Struc. Design

This document provides the design parameters and structural analysis for a proposed 9-story apartment building in Mirpur, Dhaka. It includes specifications for materials, wind and seismic load calculations, and determinations of base shear, overturning moment, and approximate lateral sway. The analyses show that wind governs the short direction design and seismic governs the long direction design. Frame stiffness and capacity checks were also performed.

Uploaded by

Salma Sharmin
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
135 views

Struc. Design

This document provides the design parameters and structural analysis for a proposed 9-story apartment building in Mirpur, Dhaka. It includes specifications for materials, wind and seismic load calculations, and determinations of base shear, overturning moment, and approximate lateral sway. The analyses show that wind governs the short direction design and seismic governs the long direction design. Frame stiffness and capacity checks were also performed.

Uploaded by

Salma Sharmin
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 486

G + 9-STORIED (WITHOUT BASEMENT) APARTMENT BUILDING

AT PLOT NO. 795/A, KAZIPARA, MIRPUR, DHAKA - 1216

MIAMI

DESIGN PARAMETERS:-

1. f'c = 3000 psi


2. fy = 60000 psi
3. Live Load = 40 psf
4. Partition Load = 5" Brick wall
5. Wind Velocity = 120 mph
6. Seismic Factor - Moderate Damage.
7. Code Follows - B.N.B.C.

Design by :- Md. Masud Sheikh


B.Sc. Engg.(civil) M.I.E.B.

WIND LOAD ANALYSIS :-


Ref. ANSI Standard A58.1-1982.

P1 = qz Gh Cp
V = 120 MPH
I = 1
qz = 0.0025 Kz(IV)2
qz = 36 Kz
Gh = 0.65 + 3.65 Tz
2.35(Do)1/2
Tz = --------------------
(Z/30)1/L
Bldg Ht. Z = 95 ft
Do = 0.01 For Exposure B.
L = 4.5 For Exposure B.
Tz = 0.1818959
Gh = 1.31392
Cp = .8+.5 = 1.3
P1 = 61.491457 Kz psf

P1 =
HT. in ft Kz 61.491457 Kz psf
---------------------------------------------------------------------------------
0 0 0 0
15 0.37 22.751839 0.3412776
20 0.42 25.826412 0.1291321
25 0.46 28.28607 0.1414304
30 0.5 30.745728 0.1537286
40 0.57 35.05013 0.3505013
50 0.63 38.739618 0.3873962
60 0.68 41.81419 0.4181419
70 0.73 44.888763 0.4488876
80 0.77 47.348422 0.4734842
95 0.82 50.422994 0.7563449
100 0.86 52.882653
105 0.93 57.187055
130 0.99 60.876542
160 1.05 64.566029
180 1.11 68.255517
185 1.16 71.33009
250 1.28 78.709064
---------------------------------------------------------------------------------
V = 3.6003248
Length of Building = 79
Width of Building = 65
Total Base Shear in the Short
direction of the Bldg. = 284.42566
Total Base Shear in the Long
direction of the Bldg. = 234.02111

SEISMIC LOAD ANALYSIS :-

No. of storied with Basement = 10


Length of Building = 79 ft
Width of Building = 65 ft
Total Shear Wall = 0 rft
Shear Wall Thickness= 0 in
Total 10" Wall = 0 rft
10" Wall Thickness= 0 in
Total 5" Wall = 1000 rft
5" Wall Thickness= 4 in
No of Column = 40 nos
Column Size = 15 in
20 in
Total Beam = 865 rft
Beam Weight per ft. = 0.2 k/ft
Slab Thickness = 4.5 in
Floor to Floor Height = 10 ft
Floor Finish Load = 20 psf
Partition Wall Load = 20 psf
Lime Terracing Load = 40 psf
Parapet Wall Height = 4 ft
Parapet Wall Thickness = 5 in
Total Building Area per Floor = 5135 sft
Total Shear Wall Area per Floor = 0 sft
Total Column Area per Floor = 83.333333 sft
Total 10" Wall Area per Floor = 0 sft
Total 5" Wall Area per Floor = 333.33333 sft
Lift core & void area = 740 sft
Net Floor Area per Floor = 3978.3333 sft

1. Self Weight of Slab per Floor = 223.78125 kip


2. Col.&S.Wall Weight per Floor = 125 kip
3. Floor Finish Weight per Floor = 79.566667 kip
4. Partition Wall Weight per Floor = 79.566667 kip
5. 10" Wall Weight per Floor = 0 kip
5. 5" Wall Weight per Floor = 350 kip
6. Beam Weight per Floor = 173 kip
7. Lime Terracing wt. at Roof = 205.4 kip
8. Parapet wt.. at Roof = 72 kip
9. Live Load per Floor = 40 psf
10. Live Load at Roof = 40 psf

Floor Dead Load 25% L.L Total Load

Roof 674.18125 51.35 725.53125 kip


15 th kip
14 th kip
13 th kip
12 th kip
11 th kip
10 th kip
9 th kip
8 th 1030.9146 39.783333 1070.6979 kip
7 th 1030.9146 39.783333 1070.6979 kip
6 th 1030.9146 39.783333 1070.6979 kip
5 th 1030.9146 39.783333 1070.6979 kip
4 th 1030.9146 39.783333 1070.6979 kip
3 rd 1030.9146 39.783333 1070.6979 kip
2nd 1030.9146 39.783333 1070.6979 kip
1 st 1030.9146 39.783333 1070.6979 kip
Gr. 1030.9146 39.783333 1070.6979 kip
------------------------------------------------------------------------
W= 9952.4125 409.4 10361.813 kip

Therefore Load = 0.201788 ksf per floor

Z= 0.15 (BNBC)
I = 1
Ct = 0.073
hn = 28.963415 meter
T = 0.9114024
S = 1.5
C = 1.9946251
R = 8
Vshort = 0.0373992 W
Vshort = 372.21248 kip < 284.42566

Vlong = 0.0373992 W
Vlong = 372.21248 kip > 234.02111

In the short direction of the building wind load


governed the design and in the long direction
of the building seismic load governed the design.

