The document discusses Doepke residual current circuit breakers (RCCBs), including: 1. Doepke RCCBs meet relevant safety standards and are individually tested to ensure safe operation. 2. The document provides information on the proper use and installation of Doepke RCCBs according to regulations, including that they should only be installed by electricians and tested regularly. 3. Doepke offers various types of RCCBs for different applications, including standard RCCBs for AC circuits and specialty devices for situations like DC leakage currents.

Uploaded by

xyz
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
280 views

Rcds

The document discusses Doepke residual current circuit breakers (RCCBs), including: 1. Doepke RCCBs meet relevant safety standards and are individually tested to ensure safe operation. 2. The document provides information on the proper use and installation of Doepke RCCBs according to regulations, including that they should only be installed by electricians and tested regularly. 3. Doepke offers various types of RCCBs for different applications, including standard RCCBs for AC circuits and specialty devices for situations like DC leakage currents.

Uploaded by

xyz
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

Doepke Residual Current Circuit Breakers

Doepke RCCBs meet EN61008 / EN62423

To reduce the risk of death or serious injury from electrocution and or fire, RCCBs are provided in AC circuits as an
additional means of protection and must operate reliably when other means of protection have failed.

Doepke RCCBs are manufactured in Doepke factories based in Germany, with individual testing and recording of the
trip characteristic and a unique serial number marked on each product. This ensures that every product leaves the
factory in safe working order and conforms to the requirements of the relevant standard or standards.

RCCB's General Principles for Use

by “skilled/instructed” (electrical) persons only. Refer to the IET Wiring Regulations for
guidance on the selection and use of RCCBs to meet the requirements for new and existing installations.
The references below are based on BS 7671: 2008 incorporating Amendment No 3: 2015.

Doepke RCCBs manufactured to the above standard are designed to protect persons against the hazards associated
with indirect contact where exposed conductive parts of the installation are connected to a suitable earth electrode
- see Regulation 411.

Doepke RCCBs with a trip rating not exceeding 30 mA, meet the requirements of Regulation 415 based on the
supplementary bonding requirements. Using RCCBs as an additional means of protection does not negate the use
of basic protection methods required under regulation 411.

Doepke RCCBs with a trip rating not exceeding 300 mA meet the requirements of Regulation 532, however within
the Regulations there are specific requirements where 300mA trip rating may not be appropriate - for example
overhead heating see clause 422.3.9

Types of RCCB required by the IET Wiring Regulations

In addition to standard RCCBs (Type AC) Doepke manufacture a wide range of devices with specific functions for
different applications.

Please contact us if you require a product that is not listed in our standard documentation.

used in applications where RCCBs have to be connected in series to achieve discrimination (Fig. 1) between
upstream and downstream devices - see clause 5.31.2.9 and example application 740.411, or 534.2.6 ( Doepke Type
S RCCBs are designed to have immunity to transient wave forms <5kA 8/20µs)

used in applications with residual sinusoidal alternating currents and pulsating direct currents with a
maximum of 6 mA smooth DC. - see clause 710.411.3.2 and 722.531.2.101

(IEC 62423) used in applications where in addition


to the above, smooth DC residual currents above 6mA are
present under certain fault conditions - see clause
712.411.3.2.1.2 and 722.531.2.101

used in applications where the RCCB could be


subject to in rush currents < 3000 A , which would cause
tripping of standard RCCB - see clause 534.2.6

used in applications where the RCCB is subjected


to mixed frequency leakage currents, such as single phase
inverter controlled washing machines, mixers or power
tools.

used in electrical vehicle charging applications


where the RCCB must trip if the smooth DC leakage current
exceeds 6mA.

6 www.doepke.co.uk
SELECTION & APPLICATION
Operating and Installation Instructions for Residual Current Circuit Breakers DFS2, DFS4

Any position. By clipping onto DIN EN 50022 rails.

Take all phase conductors and the neutral conductor (N) through the switch. The direction of the flow of energy can
be either way, i.e. the mains or the load can be connected to the upper or lower row of terminals. To ensure that the
built-in testing system operates properly
when 4-pole RCCBs are used in 2-pole
applications, use the terminals as per
wiring diagram. Aluminium conductors
must be scraped and greased just
before they are connected up to the
terminals.

Testing of the entire protective system


when putting into operation must be
performed according to the
specifications of the valid national
installation regulations. Test quarterly by
pressing the test button T for stationary
equipment and once every working day
for mobile equipment.

Please note that the above fuses provide no overload protection. At the design stage check that the downstream
overload protection does not exceed the total rated current of the RCCB.

Doepke RCCBs are calibrated for operation between +40°C to -5°C. For operation down to -25°C the maximum values
of earth fault loop impedance defined in Table 41.5 must be reduced by 20 %.

