SEBA KMT EasyflexCom
SEBA KMT EasyflexCom
Easyflex Com
Elektrizitätsnetze
Power Networks
Kommunikationsnetze
Communication Networks
Rohrleitungsnetze
Water Networks
Leitungsortung
Line Location
Time-Domain Reflectometer
MAN_Easyflex_com_eng_01.doc 3
4 MAN_Easyflex_com_eng_01.doc
TABLE OF CONTENTS
1 GENERAL ..................................................................................... 9
1.1 Advice from Hagenuk KMT GmbH ......................................................... 9
1.2 Terms and conditions of warranty ........................................................ 10
1.3 Safety Instructions ................................................................................ 11
1.4 Indications used in the description ....................................................... 12
2 TECHNICAL DESCRIPTION....................................................... 13
2.1 General Description.............................................................................. 13
2.2 Specifications........................................................................................ 15
2.3 Items Supplied and Optional Extras ..................................................... 19
3 OPERATION................................................................................ 21
3.1 Measuring Terminals ............................................................................ 21
3.2 Display .................................................................................................. 22
3.3 Functions of Keys and Rotary Encoder................................................ 24
3.4 Getting Started (Insert / Replace Accumulator) ................................... 27
3.5 Switching On and Off............................................................................ 27
3.6 Main Menu ............................................................................................ 28
3.7 Compensation of Initial Reflection........................................................ 28
3.8 How to Locate a Fault........................................................................... 29
3.8.1 Fields of Application .......................................................................... 30
3.8.1.1 Faults Causing a Negative Reflection ..................................... 30
3.8.1.2 Faults Causing a Positive Reflection....................................... 31
3.8.1.3 Further Fields of Application ................................................... 32
3.8.2 Testing a Cable with Known Nominal Velocity of Propagation NVP or
with Known Pulse Propagation Velocity (v/2) .............................................. 33
3.8.3 How to Determine an Unknown Nominal Velocity of Propagation or
Pulse Propagation Velocity......................................................................... 35
3.8.4 Simplification of Fault Location Using Comparative Tests ................ 35
3.8.5 Averaging........................................................................................... 36
3.8.6 Mode NEXT ....................................................................................... 37
3.8.7 How to Use the Marker...................................................................... 38
3.8.8 Change of Pulse Width...................................................................... 39
3.8.9 Self Test............................................................................................. 40
3.9 Memory Function .................................................................................. 41
3.10 Serial Interface ................................................................................... 43
4 NIMH ACCUMULATOR CHARGER ........................................... 44
4.1 Technical Description ........................................................................... 44
4.1.1 Specification ...................................................................................... 44
4.1.2 Start-Up ............................................................................................. 45
MAN_Easyflex_com_eng_01.doc 5
4.1.3 General Instructions on How to Handle a NiMH Accumulator .......... 46
4.2 Operation .............................................................................................. 47
4.2.1 Safety Precautions............................................................................. 47
4.2.2 Modes of Operation ........................................................................... 47
4.2.3 Practical Hints .................................................................................... 48
4.3 Troubleshooting .................................................................................... 49
5 CARE UND MAINTENANCE....................................................... 49
6 APPENDIX ................................................................................... 50
6.1 List of Abbreviations Used .................................................................... 50
6.2 Conversion: NVP ⇔ v/2 ......................................................................... 51
6.3 Table: NVP and v/2 for Common Types of Cables ................................ 52
6.4 Glossary................................................................................................ 54
6 MAN_Easyflex_com_eng_01.doc
EC - Declaration of Conformity
CE Mark
We, the company Hagenuk KMT
Kabelmesstechnik GmbH
Roederaue
D-01471 Radeburg
Germany
declare under sole responsibility that our product
Easyflex Com
is in conformity with the directive of the Council of European Communities for
the Harmonization of the Laws of Member States on Electromagnetic
Compatibility (EMC Directive 89/336/EEC) and Low Voltage (Directive
73/23/EEC).
MAN_Easyflex_com_eng_01.doc 7
8 MAN_Easyflex_com_eng_01.doc
1 GENERAL
1.1 Advice from sebaKMT
SERVICE-HOTLINE :
e-mail: [email protected]
internet: http://www.sebakmt.com
MAN_Easyflex_com_eng_01.doc 9
1.2 Terms and conditions of warranty
Hagenuk KMT guarantees that Hagenuk KMT products are at the time of
their delivery free from defects in workmanship or materials which
substantially reduce their value or serviceableness. This warranty does not
cover faults in supplied software. During the warranty term Hagenuk KMT
will repair defective parts or replace them with new or as-new parts (with
the same operability and service life as new parts) at its option.