CHECK FOR OVERTURNING


-------------------------------------------------
Overturning Moment in the Short direction
due to Wind Load Mo = 15467.922 k-ft

Registing Moment in the Short direction


due to Dead Load Mr = 323453.41 k-ft

F.S.against overturning= 20.911238 > 3 O.K.


IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FA

Total building ht. H = 95 ft


Floor to floor ht. h = 10 ft
Beam span L = 16.25 ft
Total frame width B = 62 ft
Total no. of storied = 9 + Basement
Total base shear in the short direction
of the building = 370 kip
No. of frame = 6 nos
Shear at base in each frame
V1 = 61.666667 kip
Shear above 3rd floor in each frame
V4 = 41.111111 kip
Shear above 4th floor in each frame
V5 = 34.259259 kip
Axial column forces for exterior column
at base N1 = 44.758065 kip
Axial column forces for exterior column
above 3rd floor N4 = 19.892473 kip
Axial column forces for exterior column
above 4th floor N5 = 13.814217 kip
Girder lateral load shear at 4th floor
level vg4 = 6.0782557 kip

Shear for a typical exterior column

v1 = 8.0813172 kip
v4 = 5.3875448 kip
v5 = 4.4896207 kip

Column size above 3rd


floor level = 15 in.
15 in.
Beam size above 3rd
floor level = 12 in.
21 in.

A max for Exterior Frame type - FA

Vc = 5.3875448 kip
Vg = 6.0782557 kip
Nc = 44.758065 kip
Ic = 4218.75 in4
Ig = 9261 in4
Ac = 225 sq-in.
h = 10 ft
H = 95 ft
L = 16.25 ft
B= 62 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.5823337 in 40.165047 %

Ag=HVgL2/12EIg = 0.7903012 in 54.509097 %

A'c=2NcH2/3EAcB = 0.077217 in 5.3258554 %

A max = Ac+Ag+A'c = 1.449852 in. < 2.28 in.

Flexural stiffness of the


frame is KfA = 42.533078 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FB

Total building ht. H = 95 ft


Floor to floor ht. h = 10 ft
Beam span L = 16.25 ft
Total frame width B = 62 ft
Total no. of storied = 9 +Basement
Total base shear in the short direction
of the building = 370 kip
No. of frame = 6 nos
Shear at base in each frame
V1 = 61.666667 kip
Shear above 3rd floor in each frame
V4 = 41.111111 kip
Shear above 4th floor in each frame
V5 = 34.259259 kip
Axial column forces for exterior column
at base N1 = 44.758065 kip
Axial column forces for exterior column
above 3rd floor N4 = 19.892473 kip
Axial column forces for exterior column
above 4th floor N5 = 13.814217 kip
Girder lateral load shear at 4th floor
level vg4 = 6.0782557 kip

Shear for a typical exterior column

v1 = 8.0813172 kip
v4 = 5.3875448 kip
v5 = 4.4896207 kip

Column size above 3rd


floor level = b = 15 in.
h = 20 in.
Beam size above 3rd
floor level = b = 12 in.
h = 21 in.

A max for Interior Frame type - FB

Vc = 5.3875448 kip
Vg = 6.0782557 kip
Nc = 44.758065 kip
Ic = 10000 in4
Ig = 9261 in4
Ac = 300 sq-in.
h = 10 ft
H = 95 ft
L = 16.25 ft
B= 62 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.245672 in 22.458651 %

Ag=HVgL2/12EIg = 0.7903012 in 72.247126 %

A'c=2NcH2/3EAcB = 0.0579128 in 5.2942229 %

A max = Ac+Ag+A'c = 1.093886 in. < 2.28 in.

Flexural stiffness of the


frame is KfB = 56.373941 k/in.
IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FC

Total building ht. H = 95 ft


Floor to floor ht. h = 10 ft
Beam span L = 16.25 ft
Total frame width B = 50 ft
Total no. of storied = 9 .+Basement
Total base shear in the short direction
of the building = 370 kip
No. of frame = 6 nos
Shear at base in each frame
V1 = 61.666667 kip
Shear above 3rd floor in each frame
V4 = 41.111111 kip
Shear above 4th floor in each frame
V5 = 34.259259 kip
Axial column forces for exterior column
at base N1 = 55.5 kip
Axial column forces for exterior column
above 3rd floor N4 = 24.666667 kip
Axial column forces for exterior column
above 4th floor N5 = 17.12963 kip
Girder lateral load shear at 4th floor
level vg4 = 7.537037 kip

Shear for a typical exterior column

v1 = 10.020833 kip
v4 = 6.6805556 kip
v5 = 5.5671296 kip

Column size above 3rd


floor level = b = 15 in.
h = 20 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FC


Vc = 6.6805556 kip
Vg = 7.537037 kip
Nc = 55.5 kip
Ic = 10000 in4
Ig = 7717.5 in4
Ac = 300 sq-in.
h = 10 ft
H = 95 ft
L = 16.25 ft
B= 50 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.3046333 in 19.407746 %

Ag=HVgL2/12EIg = 1.1759682 in 74.919221 %

A'c=2NcH2/3EAcB = 0.0890467 in 5.6730333 %

A max = Ac+Ag+A'c = 1.5696482 in. < 2.28 in.

