
• Check resistance
F03 – –
characteristics of TC1
sensor.
• Check for trouble in indoor
P.C. board.
I/F TD1 sensor All stop Sensor resistance is infinity • Check connection of TD1
trouble or zero (open/short circuit). sensor connector.
• Check resistance
F04 F04 – characteristics of TD1
sensor.
• Check for trouble in outdoor
P.C. board (I/F).
I/F TD2 sensor All stop Sensor resistance is infinity • Check connection of TD2
trouble or zero (open/short circuit). sensor connector.
• Check resistance
F05 F05 – characteristics of TD2
sensor.
• Check for trouble in outdoor
P.C. board (I/F).
I/F TE1 All stop Sensor resistance is infinity • Check connection of TE1
sensor trouble or zero (open/short circuit). sensor connectors.
• Check resistance
01: TE1 sensor trouble characteristics of TE1
F06 F06 sensor.
• Check for trouble in outdoor
P.C. board (I/F).
I/F TL1/TL3 All stop Sensor resistance is infinity • Check connection of TL1/
sensor trouble or zero (open/short circuit). TL3 sensor connector.
01: TL1 sensor trouble • Check resistance
characteristics of TL1/TL3
F07 F07 03: TL3 sensor trouble sensor.
• Check for trouble in outdoor
P.C. board (I/F).
- 147 -
Check code
Location
Main
Outdoor 7-segment display of Description System Check code detection Check items (locations)
status condition(s)
remote
Check detection
controller
code
Sub-code
- 148 -
Check code
Location Check code detection
Main
Outdoor 7-segment display of Description System Check items (locations)
remote detection status condition(s)
Check
controller
code
Sub-code
Indoor Other indoor Stop of Indoor P.C. board does not • Check for trouble in indoor
F29 – – unit trouble corresponding operate normally. P.C. board (Troubled EEPROM)
unit
I/F Outdoor All stop *1 Outdoor P.C. board (I/F) • Check power supply voltage.
EEPROM does not operate normally. • Check power supply noise.
F31 F31 –
trouble • Check for trouble in outdoor
P.C. board (I/F).
01: Compressor 1 side IPDU Compressor All stop Inverter current detection • Check power supply voltage.
02: Compressor 2 side breakdown circuit detects overcurrent (AC380-415V ± 10%).
and shuts system down. • Check for trouble in
compressor.
H01 H01
• Check for possible cause of
abnormal overloading.
• Check for trouble in outdoor
P.C. board (A3-IPDU).
01: Compressor 1 side IPDU Compressor All stop Overcurrent is detected • Check for trouble in
02: Compressor 2 side trouble (lockup) several seconds after compressor.
MG-CTT trouble startup of inverter • Check power supply voltage.
compressor. (AC380-415V ± 10%)
• Check compressor system
wiring, particularly for open
phase.
• Check connection of
connectors/terminals on
H02 H02 A3-IPDU P.C.board
• Check for trouble in outdoor
P.C.board (A3-IPDU)
• Check outdoor MG-CTT.
01: Compressor 1 side IPDU Current All stop Current flow of at least • Check current detection
02: Compressor 2 side detection specified magnitude is circuit wiring.
H03 H03 circuit trouble detected despite inverter • Check trouble in outdoor P.C.
compressor having been board (A3-IPDU).
shut turned off.
I/F TD1 sensor All stop Discharge temperature of • Check installation of TD1
miswiring compressor 1 (TD1) does sensor.
(incomplete not increase despite • Check connection of TD1
insertion) compressor being in sensor connector and wiring.
H05 H05 –
operation. • Check resistance
characteristics of TD1 sensor.
• Check for trouble in outdoor
P.C. board (I/F).
I/F Activation of All stop Low-pressure PS sensor • Check service valves to
low-pressure detects operating pressure confirm full opening
protection lower than 0.02MPa. (both gas and liquid sides).
- 149 -
Check code
Location Check code detection
Main
Outdoor 7-segment display of Description System status Check items (locations)
condition(s)
remote
Check detection
controller
code
Sub-code
I/F Low oil level All stop Operating compressor <All outdoor units in
protection detects continuous state of corresponding line to be
low oil level for about 2 hours. checked>
• Check connection and
installation of TK1 and
TK2 sensors.
• Check resistance
characteristics of TK1 and
TK2 sensors.
• Check for gas or oil leak in
same line.
• Check SV3D, SV3F valve
for trouble.
H07 H07 –
• Check oil return circuit of
oil separator for clogging.
• Check oil equalizing
circuit for clogging.
01: TK1 sensor trouble I/F Trouble in All stop Sensor resistance is infinity • Check connection of TK1
02: TK2 sensor trouble temperature or zero (open/short circuit). sensor connector.
sensor for oil • Check resistance
level detection characteristics of TK1
sensor.
• Check for trouble in outdoor
P.C. board (I/F).
H08 H08
All stop Sensor resistance is infinity • Check connection of TK2
or zero (open/short circuit). sensor connector.
• Check resistance
characteristics of TK2
sensor.
• Check for trouble in
outdoor P.C.board (I/F).
I/F TD2 sensor All stop Discharge temperature of • Check installation of TD2
miswiring (TD2) does not increase sensor.
(incomplete despite compressor 2 being • Check connection of TD2
insertion) in operation. sensor connector and
wiring.
H15 H15 –
• Check resistance
characteristics of TD2
sensor.
• Check for trouble in outdoor
P.C. board (I/F).
01: TK1 oil circuit trouble I/F Oil level All stop • Check for disconnection of TK1 sensor
02: TK2 oil circuit trouble detection • Check resistance characteristics of TK1
circuit trouble sensor.
No temperature • Check for connection trouble involving
change is detected TK1 and TK2 sensors
by TK1 despite • Check for clogging in oil equalizing
compressor 1 circuit capillary and trouble operation in
having been started. check valve.
• Check for refrigerant entrapment inside
compressor.
H16 H16
• Check for disconnection of TK2 sensor.
• Check resistance characteristics of TK2
sensor.
No temperature
• Check for connection trouble involving
change is detected TK1 and TK2 sensors
by TK2 despite
• Check for clogging in oil equalizing
compressor 2 circuit capillary and trouble operation in
having been started. check valve.
• Check for refrigerant entrapment inside
compressor.
- 150 -
Check code
Location
Main
Outdoor 7-segment display of Description System status Check code detection Check items (locations)
condition(s)
remote
Check detection
controller
code
Sub-code
Indoor Outdoor units Stop of In case of different outdoor • Check outdoor unit model.
unit model corresponding unit (Not corresponded to (Check whether the
L02 L02 – disagreement unit Air to Air Heat Exchanger outdoor unit corresponds
trouble type) to Air to Air Heat
Exchanger type or not.)
Indoor Duplicated Stop of There are more than one • Check indoor addresses.
unit indoor header corresponding header units in group. • Check for any change
unit unit made to remote controller
L03 – –
connection (group/
individual) since indoor
address setting.
I/F Duplicated All stop There is duplication in line • Check line addresses.
outdoor line address setting for outdoor
L04 L04 –
address units belonging to different
refrigerant piping systems.
I/F Duplicated All stop More than one indoor units • Check display on priority
priority indoor have been set up as priority indoor unit.
unit (as indoor unit.
L05 – –
displayed on
priority indoor
unit)
No. of priority indoor units I/F Duplicated All stop More than one indoor units • Check displays on priority
priority indoor have been set up as priority indoor unit and outdoor
unit (as indoor unit. unit.
L06 L06 displayed on
indoor unit other
than priority
indoor unit)
Indoor Connection of Stop of There is at least one stand- • Check indoor addresses.
unit group control corresponding alone indoor unit to which
L07 – – cable to stand- unit group control cable is
alone indoor connected.
unit
Indoor Indoor group / Stop of Address setting has not been • Check indoor addresses.
unit addresses not corresponding performed for indoor units. Note:
set unit This code is displayed
L08 L08 –
when power is turned on
for the first time after
installation.
Indoor Indoor capacity Stop of Capacity setting has not been Set indoor capacity. (DN =
L09 – – unit not set corresponding performed for indoor unit. 11)
unit
I/F Outdoor All stop Jumper wire provided on P.C. Check model setting of P.C.
capacity not set board for servicing I/F P.C. board for servicing outdoor
L10 L10 –
board has not been removed I/F P.C. board.
as required for given model.
Network Duplicated All stop There is duplication in central • Check central control
adaptor central control control address setting. addresses.
L20 – – Indoor address • Check network adaptor
unit P.C. board .
I/F SW setting All stop Outdoor P.C. board (I/F) • Check switch setting of
mistake does not operate normally. Bit 3 and 4 of SW17 in
L23 – –
outdoor P.C. board (I/F).
I/F Too many All stop There are more than three • Check No. of outdoor units
outdoor units outdoor units. connected (Only up to 3
connected units per system allowed).
• Check communication
L28 L28 –
lines between outdoor
units.
• Check for defect in outdoor
P.C. board (I/F).