Additional warranty claims, in particular claims arising from consequential
loss, cannot be asserted. All parts and products replaced under the terms
of this warranty become the property of Hagenuk KMT.
Warranty claims on Hagenuk KMT lapse 12 months after the delivery date.
Parts supplied by Hagenuk KMT within the framework of the warranty are
also covered by this warranty for the remaining warranty term, but for no
less than 90 days.
Warranty measures are undertaken exclusively through Hagenuk KMT or a
special service shop which is authorized by Hagenuk KMT.
Claims under the terms of this warranty are subject to the buyer notifying
Hagenuk KMT of defects without delay and no later than within 10 days of
the delivery date in the case of perceptible defects.
This warranty does not cover defects or damage caused by the products
being exposed to conditions which are not in accordance with the
specifications, being stored, transported or used incorrectly, or being
serviced or installed by agencies not approved by Hagenuk KMT. The
warranty does not cover damage owing to natural wear and tear, force
majeure or connection to external parts.
Hagenuk KMT is only liable for claims for damages arising from the
violation of claims for repair or replacement in the event of gross
negligence or intent. Any liability for ordinary negligence is ruled out.
10 MAN_Easyflex_com_eng_01.doc
1.3 Safety Instructions
GENERAL INSTRUCTIONS
Work on the Easyflex Com and its peripherals must only be carried out by
trained and/or instructed staff. Other persons must be kept away.
This manual must be available for the supervisory, operating and
maintenance staff to refer to.
Improper use may endanger life and limb, the Easyflex Com and
connected equipment, as well as the efficient functioning of the unit
(accident prevention regulations). The Easyflex Com may only be used for
the purpose for which it is intended by the manufacturer.
Always use the correct tools in perfect condition for all work.
Regular checks must be made to ensure that the relevant safety
regulations are being complied with during operation and maintenance.
Never operate the Easyflex Com and its peripherals if they are not in a
technically perfect condition.
Only parts specified by Hagenuk KMT as accessories must be used for the
Easyflex Com and its peripherals, as the necessary safety will not
otherwise be guaranteed. No mode of working which detracts from the
safety of the Easyflex Com must be used.
Replace a accumulator only when the device is switched off and
disconnected.
MAN_Easyflex_com_eng_01.doc 11
The user is under an obligation to report any changes in the Easyflex Com
to the supervisor responsible without delay.
The operator is under an obligation to shut the Easyflex Com down
immediately in the event of a malfunction which detracts from the safety of
staff. The Easyflex Com must only be put back into operation once the
malfunction has been rectified.
ELECTROTECHNICAL INSTRUCTIONS
Connect the Easyflex Com and all its accessories according to instructions
and regulations. Make sure the relevant regulations such as EN, DIN, VDE
or national standards, respectively, are observed.
Repair and maintenance work must only be carried out when the unit is
switched off (dead) and then only by a skilled electrician in accordance with
current accident prevention regulations. A skilled electrician in the sense of
the accident prevention regulations is a person who can assess the work
assigned to him/her and recognise possible dangers on the basis of his/her
technical training, knowledge and experience, and of his/her knowledge of
the relevant regulations.
12 MAN_Easyflex_com_eng_01.doc
2 TECHNICAL DESCRIPTION
2.1 General Description
The Easyflex Com is similar to radar in that it employs the pulse reflection
technique. Suitable test pulses are transmitted into the cable to be tested.
The pulses travel along the cable at a propagation velocity that is
dependent on the connected test object. In every place where the electric
characteristics of the cable have changed, part of the transmission pulse is
reflected and caused to travel back to the Easyflex Com where it will be
displayed on the screen with a time delay corresponding to its propagation
time.
The propagation time of the test pulse which is dependent mainly on the
material of cable insulating material is taken into account by specifying a
signal propagation velocity.
MAN_Easyflex_com_eng_01.doc 13
For measuring the distance to the fault, a movable cursor or a combination
of marker and cursor are used. Distance is display in m, ft, or µs as
selected by the user. In order for the distance to be indicated in m or ft, the
pulse propagation velocity of the cable under test has to be entered before
the test is carried out.
