Generation Subsystem Transmission Subsystem Distribution Subsystem
Generation Subsystem Transmission Subsystem Distribution Subsystem
1.0 Introduction
3
a. Switches: devices that can carry and
interrupt normal load current and thus
disconnect portions of the network.
b.Circuit breakers: devices that can carry
and interrupt normal load current, like
switches; in addition, they interrupt short-
circuit (fault) current. Circuit breakers are
always paired with a relay which senses
short-circuit condition using potential
transformers (PTs) and current
transformers (CTs).
c. Reclosers: devices similar in function to
circuit breakers, except they also have the
ability to reclose after opening, open
again, and reclose again, repeating this
cycle a predetermined number of times
until they lockout.
d.Fuses: devices that can carry a defined
load current without deterioration and
interrupt a defined short-circuit current.
Circuit breakers, reclosers, and fuses are
protection devices. Often, switches are
used on the high side of the transformer,
4
and protection devices are used on the low
side, but substations supplying large
amounts of load may have protection
devices on both sides of the transformer.
Special substation designs to achieve high
reliability may utilize multiple circuit
breakers, as shown in Fig. 1. Less
expensive designs may use protection only
in series with the feeders, as shown in Fig.
2. In these figures, switches and circuit
breakers are normally closed unless there is
a “N.O.” (normally open) indicated beside
it. The Fig. 1 design provides that all
feeders can remain supplied for a
transformer outage (caused by maintenance
or fault) or a subtransmission line outage.
The low voltage breaker scheme of Fig. 1 is
called “breaker and a half” because it
requires 3 breakers to protect 2 feeders.
5
N.O.
fuse
N.O.
N.O.
1.02
1.00
0.98
0.96
0.94
Distance from substation
7
4.Metering: Most substations do have some
sort of metering device that records, at a
minimum, existing current and current max
and min that have occurred in the last time
period (e.g., 1 hour). Digital recording is
also heavily used and capable of recording
a large amount of substation operational
information.
8
residential neighborhoods, and they are often
radial even in urban areas. In densely
populated urban areas, particularly
commercial and business districts where
reliability is critical, feeders may be looped.
The prices to pay for such a reliability benefit
are as follows:
Protection is more costly since a given fault
on the loop will require at least two
protective devices to operate, and to obtain
the reliability benefits, multiple switching
devices must be installed along the feeder.
The fault currents tend to be lower, closer
to normal load currents, and therefore there
is less margin between breaker trip current
and normal load current.
Voltage control is complex since there are
2 control points.
One way to obtain the reliability benefit of a
looped configuration while avoiding some of
the above difficulties is to operate a looped
configuration in open-loop, i.e., employ a
normally open switch mid-way in the loop.
9
Then when the loop is faulted, the normally
open switch can be closed while a switch just
downstream of the fault can be opened, and
all of the de-energized loop up to the
downstream switch can be supplied. This is
illustrated in Fig. 4.
fault
N.O.
10
may be utilized in at any operating voltage
assigned to that class. For example, an
insulator of voltage class 15 kV may utilized
in a 12.47kV, 13.2kV, and 13.8kV system.
There are four major distribution-level
voltage classes: 5kV, 15kV, 25kV, and 35kV.
The 15kV voltage class is the most prevalent.
11
interruptions due to the greater number of
customers per protected circuit.
12
The 120/240 configuration is obtained from
the low-side of a HV/240 volt transformer,
where HV is the rated voltage on the high
voltage side, and the 240 is the rated voltage
on the low voltage side. Then a center tap is
connected to the low voltage winding and
grounded along with the low side of the
primary winding. This provides three wires
on the low voltage side. One is +120V, one is
-120V, and one (the center tap) is 0. Thus,
two are “hot,” one is ground (neutral). The
240V connection is obtained by connecting
across the two hot wires. The 120V
connection is obtained by connecting from
either hot wire to the neutral wire.
14