- 151 -
Check code
Location Check code detection
Main
Outdoor 7-segment display of Description System status Check items (locations)
condition(s)
remote
Check detection
controller
code
Sub-code
A3-IPDU Fan-IPDU A3-IPDU Fan-IPDU I/F Trouble in No. of All stop Insufficient number of IPDUs • Check model setting of
1 2 1 2 1 2 1 2 IPDUs are detected when power is P.C. board for servicing
01 ○ 10 ○
02 ○ 11 ○ ○ turned on. outdoor I/F P.C. board.
03 ○ ○ 12 ○ ○ • Check connection of UART
08 ○ 13 ○ ○ ○ communication connector.
09 ○ ○ 18 ○ ○
• Check A3-IPDU, fan IPDU,
0A ○ ○ 19 ○ ○ ○
0B ○ ○ ○ 1A ○ ○ ○ and I/F P.C. board for
1B ○ ○ ○ ○ trouble.
Circle (O): Troubled. IPDU
L29 L29
Detected indoor address Indoor External Stop of • Signal is present at When external device is
unit interlock of corresponding external trouble input connected to CN80
indoor unit unit terminal (CN80) for 1 connector:
minute. 1) Check for trouble in
external device.
2) Check for trouble in indoor
L30 L30
P.C. board
When external device is not
connected to CN80
connector:
3) Check for trouble in indoor
P.C. board.
I/F Extended IC Continued There is part failure in P.C. Check outdoor P.C. board
– L31 –
trouble. operation board (I/F). (I/F).
Indoor Indoor fan Stop of • Check the lock of fan motor
P01 – – unit motor trouble. corresponding (AC fan).
unit • Check wiring.
I/F Discharge All stop Discharge temperature (TD1) • Check outdoor service
temperature exceeds 115°C. valves (gas side, liquid
TD1 trouble. side) to confirm full
opening.
• Check resistance
characteristics of TD1
sensor.
• Check for insufficiency in
refrigerant quantity.
P03 P03 –
• Check for leakage of
SV4 circuit.
• Check SV4 circuit (wiring
or installation trouble
in SV41 or SV42).
- 152 -
Check code
Location Check code detection
Main
Outdoor 7-segment display of Description System Check items (locations)
remote detection status condition(s)
Check
controller
code
Sub-code
01: Compressor 1 side IPDU Activation of high- All stop High-pressure SW is • Check connection of high-
02: Compressor 2 side pressure SW activated. pressure SW connector.
• Check for trouble in PD
pressure sensor.
• Check outdoor service valves
(gas side, liquid side) to
confirm full opening.
• Check for trouble in outdoor
fan.
• Check for trouble in outdoor
fan motor.
• Check indoor/outdoor heat
exchangers for clogging.
• Check for short-circuiting of
outdoor suction/discharge air
flows.
• Check CHECK VALVE in
liquid pipe for clogging.
• Check SV2 circuit for
P04 P04
clogging.
• Check for trouble in outdoor
P.C. board (I/F).
• Check for trouble in indoor
fan system (possible cause of
air flow reduction).
• Check opening status of
indoor PMV.
• Check indoor-outdoor
communication line for wiring
trouble.
• Check for trouble operation
of check valve in discharge
pipe convergent section.
• Check gas balancing SV4
valve circuit.
• Check for refrigerant
overcharging.
00: I/F Detection of open All stop • Open phase is • Check for trouble in outdoor
phase/phase sequence detected when P.C. board (I/F).
power is turned • Check wiring of outdoor
01: Compressor 1 side Inverter DC voltage on. power supply.
P05 P05 02: Compressor 2 side (Vdc) trouble • Inverter DC
(compressor) voltage is too high
MG-CTT trouble (overvoltage) or
too low
(undervoltage).
01: Compressor 1 side IPDU Heat sink All stop Temperature sensor • Check power supply voltage.
02: Compressor 2 side I/F overheating trouble built into IPM (TH) is • Check outdoor fan system
overheated. trouble.
• Check heat sink cooling duct
for clogging.
• Check IPM and heat sink for
P07 P07 thermal performance for
troubled installation.
(e.g. mounting screws and
thermal conductivity)
• Check for trouble in A3-
IPDU.(troubled IPM built-in
temperature sensor (TH))
Detected indoor address Indoor Indoor overflow trouble All stop • Float switch • Check float switch connector.
unit operates. • Check operation of drain
• Float switch circuit pump.
P10 P10 is open-circuited • Check drain pump circuit.
or disconnected at • Check drain pipe for clogging.
connector. • Check for trouble in indoor
P.C. board.
Indoor Indoor fan motor trouble Stop of • Motor speed • Check connection of fan
unit corresponding measurements connector and wiring.
unit continuously • Check for trouble in fan motor.
deviate from target • Check for trouble in indoor
P12 – –
value. P.C. board.
• Overcurrent • Check impact of outside air
protection is treatment (OA).
activated.
MG-CTT: Magnet contactor
- 153 -
Check code
Location Check code detection
Main
Outdoor 7-segment display of Description System status Check items (locations)
condition(s)
remote
Check detection
controller
code
Sub-code
I/F Outdoor liquid All stop <During cooling operation> • Check for trouble in PD
backflow When system is in cooling or PS sensor.
detection trouble operation, high pressure is • Check gas balancing
detected in follower unit that circuit (SV2) for clogging.
has been turned off. • Check trouble in outdoor
P.C. board (I/F).
• Check capillary of oil
separator oil return circuit
P13 P13 – for clogging.
• Check for leakage of
check valve in discharge
pipe convergent section.
01: TS condition I/F Gas All stop Protective shutdown due to • Check for insufficiency in
leakdetection sustained suction refrigerant quantity.
(TS1 condition) temperature at or above • Check outdoor service
judgment criterion valves (gas side, liquid
for at least 10 minutes is side) to confirm full
repeated four times or more. opening.
<TS trouble judgment • Check resistance
criterion> characteristics of TS1
In cooling operation: 60°C sensor.
• Check SV4 circuit for
leakage
P15 P15
02: TD condition I/F Gas leak All stop Protective shutdown due to • Check for insufficiency in
detection sustained discharge refrigerant quantity.
(TD condition) temperature (TD1 or TD2) • Check resistance
at or above 108 °C for at characteristics of TD1 and
least 10 minutes is repeated TD2 sensors.
four times or more. • Check indoor filter for
clogging.
• Check piping for clogging.
• Check SV4 circuit (for
leakage or coil installation
trouble).
I/F Discharge All stop Discharge temperature (TD2) • Check outdoor service
temperature exceeds 115°C. valves (gas side, liquid
TD2 trouble side) to confirm full
opening.
• Check resistance
characteristics of TD2
sensor.
• Check SV4 circuit for
P17 P17 – leakage.
• Check SV4 circuit (for
wiring or installation
trouble involving SV41
and SV42).
- 154 -
Check code
Location
Main
Outdoor 7-segment display of Description System status Check code detection Check items (locations)
condition(s)
remote
Check detection
controller
code
Sub-code
I/F Activation of All stop <During cooling operation> • Check for trouble in PD
high-pressure PD sensor detects pressure pressure sensor.
protection equal to or greater than • Check service valves (gas
3.85 MPa. side, liquid side) to confirm
full opening.
• Check for trouble in outdoor
fan.
• Check for trouble in outdoor
fan motor.
• Check indoor/outdoor heat
exchangers for clogging.
• Check for short-circuiting of
outdoor suction/discharge
air flows.
• Check CHECK VALVE in
liquid pipe for clogging.
• Check SV2 circuit for
P20 P20 – clogging.
• Check for trouble in outdoor
P.C. board (I/F).
• Check for trouble in indoor
fan system (possible cause
of air flow reduction).
• Check opening status of
indoor PMV.
• Check indoor-outdoor
communication line for
wiring trouble.
• Check for troubled
operation of check valve in
discharge pipe convergent
section.
• Check gas balancing SV4
valve circuit.
• Check for refrigerant
overcharging.
- 155 -
Check code
Location
Main
Outdoor 7-segment display of Description System status Check code detection Check items (locations)
condition(s)
remote
Check detection
controller
code
Sub-code
- 156 -
Check codes Detected by TCC-LINK Central Control Device
Check code
Location
Main Outdoor 7-segment display of Description System status Check code detection Check items (locations)
condition(s)
remote detection
controller Sub-code
- 157 -
Points to Note When Servicing Compressor
(1) When checking the outputs of inverters, remove the wiring from all the compressors.
* When connecting the compressor leads back to the compressor terminals after checking the output, check the
faston connectors thoroughly to ensure that they are not crooked. If there is any loose connector, tighten it with
a pair of pliers, etc. before connecting the lead.
- 158 -
Check code Check code name Cause Check code Check code name Cause
[E02] Signal transmission trouble on Unable to send signals to indoor units [E01] Communication trouble between 1. Remote controller inter-unit wire trouble
2. Indoor power trouble
the remote controller the indoor unit and remote
3. Indoor P.C. board trouble
controller (detected on the remote 4. Remote controller address setup trouble
controller) 5. Remote controller P.C. board trouble
* The check code is not indicated on the central control device or the 7-segment indication on the outdoor unit.
