Rcds
Rcds
To reduce the risk of death or serious injury from electrocution and or fire, RCCBs are provided in AC circuits as an
additional means of protection and must operate reliably when other means of protection have failed.
Doepke RCCBs are manufactured in Doepke factories based in Germany, with individual testing and recording of the
trip characteristic and a unique serial number marked on each product. This ensures that every product leaves the
factory in safe working order and conforms to the requirements of the relevant standard or standards.
by “skilled/instructed” (electrical) persons only. Refer to the IET Wiring Regulations for
guidance on the selection and use of RCCBs to meet the requirements for new and existing installations.
The references below are based on BS 7671: 2008 incorporating Amendment No 3: 2015.
Doepke RCCBs manufactured to the above standard are designed to protect persons against the hazards associated
with indirect contact where exposed conductive parts of the installation are connected to a suitable earth electrode
- see Regulation 411.
Doepke RCCBs with a trip rating not exceeding 30 mA, meet the requirements of Regulation 415 based on the
supplementary bonding requirements. Using RCCBs as an additional means of protection does not negate the use
of basic protection methods required under regulation 411.
Doepke RCCBs with a trip rating not exceeding 300 mA meet the requirements of Regulation 532, however within
the Regulations there are specific requirements where 300mA trip rating may not be appropriate - for example
overhead heating see clause 422.3.9
In addition to standard RCCBs (Type AC) Doepke manufacture a wide range of devices with specific functions for
different applications.
Please contact us if you require a product that is not listed in our standard documentation.
used in applications where RCCBs have to be connected in series to achieve discrimination (Fig. 1) between
upstream and downstream devices - see clause 5.31.2.9 and example application 740.411, or 534.2.6 ( Doepke Type
S RCCBs are designed to have immunity to transient wave forms <5kA 8/20µs)
used in applications with residual sinusoidal alternating currents and pulsating direct currents with a
maximum of 6 mA smooth DC. - see clause 710.411.3.2 and 722.531.2.101
6 www.doepke.co.uk
SELECTION & APPLICATION
Operating and Installation Instructions for Residual Current Circuit Breakers DFS2, DFS4
Take all phase conductors and the neutral conductor (N) through the switch. The direction of the flow of energy can
be either way, i.e. the mains or the load can be connected to the upper or lower row of terminals. To ensure that the
built-in testing system operates properly
when 4-pole RCCBs are used in 2-pole
applications, use the terminals as per
wiring diagram. Aluminium conductors
must be scraped and greased just
before they are connected up to the
terminals.
Please note that the above fuses provide no overload protection. At the design stage check that the downstream
overload protection does not exceed the total rated current of the RCCB.
Doepke RCCBs are calibrated for operation between +40°C to -5°C. For operation down to -25°C the maximum values
of earth fault loop impedance defined in Table 41.5 must be reduced by 20 %.
DFS2 (230V 50Hz) and DFS4 (400V 50Hz) Test circuits will operate down to approximately 50% of the nominal
voltage. For operation on a 110V supply order a 110V unit.
DFS2 and DFS4 are calibrated to operate on 50 Hz supplies, for any other frequency order a special Doepke RCCB
calibrated for the nominal supply frequency.
Doepke residual current circuit breakers have been carefully tested at several stages of production and have left the
factory in perfect condition with regard to safety. To ensure safe operation, please observe the following instructions
and warnings.
1. Installation may only be performed by an authorized electrician, who is acquainted with the relevant
national installation regulations.
2. Residual current circuit breakers without additional protective housings may be stored and operated in
dry, low dust areas only. Corrosive atmospheres must also be avoided.
3. Users must be reminded, that all devices should be periodically tested, using the test button T.
4. Trips caused by leakage current due to surge voltage cannot be completely ruled out even with surge
current proof RCCBs. In cases where an interruption in power supply could constitute a hazard to
persons or animals or cause serious damage to property, the earth leakage system should comprise
selective RCCBs with increased surge current strength and over voltage protection. In special cases the
system should be monitored with an auxiliary contact on the RCCBs and a suitable signaling device.
5. If the device is opened the warranty becomes void!
[email protected] 7
Doepke Residual Current Circuit Breakers Type AC
AC
feeding loads which do not interfere
with the standard AC supply.
8 www.doepke.co.uk
Type A RCCBs
A
feeding loads which can generate
pulsed wave forms on the AC supply.
[email protected] 9
Doepke Residual Current Circuit Breakers Type AKV
AKV
to 3kA, to reduce nuisance tripping associated with some load
characteristics, such as EV chargers, lighting and SPDs.