Flexural stiffness of the


frame is KfC = 39.286934 k/in.

No. of frame
Kf1 = 42.533078 2
Kf2 = 56.373941 3
Kf3 = 39.286934 1
-----------------------------------------
Ekf = 293.47491

Lateral load carrid


by frame = 370 kip
Lateral load carrid
by frame F1 = 53.623796 kip
Deflection A f1 = 1.2607551 in. < 2.28 in.
Lateral load carrid
by frame F2 = 71.073735 kip
Deflection A f2 = 1.2607551 in. < 2.28 in.
Lateral load carrid
by frame F3 = 49.531204 kip
Deflection A f1 = 1.2607551 in. < 2.28 in.

IN THE LONG DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FA

Total building ht. H = 95 ft


Floor to floor ht. h = 10 ft
Beam span L = 22 ft
Total frame width B = 78 ft
Total no. of storied = 9 + Basement
Total base shear in the short direction
of the building = 370 kip
No. of frame = 6 nos
Shear at base in each frame
V1 = 61.666667 kip
Shear above 3rd floor in each frame
V4 = 41.111111 kip
Shear above 4th floor in each frame
V5 = 34.259259 kip
Axial column forces for exterior column
at base N1 = 35.576923 kip
Axial column forces for exterior column
above 3rd floor N4 = 15.811966 kip
Axial column forces for exterior column
above 4th floor N5 = 10.980532 kip
Girder lateral load shear at 4th floor
level vg4 = 4.831434 kip

Shear for a typical exterior column

v1 = 8.6965812 kip
v4 = 5.7977208 kip
v5 = 4.831434 kip

Column size above 3rd


floor level = 15 in.
15 in.
Beam size above 3rd
floor level = 10 in.
21 in.

A max for Exterior Frame type - FA

Vc = 5.7977208 kip
Vg = 4.831434 kip
Nc = 35.576923 kip
Ic = 4218.75 in4
Ig = 7717.5 in4
Ac = 225 sq-in.
h = 10 ft
H = 95 ft
L = 22 ft
B= 78 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.6266692 in 30.463078 %

Ag=HVgL2/12EIg = 1.3816868 in 67.165315 %

A'c=2NcH2/3EAcB = 0.0487873 in 2.3716066 %

A max = Ac+Ag+A'c = 2.0571434 in. < 2.28 in.

Flexural stiffness of the


frame is KfA = 29.976844 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FB

Total building ht. H = 95 ft


Floor to floor ht. h = 10 ft
Beam span L = 22 ft
Total frame width B = 78 ft
Total no. of storied = 9 +Basement
Total base shear in the short direction
of the building = 370 kip
No. of frame = 6 nos
Shear at base in each frame
V1 = 61.666667 kip
Shear above 3rd floor in each frame
V4 = 41.111111 kip
Shear above 4th floor in each frame
V5 = 34.259259 kip
Axial column forces for exterior column
at base N1 = 35.576923 kip
Axial column forces for exterior column
above 3rd floor N4 = 15.811966 kip
Axial column forces for exterior column
above 4th floor N5 = 10.980532 kip
Girder lateral load shear at 4th floor
level vg4 = 4.831434 kip

Shear for a typical exterior column

v1 = 8.6965812 kip
v4 = 5.7977208 kip
v5 = 4.831434 kip

Column size above 3rd


floor level = b = 20 in.
h = 15 in.
Beam size above 3rd
floor level = b = 12 in.
h = 21 in.

A max for Interior Frame type - FB

Vc = 5.7977208 kip
Vg = 4.831434 kip
Nc = 35.576923 kip
Ic = 5625 in4
Ig = 9261 in4
Ac = 300 sq-in.
h = 10 ft
H = 95 ft
L = 22 ft
B= 78 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.4700019 in 28.347554 %

Ag=HVgL2/12EIg = 1.1514057 in 69.445537 %

A'c=2NcH2/3EAcB = 0.0365905 in 2.2069091 %


A max = Ac+Ag+A'c = 1.6579981 in. < 2.28 in.

Flexural stiffness of the


frame is KfB = 37.193448 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FC

Total building ht. H = 95 ft


Floor to floor ht. h = 10 ft
Beam span L = 15 ft
Total frame width B = 78 ft
Total no. of storied = 9 .+Basement
Total base shear in the short direction
of the building = 370 kip
No. of frame = 6 nos
Shear at base in each frame
V1 = 61.666667 kip
Shear above 3rd floor in each frame
V4 = 41.111111 kip
Shear above 4th floor in each frame
V5 = 34.259259 kip
Axial column forces for exterior column
at base N1 = 35.576923 kip
Axial column forces for exterior column
above 3rd floor N4 = 15.811966 kip
Axial column forces for exterior column
above 4th floor N5 = 10.980532 kip
Girder lateral load shear at 4th floor
level vg4 = 4.831434 kip

Shear for a typical exterior column

v1 = 5.9294872 kip
v4 = 3.9529915 kip
v5 = 3.2941595 kip

Column size above 3rd


floor level = b = 20 in.
h = 15 in.
Beam size above 3rd
floor level = b = 12 in.
h = 21 in.