The Is the
communication wiring inter-unit wire of No
between the remote No Correct inter-unit cable of
Connect the wiring properly. remote controllers (A/B)
controller and indoor units normal?
remote controller.
is connected properly.
Yes
Yes
Is there no
disconnection or
The transmission circuit in the Yes Correct connector connection
connector contact trouble on
remote controller malfunctions. harness out of terminal and check circuit wiring.
Replace the remote controller. block of indoor
unit?
No
- 159 -
Is power applied
to remote controller? No Check indoor P.C. board.
AB terminals: Approx. Failure Replace
DC18V
Yes
No Is connection
(U1/U2 terminals) of No
Correct inter-unit wire.
indoor/outdoor inter-unit
wire normal?
Is connection No
of CN40 connector on Correct wiring or connector. Yes
indoor P.C. board
normal?
Is connector
Yes
connection from U1/U2 No
terminals of indoor/outdoor Correct connector connection.
inter-unit wire
normal?
Is connection of CN01 No
connector on outdoor I/F Yes
P.C. board normal?
Yes No
Is the terminator resistor Correct the terminator resistor
setup of outdoor unit setup.
normal?
No
Is power of indoor unit
- 160 -
Turn on power of indoor unit. Yes
turned on?
Yes No
Is address setup correct? Set up address again.
Yes
Did a power failure Clear the check code. Yes
occur?
Check connection of inter-unit
wire between indoor and outdoor
No No
Is power applied to fuse is correct, and then connect
(F03) on indoor P.C. communication line connector on
board? indoor P.C. board (CN40) to
Yes CN44 (EMG).
Check noise, etc, and eliminate Yes
Is there no noise, etc?
it if any.
Check indoor P.C. board. For details, refer to “7-5. Troubleshooting in Test Operation”.
Failure Replace
Check code Check code name Cause Check code Check code name Cause
[E08] Duplicated indoor addresses Indoor addresses are duplicated. [E07] Indoor/Outdoor 1. Indoor/outdoor communication terminator
resistor setup trouble
communication circuit trouble 2. Indoor/outdoor communication connection
(Detected at outdoor side) trouble
Is setup of
Using a wired remote controller (RBC-AMT32E), check the setup CODE No. No Correct setup of terminator
terminator resistor of
(DN code) 12, 13, and 14. outdoor unit normal? resistor
When there is no address duplication, check to the following flowchart.
Yes
Correct short-circuit.
Is not communication Yes
line connected to the
Correct communication line.
different outdoor
unit?
Is connection of No
No inter-unit wire between Correct communication line.
indoor and outdoor
correct?
Yes
Is indoor unit quantity No
connected to outdoor
unit correct?
Is there no trouble on Yes
Yes power wire to outdoor Correct power wire.
unit?
- 161 -
No
Eliminate noise.
[E15] No corresponding indoor unit 1. Communication line connection trouble [E09] Duplicated header remote Setup of header remote controller is duplicated.
between indoor and outdoor
during automatic address 2. Indoor power system trouble
controller
3. Noise from surrounding devices
4. Power failure
5. Indoor P.C. board trouble
Are two remote Set up one controller as the header and
controllers set up as two Yes
the other follower.
header remote
controllers? (Remote controller address connector)
Is communication No
No Correct communication line.
line between indoor Check remote controller P.C. board.
and outdoor Failure Replace
normal?
Yes
Yes
No
No
- 162 -
resetting power supply.
No
Yes
Is there no noise source? Eliminate noise.
Sub-code: 01: Communication between indoor and outdoor 02: Communication between outdoor units
Yes
No
Yes
- 163 -
Check indoor address.
Failure Replace
Is total capacity Set capacity of connected indoor
No
of connected indoor units within each model
units correct? specification of outdoor units.
Correct indoor address.
Yes
For a service
P.C. board, check OK Set up outdoor HP.
outdoor HP setup. (Refer “13 P.C. BOARD
(Set up jumper 9, 10, 11, EXCHANGE PROCEDURES”.)
and 12.)
NG
Is there no
miswiring or disconnection Yes Correct communication line.
on communication line Are not
between outdoor communication lines Connect communication line
units? (U1, U2) between indoor Yes
between indoor and outdoor
No and outdoor connected
to multiple outdoor to one unit per 1 system.
units?
Is connection No
of CN03 connector on No
Correct wiring or connector.
outdoor I/F P.C. board
normal?
Yes Is
communication
line between indoor and No Connect communication line
outdoor connected to between indoor and outdoor.
Is not main power of Yes Turn on main power of one unit per 1
outdoor unit turned outdoor unit. system?
off?
Yes
No
Is the Reference)
terminator resistor between No Turn the terminator resistor The outdoor unit connected with communication wires (U1, U2) between
Check I/F board.
outdoor units turned on? to ON. indoor and outdoor is automatically recognized as the header unit.
(SW30 Bit 2)
Yes
- 164 -
Did power failure Yes
occur? Clear check code.
No
Separate the connection between the lines following the address setup method.
Check code Check code name Cause Check code Check code name Cause
[E31] IPDU communication trouble 1. Connection trouble of communication line Duplicated follower outdoor Addresses are duplicated by manual setup of outdoor
between IPDU and I/F P.C. board [E25]
address
2. I/F P.C. board trouble address setup
3. IPDU P.C. board trouble
4. External noise
Do not set up outdoor addresses manually.
Sub-code
A3-IPDU Fan-IPDU A3-IPDU Fan-IPDU
1 2 1 2 1 2 1 2 Check code Check code name Cause
01 ○ 10 ○
02 ○ 11 ○ ○ [E26] Decrease of connected outdoor 1. Outdoor unit backup setup
03 ○ ○ 12 ○ ○ 2. Outdoor power trouble
units 3. Communication line connection trouble between
08 ○ 13 ○ ○ ○
09 ○ ○ 18 ○ ○
outdoor units
4. Communication connector connection trouble
0A ○ ○ 19 ○ ○ ○
5. Outdoor I/F P.C. board trouble
0B ○ ○ ○ 1A ○ ○ ○
1B ○ ○ ○ ○
Circle (O): Troubled IPDU
Sub-code: Address of the outdoor unit receiving signal abnormally
Is
communication
connector between IPDU No Yes Clear the trouble, and then
Correct connection of connector. During setup of outdoor
and I/F P.C. board unit backup? start operation. (*1)
connected?
Yes No
Is there
no disconnection on Is main power of No
Yes follower unit turned on? Turn on the main power supply.
communication line Replace communication line.
between IPDU and I/F
P.C. board?
No Yes
Is
communication line
Is there No Correct connection of
between outdoor
voltage deflection communication line.
between 4 and 5 pin of units connected
CN600 on I/F P.C. board? No normally?
- 165 -
I/F P.C. board trouble
(Measurement with tester:
DC 0 to 5V, Yes
5 pins GND)
Yes Is communication
connector (CN03) No Correct connector connection.
between follower outdoor (Communication connector: CN03)
units connected?
Is there
voltage deflection
between 3 and 5 pin of
CN600 on I/F P.C. board? No Yes
I/F P.C. board trouble
(Measurement with tester:
DC0 to 5V, In the case that All IPDUs (A3- IPDUs and
5 pins GND) fan IPDUs) do not return response. (*1) How to clear the trouble
* From 8 to 14HP models, one A3-IPDU (No.1) exist. Check I/F P.C. board. Set SW01/SW02/SW03 on I/F P.C. board of header unit to 2/16/1, and
Yes From 14A to 24HP models, two A3-IPDU (No.1 and No.2) exist. push SW04 for 5 seconds or more.
From 8 to 20HP models, one Fan-IPDU exist. (7-segment display: [Er.] [CL])
22 and 24HP models, two Fan-IPDUs exist.
Replace defective IPDU
P.C. board.
Check code Check code name Cause
[E28] Follower outdoor unit trouble Trouble has occurred on a follower outdoor unit.
Sub-code : 80
Communication trouble
between MCU and MCU Sub-code: Detected outdoor unit No.
A trouble occurred on a follower unit. See the check code on the 7-segment display on I/F P.C. board of the follower
Was power unit, and then check it according to diagnose procedure for the check code.
supply correctly reset? No
(Power supply OFF for Reset power supply and reactivate. (How to specify the follower outdoor unit in which trouble occurred)
60 seconds or more) Push SW04 for 1 second or more under condition that [E28] is displayed on the 7-segment display of the header unit.
The fan of the outdoor unit which stopped due to occurrence of trouble starts rotating. Push SW05 to stop the fan.
Yes
Is TC1 Is TCJ
sensor connector No sensor connector No
(CN100: Brown) on indoor Correct connection of (CN102: Red) on indoor Correct connection of
P.C. board normally connector. P.C. board normally connector.
connected? connected?