Selection in the same way as standard RCCBs. Available in 2 and 4 pole versions from
16-125A with various sensitivities, see below:-
16-2/0.03.DFS2.AKV 16-4/0.03.DFS4.AKV
16-2/0.10.DFS2.AKV 16-4/0.10.DFS4.AKV
16-2/0.30.DFS2.AKV 16-4/0.30.DFS4.AKV
16-2/0.50.DFS2.AKV 16-4/0.50.DFS4.AKV
25-2/0.03.DFS2.AKV 25-4/0.03.DFS4.AKV
25-2/0.10.DFS2.AKV 25-4/0.10.DFS4.AKV
25-2/0.30.DFS2.AKV 25-4/0.30.DFS4.AKV
25-2/0.50.DFS2.AKV 25-4/0.50.DFS4.AKV
40-2/0.03.DFS2.AKV 40-4/0.03.DFS4.AKV
40-2/0.10.DFS2.AKV 40-4/0.10.DFS4.AKV
40-2/0.30.DFS2.AKV 40-4/0.30.DFS4.AKV
40-2/0.50.DFS2.AKV 40-4/0.50.DFS4.AKV
63-2/0.03.DFS2.AKV 63-4/0.03.DFS4.AKV
63-2/0.10.DFS2.AKV 63-4/0.10.DFS4.AKV
63-2/0.30.DFS2.AKV 63-4/0.30.DFS4.AKV
63-2/0.50.DFS2.AKV 63-4/0.50.DFS4.AKV
80-2/0.03.DFS2.AKV 80-4/0.03.DFS4.AKV
80-2/0.10.DFS2.AKV 80-4/0.10.DFS4.AKV
80-2/0.30.DFS2.AKV 80-4/0.30.DFS4.AKV
80-2/0.50.DFS2.AKV 80-4/0.50.DFS4.AKV
100-2/0.03.DFS2.AKV 100-4/0.03.DFS4.AKV
100-2/0.10.DFS2.AKV 100-4/0.10.DFS4.AKV
100-2/0.30.DFS2.AKV 100-4/0.30.DFS4.AKV
100-2/0.50.DFS2.AKV 100-4/0.50.DFS4.AKV
125-2/0.03.DFS2.AKV 125-4/0.03.DFS4.AKV
125-2/0.10.DFS2.AKV 125-4/0.10.DFS4.AKV
125-2/0.30.DFS2.AKV 125-4/0.30.DFS4.AKV
125-2/0.50.DFS2.AKV 125-4/0.50.DFS4.AKV
10 www.doepke.co.uk
Type F RCCBs
Verify if you need Type F or Type B and the required sensitivity for the equipment.
16-2/0.03.DFS2.F 16-4/0.03.DFS4.F
16-2/0.10.DFS2.F 16-4/0.10.DFS4.F
16-2/0.30.DFS2.F 16-4/0.30.DFS4.F
16-2/0.50.DFS2.F 16-4/0.50.DFS4.F
25-2/0.03.DFS2.F 25-4/0.03.DFS4.F
25-2/0.10.DFS2.F 25-4/0.10.DFS4.F
25-2/0.30.DFS2.F 25-4/0.30.DFS4.F
25-2/0.50.DFS2.F 25-4/0.50.DFS4.F
40-2/0.03.DFS2.F 40-4/0.03.DFS4.F
40-2/0.10.DFS2.F 40-4/0.10.DFS4.F
40-2/0.30.DFS2.F 40-4/0.30.DFS4.F
40-2/0.50.DFS2.F 40-4/0.50.DFS4.F
63-2/0.03.DFS2.F 63-4/0.03.DFS4.F
63-2/0.10.DFS2.F 63-4/0.10.DFS4.F
63-2/0.30.DFS2.F 63-4/0.30.DFS4.F
63-2/0.50.DFS2.F 63-4/0.50.DFS4.F
80-2/0.03.DFS2.F 80-4/0.03.DFS4.F
80-2/0.10.DFS2.F 80-4/0.10.DFS4.F
80-2/0.30.DFS2.F 80-4/0.30.DFS4.F
80-2/0.50.DFS2.F 80-4/0.50.DFS4.F
100-2/0.03.DFS2.F 100-4/0.03.DFS4.F
100-2/0.10.DFS2.F 100-4/0.10.DFS4.F
100-2/0.30.DFS2.F 100-4/0.30.DFS4.F
100-2/0.50.DFS2.F 100-4/0.50.DFS4.F
125-2/0.03.DFS2.F 125-4/0.03.DFS4.F
125-2/0.10.DFS2.F 125-4/0.10.DFS4.F
125-2/0.30.DFS2.F 125-4/0.30.DFS4.F
125-2/0.50.DFS2.F 125-4/0.50.DFS4.F
[email protected] 11
Doepke Residual Current Circuit Breakers Type AEV
The upstream RCCB can be Type A or Type A KV The smooth DC current flowing through the
depending on the inrush current of up stream RCCB is equal to the sum of all the
the vehicle charger. chargers connected down stream.