A max for Interior Frame type - FC

Vc = 3.9529915 kip
Vg = 4.831434 kip
Nc = 35.576923 kip
Ic = 5625 in4
Ig = 9261 in4
Ac = 300 sq-in.
h = 10 ft
H = 95 ft
L = 15 ft
B= 78 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.3204558 in 35.913172 %

Ag=HVgL2/12EIg = 0.5352609 in 59.986165 %

A'c=2NcH2/3EAcB = 0.0365905 in 4.1006627 %

A max = Ac+Ag+A'c = 0.8923073 in. < 2.28 in.

Flexural stiffness of the


frame is KfC = 69.109229 k/in.

No. of frame
Kf1 = 29.976844 2
Kf2 = 37.193448 2
Kf3 = 69.109229 2
-----------------------------------------
Ekf = 272.55904

Lateral load carrid


by frame = 370 kip
Lateral load carrid
by frame F1 = 40.693687 kip
Deflection A f1 = 1.357504 in. < 2.28 in.
Lateral load carrid
by frame F2 = 50.490256 kip
Deflection A f2 = 1.357504 in. < 2.28 in.
Lateral load carrid
by frame F3 = 93.816057 kip
Deflection A f1 = 1.357504 in. < 2.28 in.
G + 8-STORIED (WITH BASEMENT) APARTMENT BUILDING
AT PLOT NO. 2 / B, GOLDEN STREET, MOHAMMADPUR,
RING ROAD, DHAKA.

SEL SOBHAN PALACE

DESIGN PARAMETERS:-

1. f'c = 3000 psi


2. fy = 60000 psi
3. Live Load = 40 psf
4. Partition Load = 5" Brick wall
5. Wind Velocity = 120 mph
6. Seismic Factor - Moderate Damage.
7. Code Follows - B.N.B.C.

Design by :- Md. Masud Sheikh


B.Sc. Engg.(civil) M.I.E.B.

WIND LOAD ANALYSIS :-


Ref. ANSI Standard A58.1-1982.

P1 = qz Gh Cp
V = 120 MPH
I = 1
qz = 0.0025 Kz(IV)2
qz = 36 Kz
Gh = 0.65 + 3.65 Tz
2.35(Do)1/2
Tz = --------------------
(Z/30)1/L
Bldg Ht. Z = 105 ft
Do = 0.01 For Exposure B.
L = 4.5 For Exposure B.
Tz = 0.177895
Gh = 1.2993169
Cp = .8+.5 = 1.3
P1 = 60.808032 Kz psf

P1 =
HT. in ft Kz 60.808032 Kz psf
---------------------------------------------------------------------------------
0 0 0 0
15 0.37 22.498972 0.3374846
20 0.42 25.539373 0.1276969
25 0.46 27.971695 0.1398585
30 0.5 30.404016 0.1520201
40 0.57 34.660578 0.3466058
50 0.63 38.30906 0.3830906
60 0.68 41.349462 0.4134946
70 0.73 44.389863 0.4438986
80 0.77 46.822184 0.4682218
90 0.82 49.862586 0.4986259
100 0.86 52.294907 0.5229491
105 0.93 56.551469 0.2827573
130 0.99 60.199951
160 1.05 63.848433
180 1.11 67.496915
185 1.16 70.537317
250 1.28 77.834281
---------------------------------------------------------------------------------
V = 4.1167037
Length of Building = 47
Width of Building = 35
Total Base Shear in the Short
direction of the Bldg. = 193.48508
Total Base Shear in the Long
direction of the Bldg. = 144.08463
SEISMIC LOAD ANALYSIS :-

No. of storied with Basement = 11


Length of Building = 47 ft
Width of Building = 35 ft
Total Shear Wall = 0 rft
Shear Wall Thickness= 0 in
Total 10" Wall = 50 rft
10" Wall Thickness= 7 in
Total 5" Wall = 230 rft
5" Wall Thickness= 4 in
No of Column = 16 nos
Column Size = 15 in
20 in
Total Beam = 280 rft
Beam Weight per ft. = 0.2 k/ft
Slab Thickness = 4.5 in
Floor to Floor Height = 10 ft
Floor Finish Load = 20 psf
Partition Wall Load = 0 psf
Lime Terracing Load = 40 psf
Parapet Wall Height = 4 ft
Parapet Wall Thickness = 5 in
Total Building Area per Floor = 1645 sft
Total Shear Wall Area per Floor = 0 sft
Total Column Area per Floor = 33.333333 sft
Total 10" Wall Area per Floor = 29.166667 sft
Total 5" Wall Area per Floor = 76.666667 sft
Lift core & void area = 150 sft
Net Floor Area per Floor = 1355.8333 sft

1. Self Weight of Slab per Floor = 76.265625 kip


2. Col.&S.Wall Weight per Floor = 50 kip
3. Floor Finish Weight per Floor = 27.116667 kip
4. Partition Wall Weight per Floor = 0 kip
5. 10" Wall Weight per Floor = 28.875 kip
5. 5" Wall Weight per Floor = 80.5 kip
6. Beam Weight per Floor = 56 kip
7. Lime Terracing wt. at Roof = 65.8 kip
8. Parapet wt.. at Roof = 41 kip
9. Live Load per Floor = 40 psf
10. Live Load at Roof = 40 psf