Yes Yes
Yes *See “Indoor unit temperature sensor characteristics” on “8-10. Sensor Characteristics”. Yes * See “Indoor unit temperature sensor characteristics” on “8-10. Sensor Characteristics”.
This check code means detection of Open/Short of TD1 sensor. Check disconnection of circuit for connection
of connector (TD1 sensor: CN502, White) and characteristics of sensor resistance value. (See “Outdoor unit
temperature sensor characteristics” on “8-10. Sensor Characteristics”.) Is TC2
- 166 -
If sensor is normal, replace outdoor I/F P.C. board. sensor connector
(CN101: Black) on indoor
No Correct connection of
P.C. board normally connector.
connected?
Yes
Check code Check code name Cause
[F05] TD2 sensor trouble TD2 sensor Open/Short
Are characteristics of No
TC2 sensor resistance Replace TC2 sensor.
value normal?
This check code means detection of Open/Short of TD2 sensor. Check disconnection of circuit for connection Yes * See “Indoor unit temperature sensor characteristics” on “8-10. Sensor Characteristics”.
of connector (TD2 sensor: CN503, Pink) and characteristics of sensor resistance value. (See “Outdoor unit
temperature sensor characteristics” on “8-10. Sensor Characteristics”.)
If sensor is normal, replace outdoor I/F P.C. board.
Check indoor P.C. board.
Failure Replace
This check code means detection of Open/Short of TE1 sensor. Check disconnection of circuit for connection
of connector (TE1 sensor: CN520,Green) and characteristics of sensor resistance value. (See “Outdoor unit
temperature sensor characteristics” on “8-10. Sensor Characteristics”.)
If sensor is normal, replace outdoor I/F P.C. board.
Check code Check code name Cause Check code Check code name Cause
[F13] TH sensor trouble IPM built-in sensor trouble in A3-IPDU [F07] TL1,TL3 sensor trouble TL1,TL3 sensor Open/Short
This check code means detection of Open/Short of TL1,TL3 sensor. Check disconnection of circuit for
This check code means IPM built-in temperature sensor trouble. connection of connector (TL1 sensor: CN523WHI, TL3 sensor: CN902 PNK) and characteristics of sensor
If sensor is normal, replace IPDU P.C. board. resistance value. (See “Outdoor unit temperature sensor characteristics” on “8-10. Sensor Characteristics”.)
If sensor is normal, replace outdoor I/F P.C. board.
This check code means detection of Open/Short of TO sensor. Check disconnection of circuit for connection
of connector (TO sensor: CN507, Yellow) and characteristics of sensor resistance value. (See “Outdoor unit
No Correct installed positions of
temperature sensor characteristics” on “8-10. Sensor Characteristics”.)
Are installed positions
of TE1 sensor and TL1
If sensor is normal, replace outdoor I/F P.C. board.
TE1 sensor and TL1 sensor.
sensor correct?
Are connection
of TE1 sensor connector No Correct connection of
and TL1 sensor connector connectors.
normal?
This check code means detection of Open/Short of TA sensor. Check disconnection of circuit for connection
of connector (TA /TSA sensor: CN104, Yellow) and characteristics of sensor resistance value. (See “Indoor
unit temperature sensor characteristics” on “8-10. Sensor Characteristics”.)
If sensor is normal, replace indoor P.C. board.
Yes
- 167 -
Are resistance Check code Check code name Cause
characteristics of TL1 No Correct connection of
sensor and TE1 sensor connectors. [F12] TS1,TS3 sensor trouble TS1,TS3 sensor Open/Short
normal? TS3 sensor position trouble
*See “Outdoor unit temperature sensor characteristics” on “8-10. Sensor Characteristics”. Sub-code: 01: TS1, 03: TS3, 04: TS3
Yes
Check outdoor I/F P.C. board. This check code means detection of Open/Short of TS1,TS3 sensor. Check disconnection of circuit for
Failure Replace connection of connector (TS1 sensor: CN505 WHI, TS3 sensor: CN903 PUR) and characteristics of sensor
resistance value. (See “Outdoor unit temperature sensor characteristics” on “8-10. Sensor Characteristics”.)
If sensor is normal, replace outdoor I/F P.C. board.
TE1 sensor: Outdoor heat exchanger temp sensor
TL1 sensor: Temp sensor between liquid tank of outdoor PMV
Check code Check code name Cause Check code Check code name Cause
[F18] Indoor TRA sensor trouble TRA sensor Open/Short 1. High-pressure PD sensor and low pressure
[F16] Outdoor pressure sensor
sensor PS are exchanged.
miswiring (PD, PS) 2. Output voltage of each sensor is zero.
Is TRA
sensor connector
on indoor No Correct connection of
P.C. board normally connector.
connected? Are connection of No Correct connection of connectors.
PD sensor and PS PD sensor: CN501, Red
Yes sensor connectors
PS sensor: CN500, White
correct?
Yes
Are characteristics of No
Replace TRA sensor.
TRA sensor resistance
value normal?
Are output
*See "Indoor unit temperature sensor characteristics" on "8-. Sensor Characteristics". voltage characteristics No
Yes Sensor trouble Replace
of PD sensor and PS
sensor normal?
(1) Pressure (Check joint) by pressure gauge
(2) Pressure display on 7-segment display
Check indoor P.C. board.
(3) Output voltage of I/F P.C. board
Failure → Replace Yes
If (1) and (2), (3) are different, trouble pressure
sensor itself is considered.
If (2) and (3) are different, check interface P.C. board.
Are PD/PS
output values No
PD>PS during Check compressor.
Check code Check code name Cause compressor Value can be confirmed by 7-segment
PS sensor trouble Output voltage trouble of PS sensor operation? display function on outdoor I/F P.C. board.
[F23]
Yes PD SW01/02/03=1/1/2
PS SW01/02/03=1/2/2
- 168 -
Is connection of PS No Correct connection of
sensor connector connector.
correct? Connector: CN500, White
Check code Check code name Cause
Yes [F17] Indoor TOA sensor trouble TOA sensor Open/Short
Are output
voltage characteristics No
of PS sensor Sensor trouble Replace
normal? (1) Pressure (Check joint) by pressure gauge
(2) Pressure display on 7-segment display Is TOA
Yes (3) Output voltage of I/F P.C. board sensor connector No
on indoor Correct connection of
If (1) and (2), (3) are different, a trouble of pressure connector.
sensor itself is considered. P.C. board normally
connected?
If (2) and (3) are different, check interface P.C. board.
Yes
Is there no leakage
Check compressor.
from SV4 valve? No Are characteristics No
of TOA sensor resistance Replace TOA sensor.
Yes value normal?
This trouble is detected during operation of air conditioner of IC10 non-volatile memory (EEPROM) It is output voltage trouble of PD sensor. Check disconnection of connection of connector (PD sensor: CN501,
on indoor unit P.C.board. Replace service P.C. board. red) circuit and output voltage of sensor.
If the sensor is normal, replace outdoor I/F P.C. board.
* If EEPROM was not inserted when power was turned on or it is absolutely impossible to read/write
EEPROM data, the automatic address mode is repeated.
- 169 -
of outdoor unit
power supply? Check external noise, etc.
Yes
Sub-code:
01: Compressor 1,
02: Compressor 2 Sub-code:
01: Compressor 1,
02: Compressor 2
Is power voltage No
of outdoor unit Correct power line.
normal? *1 Is power voltage No
*1: 380-415V ± 10% of outdoor unit Correct power line.
Yes normal? * 380-415V ± 10%
Yes
Does voltage drop Yes
occur when other
compressor Does voltage
starts? drop occur when Yes
other compressor
No starts?
Is wiring No
or connector No
connection on A3-
Correct connector connection
IPDU P.C. board or wiring.
Is connection
normal? No Correct connector connection
of wiring or connection of
Yes connector on A3-IPDU P.C. or wiring.
board normal?
Yes
No
Is MG-CTT normal? *2 Exchange MG-CTT
- 170 -
Is winding
*2 Check connection wiring resistance between No
Yes Check operation of MG-CTT Compressor trouble (Motor
phases of corresponding
Check the short circuit of MG-CTT compressor normal? burning, etc.)
(Note 1)
Take off lead wire of compressor.
1. Check resistance between windings:
Yes It is normal if there are 0.1Ω to 1.0Ω.
Abnormal overload? Correct cause of overload. Yes 2. Check insulation between outdoor cabinet and terminal:
It is normal if there are 10MΩ or more.
No Yes
Is not it an abnormal
overload? Correct cause of overload.
Is there no
refrigerant stagnation Yes Correct refrigerant stagnation No
in compressor shell? in compressor shell.
Sub-code:
01: Compressor 1,
No 02: Compressor 2
Is TD1 sensor Correct installation of sensor.
installed correctly?
Wiring or
Yes
connector No Correct connector connection
connection on
IPDU P.C. board or wiring.