Type B RCCB required upstream.
12 www.doepke.co.uk
DFL8 Type A RCCBs
The DFL8 range incorporates type ‘A’ RCD trips with current ratings up to 250 Amps.
Each unit comprises: 4 Pole Circuit Breaker (Ics 50kA at 415V & 5kA at 690V) with adjustable
overload setting (0.8-1 x In) and short circuit trip (6-10 x In).
RCCB trip function module available in non adjustable and adjustable versions (factory fitted).
I n = 0.03A
Rating Sensitivity Reference
DFL8 100-4/0.03 A
DFL8 125-4/0.03 A
DFL8 160-4/0.03 A
DFL8 200-4/0.03 A
DFL8 250-4/0.03 A
I n : 0.3A-0.5A-1A
Time delay: 60-150-300-450ms
Rating Sensitivity Reference
DFL8 100-4/X A
DFL8 125-4/X A
DFL8 160-4/X A
DFL8 200-4/X A
DFL8 250-4/X A
[email protected] 13
Doepke Residual Current Circuit Breakers
B
circuits feeding loads which can
generate AC & DC leakage currents
The IEE Wiring Regs. make specific reference to ‘B’ type RCCBs
14 www.doepke.co.uk
Type B RCCBs
provides the “classic” 300mA fire protection up to provides a 2A tripping threshold above 2kHz.
1,000,000Hz (1MHz).
[email protected] 15
Doepke Residual Current Circuit Breakers
B
circuits feeding loads which can
generate AC & DC leakage currents
The DFL8 range incorporates type ‘B’ RCD trips with current ratings up to 250 Amps.
Each unit comprises: 4 Pole Circuit Breaker (Ics 50kA at 415V) with adjustable overload
setting (0.8-1 x In) and short circuit trip (6-10 x In). RCCB trip function module available
in non adjustable and adjustable versions (factory fitted).
I n = 0.03A
Rating Sensitivity Reference
DFL8 100-4/0.03 B NK
DFL8 125-4/0.03 B NK
DFL8 160-4/0.03 B NK
DFL8 200-4/0.03 B NK
DFL8 250-4/0.03 B NK
I n : 0.3A-0.5A-1A
Time delay: 60-150-300-450ms
Rating Sensitivity Reference
DFL8 100-4/X B NK
DFL8 125-4/X B NK
DFL8 160-4/X B NK
DFL8 200-4/X B NK
for use in installations designed to DFL8 250-4/X B NK
withstand high leakage currents.
I n = 0.03A
Rating Sensitivity Reference
DFL8 100-4/0.03 B SK Pictured above is the panel
DFL8 125-4/0.03 B SK where the overload setting
DFL8 160-4/0.03 B SK (0.8 -1 x In) and short circuit
DFL8 200-4/0.03 B SK trip (6 -10 x In) can be
DFL8 250-4/0.03 B SK adjusted.
I n : 0.3A-0.5A-1A
Time delay: 60-150-300-450ms The illustration right shows
Rating Sensitivity Reference the optional IP54 insulated
DFL8 100-4/X B SK enclosure available for
DFL8 125-4/X B SK mounting a DFL8 device.
DFL8 160-4/X B SK
DFL8 200-4/X B SK The part No. is 09 200 028
DFL8 250-4/X B SK Dimensions: 295W x 690H x 170D
16 www.doepke.co.uk
Type B RCCBs
Both 2 & 4 pole devices are 4 modules wide. A DHi 11 switch attached
to a four pole RCCB.
Description Reference
for 2 & 4 pole RCCBs WES
[email protected] 17
Doepke RCCBs - Practical Applications Guide
18 www.doepke.co.uk
Doepke
Design requirements:
overload trip & residual current trip EN 60947-2 & EN 60947-2 Appx. B
36 www.doepke.co.uk
TECHNICAL SPECIFICATIONS
Technical Data Dimensions Contact Assignments
400/415 V AC 50 kA 50kA
[email protected] 37
Doepke
38 www.doepke.co.uk