The greatest advantage of the pulse reflection method is its ability not only
to find out that there is a fault but also to find its location and type.
The Easyflex Com allows two cables under test to be connected to L1 and
L2 at the same time and to show two reflectograms simultaneously. This
can be done using currently taken reflectograms or test results stored in
memory.
There are two display modes the user can choose between. When you
wish to get a revealing overview of the cable under test and, at the same
time, have a closer look at a cable section, you can choose the display
mode which divides the screen of the Easyflex Com into two windows. The
upper window shows the full distance range with a movable window
marking a section the content of which is displayed zoomed in the lower
window. There is yet another display mode with a full-screen display of the
selected cable section.
14 MAN_Easyflex_com_eng_01.doc
2.2 Specifications
Modes of testing:
L1: Reflection test of cable connected to
socket L1 versus built-in balancing
network
L2: Reflection test of cable connected to
socket L2 versus built-in balancing
network
Alt: A reflection test is carried out alternately on
cables connected to sockets L1 / L2
Diff: Measurement of difference between
cables connected to sockets L1 and L2
NEXT: Location of crosstalk between cables
connected to sockets L1 and L2
Pairs to be connected: 2
Modes of operation:
Single Single test
Cont Continuous testing
Average Averaging of up to 256 test results
MAN_Easyflex_com_eng_01.doc 15
Maximum resolution 1.25 cm for range 50 m at 50 m/µs
2.5 cm for range 50 m at 100 m/µs
2.5 cm for range 100 m
5 cm for range 200 m
10 cm for range 400 m
25 cm for range 1000 m
50 cm for range 2000 m
1m for range 4000 m
2.5 m for range 7500 m
5m for range 15 km
16 MAN_Easyflex_com_eng_01.doc
Pulse width Pulse width is linked to range of
measurement:
5 ns for range 50 m (100 m/µs)
5 ns for range 100 m
10 ns for range 200 m
20 ns for range 400 m
50 ns for range 1 km
200 ns for range 2 km
200 ns for range 4 km
750 ns for range 7,5 km
750 ns for range 15 km
MAN_Easyflex_com_eng_01.doc 17
Environmental conditions
Operating temperature -10 °C … +50 °C
Storage temperature -20 °C … +60 °C (without accum ulator)
Storage temperature -20 °C … +50 °C
(accumulator)
18 MAN_Easyflex_com_eng_01.doc
2.3 Items Supplied and Optional Extras
Items supplied:
Description
Easyflex Com, consisting of
Easyflex Com
(G,E, two languages on request)
- 2 pcs. set of test leads
- Case for Easyflex Com
- Accumulator 7,2 V / 1,7 Ah / NiMH
- Charge case
- Plug-in mains unit, for charger
case;
according to country:
EURO 230 V / 50 Hz
USA 120 V / 60 Hz
UK 230 V / 50 Hz
- Instruction manual, according to
country:
German
English
More languages on request
MAN_Easyflex_com_eng_01.doc 19
Optional Extras:
20 MAN_Easyflex_com_eng_01.doc
3 OPERATION
MAN_Easyflex_com_eng_01.doc 21
3.2 Display
The LC-Display has 256 x 128 pixels, controls for setting contrast, and
switchable back lighting. This enables graphic information to be readable
even in difficult lighting conditions.
Comp ...Ω
Trace
2 3 2nd
There are two modes of displaying the reflectograms: Press ”Display” when
you want to work with two images of the trace, see Fig 3. The upper is the
reflectogram of the full range of measurement. There is a black bar below
this overview indicating a section the position of which can be moved by
means of the cursor. The lower and larger part of the display shows this
black section magnified in full detail.
22 MAN_Easyflex_com_eng_01.doc
Use the cursor when you want to change the position of the section and
change the X zoom factor when you want to change the width of the
section.
The LC display will display a warning signal top left when the remaining
charge of the accumulator is insufficient for further operation. Replace the
accumulator or charge it in order to restore readiness for operation. Switch
the instrument off before replacing the accumulator to retain all data.
Press one of the following keys for ca. 1.5 s to return to the default value.