Is there no Correct miswiring/misinstallation. normal?
miswiring or Yes TD1: CN502, white
misinstallation on TD2: CN503, pink Yes
TD1/TD2
sensors?
No
Check IPDU P.C. board.
Are resistance No
characteristics of TD1 Sensor trouble Replace the sensor.
sensor normal?
Yes
- 171 -
Check code Check code name Cause Check code Check code name Cause
[H07] Oil level down detection 1. Miswiring or misinstallation of TK1, TK2 [H06] Low-pressure protective operation 1. Service valve close
sensors 2. PS sensor trouble
protection 2. TK1, TK2 sensor trouble 3. SV2, SV4 circuit trouble
3. Gas leak or oil leak in a line 4. Miswiring of communication between indoor
4. SV3D, SV3F valve trouble and outdoor
5. Clogging of oil return circuit from oil separator 5. Indoor/outdoor fan and condenser trouble
6. Clogging of oil-equation circuit system 6. Indoor/outdoor PMV clogging
7. Indoor/outdoor heat exchanger clogging
8. Refrigerant shortage
Are
service valves of No Open service valves
gas and liquid pipe of
outdoor unit fully fully.
opened?
Are
TK1 and TK2 sensors Yes
Correct miswiring and Are
of the trouble-detected unit No characteristics of No
misinstallation. Exchange low-pressure
correctly connected? low-pressure sensor sensor.
TK1: CN531, black normal? * 1. Pressure by pressure gauge (Check joint)
Are all the sensors properly 2. Pressure display on 7-segment display
TK2: CN532, green
connected? 3. Output voltage of I/F P.C. board
Yes If 1 and 2, 3 are different, a failure of pressure sensor is considered.
If 2 and 3 are different, check I/F P.C. board.
Yes No
Are SV2 and SV4 Correct SV2 and SV4
circuits normal? circuits.
Check miswiring, misinstallation and connector connection.
Yes
Are characteristics of TK1 No
and TK2 of trouble-detected Sensor trouble replace
Is any indoor unit Yes
unit normal? in a different line Correct wiring.
*See "Outdoor unit temperature sensor characteristics" (Check with miswiring check function of outdoor unit.)
connected?
on "8-10. Sensor Characteristics."
Yes
No
In cooling season, go to (A)
(*1)(*2) In heating season, go to (B)
Check clogging
of oil return circuit from oil Clogging
separator. (Capillary tube,strainer) Replace trouble part.
(A) Cooling
- 172 -
Check clogging of
Are
SV3D valve. following items
Does indoor concerned to indoor fan No
No motor normal?
fan normally operate Repair failure parts.
No clogging in cooling season? 1. Connector connection
2. Condenser
3. Motor
Yes 4. Fan
Check indoor P.C. board.
(*3) Check clogging of oil Clogging Failure Replace
Replace trouble part. Is there Yes
equalization circuit. clogging of indoor air filter Cleaning
or heat exchanger?
No
No clogging
No Is connector No
Is indoor PMV Repair failure parts.
connection or coil
normal?
normal?
Clogging Yes
(*4) Check clogging of Yes
Replace trouble part. Refrigerant shortage or clogging or pipe deformed
SV3F valve. Is there clogging Yes
on whole valve? Replace PMV body.
No
No clogging
Is indoor fan system normal? No
• Fan crack Repair failure parts.
Refrigerant shortage or oil shortage • Fan coming-off
(Refigerant recharging, refill oil)
(*1) (*2) Checking the oil return circuit from oil separator and clogging in
Oil separator
SV3D valve
a) Oil return circuit
(1) • While outdoor unit is operating, check temperature (secondary side of capillary) on oil return circuit.
Accumulator ((1) in the figure.)
(SV2) If temperature is low equivalent to suction temperature), a clogging of strainer of oil return circuit or
capillary is considered. Replace the clogged part.
(SV3D) SV
b) Clogging check for SV3D valve
SV • While outdoor unit is operated, set up SW01/02/03 = [2] [1] [3] (7-segment display [Hr] [... ... ...]), and
push SW04 for 2 seconds or more.
• Set up SW02 = [10], and turn on SV3D valve. (7-segment display [Hr] [... 3 d])
(2) • If temperature is low at secondary side of the valve or it does not change, clogging of valve,
(SV41) (SV42)
capillary, or strainer is considered. ((2) in the figure.) Replace the clogged part.
SV SV (SV3F)
(*3)
SV
High- High-
pressure pressure a) Clogging check for oil-equalization circuit
(TD1) switch (TD2) • Drive the outdoor unit. (Drive all compressors in the unit.)
switch
• After driving for 10 minutes or more, check whether temperature of TK1, TK2 sensors and
(4) temperature of oil-equalization circuit capillary ((3) in the figure) has increased.
(Criterion)
Com- Com- TK1, TK2=Td1, Td2 temperature - Approx. 10 to 30°C
pressor pressor Oil-equalization capillary tubes should be higher sufficiently than outside air temperature and
1 2
suction temperature.
- 173 -
• If temperature is low, a malfunction on check valves or clogging of capillary, strainer or distributor is
considered. Repair the defective parts.
Yes
Is not TK1 sensor Correct installation of sensor. The detected trouble is an oil level detective temperature sensor trouble. Check disconnection of the wiring and
detached? resistance value of the sensor.
If the sensors are normal, replace the outdoor I/F P.C. board.
No
Circuit Connector
Is there TK1 CN531 (Black)
no miswiring or Yes Correct miswiring/misinstallation.
misinstallation on TD1: CN502 white TD2: CN503 pink TK2 CN532 (Green)
TD1/TD2/TK1/TK2 TK1: CN531, black TK2: CN532, green
sensors?
No
Are
characteristics of No
TK1 sensor resistance Sensor trouble
value normal? *See "Outdoor unit temperature sensor
Check code Check code name Cause
characteristics" on "8-10. Sensor Characteristics".
Yes [H15] Outdoor discharge temperature 1. Coming-off of TD2 sensor
2.Misinstallation of TD1 or TD2 sensor, miswiring,
sensor (TD2) misconnection characteristics trouble of resistance value
Start a test operation in COOL or HEAT mode. Trouble
Replace clogging part.
↓
Display TK1 sensor temperature on 7-segment display with
SW01/02/03=[1] [12] [2].
↓
Check TK1 sensor temp approx. 10 minutes after compressor 1 has operated.
No
Is TD2 sensor Correct installation of sensor.
If low temperature continues (approximately outside temp) or temperature has installed correctly?
little change, a clogging of strainer of oil-equalization circuit, clogging of
capillary tube, or malfunction of check valve is considered.
Yes
- 174 -
No trouble
Com-
pressor Is there no
Check I/F P.C. board 1 Correct miswiring/misinstallation.
miswiring or Yes
TD1: CN502, white
misinstallation on
TD1/TD2 TD2: CN503, pink
sensors?
(TK1) No
Are resistance No
characteristics of TD2 Sensor trouble Replace the sensor.
sensor normal?
Yes
No
Correct miswiring/misinstallation.
Is there TD1: CN502, white
no miswiring or Yes
misinstallation on TD2: CN503, pink
TD1/TD2/TK1/TK2 TK1: CN531, black
sensors? TK2: CN532, green
No
Are
characteristics of TK2 No
sensor resistance Sensor trouble
value normal? *See "Outdoor unit temperature sensor
characteristics" on "8-10. Sensor Characteristics".
After resetting
the power Yes
- 175 -
No trouble
Com-
Check I/F P.C. board pressor
2
(TK2)
Check code Check code name Cause Check code Check code name Cause
Two or more prior indoor units exist. Outdoor units model disagreed trouble When the indoor unit that does not correspond is
[L05] Duplicated indoor units with [L02]
connected with the outdoor unit
priority
(Displayed on indoor unit with
priority)
1) Check whether the connection on remote controllers (group and/or individual) has been changed since the
group configuration and address checking on the remote controllers finished.
Check code Check code name Cause
2) If the group configuration and address are normal when power has been turned on, the mode automatically
[L06] Duplicated indoor units with priority Two or more indoor units with priority are duplicated. shifts to address setup mode. For setting up addresses again, refer to "Address setup".
(Displayed on the indoor units other than
ones with priority and on the outdoor unit)
When priority is given to two or more indoor units, this check code is displayed on indoor units other than the units
set as prior ones and the outdoor unit. Check code Check code name Cause
• As only one indoor unit with priority is valid, change the setup.
[L04] Duplicated setup of outdoor line Outdoor line addresses are duplicated.
address
- 176 -
indoor unit
No
Are
communication
wire connections of No
Yes Check the addresses of setup [U1.U2], [U3.U4], and Correct the wire connection.
Is there group cabling?
item code DN 12, 13, and 14. [U5, U6] normal?
Yes
No
No
• SMMS-7 series outdoor unit can't be connected with another SMMS series
outdoor unit (SMMS* series unit). Use it with same SMMS-7 series unit. Are powers of all the No
• MAP2207* and MAP2407* can't combine with another unit. indoor units turned on? Turn on the power of indoor units.