Floor Dead Load 25% L.L Total Load


Roof 239.06563 16.45 255.51563 kip
15 th kip
14 th kip
13 th kip
12 th kip
11 th kip
10 th kip
9 th 318.75729 13.558333 332.31563 kip
8 th 318.75729 13.558333 332.31563 kip
7 th 318.75729 13.558333 332.31563 kip
6 th 318.75729 13.558333 332.31563 kip
5 th 318.75729 13.558333 332.31563 kip
4 th 318.75729 13.558333 332.31563 kip
3 rd 318.75729 13.558333 332.31563 kip
2nd 318.75729 13.558333 332.31563 kip
1 st 318.75729 13.558333 332.31563 kip
Gr. 318.75729 13.558333 332.31563 kip
------------------------------------------------------------------------
W= 3426.6385 152.03333 3578.6719 kip

Therefore Load = 0.1977713 ksf per floor

Z= 0.15 (BNBC)
I = 1
Ct = 0.073
hn = 32.012195 meter
T = 0.9824477
S = 1.5
C = 1.8972665
R = 8
Vshort = 0.0355737 W
Vshort = 121.89837 kip < 193.48508

Vlong = 0.0355737 W
Vlong = 121.89837 kip > 144.08463

In the short direction of the building wind load


governed the design and in the long direction
of the building seismic load governed the design.

CHECK FOR OVERTURNING


-------------------------------------------------
Overturning Moment in the Short direction
due to Wind Load Mo = 11713.421 k-ft

Registing Moment in the Short direction


due to Dead Load Mr = 59966.174 k-ft
F.S.against overturning= 5.1194417 > 3 O.K.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FA

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 15 ft
Total frame width B = 35 ft
Total no. of storied = 10 + Basement
Total base shear in the short direction
of the building = 180 kip
No. of frame = 4 nos
Shear at base in each frame
V1 = 45 kip
Shear above 3rd floor in each frame
V4 = 31.5 kip
Shear above 4th floor in each frame
V5 = 27 kip
Axial column forces for exterior column
at base N1 = 64.285714 kip
Axial column forces for exterior column
above 3rd floor N4 = 31.5 kip
Axial column forces for exterior column
above 4th floor N5 = 23.142857 kip
Girder lateral load shear at 4th floor
level vg4 = 8.3571429 kip

Shear for a typical exterior column

v1 = 9.6428571 kip
v4 = 6.75 kip
v5 = 5.7857143 kip

Column size above 3rd


floor level = 15 in.
20 in.
Beam size above 3rd
floor level = 12 in.
21 in.

A max for Exterior Frame type - FA

Vc = 6.75 kip
Vg = 8.3571429 kip
Nc = 64.285714 kip
Ic = 10000 in4
Ig = 9261 in4
Ac = 300 sq-in.
h = 10 ft
H = 105 ft
L = 15 ft
B= 35 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.3402 in 22.040479 %

Ag=HVgL2/12EIg = 1.0233236 in 66.297892 %

A'c=2NcH2/3EAcB = 0.18 in 11.661629 %

A max = Ac+Ag+A'c = 1.5435236 in. < 2.52 in.

Flexural stiffness of the


frame is KfA = 29.154073 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FB

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 15 ft
Total frame width B = 35 ft
Total no. of storied = 10 Basement
Total base shear in the short direction
of the building = 180 kip
No. of frame = 4 nos
Shear at base in each frame
V1 = 45 kip
Shear above 3rd floor in each frame
V4 = 31.5 kip
Shear above 4th floor in each frame
V5 = 27 kip
Axial column forces for exterior column
at base N1 = 64.285714 kip
Axial column forces for exterior column
above 3rd floor N4 = 31.5 kip
Axial column forces for exterior column
above 4th floor N5 = 23.142857 kip
Girder lateral load shear at 4th floor
level vg4 = 8.3571429 kip

Shear for a typical exterior column

v1 = 9.6428571 kip
v4 = 6.75 kip
v5 = 5.7857143 kip

Column size above 3rd


floor level = b = 15 in.
h = 20 in.
Beam size above 3rd
floor level = b = 12 in.
h = 21 in.

A max for Interior Frame type - FB

Vc = 6.75 kip
Vg = 8.3571429 kip
Nc = 64.285714 kip
Ic = 10000 in4
Ig = 9261 in4
Ac = 300 sq-in.
h = 10 ft
H = 105 ft
L = 15 ft
B= 35 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.3402 in 22.040479 %

Ag=HVgL2/12EIg = 1.0233236 in 66.297892 %

A'c=2NcH2/3EAcB = 0.18 in 11.661629 %


A max = Ac+Ag+A'c = 1.5435236 in. < 2.52 in.

Flexural stiffness of the


frame is KfB = 29.154073 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FC

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 15 ft
Total frame width B = 20 ft
Total no. of storied = 10 Basement
Total base shear in the short direction
of the building = 180 kip
No. of frame = 4 nos
Shear at base in each frame
V1 = 45 kip
Shear above 3rd floor in each frame
V4 = 31.5 kip
Shear above 4th floor in each frame
V5 = 27 kip
Axial column forces for exterior column
at base N1 = 112.5 kip
Axial column forces for exterior column
above 3rd floor N4 = 55.125 kip
Axial column forces for exterior column
above 4th floor N5 = 40.5 kip
Girder lateral load shear at 4th floor
level vg4 = 14.625 kip

Shear for a typical exterior column

v1 = 16.875 kip
v4 = 11.8125 kip
v5 = 10.125 kip

Column size above 3rd


floor level = b = 15 in.
h = 20 in.
Beam size above 3rd
floor level = b = 12 in.
h = 21 in.