MAN_Easyflex_com_eng_01.doc 23
3.3 Functions of Keys and Rotary Encoder
How to proceed:
• press key(s) to call function
• use rotary encoder for selection
When you press the help key (?) the Easyflex Com will display informations
on one of the following topics :
(key ?; select with rotary encoder; press key Mark, key ? for return):
• Information on help
• Fault location
• Operation
• Compensation
• Averaging
• Mode of display
• NVP or v/2
• Types of cables
• Storage
• Device set-up
• Self test (via 2nd Menu)
• Accumulator charging
• DC external
• 2nd keys
24 MAN_Easyflex_com_eng_01.doc
Marker:
Activate cursor; move
cursor to start point of Cursor
measurement; set
marker
Cancel
Range(Measuring Range)
X-Zoom
Gain, dB
Compensation
Propagation velocity /
NVP
Modes:
Single
Single or Dual Display Continuous
Average
Menu
Menu/Units Mode of connection:
Menu/Interface L1, L2, ALT (alternating)
Menu/Printer Diff (Difference L1-L2)
Menu/System NEXT (cross talk)
Menu/Power supply
Second key functions
Help
MAN_Easyflex_com_eng_01.doc 25
Possible settings in Menu:
Parity None
(Parity bit) Even
Odd
Menu/Printer Printer HP Deskjet
Epson compatib.
Epson 9 pin
Kodak Diconix
Layout Normal
Special
Menu/System Self test Software version
Serial number
26 MAN_Easyflex_com_eng_01.doc
3.4 Getting Started (Insert / Replace Accumulator)
Press key to switch the Easyflex Com on. During run-up the
manufacturer’s logo will be shown for about 2 seconds.
After run-up has been completed, the Easyflex Com can be switched off any
time by pressing key . When being switched off the device saves all
device settings, so the same operating status is restored when the
instrument is switched on next time.
The Easyflex Com cuts back its function automatically some time after a key
has been pressed last time in order to save accumulator power:
• The device is switched off after 360 sec,
• The back light of the display is switched off after 60 sec,
• The reduction of measuring rate is disabled
These default values as mentioned above can be changed in menu Power
Supply.
Key operations: 2nd; Menu; rotary encoder to Supply menu; Mark; rotary
encoder for Vertical selection; Mark; use rotary encoder to set Time; Mark;
Display
MAN_Easyflex_com_eng_01.doc 27
3.6 Main Menu
Main Menu will appear automatically after the Easyflex Com has been
switched on. In this menu measurements are taken employing the device
settings that were in effect when the device was used last time. Most
functions of Easyflex Com can be started directly from menu Measurement
by means of the keys or rotary encoder as described in section 3.3.
Use key Comp and the rotary encoder to adjust compensation such that
the initial reflection is suppressed on the display. In principle this
adjustment should be made in order to provide for optimum matching of the
Easyflex Com to the impedance of the respective cable so as to be able to
detect and locate a fault at close range, i.e. at a distance of up to 10
meters.
When a faultless pair of conductors of the same type of cable as the faulty
one is available and when it is connect to sockets L2, the impedance of the
faultless cable is used for reference in mode Diff. In this case
compensation is not operational and matching is guaranteed. Use
compensation when no faultless pair of conductors is available. Switch to
mode L1 or L2 according to the socket pair used and select display mode
”DUAL”. Set cursor to distance zero and adjust compensation such that the
upper image of the reflectogram is displayed as a horizontal line, if
possible, and the initial reflection shown in the lower window of the display
shows as small as possible. For facilitating the setting procedure, first set
gain to 0 dB for coarse balancing and then increase it for doing the fine
adjustment.
28 MAN_Easyflex_com_eng_01.doc
3.8 How to Locate a Fault
When you test a defective cable, always obey by the following basic rules:
(3) The Easyflex Com is able to measure the length of the cable and the
distance to a point of fault. It is not able, however, to find out the route
of the cable between the point of measurement and the location of the
fault.
(4) The precision of the distance reading by the Easyflex Com can only be
as good as the precision with which you know the pulse propagation
velocity of the connected cable. In a wet cable the pulse travel time is
increased, so the distance display is too long when the same settings
are used as for a dry cable.
MAN_Easyflex_com_eng_01.doc 29
3.8.1 Fields of Application
The Easyflex Com allows various type of faults to be detected. These are a
few examples:
(1) Short circuit: Direct contact of two conductors of a cable. This will
cause a negative reflection, see Fig 4.