Yes
- 177 -
Check code Check code name Cause [L09] Indoor capacity unset Indoor unit's capacity is unset
Is
communication
connector between IPDU No
and I/F P.C. board
Correct connection of connector.
Yes Check power voltage and connected?
Is there any trouble
of outdoor unit power line.
- 178 -
supply? Check auxiliary noise, etc. Yes
No
Is there
no disconnection of Yes
communication line between Replace communication line.
Check outdoor I/F P.C. IPDU and I/F P.C.
board. board?*
No
Is there
Check code Check code name Cause voltage fluctuation
between 4 and 5 pins of No
[P01] Indoor fan motor trouble 1. Wiring trouble CN600 on I/F P.C. board? I/F P.C. board trouble
2. Check fan motor. (Measurement by tester:
DC0 to 5V,
5 pin GND)
* For the models equipped with AC fan motor only
Yes
Is there no
connection trouble or Yes Correct cabling circuit for
disconnection of CN076 the connector connection. Is there
connector? voltage fluctuation
between 3 and 5 pins of No
No CN600 on I/F P.C. board? I/F P.C. board trouble
(Measurement by tester: In the case that All IPDUs (A3- IPDUs and fan IPDUs) do
DC0 to 5V, not return response.
5 pin GND) * Two A3-IPDUs (NO. 1 and 2) exist in all models.
From 8 to 20 HP models, one Fan-IPDU exists.
Is not there lock of fan Yes Yes From 22 to 24 HP models, two Fan-IPDUs exist.
Replace fan motor.
motor?
Yes
Are parts of high- No Check parts.
pressure SW normal? Are
Failure Replace characteristics of No
TD1 sensor resistance Replace TD1 sensor.
No normal? * See “Outdoor unit temperature sensor
Yes Is circuit cabling Check and correct characteristics” on “8-10. Sensor Characteristics”.
normal? cabling. Yes
Yes SV4 circuit
No 1. Are SV41 and SV42
Is service valve fully Open service valve Correct installation of valve
valve coils No
opened? fully. installed correctly? coil.
2. Is SV41 circuit sealed Replace SV41 valve.
Yes
correctly (no leakage)?
Reset power supply, and start a test Cooling To (B)
operation corresponded to the season. Yes
- 179 -
No
Are characteristics of Replace the high-
high-pressure sensor pressure sensor. Are indoor units of a Yes
Correct wiring
normal? different refrigerant line
connected? (Check it using the miswiring check
function of the outdoor unit.)
(B) Cooling operation No
Yes
Is there any
interference of heat- Yes
exchanging of outdoor unit? Eliminate the
1. Heat exchanger clogging interference.
2. Air short circuit
No
Sub-code:
01: Compressor 1,
02: Compressor 2
No
Is power voltage Correct power line.
normal?*
* 380-415V±10%
Yes
- 180 -
No Correct wiring to
Is wiring of A3-IPDU compressor or connector
normal?
connection.
Yes
No
Is indoor fan normal? Check fan and fan motor.
Yes
No
Is there no
clogging of heat Yes
Clear clogging.
sink cooling duct?
No
Yes
No
Yes
Yes
Is Check indoor P.C. board.
resistance value Failure Replace
between each phase at No
motor side of fan motor connector Replace indoor fan motor.
CN333 on indoor P.C.
board (MCC-1402) * 1
• Is not winding 1 (Red lead) to 3 (White lead), 3 (White lead) to 5 (Black lead), 5 (Black Does drain pump No
correct? *1
lead) to 1 (Red lead) opened/shorted? Resistance value should satisfy the follows. operate?
Yes [4-way Cassette type]
AP007 to AP030: Approx. 70 to 100Ω
AP036 to AP056: Approx. 35 to 50Ω
[2-way Cassette type] Yes
Is power supply to No Check indoor P.C. board.
AP007 to AP015: Approx. 70 to 100Ω drain pump normal?* Failure Replace
- 181 -
AP018 to AP030: Approx. 30 to 70Ω
AP036 to AP056: Approx. 20 to 50Ω
[1-way Cassette type]
Approx. 30 to 70Ω Yes
[Ceiling type]
AP015 to AP027: Approx. 30 to 70Ω
AP036 to AP056: Approx. 20 to 50Ω
[High Wall and concealed duct types] Check drain pipe, etc. Replace drain pump, and check cabling.
Approx. 15 to 35Ω
Is resistance • Is not grounded between cabinet and 1, 3, 5? Should be 10MΩ or more.
value at motor side of fan * Check there is 220-240V voltage of 1-3 pin of CN68 on indoor P.C. board.
No
motor connector CN334 on Replace indoor fan motor.
indoor P.C. board (MCC- *2
1402) correct? *2 Check resistance value of fan motor position detective circuit.
• Is not winding 1 (Yellow lead) to 4 (Pink lead)
Yes opened/shorted? Resistance should be 5 to 20kΩ.
Is output
of indoor fan motor No
position detective signal Replace indoor fan motor.
correct? *3 *3
Check fan motor position detective signal.
• Measure voltage with tester between 1 and 5 of CN334 on
Yes indoor P.C. board (MCC-1402) under condition of CN333
and CN334 installed and power-ON. Turn fan slowly with
hands so that pin voltage fluctuates between 0 and 5V.
• Between 4 and 5: 5V Check indoor P.C. board
(MCC-1402).
Failure Replace
CN333
CN334
Check code Check code name Cause Check code Check code name Cause
[P13] Outdoor liquid back 1. TS3 sensor trouble [P13] Outdoor liquid back 1. TS3 sensor trouble
detection trouble 2. TL1, TL3 sensor trouble detection trouble 2. PS sensor trouble (TU trouble)
3. PS sensor trouble (TU trouble) 3. Outdoor PMV4 trouble
(Header unit) (while compressors ON) 4. Outdoor PMV4 trouble (Follower unit) (while compressors OFF) 4. Leakage of outdoor PMV4
5. Leakage of outdoor PMV4
YES YES
NO Is operations of outdoor NO
Is operations of outdoor PMV4 trouble PMV4 trouble
PMV4 normal? PMV4 normal?
YES YES
No No
- 182 -
Is there no miswiring or Is there no miswiring or Correct miswiring/misinstallation.
TS3:CN903, TL1:CN523 misinstallation on TS3:CN903, TO:CN507
misinstallation on sensors?
TL3:CN902, TO:CN507 sensors?
No No
NO Is characteristic of PS sensor NO
Is characteristic of PS sensor PS sensor trouble PS sensor trouble
output voltage normal? output voltage normal?
*See "Outdoor unit pressure sensor characteristics" *See "Outdoor unit pressure sensor characteristics"
on "8-11. PS sensor Characteristics." on "8-11. PS sensor Characteristics."
YES YES
PMV4 leakage. Replace PMV4. PMV4 leakage. Replace PMV4.
Check code Check code name Cause
Check code Check code name Cause
[P15] Gas leak detection 1. Outdoor unit service valve closed
[P15] Gas leak detection 1. Outdoor unit service valve closed
2. Outdoor PMV trouble
2. Outdoor PMV trouble TS condition (Sub-code: 01)
TD condition (Sub-code: 02) 3. TS1 sensor trouble
3. TD sensor trouble
4. Refrigerant shortage, clogging refrigerant circuit
4. SV4 circuit trouble
5. SV4 circuit trouble
5. Refrigerant shortage, clogging refrigerant circuit
Yes Yes
Are Are
characteristics characteristics No
No Replace TD1 and TD2 of TS1 sensor Replace TS1 sensor.
of TD1 and TD2
sensor resistance sensor. resistance * See “Outdoor unit temperature sensor
* See “Outdoor unit temperature sensor normal?
normal? characteristics” on “8-10. Sensor Characteristics”. characteristics” on “8-10. Sensor Characteristics”.
Yes
Yes
Is there any
Is SV4 valve No
No leakage on SV41 Repair SV41/SV42 valve
circuit normal?
Repair SV4 valve circuits. and SV42 valve circuits.
(Coil misinstallation,
circuits?
valve leakage)
- 183 -
(Coil, valve body, coil installation, (Coil, valve body, disconnection
disconnection of cable, etc.) Yes of wire, etc.)
Yes
Are not indoor Refrigerant shortage, (Check there is no clogging and pipe
units in different
Yes
Correct wiring. clogging, pipe breakage. breakage, and then recharge refrigerant.)
refrigerant circuit
connected? (Check it using the miswiring check
function of the outdoor unit.)
No
- 184 -
correctly (no leakage)?
No (Connector connection, fan IPDU,
fan motor, cabling)
Yes
Is there any
interference of heat- Yes
exchanging of outdoor unit?
1. Heat exchanger clogging Eliminate the interference. Are indoor units of a Yes
2. Air short circuit different refrigerant line Correct wiring
connected? (Check it using the miswiring check
function of the outdoor unit.)
