Power System
Power System
1
U.S.N
UNIT - II
3 a. Explain clearly the variation of current and impedance of an alternator when 3φ sudden short
6
circuit occurs at its terminals on no load condition.
b. Two generators are connected in parallel to the low voltage side of a 3φ ∆-Y transformer as
shown in Fig. 3(a). Generator 1 is rated 50,000 kVA, 13.8 kV. Generator 2 is rated
25,000 kVA, 13.8 kV. Each generator has a sub transient reactance of 25%. The transformer
is rated 75,000 kVA, 13.8 ∆/69 kV, Y with a reactance of 10%. Before the fault occurs, the
voltage on HT side of transformer is 66 kV. The transformer is not loaded and there is no
circulating current between the generators. Find the sub transient current in each generator
8
and in the HT side of the transformer, when 3φ short circuit occurs on the HT side of the
transformer. Select a base of 75,000 kVA, 69 kV on the HT side of the transformer.
UNIT - IV
7 a. A line to line fault occurs at the terminals of an unloaded generator. Derive the expression
for the fault currents. Also draw the interconnection of the sequence networks to simulate 8
the fault.
Contd…4
P13EE61 Page No... 4
b. A generator supplies a group of identical motors as shown in Fig. 7(b). The motors are rated
600 V, 90% η at full load upf with the sum of their output rating being 5 MW. The motors
are sharing equally a load of 4 MW at rated voltage, 0.8 pf lagging and 90% η when an LG
fault occurs on the L.V. side of the transformer. Draw sequence networks. The group of
motors can be treated as a single equivalent motor. Find the sub transient line currents in all
parts of the system, with pre-fault current ignored.
12
8 a. An unsymmetrical line to ground fault occurs on unloaded generator with fault impedances
Zf. Derive the expression for the fault current, If and draw the equivalent circuit which 10
simulate the fault.
b. Obtain the inter connection of sequence networks for the following types of open conductor
faults on power systems : 10
(i) One conductor open (ii) Two conductor open
UNIT - V
9 a. Define stability of a power system. Explain clearly the difference between steady state
8
stability and transient stability.
b. Derive the power angle equation for a non-salient pole synchronous machine, connected to
8
an infinite bus. Draw the power angle diagram.
c. A 60 Hz, 4 pole turbo-generator is delivering rated 500 MVA at 0.8 p.f. lag, when a fault
reduces the electrical power output by 40%. Determine the accelerating torque in Nm at the 4
time of fault.
10 a. Derive the expression for the swing equation and draw swing curves for unstable and stable
8
conditions.
b. Mention the methods of improving transient stability of a power system. 6
c. A 2 pole, 50 Hz, 11 kV turbo alternator has a rating of 100 MW, 0.85 p.f lagging. The rotor
6
has a moment of inertia of 10,000 kg-m2. Calculate H and M.
****