30 MAN_Easyflex_com_eng_01.doc
3.8.1.2 Faults Causing a Positive Reflection
(1) Open circuit: Open circuit means that one or both conductors of a pair
of conductors are broken or have become detached. This will cause a
positive reflection, see Fig 5.
(3) Shield interrupt means that the metal shield of a cable is broken or has
become detached. To locate such faults and to suppress noise signals
on the display, connect the test leads to the shield and to as many
conductors of the cable as possible. This type of fault generates a fault
reflection the size of which is dependent on the resistance of the
interrupt.
(4) Crossed lines (”split pairs”) and restored reversed lines occur when a
telecommunication cable is twisted or untwisted. Usually this may
happen at a cable joint. This phenomenon is one of the main causes
of crosstalk interference. Reversed wires in an untwisted cable will
generate a positive error reflection. If an individual cable is twisted, a
negative error reflection appears. As the distance between the points
of crossing and crossing is usually very small, both reflections occur
almost simultaneously and appear as a single weak reflection.
MAN_Easyflex_com_eng_01.doc 31
(5) A humidity-induced fault is brought about by water penetrating into a
defective line. At the beginning of a wet section a negative reflection
similar to a short-circuit can be observed, followed at the end of the
wet section by a small positive fault reflection typical of an open cable
end. In some cases, e.g. if the moisture gradually increases or
decreases with distance, these points of reflection spread into a
constant up and down in the horizontal traceform. In an old cable
which is wet along its entire length it may be difficult to detect a
moisture-induced fault because the beginning and the end of the zone
of moisture exposure are not clearly marked. It is only in rare cases
that the fault reflection becomes apparent as clearly as for a short-
circuit or broken line. Moisture in a cable filled with petrolatum may
possibly result in very small fault reflections as the volume of moisture
is only limited.
32 MAN_Easyflex_com_eng_01.doc
3.8.2 Testing a Cable with Known Nominal Velocity of Propagation
NVP or with Known Pulse Propagation Velocity (v/2)
In many instances the route and characteristics of the cable are known in
which case the nature and position of the fault can located quickly. In such
circumstances proceed as follows:
(2) Use the test leads supplied with the Easyflex Com to connect the
Faulty pair to Line 1 and, when appropriate, the good pair to Line 2.
(3) Press key to switch the Easyflex Com on. Menu Measurement will
appear after a few seconds.
(4) Press key (Line) to select the appropriate mode of measurement, e.g.
Diff when a good pair is available or L1 when you test the Faulty pair
alone.
(5) Use keys (v/2) and the rotary encoder to set the cable-specific
propagation time to the value specific value of the cable to be tested.
(6) Match the Easyflex Com to the object under test as described in
section 0.
(7) First of all, try to find the (open) end of the cable.
MAN_Easyflex_com_eng_01.doc 33
(8) Look for a fault reflection in the overview trace displayed on top. In
doing so, increase gain or amplitude correction steadily until the point
of fault is clearly visible.
Fig 6. Display
(9) Use the cursor to move the section marker (black bar between the two
traces) such that the reflection is located above the bar. Then use the
rotary encoder to move the cursor in the lower part of the screen to the
place where the foot point of the fault is located (see Fig. 6).
(10) The distance to the fault can now be read off directly. This value can
be indicated in meters, feet, or nanoseconds depending on the setting
in menu Units. The reflectogram can be saved in a the memory for
documentation purposes .
(11) Press to switch the Easyflex Com off after the test has been
completed.
34 MAN_Easyflex_com_eng_01.doc
3.8.3 How to Determine an Unknown Nominal Velocity of
Propagation or Pulse Propagation Velocity
Set the cursor to the foot point of the known reflection. Then adjust the
NVP or pulse velocity setting such that the indicated distance to the fault
correlates with the actual length of the sample. After that the distance to a
fault reflection in the defective cable can be measured.
The reflectogram shown in Fig 6 shows cable and fault in virtually ideal
conditions. In reality, however, there are cable junctions and other
connections resulting in a trace which is normally similar to that shown in
Fig 7 (good pair). In Fig. 8 (Faulty pair), in addition to the fault other cable
reflections are visible which are caused commonly by connections with an
impedance different from that of the line. These jumps in impedance also
appear as reflections and thus render the detection of the reflection caused
by the fault almost impossible. When a multi-pair cable is tested, a
comparative test (see Fig 9) using a good pair (provided that not all
conductors are defective) allows the point of fault to be detected. Connect
the good pair to L2, the faulty pair to L1. Then select mode Alt by pressing
key (Line). Move the cursor to the points where both trace diverge. In Fig
10 mode Diff was used which means that differences between both
reflectograms (fault reflections in the defective cable) occur in places where
the difference on display deviates from the horizontal. Use the cursor to
measure the distance to the foot point of the deviation.