No
No
Is CHECK VALVE No Replace CHECK VALVE Refrigerant shortage, (Check there is no pipe breakage, and
in liquid line normal? in liquid line clogging, pipe breakage then recharge the refrigerant.)
Yes
Is SV2 bypass No
circuit normal? Repair SV2 bypass circuit.
Sub-code:
∗0: short circuit
∗1: Position detection circuit trouble
∗3: Motor lock
∗4: Motor current trouble detected
∗C: TH sensor temperature trouble
∗D: TH sensor trouble
∗E: Fan Vdc trouble
∗: Fan1,2:Fan2
Is wire
connector connection No Correct wire connector
on fan IPDU P.C. board connection.
normal?
Yes
No
Is the resistance of No
the motor's winding Replace motor.
- 185 -
wire normal? *Resistance of the winding: 8.1-9.9Ω (between R-S, R-T and S-T)
Yes
Is sub-code of Yes
outdoor I/F P.C. Replace fan IPDU.
board [0*]?
No
Is there
no problem such as
stuffing or blast blowing
Yes
Clear the cause of overload.
to discharge port of
outdoor fan?
No
Sub-code:
01: Compressor 1, 02: Compressor 2
Sub-code:
01: Compressor 1, 02: Compressor 2
Are connector Check and correct circuit and
No
connection and wiring cables such as wiring to
normal? compressor, etc.
Is power voltage No
of outdoor unit
Correct power line.
Yes
normal?
Yes Yes
Is the unit grounded? Compressor trouble Replace
No
No
- 186 -
No
Yes
No
Is compressor Replace compressor.
normal?
Yes
When the header unit of the group detected trouble [E03], [L03], [L07] or [L08], the follower unit of the group
displays [P31] trouble and stops. There are no check code display and alarm record of the main remote controller.
8-6. 7-Segment Display Function
7-segment display on outdoor unit (interface P.C. board)
The interface control P.C. board features a 7-segment LED display designed to check operational status. Display
items can be changed by changing the combination of the number settings of rotary switches provided on the P.C.
board (SW01, SW02 and SW03).
Interface P.C. board
Rotary switches
4 Perform checks in accordance with the diagnostic procedure applicable to the check code.
- 187 -
(1)Display of System Information (Displayed on Header Outdoor Unit Only)
SW01 SW02 SW03 Display detail
1 − −
14
Optional control Same as above
(BUS line input)
15 – –
16 – –
- 188 -
(2)Display of Outdoor Unit Information (Displayed on Each Outdoor Unit)
SW01 SW02 SW03 Display detail
Check code data A Outdoor unit No.: [U1] to [U3]
B Check code (only latest one displayed)
If there is no check code, [– – –] is displayed.
If there is sub-code, check code [ ] and sub-code [– ] are displayed
1
alternately, for 3 seconds and 1 second, respectively.
<SW04> push SW function: Fan operation at outdoor unit with trouble. 7-segment display section A: [E.1]
<SW04 + SW05> push SW function: Fan operation at outdoor unit without trouble. 7-segment display section A: [E.0]
<SW05> push SW function: Fan operation function check mode is cancelled.
– A –
2
B –
Operation mode A Stop [… …]
3 Normal cooling: [… C]
B –
Outdoor unit HP capacity A 8HP: [… 8], 10HP: [… 10], 12HP: [… 12],
4 14HP: [14], 16HP: [16], 18HP: [18], 20HP: [20], 22HP: [22], 24HP : [24]
B […HP]
Compressor operation command * Operation data of each compressor is displayed in turn in 2 second intervals.
1 1 – A –
8
B –
Control valve output data Displays control output status of solenoid valve A B
10 SV2: ON 2. … 100
11 SV3D: ON 3. 0 001
SV41: ON / SV42: OFF 4. … 100
12
SV41: OFF / SV42: ON 4. … 010
13 SV3F : ON A. … ... ... 1
15 PMV4 o pen in g Displays opening data in decimal format. PMV4 … .P
Oil level judgment status
Normal A [o L .]
B Initial display: [… … …], Oil level judgment result: [#. .$]
Displayed letters #, and $ represent judgment results for compressor Nos.
16 1 and 2, respectively (“0” for normal and “1” or “2” for low level).
<SW04> push SW function: Displays low level confirmed judgment result of each compressor.
* Pressing of <SW05> restores A [L d.]
normal display. B Compressor No. 1 low level being confirmed: [L … …]
Compressor No. 2 low level being confirmed: [… L …]
- 189 -
(3)Display of Outdoor Cycle Data (Displayed at Each Outdoor Unit)
SW01 SW02 SW03 Display detail
PD pressure data PD pressure (MPaG) is displayed in decimal format. A B
1
(MPaG: Approx. 10 times magnitude of kg/cm2G) P d. ∗. ∗ ∗
2 PS pressure data PS pressure (MPaG) is displayed in decimal format. P s. ∗. ∗ ∗
3 PL pressure conversion data Converted PL pressure (MPaG) is displayed in decimal format. P L. ∗. ∗ ∗
TD1 sensor data Temperature sensor reading (°C) is displayed Letter symbol td 1 ... ...
4
in decimal format. Data ∗ ∗. ∗ ∗
TD2 sensor data • Letter symbol and data are displayed Letter symbol td 2 ... ...
5
alternately, for 1 second and display for 3 Data ∗ ∗. ∗ ∗
TS1 sensor data seconds, respectively. Letter symbol tS 1 ... ...
7
• Data is displayed in [ ∗ ]. Data ∗ ∗. ∗ ∗
TS3 sensor data • Data with negative value is displayed as [– ∗]. Letter symbol tS 3 ... ...
9
Data ∗ ∗. ∗ ∗
1 2
TE1 sensor data Letter symbol tE 1 ... ...
10
Data ∗ ∗. ∗ ∗
TL1 sensor data Letter symbol tL 1 ... ...
13
Data ∗ ∗. ∗ ∗
TL3 sensor data Letter symbol tL 3 ... ...
15
Data ∗ ∗. ∗ ∗
TO sensor data Letter symbol to ... ... ...
16
Data ∗ ∗. ∗ ∗
- 190 -
(4)Display of Outdoor Cycle Data (Displayed at Header Unit)
* This method is used when displaying follower unit information on the 7-segment display of the header unit.
SW01 SW02 SW03 Display detail
Check code data A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
1 B Check code is displayed (latest one only).
If there is no check code: [– – –].
Type of compressor installed A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
2
B
Outdoor unit HP capacity A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
3 B 8HP: [… 8], 10HP: [… 10], 12HP: [… 12],
14HP: [14], 16HP: [16], 18HP: [18], 20HP: [20], 22HP: [22], 24HP: [24]
Compressor operation command A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
B Indicates which compressor is ON.
Any unconnected compressors is represented by “–”. B
4
Wh en co mpres sor No. 1 is O N 10
1~3
Wh en co mpres sor No. 2 is O N 01
3 Fan operation mode A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
5
B At rest: [F … 0], In mode 63: [F 6 3]
Release signal A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
6
B Normal: [r … …], Upon receiving release signal: [r … 1]
Oil level judgment A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
7
B Normal: [… … …], Low level: [… … L]
Compressor 1 operating current A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
8
B [ . ], . is value of operating current in decimal format.
Compressor 2 operating current A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
9
B [ . ], . is value of operating current in decimal format.
- 191 -
(5) Display of Indoor Unit Information (Displayed on Header Unit Only)
SW01 SW02 SW03 Display detail
4 Indoor BUS communication signal B Upon receiving signal: [... ... 1], Other times: [... ... ...]
receiving status
5 Indoor check code B No check code: [– – –]
Note: Indoor address No. is selected by setting SW02 and SW03 and displayed on 7-segment display, section A.
SW02 SW03 Indoor address 7-segment display section A
1 SW02 setting number [01]~[16]
11
2 SW02 setting number +16 [17]~[32]
1~16
12
3 SW02 setting number +32 [33]~[48]
13
4 SW02 setting number +48 [49]~[64]
14
(6) Display of Outdoor EEPROM Writing Check Code (Displayed on Header Unit Only)
* The latest check code written in the EEPROM of each outdoor unit is displayed.
(This function is used to check the check code after the resetting of the power supply.)
To display the check code, push SW04 and hold for at least 5 seconds after setting SW01 to 03 as shown in
the table below.
• 7-Segment Display
Section A Section B
D600 D601 D602 D603 D604
Set SW01/SW02/SW03 to [1/1/16] and push SW04 and hold for at least 5 seconds. The latest check code of
the header unit (U1) will be displayed.
If the setting of SW02 is changed, the latest check code of a follow unit (U2-U3) will be displayed.
- 192 -
8-7. Oil Level Judgment Display
The current compressor oil level judgment results can be accessed by setting the switches provided on the
interface P.C. board of an outdoor unit.
Perform the checks in accordance with the procedure described below.
1 Operation Procedure
(1) Start the operation.
(2) Set the switches provided on the interface P.C. board of the outdoor unit for which oil level judgment results are
required as follows:
SW01/SW02/SW03 = 1/16/1
(3) The oil level judgment result will be displayed on the 7-segment display.