A max for Interior Frame type - FC

Vc = 11.8125 kip
Vg = 14.625 kip
Nc = 112.5 kip
Ic = 10000 in4
Ig = 9261 in4
Ac = 300 sq-in.
h = 10 ft
H = 105 ft
L = 15 ft
B= 20 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.59535 in 20.267811 %

Ag=HVgL2/12EIg = 1.7908163 in 60.965697 %

A'c=2NcH2/3EAcB = 0.55125 in 18.766492 %

A max = Ac+Ag+A'c = 2.9374163 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 15.319585 k/in.

No. of frame
Kf1 = 29.154073 1
Kf2 = 29.154073 2
Kf3 = 15.319585 1
-----------------------------------------
Ekf = 102.7818

Lateral load carrid


by frame = 180 kip
Lateral load carrid
by frame F1 = 51.057025 kip
Deflection A f1 = 1.7512827 in. < 2.52 in.
Lateral load carrid
by frame F2 = 51.057025 kip
Deflection A f2 = 1.7512827 in. < 2.52 in.
Lateral load carrid
by frame F3 = 26.828925 kip
Deflection A f1 = 1.7512827 in. < 2.52 in.

GRID
A1, A19 TO L1, L19

G + 8-STORIED (WITH BASEMENT) APARTMENT BUILDING


AT PLOT NO. 2 / B, GOLDEN STREET, MOHAMMADPUR,
RING ROAD, DHAKA.

SEL SOBHAN PALACE

DESIGN PARAMETERS:-

1. f'c = 3000 psi


2. fy = 60000 psi
3. Live Load = 40 psf
4. Partition Load = 5" Brick wall
5. Wind Velocity = 120 mph
6. Seismic Factor - Moderate Damage.
7. Code Follows - B.N.B.C.

Design by :- Md. Masud Sheikh


B.Sc. Engg.(civil) M.I.E.B.

WIND LOAD ANALYSIS :-


Ref. ANSI Standard A58.1-1982.

P1 = qz Gh Cp
V = 120 MPH
I = 1
qz = 0.0025 Kz(IV)2
qz = 36 Kz
Gh = 0.65 + 3.65 Tz
2.35(Do)1/2
Tz = --------------------
(Z/30)1/L
Bldg Ht. Z = 105 ft
Do = 0.01 For Exposure B.
L = 4.5 For Exposure B.
Tz = 0.177895
Gh = 1.2993169
Cp = .8+.5 = 1.3
P1 = 60.808032 Kz psf

P1 =
HT. in ft Kz 60.808032 Kz psf
---------------------------------------------------------------------------------
0 0 0 0
15 0.37 22.498972 0.3374846
20 0.42 25.539373 0.1276969
25 0.46 27.971695 0.1398585
30 0.5 30.404016 0.1520201
40 0.57 34.660578 0.3466058
50 0.63 38.30906 0.3830906
60 0.68 41.349462 0.4134946
70 0.73 44.389863 0.4438986
80 0.77 46.822184 0.4682218
90 0.82 49.862586 0.4986259
100 0.86 52.294907 0.5229491
105 0.93 56.551469 0.2827573
130 0.99 60.199951
160 1.05 63.848433
180 1.11 67.496915
185 1.16 70.537317
250 1.28 77.834281
---------------------------------------------------------------------------------
V = 4.1167037
Length of Building = 95.5
Width of Building = 84.75
Total Base Shear in the Short
direction of the Bldg. = 393.14521
Total Base Shear in the Long
direction of the Bldg. = 348.89064
SEISMIC LOAD ANALYSIS :-

No. of storied with Basement = 11


Length of Building = 95.5 ft
Width of Building = 84.75 ft
Total Shear Wall = 0 rft
Shear Wall Thickness= 0 in
Total 10" Wall = 150 rft
10" Wall Thickness= 7 in
Total 5" Wall = 1500 rft
5" Wall Thickness= 4 in
No of Column = 45 nos
Column Size = 15 in
20 in
Total Beam = 1650 rft
Beam Weight per ft. = 0.2 k/ft
Slab Thickness = 4.5 in
Floor to Floor Height = 10 ft
Floor Finish Load = 20 psf
Partition Wall Load = 0 psf
Lime Terracing Load = 40 psf
Parapet Wall Height = 4 ft
Parapet Wall Thickness = 5 in
Total Building Area per Floor = 8093.625 sft
Total Shear Wall Area per Floor = 0 sft
Total Column Area per Floor = 93.75 sft
Total 10" Wall Area per Floor = 87.5 sft
Total 5" Wall Area per Floor = 500 sft
Lift core & void area = 1200 sft
Net Floor Area per Floor = 6212.375 sft

1. Self Weight of Slab per Floor = 349.44609 kip


2. Col.&S.Wall Weight per Floor = 140.625 kip
3. Floor Finish Weight per Floor = 124.2475 kip
4. Partition Wall Weight per Floor = 0 kip
5. 10" Wall Weight per Floor = 86.625 kip
5. 5" Wall Weight per Floor = 525 kip
6. Beam Weight per Floor = 330 kip
7. Lime Terracing wt. at Roof = 323.745 kip
8. Parapet wt.. at Roof = 90.125 kip
9. Live Load per Floor = 40 psf
10. Live Load at Roof = 40 psf

Floor Dead Load 25% L.L Total Load

Roof 1093.3161 80.93625 1174.2523 kip


15 th kip
14 th kip
13 th kip
12 th kip
11 th kip
10 th kip
9 th 1555.9436 62.12375 1618.0673 kip
8 th 1555.9436 62.12375 1618.0673 kip
7 th 1555.9436 62.12375 1618.0673 kip
6 th 1555.9436 62.12375 1618.0673 kip
5 th 1555.9436 62.12375 1618.0673 kip
4 th 1555.9436 62.12375 1618.0673 kip
3 rd 1555.9436 62.12375 1618.0673 kip
2nd 1555.9436 62.12375 1618.0673 kip
1 st 1555.9436 62.12375 1618.0673 kip
Gr. 1555.9436 62.12375 1618.0673 kip
------------------------------------------------------------------------
W= 16652.752 702.17375 17354.926 kip