DFS2 (230V 50Hz) and DFS4 (400V 50Hz) Test circuits will operate down to approximately 50% of the nominal
voltage. For operation on a 110V supply order a 110V unit.

DFS2 and DFS4 are calibrated to operate on 50 Hz supplies, for any other frequency order a special Doepke RCCB
calibrated for the nominal supply frequency.

Doepke residual current circuit breakers have been carefully tested at several stages of production and have left the
factory in perfect condition with regard to safety. To ensure safe operation, please observe the following instructions
and warnings.

1. Installation may only be performed by an authorized electrician, who is acquainted with the relevant
national installation regulations.
2. Residual current circuit breakers without additional protective housings may be stored and operated in
dry, low dust areas only. Corrosive atmospheres must also be avoided.
3. Users must be reminded, that all devices should be periodically tested, using the test button T.
4. Trips caused by leakage current due to surge voltage cannot be completely ruled out even with surge
current proof RCCBs. In cases where an interruption in power supply could constitute a hazard to
persons or animals or cause serious damage to property, the earth leakage system should comprise
selective RCCBs with increased surge current strength and over voltage protection. In special cases the
system should be monitored with an auxiliary contact on the RCCBs and a suitable signaling device.
5. If the device is opened the warranty becomes void!

[email protected] 7
Doepke Residual Current Circuit Breakers Type AC

Type For use in 50Hz AC electrical circuits

AC
feeding loads which do not interfere
with the standard AC supply.

2 Pole 2 Module 4 Pole 4 Module


Rating Sensitivity Reference Reference
16-2/0.01.DFS2 16-4/0.01.DFS4
16-2/0.03.DFS2 16-4/0.03.DFS4
16-2/0.10.DFS2 16-4/0.10.DFS4
16-2/0.30.DFS2 16-4/0.30.DFS4
16-2/0.50.DFS2 16-4/0.50.DFS4
25-2/0.03.DFS2 25-4/0.03.DFS4
25-2/0.10.DFS2 25-4/0.10.DFS4
25-2/0.30.DFS2 25-4/0.30.DFS4
25-2/0.50.DFS2 25-4/0.50.DFS4
40-2/0.03.DFS2 40-4/0.03.DFS4
40-2/0.10.DFS2 40-4/0.10.DFS4
40-2/0.30.DFS2 40-4/0.30.DFS4
40-2/0.50.DFS2 40-4/0.50.DFS4
63-2/0.03.DFS2 63-4/0.03.DFS4
63-2/0.10.DFS2 63-4/0.10.DFS4
63-2/0.30.DFS2 63-4/0.30.DFS4
63-2/0.50.DFS2 63-4/0.50.DFS4
80-2/0.03.DFS2 80-4/0.03.DFS4
80-2/0.10.DFS2 80-4/0.10.DFS4
80-2/0.30.DFS2 80-4/0.30.DFS4
80-2/0.50.DFS2 80-4/0.50.DFS4
100-2/0.03.DFS2 100-4/0.03.DFS4
100-2/0.10.DFS2 100-4/0.10.DFS4
100-2/0.30.DFS2 100-4/0.30.DFS4
100-2/0.50.DFS2 100-4/0.50.DFS4
125-2/0.03.DFS2 125-4/0.03.DFS4
125-2/0.10.DFS2 125-4/0.10.DFS4
125-2/0.30.DFS2 125-4/0.30.DFS4
125-2/0.50.DFS2 125-4/0.50.DFS4

2 Pole 2 Module 4 Pole 4 Module


Rating Sensitivity Reference Reference
63-2/0.10.DFS2.S 63-4/0.10.DFS4.S
63-2/0.30.DFS2.S 63-4/0.30.DFS4.S
63-2/0.50.DFS2.S 63-4/0.50.DFS4.S
100-2/0.10.DFS2.S 100-4/0.10.DFS4.S
100-2/0.30.DFS2.S 100-4/0.30.DFS4.S
100-2/0.50.DFS2.S 100-4/0.50.DFS4.S
125-2/0.10.DFS2.S 125-4/0.10.DFS4.S
125-2/0.30.DFS2.S 125-4/0.30.DFS4.S
125-2/0.50.DFS2.S 125-4/0.50.DFS4.S

Some of the above RCCBs are available


in the following variations to special order only

Hz Frequencies > 50 Hz 110 V versions (DFS2only) 500 V versions (DFS4 only)

8 www.doepke.co.uk
Type A RCCBs

Type For use in 50Hz AC electrical circuits

A
feeding loads which can generate
pulsed wave forms on the AC supply.