7-segment display: [oL] [#. .$]
The letters #, and $ are digits that represent judgment results for compressor Nos. 1 and 2, respectively.
(See the table below for the interpretation of the judgment results.)
(4) When checking is completed, revert the SW01/SW02/SW03 setting to [1/1/1].
Interface P.C. board of outdoor unit for
which oil level judgment results are
1
Start operation.
3
Oil level judgment
results are displayed
2 4
Set SW01/SW02/SW03 to Upon completion of checking, revert
1/16/1. SW01/SW02/SW03 setting to 1/1/1.
Display example
7-segment display [ oL ] [ 0 0 ] Oil level is normal for compressors 1 and 2.
[ oL ] [ 2 2 ] Oil level is low for compressors 1 and 2.
[ oL ] [ 0 2 ] Oil level is low for compressor 2 and normal for compressors 1.
- 193 -
8-8. SMMS-7 Outdoor Interface P.C. Board Function Setting
Exchange Table
1. Switch/Function Setting Exchange
Initial setting
Part type Exchange contents
at shipment
bit 1 Compressor 1 backup OFF: Normal, ON: Backup when compressor 1 OFF
was in trouble
bit 2 Compressor 2 backup OFF: Normal, ON: Backup when compressor 2 OFF
SW06 DIP SW 4 bit was in trouble
All bit1 and 2 are ON: Setup of outdoor unit backup OFF
bit 1 Demand control 1 OFF: 0 to 100%
(Standard specifications) ON : Middle to 100% OFF
Exchange of upper limit regulation
SW07 DIP SW 4 bit
bit 2 Demand control 2 (Expansion function) OFF: 2 steps (Standard)
Exchange of 2 steps to 4 steps of ON : 4 steps OFF
upper limit
bit 3 Judgment of refrigerant OFF: Judgment OFF
over charge ON : No judgment
*1 PMV full open/full close operation by short-circuited CN30/CN31 is for PMV which was selected by setting
of SW12.
- 194 -
2. Switching of Jumper Wire/Function
Setup Function switching setup
O : With jumper, × : Without jumper (Cut)
Initial setting
jumper Part type Exchange contents at shipment
Optional function O Indoor unit at not selected side is kept with waiting status.
J01 Operation mode selection The mode is changed a mode which selected the operation mode of the O
operation switching × indoor unit at not selected side.
Upper limit setup of demand
capacity command in O Approx. 75% (Normal)
J04
corresponding indoor during O
saving operation in indoor × Approx. 60%
Demand control 1 (Standard Normal (3-core wire <Successive MAKE signal> or
J16 specification) O 4-core wire <Successive MAKE or Pulse signal>) O
Corresponds to 2-core wire
× 2-core wire <Successive MAKE signal>
*4 When you replace the board with a service board, be sure to cut the jumper wire matching with the outdoor
unit model to be installed. (The jumper wires J09 to J12 which were mounted at shipment from the factory
are provided to all the boards regardless of model type.)
- 195 -
Interface Board Switches and jumper wire positions to be used in the Function setup
switching table
SW30
ON
Interface P.C.board
1 2
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
SW11 SW12 SW13 SW14
ON ON ON ON
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
SW16 SW17
ON ON
1 2 3 4 1 2 3 4
- 196 -
8-9. Leakage/Clogging of Refrigerating Cycle Circuit
List of Check Codes Generated upon Occurrence of Leakage/Clogging in Outdoor Cycle
or Oil Circuit Part
(MMY-MAP0807*, 1007*, 1207*, 1407*)
Clogging
Location of
Part problem
Unit generating Detected problem and check code Symptom
(see next page) check code
Check valve in liquid pipe section Corresponding unit Activation of high-pressure protection P20 Rise of pressure
Activation of low-pressure protection H06 Fall of pressure
A Discharge temp. trouble (TD1) P03 Rise of discharge
temp. (compressor 1)
Check valve in discharge pipe Corresponding unit High-pressure protection trouble P20 Abnormal rise of pressure
B
High-pressure SW system trouble P04-XX
Oil-equalization circuit capillary Corresponding unit Oil level detection circuit trouble H16-XX Oil circuit trouble or oil
Strainer D Oil level low detection and protection H07 level low
SV3D valve Corresponding unit Oil level low detection and protection H07 Oil level low
SV3D valve circuit capillary E
Strainer
SV3F valve F Corresponding unit Oil level low detection and protection H07 Oil level low
Leakage
Location of Unit generating
Part problem Detected problem and check code Symptom
(see next page) check code
Check valve in liquid pipe section Corresponding unit Outdoor liquid backflow trouble P13 Refrigerant entrapment
Oil level low detection and protection H07
A
Other connected unit Discharge temp. trouble (TD1) P03 Rise of discharge
temp. (compressor 1)
Check valve in discharge pipe Corresponding unit Oil level low detection and protection H07 Refrigerant entrapment
B Compressor breakdown H01-XX
Compressor trouble (lockup) H02-XX
Outdoor PMV4 Corresponding unit Outdoor liquid backflow trouble P13 Oil level low
G Oil level low detection and protection H07
- 197 -
Outdoor unit (8, 10, 12, 14HP)
Model : MMY-MAP0807*, 1007*, 1207*, 1407*
Fan
M
Fan motor
Right side
Heat exchanger (TO)
Left side
Heat exchanger
B
A (TE1)
Sub cool pass
(TL1)
(TS1)
High-pressure
sensor
Low-pressure
sensor
Oil separator
(TS3)
Accumulator
E (SV3D)
(SV2)
SV
SV
(SV41) F
SV (SV3F)
Sub cool
heat exchanger
SV
G (TD1)
High-
pressure
switch
D
(PMV4) Com-
pressor
1
(TL3)
(TK1)
Symbol
Liquid side Gas side
Service valve Service valve SV
- 198 -
List of Check Codes Generated upon Occurrence of Leakage/Clogging in Outdoor Cycle
or Oil Circuit Part
(MMY-MAP14A7*, 1607*, 1807*, 2007*)
Clogging
Location of Unit generating
Part problem Detected problem and check code Symptom
check code
(see next page)
Check valve in liquid pipe section Corresponding unit Activation of high-pressure protection P20 Rise of pressure
Activation of low-pressure protection H06 Fall of pressure
Discharge temp. trouble (TD1) P03 Rise of discharge temp.
Discharge temp. trouble (TD2) P17 (compressor 1)
A
Rise of discharge temp.
(compressor 2)
Check valve in discharge pipe Corresponding unit High-pressure protection trouble P20 Abnormal rise of pressure
B
convergent section High-pressure SW system trouble P04-XX
Check valve in discharge pipe C Corresponding unit High-pressure SW system trouble P04-XX Abnormal rise of pressure
Oil-equalization circuit capillary Corresponding unit Oil level detection circuit trouble H16-XX Oil circuit trouble or
Strainer D Oil level low detection and protection H07 oil level low
SV3D valve Corresponding unit Oil level low detection and protection H07 Oil level low
SV3D valve circuit capillary E
Strainer
SV3F valve Corresponding unit Oil level detection circuit trouble H07 Oil level low
F Oil level low detection and protection
Leakage
Location of Unit generating
Part problem Detected problem and check code Symptom
check code
(see next page)
Check valve in liquid pipe section Corresponding unit Outdoor liquid backflow trouble P13 Refrigerant entrapment
Oil level low detection and protection H07
Other connected unit Discharge temp. trouble (TD1) P03 Rise of discharge temp.
A Discharge temp. trouble (TD2) P17 (compressor 1)
Rise of discharge temp.
(compressor 2)
Check valve in discharge pipe Corresponding unit Oil level low detection and protection H07 Refrigerant entrapment
convergent section B Compressor breakdown H01-XX
Compressor trouble (lockup) H02-XX
Check valve in discharge pipe Corresponding unit Oil level low detection and protection H07 Refrigerant entrapment
C Compressor breakdown H01-XX
Compressor trouble (lockup) H02-XX
Outdoor PMV4 Corresponding unit Outdoor liquid backflow trouble P13 Oil level low
G Oil level low detection and protection H07
- 199 -
Outdoor Unit (14, 16, 18, 20HP)
Model: MMY-MAP14A7*, 1607*, 1807*, 2007*
Fan
M
Fan motor
Right side
Heat exchanger (TO)
Left side
Heat exchanger
B
A (TE1)
Sub cool pass
(TL1)
(TS1)
High-pressure
sensor
Low-pressure
sensor
Oil separator
(TS3)
C
Accumulator
E (SV3D)
(SV2)
SV
SV
(SV41) (SV42) F
SV SV (SV3F)
Sub cool
heat exchanger
SV
G (TD1)
High-
pressure
switch
High-
pressure
switch
(TD2)
D
(PMV4) Com- Com-
pressor pressor
1 2
(TL3)
(TK1) (TK2)
Symbol
Liquid side Gas side
Service valve Service valve SV
- 200 -