The document provides an ice plant flow diagram and calculations. It calculates the required compressor size and power based on mass flow rates and enthalpies at different temperatures. It then sizes key components like the freezing tank, number of ice cans produced, length of evaporator coils, and determines the coefficient of performance is 2.024.

Uploaded by

Gerk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views

Ice Plant Computation

The document provides an ice plant flow diagram and calculations. It calculates the required compressor size and power based on mass flow rates and enthalpies at different temperatures. It then sizes key components like the freezing tank, number of ice cans produced, length of evaporator coils, and determines the coefficient of performance is 2.024.

Uploaded by

Gerk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 6

ICE PLANT FLOW DIAGRAM

Size of Compressor Motor

Brine Tank Temperature -24 °C (-11.2 °F)

Cold Storage Temperature -16 °C (3.2 °F)

Condenser Temperature 40 °C (104°F)

h3 = h4 = h7 = hf @ 40 °C 390.587 kj/kg

h5 = h6 = hg -16 °C 1442.6 kj/kg

h8 = hg = -24 °C 1431.64 kj/kg

Cold Storage (-16 °C)

75
𝑚4 =
1442.6 − 390.587
𝑚4 = 0.07129189468 𝑘𝑔/𝑠

Brine Tank (-24 °C)

125
𝑚7 =
1431.64 − 390.587
𝑚7 = 0.1200707361 𝑘𝑔/𝑠

𝑚1 = 𝑚4 + 𝑚7

𝑚1 = 0.07129189468 + 0.1200707361

𝑚1 = 0.1913626308 𝑘𝑔/𝑠
𝑚1 ℎ1 = 𝑚6 ℎ6 + 𝑚8 ℎ8

0.1913626308ℎ1 = 0.07129189468(1442.6) + 0.1200707361(1431.64)

ℎ1 = 1435.72134 𝑘𝑗/𝑘𝑔

ℎ2 = ℎ @1557 𝑘𝑝𝑎

ℎ2 = 1780 𝑘𝑗/𝑘𝑔

𝑃𝑜𝑤𝑒𝑟 = 𝑚1 (ℎ2 − ℎ1 )

𝑃𝑜𝑤𝑒𝑟 = 0.1913626308 (1780 − 1435.72134)(1.5)

𝑃𝑜𝑤𝑒𝑟 = 65.88(1.5) = 98.82 𝑘𝑤

𝑃𝑜𝑤𝑒𝑟
𝑇𝑅 =
3.52
98.82
𝑇𝑅 =
3.52
𝑇𝑅 = 28.07 → 28.2 → 15 𝑡𝑜𝑛𝑠 𝑝𝑒𝑟 𝑑𝑎𝑦

Freezing Tank

Design Condition:

Production Rate 15 tons/day

Ice Temperature -10 °C (14 °F)

Brine Temperature -24 °C (-11.2 °F)

Raw Water Temperature 25 °C (77 °F)


Ice Can Dimension 0.57mx0.29mx1.145m

(22.44”x11.42”x45.08”)

Weight of Ice per Can 300 lbs (136kg)

Freezing Time:
7𝑥 2
TF = 32−𝑡
𝑏

7(11.42)2
TF = 32−(−11.2)

TF = 21.13 hrs = 21 hrs, 7 mins & 48 secs

𝑃𝑟𝑜𝑑𝑢𝑐𝑡 𝑅𝑎𝑡𝑒
Block per Day = 𝑊𝑒𝑖𝑔ℎ𝑡 𝑜𝑓 𝐼𝑐𝑒

15000 𝑘𝑔/𝑑𝑎𝑦
Block per Day = 136 𝑘𝑔/𝑐𝑎𝑛

Block per Day = 110.29 ≈ 111 Blocks per Day

𝑃𝑟𝑜𝑑𝑢𝑐𝑡𝑖𝑜𝑛(𝑇 )
𝑓
No. of Ice Can = 𝑊𝑒𝑖𝑔ℎ𝑡 𝑜𝑓 𝐼𝑐𝑒 𝐵𝑙𝑜𝑐𝑘/𝑐𝑎𝑛

1
15(21.13)( )
24
No. of Ice Can = 𝑙𝑏𝑠 1 𝑇𝑜𝑛𝑠
300 ( )
𝑐𝑎𝑛 2204.613

No. of Ice Can = 97.048 cans ≈ 98 cans

Length of Cooling Coil

Q = Cooling Load

U = Overall heat transfer coefficient

Brine temperature before cooling = 27 ˚C

Brine temperature after cooling = -8˚C

Refrigerant temperature entering evaporator = -10 ˚C


Refrigerant temperature leaving evaporator = 7 ˚C

Q = (U)(Am)(LMTD)
∆𝑇𝑏 − ∆𝑇𝑎
LMTD = ∆𝑇𝑏
𝑙𝑛
∆𝑇𝑎

∆T𝑏 = 27— (5 )

∆T𝑏 = 20 ˚C

∆T𝑎 = −8 − (−10)

∆T = 2
22− 2
LMTD = 22
ln
2

LMTD = 8.34 ˚C

Area of evaporator in Brine Tank :


Q
Aevap. = U(LMTD)

125 𝑘𝑤
Aevap. = W
(0.6 2 )(8.34˚K)
m −˚W

Aevap. = 24.98 m2

Area of evaporator in Cold Storage :


𝑄
Aevap. = 𝑈(𝐿𝑀𝑇𝐷)

75 𝑘𝑤
Aevap. = 𝑊
(0.6 2 )(8.34˚𝐾 )
𝑚 −˚𝑊

Aevap. = 14.99 m2

Length of evaporator coil in brine tank


A
L = π x Do

24.98 m²
L = π x 0.0254

L = 313.046 m
Length of evaporator coil in Cold Storage
A
L = π x Do

014.99 m²
L = π x 0.0254

L = 187.85 m

Coefficient of Performance (COP)

𝑇𝑜𝑡𝑎𝑙 𝑅𝑒𝑓𝑟𝑖𝑔𝑒𝑟𝑎𝑡𝑖𝑛𝑔 𝐿𝑜𝑎𝑑


𝐶𝑂𝑃 =
𝐶𝑜𝑚𝑝𝑟𝑒𝑠𝑠𝑜𝑟 𝑃𝑜𝑤𝑒𝑟

125 + 75
𝐶𝑂𝑃 =
98.82
𝐶𝑂𝑃 = 2.024