2 Pole 2 Module 4 Pole 4 Module


Rating Sensitivity Reference Reference
16-2/0.01.DFS2.A 16-4/0.01.DFS4.A
16-2/0.03.DFS2.A 16-4/0.03.DFS4.A
16-2/0.10.DFS2.A 16-4/0.10.DFS4.A
16-2/0.30.DFS2.A 16-4/0.30.DFS4.A
16-2/0.50.DFS2.A 16-4/0.50.DFS4.A
25-2/0.03.DFS2.A 25-4/0.03.DFS4.A
25-2/0.10.DFS2.A 25-4/0.10.DFS4.A
25-2/0.30.DFS2.A 25-4/0.30.DFS4.A
25-2/0.50.DFS2.A 25-4/0.50.DFS4.A
40-2/0.03.DFS2.A 40-4/0.03.DFS4.A
40-2/0.10.DFS2.A 40-4/0.10.DFS4.A
40-2/0.30.DFS2.A 40-4/0.30.DFS4.A
40-2/0.50.DFS2.A 40-4/0.50.DFS4.A
63-2/0.03.DFS2.A 63-4/0.03.DFS4.A
63-2/0.10.DFS2.A 63-4/0.10.DFS4.A
63-2/0.30.DFS2.A 63-4/0.30.DFS4.A
63-2/0.50.DFS2.A 63-4/0.50.DFS4.A
80-2/0.03.DFS2.A 80-4/0.03.DFS4.A
80-2/0.10.DFS2.A 80-4/0.10.DFS4.A
80-2/0.30.DFS2.A 80-4/0.30.DFS4.A
80-2/0.50.DFS2.A 80-4/0.50.DFS4.A
100-2/0.03.DFS2.A 100-4/0.03.DFS4.A
100-2/0.10.DFS2.A 100-4/0.10.DFS4.A
100-2/0.30.DFS2.A 100-4/0.30.DFS4.A
100-2/0.50.DFS2.A 100-4/0.50.DFS4.A
125-2/0.03.DFS2.A 125-4/0.03.DFS4.A
125-2/0.10.DFS2.A 125-4/0.10.DFS4.A
125-2/0.30.DFS2.A 125-4/0.30.DFS4.A
125-2/0.50.DFS2.A 125-4/0.50.DFS4.A

2 Pole 2 Module 4 Pole 4 Module


Rating Sensitivity Reference Reference
63-2/0.10.DFS2.A.S 63-4/0.10.DFS4.A.S
63-2/0.30.DFS2.A.S 63-4/0.30.DFS4.A.S
63-2/0.50.DFS2.A.S 63-4/0.50.DFS4.A.S
100-2/0.10.DFS2.A.S 100-4/0.10.DFS4.A.S
100-2/0.30.DFS2.A.S 100-4/0.30.DFS4.A.S
100-2/0.50.DFS2.A.S 100-4/0.50.DFS4.A.S
125-2/0.10.DFS2.A.S 125-4/0.10.DFS4.A.S
125-2/0.30.DFS2.A.S 125-4/0.30.DFS4.A.S
125-2/0.50.DFS2.A.S 125-4/0.50.DFS4.A.S

Some of the above RCCBs are available


in the following variations to special order only

Hz Frequencies > 50 Hz 110 V versions (DFS2only) 500 V versions (DFS4 only)

[email protected] 9
Doepke Residual Current Circuit Breakers Type AKV

Type Type A KV RCCBs are designed to withstand supply transients up

AKV
to 3kA, to reduce nuisance tripping associated with some load
characteristics, such as EV chargers, lighting and SPDs.

Type AKV devices must not trip when


subjected to an 8/20µs 3kA transient or
short duration leakage currents flowing for
<10ms associated with capacitor charging,
EV and machines. AKV devices still meet
the tripping requirements for General/Non-
delay RCCBs to EN61008-1, required for
additional protection (30mA) and fire
protection (300mA).

Selection in the same way as standard RCCBs. Available in 2 and 4 pole versions from
16-125A with various sensitivities, see below:-