Therefore Load = 0.1949337 ksf per floor

Z= 0.15 (BNBC)
I = 1
Ct = 0.073
hn = 32.012195 meter
T = 0.9824477
S = 1.5
C = 1.8972665
R = 8
Vshort = 0.0355737 W
Vshort = 592.40077 kip < 393.14521

Vlong = 0.0355737 W
Vlong = 592.40077 kip > 348.89064

In the short direction of the building wind load


governed the design and in the long direction
of the building seismic load governed the design.

CHECK FOR OVERTURNING


-------------------------------------------------
Overturning Moment in the Short direction
due to Wind Load Mo = 23800.674 k-ft

Registing Moment in the Short direction


due to Dead Load Mr = 705660.37 k-ft

F.S.against overturning= 29.648756 > 3 O.K.


IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FA

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 20 ft
Total frame width B = 35 ft
Total no. of storied = 10 + Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 64.835165 kip
Axial column forces for exterior column
above 3rd floor N4 = 31.769231 kip
Axial column forces for exterior column
above 4th floor N5 = 23.340659 kip
Girder lateral load shear at 4th floor
level vg4 = 8.4285714 kip

Shear for a typical exterior column

v1 = 12.967033 kip
v4 = 9.0769231 kip
v5 = 7.7802198 kip

Column size above 3rd


floor level = 15 in.
15 in.
Beam size above 3rd
floor level = 10 in.
21 in.
A max for Exterior Frame type - FA

Vc = 9.0769231 kip
Vg = 8.4285714 kip
Nc = 64.835165 kip
Ic = 4218.75 in4
Ig = 7717.5 in4
Ac = 225 sq-in.
h = 10 ft
H = 105 ft
L = 20 ft
B= 35 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 1.0843897 in 30.735013 %

Ag=HVgL2/12EIg = 2.2017493 in 62.404493 %

A'c=2NcH2/3EAcB = 0.2420513 in 6.860494 %

A max = Ac+Ag+A'c = 3.5281903 in. < 2.52 in.

Flexural stiffness of the


frame is KfA = 12.863426 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FB

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 15 ft
Total frame width B = 37.5 ft
Total no. of storied = 10 Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 60.512821 kip
Axial column forces for exterior column
above 3rd floor N4 = 29.651282 kip
Axial column forces for exterior column
above 4th floor N5 = 21.784615 kip
Girder lateral load shear at 4th floor
level vg4 = 7.8666667 kip

Shear for a typical exterior column

v1 = 9.0769231 kip
v4 = 6.3538462 kip
v5 = 5.4461538 kip

Column size above 3rd


floor level = b = 15 in.
h = 15 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FB

Vc = 6.3538462 kip
Vg = 7.8666667 kip
Nc = 60.512821 kip
Ic = 4218.75 in4
Ig = 7717.5 in4
Ac = 225 sq-in.
h = 10 ft
H = 105 ft
L = 15 ft
B= 37.5 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.7590728 in 35.706879 %

Ag=HVgL2/12EIg = 1.1559184 in 54.374543 %

A'c=2NcH2/3EAcB = 0.2108536 in 9.9185776 %

A max = Ac+Ag+A'c = 2.1258447 in. < 2.52 in.

Flexural stiffness of the


frame is KfB = 21.348979 k/in.
IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FC

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 20 ft
Total frame width B = 47.5 ft
Total no. of storied = 10 .+ Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 47.773279 kip
Axial column forces for exterior column
above 3rd floor N4 = 23.408907 kip
Axial column forces for exterior column
above 4th floor N5 = 17.198381 kip
Girder lateral load shear at 4th floor
level vg4 = 6.2105263 kip

Shear for a typical exterior column

v1 = 9.5546559 kip
v4 = 6.6882591 kip
v5 = 5.7327935 kip

Column size above 3rd


floor level = b = 20 in.
h = 15 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FC


Vc = 6.6882591 kip
Vg = 6.2105263 kip
Nc = 47.773279 kip
Ic = 5625 in4
Ig = 7717.5 in4
Ac = 300 sq-in.
h = 10 ft
H = 105 ft
L = 20 ft
B= 47.5 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.599268 in 25.828587 %

Ag=HVgL2/12EIg = 1.6223416 in 69.92329 %

A'c=2NcH2/3EAcB = 0.0985638 in 4.2481229 %

A max = Ac+Ag+A'c = 2.3201734 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 19.560872 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FD

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 15 ft
Total frame width B = 64.5 ft
Total no. of storied = 10 .+ Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 35.181872 kip
Axial column forces for exterior column
above 3rd floor N4 = 17.239117 kip
Axial column forces for exterior column
above 4th floor N5 = 12.665474 kip
Girder lateral load shear at 4th floor
level vg4 = 4.5736434 kip

Shear for a typical exterior column

v1 = 5.2772809 kip
v4 = 3.6940966 kip
v5 = 3.1663685 kip

Column size above 3rd


floor level = b = 20 in.
h = 15 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FD

Vc = 3.6940966 kip
Vg = 4.5736434 kip
Nc = 35.181872 kip
Ic = 5625 in4
Ig = 7717.5 in4
Ac = 300 sq-in.
h = 10 ft
H = 105 ft
L = 15 ft
B= 64.5 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.3309911 in 31.329276 %