MAN_Easyflex_com_eng_01.doc 35
Fig. 7 Fig. 8
Fig. 9 Fig. 10
3.8.5 Averaging
Interfering noisy signals may make the location of faults very difficult in
particular when a fault has to be located in a long cable and when high gain
is used. In order to solve this problem, the Easyflex Com is equipped with
an averaging mode. Press function key Mode and use the rotary encoder
to enable mode Averaging. The display will display the number of
measurements taken for averaging (max. N256) top right. You can cancel
averaging at any time if the number of measurements taken so far is
sufficient for an efficient interference suppression. Pressing key Start one
more time to start another averaging run.
36 MAN_Easyflex_com_eng_01.doc
3.8.6 Mode NEXT
Mode NEXT (Near End cross (X) Talk) is for measuring the cross-talk
coupling k1 between two pairs of conductors. Unwanted crosstalk coupling
occurs in particular when wires have been crossed.
The Easyflex Com is able to pinpoint the fault precisely, so the fault can
subsequently be eliminated to the point. For instance, the device can
determine the beginning and the end of a ”split pairs” section in a longer
trunk line which is composed of a number of sections.
The point of crosstalk coupling is located as in any normal reflection test.
This mode is different, however, in that the pair which shall carry the
transmitter pulse is connected to L2 and the pair tested for crosstalk to L1.
Press key Line and use the rotary encoder to enable mode NEXT.
pair 1
pair 2
Easyflex Com
Fig. 11
MAN_Easyflex_com_eng_01.doc 37
The direction of the pulse at the beginning of the ”Split Pairs” section may
be positive or negative depending on the direction in which the wires have
been connected to the device. At the end of the ”Split-Pairs” section the
reflection is always inverted as compared with its beginning.
If you use only the cursor you can just determine the distance from the
Easyflex Com to the point of reflection in the cable. The marker offers you
additional means to set a point of reference in the cable and to take
measurements in relation to this point by means of the cursor. We
recommend to use the marker
Press key Mark to set or erase the marker. To this end press key Cursor
and move the vertical line by means of the rotary encoder to the desired
point of reference. Then press key Mark; the marker will now be displayed
as a vertical dotted line. When you subsequently use the rotary encoder to
move the cursor away from the marked position, the numerical values on
display top right will change. The numerical value behind Cursor indicates
the distance between the output of the Easyflex Com and the position of the
cursor whereas the numerical value behind ∆ indicates the distance
between the marked point of reference and the cursor position. Pressing
key Mark one more time will erase the marker. The marker cannot be set to
position 0 m.
38 MAN_Easyflex_com_eng_01.doc
3.8.8 Change of Pulse Width
Press keys 2nd Range to change pulse width. Doing so will not change the
display range.
The offered combinations of pulse width and display range take into
account that not every pulse width is suitable for every display range. Thus
short pulses are only suitable for testing at close range. On the one hand,
they allow tests to be made with high resolution but they are too heavily
attenuated and spread at longer distance, on the other. Long pulses are
much less attenuated with distance, so clear echos can be received from
distant points. At close range, however, they are inferior to shorter pulses
due to their poor resolution.
MAN_Easyflex_com_eng_01.doc 39
3.8.9 Self Test
After turn on, the Easyflex Com performs an automatic selftest. If error code
1 is display the Lithium accumulator is (almost) discharged (the device will
still operate for a short while, but you should submit it to the Customer
Service to have the Lithium accumulator replaced).
Error code 2 asks for setting the clock (2nd Menu, Menu/System Mark, go
with rotary encoder to Date&Time Mark, select unit of time with rotary
encoder Mark, select unit of time with rotary encoder Mark for return). If
both errors occur at the same time, error code 3 is display.
Key combination (2nd Menu, Menu/System Mark, Self test Mark) starts a
comprehensive self test. Please contact our Customer Service should any
error code be display.