2 Pole 2 Module (230V) 4 Pole 4 Module (400V)


Rating Sensitivity Reference Reference

16-2/0.03.DFS2.AKV 16-4/0.03.DFS4.AKV
16-2/0.10.DFS2.AKV 16-4/0.10.DFS4.AKV
16-2/0.30.DFS2.AKV 16-4/0.30.DFS4.AKV
16-2/0.50.DFS2.AKV 16-4/0.50.DFS4.AKV
25-2/0.03.DFS2.AKV 25-4/0.03.DFS4.AKV
25-2/0.10.DFS2.AKV 25-4/0.10.DFS4.AKV
25-2/0.30.DFS2.AKV 25-4/0.30.DFS4.AKV
25-2/0.50.DFS2.AKV 25-4/0.50.DFS4.AKV
40-2/0.03.DFS2.AKV 40-4/0.03.DFS4.AKV
40-2/0.10.DFS2.AKV 40-4/0.10.DFS4.AKV
40-2/0.30.DFS2.AKV 40-4/0.30.DFS4.AKV
40-2/0.50.DFS2.AKV 40-4/0.50.DFS4.AKV
63-2/0.03.DFS2.AKV 63-4/0.03.DFS4.AKV
63-2/0.10.DFS2.AKV 63-4/0.10.DFS4.AKV
63-2/0.30.DFS2.AKV 63-4/0.30.DFS4.AKV
63-2/0.50.DFS2.AKV 63-4/0.50.DFS4.AKV
80-2/0.03.DFS2.AKV 80-4/0.03.DFS4.AKV
80-2/0.10.DFS2.AKV 80-4/0.10.DFS4.AKV
80-2/0.30.DFS2.AKV 80-4/0.30.DFS4.AKV
80-2/0.50.DFS2.AKV 80-4/0.50.DFS4.AKV
100-2/0.03.DFS2.AKV 100-4/0.03.DFS4.AKV
100-2/0.10.DFS2.AKV 100-4/0.10.DFS4.AKV
100-2/0.30.DFS2.AKV 100-4/0.30.DFS4.AKV
100-2/0.50.DFS2.AKV 100-4/0.50.DFS4.AKV
125-2/0.03.DFS2.AKV 125-4/0.03.DFS4.AKV
125-2/0.10.DFS2.AKV 125-4/0.10.DFS4.AKV
125-2/0.30.DFS2.AKV 125-4/0.30.DFS4.AKV
125-2/0.50.DFS2.AKV 125-4/0.50.DFS4.AKV

10 www.doepke.co.uk
Type F RCCBs

Type Type F RCCBs are designed to detect mixed frequency residual


currents 10Hz< 1kHz, associated with single phase inverter

F control, used in modern domestic appliances. Type AC and A


RCCBs are designed to detect leakage currents at 50Hz.

Type F RCCBs dectect AC, A and mixed


frequency leakage currents (F) as defined
in .
They also incorporate 3kA transient
resistance and 10mS short time delay, to
reduce nuisance tripping associated with
this type of load.
These devices must not be used with
loads/inverters that can produce
smooth DC leakage currents -

Verify if you need Type F or Type B and the required sensitivity for the equipment.

2 Pole 2 Module (230V) 4 Pole 4 Module (400V)


Rating Sensitivity Reference Reference

16-2/0.03.DFS2.F 16-4/0.03.DFS4.F
16-2/0.10.DFS2.F 16-4/0.10.DFS4.F
16-2/0.30.DFS2.F 16-4/0.30.DFS4.F
16-2/0.50.DFS2.F 16-4/0.50.DFS4.F
25-2/0.03.DFS2.F 25-4/0.03.DFS4.F
25-2/0.10.DFS2.F 25-4/0.10.DFS4.F
25-2/0.30.DFS2.F 25-4/0.30.DFS4.F
25-2/0.50.DFS2.F 25-4/0.50.DFS4.F
40-2/0.03.DFS2.F 40-4/0.03.DFS4.F
40-2/0.10.DFS2.F 40-4/0.10.DFS4.F
40-2/0.30.DFS2.F 40-4/0.30.DFS4.F
40-2/0.50.DFS2.F 40-4/0.50.DFS4.F
63-2/0.03.DFS2.F 63-4/0.03.DFS4.F
63-2/0.10.DFS2.F 63-4/0.10.DFS4.F
63-2/0.30.DFS2.F 63-4/0.30.DFS4.F
63-2/0.50.DFS2.F 63-4/0.50.DFS4.F
80-2/0.03.DFS2.F 80-4/0.03.DFS4.F
80-2/0.10.DFS2.F 80-4/0.10.DFS4.F
80-2/0.30.DFS2.F 80-4/0.30.DFS4.F
80-2/0.50.DFS2.F 80-4/0.50.DFS4.F
100-2/0.03.DFS2.F 100-4/0.03.DFS4.F
100-2/0.10.DFS2.F 100-4/0.10.DFS4.F
100-2/0.30.DFS2.F 100-4/0.30.DFS4.F
100-2/0.50.DFS2.F 100-4/0.50.DFS4.F
125-2/0.03.DFS2.F 125-4/0.03.DFS4.F
125-2/0.10.DFS2.F 125-4/0.10.DFS4.F
125-2/0.30.DFS2.F 125-4/0.30.DFS4.F
125-2/0.50.DFS2.F 125-4/0.50.DFS4.F

[email protected] 11
Doepke Residual Current Circuit Breakers Type AEV

Type Type A EV RCCBs are designed specifically for individual EV


chargers, where the model and make of the vehicle being charged
AEV is unknown. The EV RCCB will trip if the smooth dc residual
current exceeds 6mA.
Type A EV RCCBs in addition to providing
normal residual current protection, also protect
upstream RCCBs (Type A) from the effects of
smooth DC residual currents >6mA. Type A
RCCBs cannot detect smooth DC and must not
be subjected to levels above 6mA - see Wiring
Regulation 722.531.2.101.

