Technical Data Sheet: PXW Ac Ups System
Technical Data Sheet: PXW Ac Ups System
General data Ambient temperature range for storage from -20 to +70 °C
Ambient temperature range for operation from -10 to +40 °C (100 % nominal load)
Altitude above sea level 1000 m without load de-rating
Allowable air humidity <95 % (non condensing)
Noise level standard n+1 fan system 60 – 70 dBA depending on type
Noise level 100 % redundant fans 65 – 75 dBA depending on type
Degree of protection IP20 according to IEC 60529
Paint pebble gray, RAL 7032 structured
Efficiency up to 93 % depending on type
Cooling forced ventilation with redundant n+1 monitored
fans
Standards:
Safety IEC / EN 62040-1
EMC IEC 62040-2, EN 50091-2
Performance IEC / EN 62040-3
UPS classification VFI-SS-111 acc. to IEC 62040-3
Conformity CE-Label
The front panel includes a comprehensive and flexible human-machine interface. It is divided into four sections:
Operational parameters
Measurements