40 MAN_Easyflex_com_eng_01.doc
3.9 Memory Function
The Easyflex Com has 16 memory locations. This is how to save a trace:
• Press key Save
• Use the rotary encoder to select a free memory location or a location
that will be overwritten. The selected memory location is displayed in
inverted mode
• Press key Mark
The memory window will display location number, date and time of
measurement, and parameter Range of the stored reflectogram. Parameter
Range is display according to the value of v/2 or NVP which is currently set.
This has the consequence that any change of the v/2 setting will also
change this value in the reflectogram. When a trace is loaded, v/2 is re-set
to its stored value. In mode ALT two adjacent memory locations are made
available for storage. Memory location 1 is for quick saving triggered by key
combination 2nd Save. If mode ALT is set, quick saving will use memories
1 and 2. For this reason we suggest not to use memory locations 1 and 2
for any reflectograms which shall be retained in memory for a longer period
of time.
MAN_Easyflex_com_eng_01.doc 41
Mode of Mode of display Indication
loading
Use key combination 2nd Recall for a quick download of a trace from
memory location 1.
The traces stored in memory can later be used for processing or for
printing out a hardcopy. It is also possible, however, to upload them to a
PC using the PC software program Winkis Com which is available as an
optional extra. For printing out a reflectogram it is important first to use
Recall to load the trace from memory before pressing key Print. Another
benefit of the memory mode is that it simplifies fault locating and diagnosis.
When a number of test objects with identical cable characteristics are
tested, the entire test set-up can be taken over from a reflectogram already
stored in a memory location, so fault locating can be started without any
delay. The memory mode also allows a current reflectogram to be
compared with up to 16 reflectograms stored in memory.
42 MAN_Easyflex_com_eng_01.doc
3.10 Serial Interface
MAN_Easyflex_com_eng_01.doc 43
4 NIMH ACCUMULATOR CHARGER
4.1 Technical Description
4.1.1 Specification
Plug-in mains unit (Euro, USA, UK):
Input voltage
EURO 230 VAC , ±10 %, 50 Hz
USA 120 VAC , ±10 %, 60 Hz
UK 230 VAC , ±10 %, 50 Hz
Power consumption
EURO and UK 13.8 VA
USA 14.5 VA
Output voltage 12 V DC
Interelement protection class II
Operating temperature range 0 … 40 °C
Storage temperature range -40 … 70 °C
Charger:
Input voltage 12.,0 V DC
Maximum input current 580 mA
Interelement protection class III
Operating temperature range 0 … 50 °C
Storage temperature range -40 … 70 °C
Type of accumulator Replaceable NiMH rechargeable
accumulator 7,2 V (Energy
DC17AA)
44 MAN_Easyflex_com_eng_01.doc
4.1.2 Start-Up
First connect the cable from the plug-in mains unit to the DC-IN 12 V
socket of the charger, and only then plug the mains unit into a mains outlet
(see Fig 13).
The green LED of the charger case should now be on continuously, while
the amber LED should flash up at regular intervals.
Please make sure that the accumulator contacts face the direction of the
LEDs because this is the only way contact is made to the electronic
charger circuit (see enlarged details).
The amber indicator lamp shall light up continuously after the accumulator
has been inserted. If it does not, shortly disconnect the charger from the
mains.
After charging has been completed (approx. 3.5 hours), the amber LED will
flash again. You may now remove the accumulator or leave it in the
charger.
Disconnect the charger from the mains whenever you intend not to use it
for an extended period of time. To do so, just unplug the mains unit from
the mains outlet - you need not disconnect the cable from the mains unit to
the DC-IN 12V socket of the charger. We suggest to install the charger
close to an easily accessible mains outlet.
green
and
amber
mains
LEDs
DC-IN 12 V
Charger case Plug-in mains unit
MAN_Easyflex_com_eng_01.doc 45
The accumulator can also be charged from the on-board network of a
vehicle. To do this, use the vehicle adapter cable to connect the charger
case to the 12 V DC on-board network.
12 V s upply
D C -IN 12 V
C harger cas e
Light-emitting diodes
Fig 14 How to Insert the NiMH accumulator into the Charger Case
46 MAN_Easyflex_com_eng_01.doc
4.2 Operation
OPERATION
Please pay also attention to section 4.3, to extend the service life
of the NiMH accumulator.