Modules Poles Amps Sensitivity Reference

4 2 25 30mA DSF4 025-2/0.03-A EV


4 4 40 30mA DSF4 040-4/0.03-A EV
4 4 63 30mA DSF4 063-4/0.03-A EV

The upstream RCCB can be Type A or Type A KV The smooth DC current flowing through the
depending on the inrush current of up stream RCCB is equal to the sum of all the
the vehicle charger. chargers connected down stream.
Type B RCCB required upstream.

12 www.doepke.co.uk
DFL8 Type A RCCBs

The DFL8 range incorporates type ‘A’ RCD trips with current ratings up to 250 Amps.
Each unit comprises: 4 Pole Circuit Breaker (Ics 50kA at 415V & 5kA at 690V) with adjustable
overload setting (0.8-1 x In) and short circuit trip (6-10 x In).
RCCB trip function module available in non adjustable and adjustable versions (factory fitted).

For use in 50Hz AC electrical circuits


feeding loads which can generate pulsed wave forms
on the AC supply.

I n = 0.03A
Rating Sensitivity Reference
DFL8 100-4/0.03 A
DFL8 125-4/0.03 A
DFL8 160-4/0.03 A
DFL8 200-4/0.03 A
DFL8 250-4/0.03 A
I n : 0.3A-0.5A-1A
Time delay: 60-150-300-450ms
Rating Sensitivity Reference
DFL8 100-4/X A
DFL8 125-4/X A
DFL8 160-4/X A
DFL8 200-4/X A
DFL8 250-4/X A

Pictured above is the panel where the overload


setting (0.8 -1 x In) and short circuit trip (6 -10 x In)
can be adjusted.

The part No. is 09 200 028


Dimensions: 295W x 690H x 170D

[email protected] 13
Doepke Residual Current Circuit Breakers

Type For use in 50Hz AC electrical

B
circuits feeding loads which can
generate AC & DC leakage currents

Many electrical installations now contain products which


incorporate power electronics, such as inverters for PV
installations, speed control in HVAC, some running machines,
UPS, medical equipment etc. This type of equipment can
produce, in addition to standard 50Hz earth leakage currents,
pure DC and high frequency AC leakage currents which would
not be detected by a standard AC or A type RCCB.

‘B’ type RCCBs in addition to normal AC, can detect high


frequency AC and pure DC earth leakage currents.

Reducing the risk of fire and/or electrocution through automatic


disconnection of the electrical supply (Reg 411), relies on the
selection and installation of the correct type of RCCB.

The IEE Wiring Regs. make specific reference to ‘B’ type RCCBs

provides the “classic” 300mA fire protection up


to 1,000,000 Hz (1MHz).

provides a 2A tripping threshold above 2kHz.

provides 420mA fire protection up to 20kHz.

incorporating Type 'B' RCCB trips providing


classic 300mA fire protection up to 100kHz.

incorporating Type 'B' RCCB trips is suitable for


use in installations designed to withstand high
leakage currents.

14 www.doepke.co.uk
Type B RCCBs

provides the “classic” 300mA fire protection up to provides a 2A tripping threshold above 2kHz.
1,000,000Hz (1MHz).