MAN_Easyflex_com_eng_01.doc 47
4.2.3 Practical Hints
"Overnight charging" will not cause any trouble since an intact accumulator
cannot be overcharged. Once charging has been completed, the device will
change over to trickle charging to compensate for natural self-discharge.
The charger and the inserted accumulator will heat up during charging
(hand hot). This is normal and does not indicate any defect.
48 MAN_Easyflex_com_eng_01.doc
4.3 Troubleshooting
The green indicator lamp does not light up after the unit has been
plugged into a mains outlet.
− Has the accumulator been pushed into the charger down to the stop ?
In case none of these hints allows you to solve the problem, please submit
the device to your service station for inspection or contact the Hagenuk
KMT hotline.
Never use any aggressive solvent or detergent for cleaning your Easyflex
Com and its accessories. Use a soft, dry cloth for cleaning your Easyflex
Com and its accessories. When the device is very dirty, moisten the cloth
with some mild soap (do not use any abrasive agents) and clean it. Make
sure that all traces of moisture have evaporated before the Easyflex Com
and its accessories are used again.
MAN_Easyflex_com_eng_01.doc 49
6 APPENDIX
DC Direct current
50 MAN_Easyflex_com_eng_01.doc
6.2 Conversion: NVP ⇔ v/2
v
Conversion NVP /2 (m/µs)
m
NVP • 299.79
v µs
=
2 2
v
2•
NVP = 2
m
299.79
µs
MAN_Easyflex_com_eng_01.doc 51
6.3 Table: NVP and v/2 for Common Types of Cables
Typical propagation time
v v
Insulation /2 , /2 , ft/µs NVP
m/µs
Oil- 75-84 246-276 0.50-
impregnated 0.56
paper
Poly, cross- 78-87 256-285 0.52-
linked 0.58
Poly, filled with 96.0 314.8 0.64
Petrolat
Polyethylene 100.5 329.6 0.67
PTFE 106.5 349.3 0.71
Paper 108-132 354-433 0.72-
0.88
Poly, foamed 122.9 403.4 0.82
Air 141-147 462-482 0.94-
0.98
52 MAN_Easyflex_com_eng_01.doc
From your own measurements:
Propagation time
v
Insulation or /2, m/µs v/2, ft/µs NVP
type of cable
MAN_Easyflex_com_eng_01.doc 53
6.4 Glossary
Resolution In a → TDR device, resolution describes the minimum
distance between two successive faults in a cable at which
the events are depicted on the screen as individual echoes
which can be discriminated and, consequently, can be
measured. When the echoes superpose each other, the
starting time of the second echo – its so-called foot point –
cannot be measured. In this event the resolution is too
small. Resolution depends on the duration of the used
→ pulse. Obviously short pulses mean much better
resolution than long pulses. The distance range which can
be covered, on the other hand, is much shorter for short
pulses as compared with long ones.
Pulse In a → TDR device, pulses are used as transmitter signals.
A pulse is an electrical signal with high amplitude and short
duration. When travelling along the cable, each pulse is
more and more deformed (attenuation of amplitude,
increase in signal duration). The width (duration) of a pulse
is measured between those points at which the pulse has
half its maximum amplitude. In locating a fault, its distance
is determined by moving the cursor to the foot point of the
echo – i.e. to its starting point. As each pulse grows wider
and wider when travelling along the cable, the achievable →
resolution is more and more reduced with growing distance.
(Factor of) NVP
Propagation Time
Balancing Network The balancing network is for simulating the input resistance
of the cable to be tested. It is used for suppressing the
display of the transmitter pulse so that reflections can be
depicted and measured directly from the output of the
Easyflex Com – there is no dead zone as otherwise usual.
54 MAN_Easyflex_com_eng_01.doc
NEXT Near End Cross (X) Talk
MAN_Easyflex_com_eng_01.doc 55
Impulse → Pulse
56 MAN_Easyflex_com_eng_01.doc
v
/2 In cable testing it is common practice to specify the signal
propagation velocity in term of half the actual velocity.
When employing the reflection technique, this is a usual
way of taking twice the signal travel path into account. To
depict a reflection on the screen, the signal has to travel
from the meter to the fault and back. If the v/2 values of
various cables are listed in a table, these values can directly
be used to convert the measured signal propagation time tx
into fault distance E.
MAN_Easyflex_com_eng_01.doc 57