4 Modules wide 4 Modules wide 4 Modules wide 4 Modules wide


Rating Sensitivity 2 Pole Reference 4 Pole Reference 2 Pole Reference 4 Pole Reference
DFS4 016-2/0.03-B NK DFS4 016-4/0.03-B NK DFS4 016-2/0.03-B SK DFS4 016-4/0.03-B SK
DFS4 016-2/0.10-B NK DFS4 016-4/0.10-B NK DFS4 016-2/0.10-B SK DFS4 016-4/0.10-B SK
DFS4 016-2/0.30-B NK DFS4 016-4/0.30-B NK DFS4 016-2/0.30-B SK DFS4 016-4/0.30-B SK
n/a n/a DFS4 016-2/0.50-B SK DFS4 016-4/0.50-B SK
DFS4 025-2/0.03-B NK DFS4 025-4/0.03-B NK DFS4 025-2/0.03-B SK DFS4 025-4/0.03-B SK
DFS4 025-2/0.10-B NK DFS4 025-4/0.10-B NK DFS4 025-2/0.10-B SK DFS4 025-4/0.10-B SK
DFS4 025-2/0.30-B NK DFS4 025-4/0.30-B NK DFS4 025-2/0.30-B SK DFS4 025-4/0.30-B SK
n/a n/a DFS4 025-2/0.50-B SK DFS4 025-4/0.50-B SK
DFS4 040-2/0.03-B NK DFS4 040-4/0.03-B NK DFS4 040-2/0.03-B SK DFS4 040-4/0.03-B SK
DFS4 040-2/0.10-B NK DFS4 040-4/0.10-B NK DFS4 040-2/0.10-B SK DFS4 040-4/0.10-B SK
DFS4 040-2/0.30-B NK DFS4 040-4/0.30-B NK DFS4 040-2/0.30-B SK DFS4 040-4/0.30-B SK
n/a n/a DFS4 040-2/0.50-B SK DFS4 040-4/0.50-B SK
DFS4 063-2/0.03-B NK DFS4 063-4/0.03-B NK DFS4 063-2/0.03-B SK DFS4 063-4/0.03-B SK
DFS4 063-2/0.10-B NK DFS4 063-4/0.10-B NK DFS4 063-2/0.10-B SK DFS4 063-4/0.10-B SK
DFS4 063-2/0.30-B NK DFS4 063-4/0.30-B NK DFS4 063-2/0.30-B SK DFS4 063-4/0.30-B SK
n/a n/a DFS4 063-2/0.50-B SK DFS4 063-4/0.50-B SK
DFS4 080-2/0.03-B NK DFS4 080-4/0.03-B NK DFS4 080-2/0.03-B SK DFS4 080-4/0.03-B SK
DFS4 080-2/0.10-B NK DFS4 080-4/0.10-B NK DFS4 080-2/0.10-B SK DFS4 080-4/0.10-B SK
DFS4 080-2/0.30-B NK DFS4 080-4/0.30-B NK DFS4 080-2/0.30-B SK DFS4 080-4/0.30-B SK
n/a n/a DFS4 080-2/0.50-B SK DFS4 080-4/0.50-B SK
DFS4 100-2/0.03-B NK DFS4 100-4/0.03-B NK DFS4 100-2/0.03-B SK DFS4 100-4/0.03-B SK
DFS4 100-2/0.10-B NK DFS4 100-4/0.10-B NK DFS4 100-2/0.10-B SK DFS4 100-4/0.10-B SK
DFS4 100-2/0.30-B NK DFS 4 100-4/0.30-B NK DFS4 100-2/0.30-B SK DFS4 100-4/0.30-B SK
n/a n/a DFS4 100-2/0.50-B SK DFS4 100-4/0.50-B SK
DFS4 125-2/0.03-B NK DFS4 125-4/0.03-B NK DFS4 125-2/0.03-B SK DFS4 125-4/0.03-B SK
DFS4 125-2/0.10-B NK DFS4 125-4/0.10-B NK DFS4 125-2/0.10-B SK DFS4 125-4/0.10-B SK
DFS4 125-2/0.30-B NK DFS4 125-4/0.30-B NK DFS4 125-2/0.30-B SK DFS4 125-4/0.30-B SK
n/a n/a DFS4 125-2/0.50-B SK DFS4 125-4/0.50-B SK

Both 2 & 4 pole devices are 4 modules wide.

Time Delay SK devices and 500V


versions of NK & SK devices are available.
Please contact our sales office for details.

[email protected] 15
Doepke Residual Current Circuit Breakers

Type For use in 50Hz AC electrical

B
circuits feeding loads which can
generate AC & DC leakage currents

The DFL8 range incorporates type ‘B’ RCD trips with current ratings up to 250 Amps.
Each unit comprises: 4 Pole Circuit Breaker (Ics 50kA at 415V) with adjustable overload
setting (0.8-1 x In) and short circuit trip (6-10 x In). RCCB trip function module available
in non adjustable and adjustable versions (factory fitted).

provides classic 300mA fire protection


up to 100kHz.

I n = 0.03A
Rating Sensitivity Reference
DFL8 100-4/0.03 B NK
DFL8 125-4/0.03 B NK
DFL8 160-4/0.03 B NK
DFL8 200-4/0.03 B NK
DFL8 250-4/0.03 B NK
I n : 0.3A-0.5A-1A
Time delay: 60-150-300-450ms
Rating Sensitivity Reference
DFL8 100-4/X B NK
DFL8 125-4/X B NK
DFL8 160-4/X B NK
DFL8 200-4/X B NK
for use in installations designed to DFL8 250-4/X B NK
withstand high leakage currents.

I n = 0.03A
Rating Sensitivity Reference
DFL8 100-4/0.03 B SK Pictured above is the panel
DFL8 125-4/0.03 B SK where the overload setting
DFL8 160-4/0.03 B SK (0.8 -1 x In) and short circuit
DFL8 200-4/0.03 B SK trip (6 -10 x In) can be
DFL8 250-4/0.03 B SK adjusted.
I n : 0.3A-0.5A-1A
Time delay: 60-150-300-450ms The illustration right shows
Rating Sensitivity Reference the optional IP54 insulated
DFL8 100-4/X B SK enclosure available for
DFL8 125-4/X B SK mounting a DFL8 device.
DFL8 160-4/X B SK
DFL8 200-4/X B SK The part No. is 09 200 028
DFL8 250-4/X B SK Dimensions: 295W x 690H x 170D

16 www.doepke.co.uk
Type B RCCBs

provides 420mA fire protection up to 20,000Hz.

4 Modules wide 4 Modules wide


Rating Sensitivity 2 Pole Reference 4 Pole Reference
DFS4 016-2/0.03-B DFS4 016-2/0.03-B
DFS4 016-2/0.10-B DFS4 016-2/0.10-B
DFS4 016-2/0.30-B DFS4 016-2/0.30-B
DFS4 025-2/0.03-B DFS4 025-2/0.03-B
DFS4 025-2/0.10-B DFS4 025-2/0.10-B
DFS4 025-2/0.30-B DFS4 025-2/0.30-B
DFS4 040-2/0.03-B DFS4 040-2/0.03-B
DFS4 040-2/0.10-B DFS4 040-2/0.10-B
DFS4 040-2/0.30-B DFS4 040-2/0.30-B
DFS4 063-2/0.03-B DFS4 063-2/0.03-B
DFS4 063-2/0.10-B DFS4 063-2/0.10-B
DFS4 063-2/0.30-B DFS4 063-2/0.30-B
DFS4 080-2/0.03-B DFS4 080-2/0.03-B
DFS4 080-2/0.10-B DFS4 080-2/0.10-B
DFS4 080-2/0.30-B DFS4 080-2/0.30-B
DFS4 100-2/0.03-B DFS4 100-2/0.03-B
DFS4 100-2/0.10-B DFS4 100-2/0.10-B
DFS4 100-2/0.30-B DFS4 100-2/0.30-B
DFS4 125-2/0.03-B DFS4 125-2/0.03-B
DFS4 125-2/0.10-B DFS4 125-2/0.10-B
DFS4 125-2/0.30-B DFS4 125-2/0.30-B

Both 2 & 4 pole devices are 4 modules wide. A DHi 11 switch attached
to a four pole RCCB.

Description Modules Reference

DFA 2 Remote Actuator 4 09 100 110


Power supply RK 24 2 09 980 654
Auxiliary switch DHi 11 0.5 09 200 040

DFA 2 is a remote RCCB actuator which is


powered by a 24V supply (RK 24 see page 23).

The DHi 11 switch is retrofittable to all DFS2 & 4 RCCBs.

Description Reference
for 2 & 4 pole RCCBs WES

To avoid reconnection during maintenance or


repair work. Avoids the possibility of accidental
connection to mains voltage. Made of stainless
steel they are easily fitted.

[email protected] 17
Doepke RCCBs - Practical Applications Guide

Checklist - General Limits of Operation for RCDs / RCCBs


Understanding the different types of RCCB and the characteristics that may be
specified by equipment manufacturers, reduces the risk of installing inappropriate and
unsafe protection. In addition it also helps during risk assessment for existing
installations, to identify potential dangerous situations and installations.

Equipment Requiring Special Types of RCD / RCCB


The table below gives some generic examples based on the installed technology used
and the associated RCCB. It is imperative that the Equipment Manufacturer’s
Installation Instructions are checked, with regard to advice relating to the minimum
sensitivity and the Type of RCCB that can be used safely with their equipment.

18 www.doepke.co.uk
Doepke

Technical Data Dimensions Contact Assignments

Number of poles 2-pole or 4-pole


Rated voltage Un 230 V AC
Frequency 50 Hz
Max. operating voltage Un + 10 %
Working voltage range
of the test circuit 150 V - 250 V AC 250 V - 440 V AC
Short circuit resistance
(In 16-40A) 10 kA with 63 A fuse
(In 63A) 10 kA with 80 A fuse
(In 80A) 10 kA with 100 A fuse
(In 100A) 10 kA with 125 A fuse
(In 125A) 10 kA with 125 A fuse
Ambient temperature -250 C to +400 C
Resistance to climatic changes Conforming to DIN IEC 68 Parts 2 - 30 :
damp, heat cyclic (550 C / 28 cycles)
Impact resistance 20 g / 20 ms duration
Vibration resistance > 5 g (f <_ 80 Hz, duration > 30 min.)
Enclosure protection type IP 40 (after installation in distribution board)
Terminals 1,5 up to 50mm2, multicore
Service life >_ 5000 switching cycles
Standards EN 61008

Technical Data Dimensions Contact Assignments (below)

Number of poles 4-poles


Rated voltage Un 400/690 V AC 50/60Hz

Residual current detection range AC: 50Hz or 60Hz


Pulsating DC: 50 or 60Hz
Working voltage range
of the test circuit 280 -690 V AC

Short circuit resistance Icu Ics


400/415 V AC 50 kA 50kA
690 V AC 20 kA 5kA

If short circuit current > Icu Back up fuse 250A/gL

Tripping Char DFL8 A 0.03A fixed


DFL8 AX 0.3A; 0.5A; 1.0A

Thermal Trip Ir 0.8-1 x In


Magnetic Trip Ii 6-10 x In

Design requirements:
overload trip & residual current trip EN 60947-2 & EN 60947-2 Appx. B

Surge current resistance Verification of CBR resistance to unintentional


response due to surge currents caused by
impulse voltages EN 60947-2:2003 (B.8.6)
Ambient temperature -250 C to +400 C
Resistance to climatic changes Constant IEC 60068-2-78
Cyclic IEC 60068-2-30
Impact resistance 20 g / 20 ms IEC 60068-2-27
Vibration resistance 1g @ f=1-200Hz IEC 60068-2-30
Protection IP 20
Terminals 1 x 185mm2 2 x 70mm2

Standards IEC 947-2 & Appx. B

36 www.doepke.co.uk
TECHNICAL SPECIFICATIONS
Technical Data Dimensions Contact Assignments

Number of poles 2-pole or 4-pole


Rated voltage Un AC 230 V 400 V
Rated Frequency (NK version) 0-1MHz
Min operating voltage for
detecting Type B residual current 30 V AC
Working voltage range
of the test circuit 100 V - 250 V AC 185 V - 440 V AC
Short circuit resistance with
fuse back up 10kA
Maximum fuse size In 16<80A 100 A/gL
In 100<125A 125 A/gL
Surge current resistance Ring wave 0.5ms/100kHz:200A
Impulse 8/20 s: 3kA
Ambient temperature -250 C to +400 C
Resistance to climatic changes Conforming to DIN IEC 68 Parts 2 - 30 :
damp, heat cyclic (550 C / 28 cycles)
Impact resistance 20 g / 20 ms duration
Vibration resistance > 5 g (f <_ 80 Hz, duration > 30 min.)
Enclosure protection type IP 40 (after installation in distribution board)
Terminals 1,5 up to 50mm2, multicore
Service life >_ 5000 switching cycles
Standards EN 61008 & EN 62423

Technical Data Dimensions Contact Assignments (below)

Number of poles 4-poles


Rated voltage Un 400 V AC 50/60Hz

Residual current detection range AC: 0-100kHz


Pulsating DC: 50 or 60Hz

Min operating voltage for


detecting Type B residual current 50 V AC

Working voltage range


of the test circuit 50-400 V AC

Short circuit resistance Icu Ics

400/415 V AC 50 kA 50kA

If short circuit current > Icu Back up fuse 250A/gL

Tripping Char DFL8 B 0.03A fixed


DFL8 BX 0.3A; 0.5A; 1.0A

Thermal Trip Ir 0.8-1 x In


Magnetic Trip Ii 6-10 x In

Ambient temperature -250 C to +400 C


Resistance to climatic changes Constant IEC 60068-2-78
Cyclic IEC 60068-2-30
Impact resistance 20 g / 20 ms IEC 60068-2-27
Vibration resistance 1g @ f=1-200Hz IEC 60068-2-30
Protection IP 20
Terminals 1 x 185mm2 2 x 70mm2

Standards IEC 947-2 & Appx. B & J

[email protected] 37
Doepke

Technical Data Dimensions Contact Assignments (below)

Number of poles 2-pole or 4-pole


Rated voltage Un 230 V AC 400 V AC
Frequency 50 Hz
Operating voltage for detecting
6mA DC (trips if value exceeded) >_ 85V AC
Test circuit voltage range 150 V - 250 V AC 185 V - 440 V AC
Neutral position on the right on the left
Surge current resistance Impulse 8/20us: 3kA
Ambient temperature -250 C to +400 C
Resistance to climatic changes Conforming to DIN IEC 680068-2-30 :
humid heat cyclic (250C/550C; 93%/97%)
Impact resistance 20 g / 20 ms duration
Vibration resistance > 5 g (f <_ 80 Hz, duration > 30 min.)
Enclosure protection type IP 40 (after installation in distribution board)
Terminals 1,5 up to 50mm2, multicore
Service life >_ 5000 switching cycles
Standards Pr EN standard in development

Technical Data Dimensions

38 www.doepke.co.uk