Ag=HVgL2/12EIg = 0.6720456 in 63.611087 %

A'c=2NcH2/3EAcB = 0.0534546 in 5.0596376 %

A max = Ac+Ag+A'c = 1.0564912 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 42.957872 k/in.
IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FE

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 20 ft
Total frame width B = 21 ft
Total no. of storied = 10 .+ Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 108.05861 kip
Axial column forces for exterior column
above 3rd floor N4 = 52.948718 kip
Axial column forces for exterior column
above 4th floor N5 = 38.901099 kip
Girder lateral load shear at 4th floor
level vg4 = 14.047619 kip

Shear for a typical exterior column

v1 = 21.611722 kip
v4 = 15.128205 kip
v5 = 12.967033 kip

Column size above 3rd


floor level = b = 15 in.
h = 15 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FE

Vc = 15.128205 kip
Vg = 14.047619 kip
Nc = 108.05861 kip
Ic = 4218.75 in4
Ig = 7717.5 in4
Ac = 225 sq-in.
h = 10 ft
H = 105 ft
L = 20 ft
B= 21 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 1.8073162 in 29.390778 %

Ag=HVgL2/12EIg = 3.6695821 in 59.675153 %

A'c=2NcH2/3EAcB = 0.6723647 in 10.934069 %

A max = Ac+Ag+A'c = 6.149263 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 7.3804967 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FF

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 21 ft
Total frame width B = 36 ft
Total no. of storied = 10 .+ Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 63.034188 kip
Axial column forces for exterior column
above 3rd floor N4 = 30.886752 kip
Axial column forces for exterior column
above 4th floor N5 = 22.692308 kip
Girder lateral load shear at 4th floor
level vg4 = 8.1944444 kip

Shear for a typical exterior column

v1 = 13.237179 kip
v4 = 9.2660256 kip
v5 = 7.9423077 kip

Column size above 3rd


floor level = b = 15 in.
h = 15 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FF

Vc = 9.2660256 kip
Vg = 8.1944444 kip
Nc = 63.034188 kip
Ic = 4218.75 in4
Ig = 7717.5 in4
Ac = 225 sq-in.
h = 10 ft
H = 105 ft
L = 21 ft
B= 36 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 1.1069812 in 29.952638 %

Ag=HVgL2/12EIg = 2.36 in 63.856754 %

A'c=2NcH2/3EAcB = 0.2287908 in 6.1906081 %

A max = Ac+Ag+A'c = 3.695772 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 12.280145 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FG
Total building ht. H = 105 ft
Floor to floor ht. h = 10 ft
Beam span L = 15 ft
Total frame width B = 27 ft
Total no. of storied = 10 .+ Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 84.045584 kip
Axial column forces for exterior column
above 3rd floor N4 = 41.182336 kip
Axial column forces for exterior column
above 4th floor N5 = 30.25641 kip
Girder lateral load shear at 4th floor
level vg4 = 10.925926 kip

Shear for a typical exterior column

v1 = 12.606838 kip
v4 = 8.8247863 kip
v5 = 7.5641026 kip

Column size above 3rd


floor level = b = 20 in.
h = 15 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FG

Vc = 8.8247863 kip
Vg = 10.925926 kip
Nc = 84.045584 kip
Ic = 5625 in4
Ig = 7717.5 in4
Ac = 300 sq-in.
h = 10 ft
H = 105 ft
L = 15 ft
B= 27 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.7907009 in 29.272235 %

Ag=HVgL2/12EIg = 1.6054422 in 59.434464 %

A'c=2NcH2/3EAcB = 0.3050543 in 11.293301 %

A max = Ac+Ag+A'c = 2.7011974 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 16.801666 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FH

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 20 ft
Total frame width B = 64.5 ft
Total no. of storied = 10 .+ Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 35.181872 kip
Axial column forces for exterior column
above 3rd floor N4 = 17.239117 kip
Axial column forces for exterior column
above 4th floor N5 = 12.665474 kip
Girder lateral load shear at 4th floor
level vg4 = 4.5736434 kip

Shear for a typical exterior column


v1 = 7.0363745 kip
v4 = 4.9254621 kip
v5 = 4.2218247 kip

Column size above 3rd


floor level = b = 20 in.
h = 15 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FH

Vc = 4.9254621 kip
Vg = 4.5736434 kip
Nc = 35.181872 kip
Ic = 5625 in4
Ig = 7717.5 in4
Ac = 300 sq-in.
h = 10 ft
H = 105 ft
L = 20 ft
B= 64.5 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.4413214 in 26.121055 %

Ag=HVgL2/12EIg = 1.1947477 in 70.715058 %

A'c=2NcH2/3EAcB = 0.0534546 in 3.1638874 %

A max = Ac+Ag+A'c = 1.6895237 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 26.862373 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FI

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 14 ft
Total frame width B = 37.5 ft
Total no. of storied = 10 .+ Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 60.512821 kip
Axial column forces for exterior column
above 3rd floor N4 = 29.651282 kip
Axial column forces for exterior column
above 4th floor N5 = 21.784615 kip
Girder lateral load shear at 4th floor
level vg4 = 7.8666667 kip

Shear for a typical exterior column

v1 = 8.4717949 kip
v4 = 5.9302564 kip
v5 = 5.0830769 kip

Column size above 3rd


floor level = b = 15 in.
h = 15 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FI

Vc = 5.9302564 kip
Vg = 7.8666667 kip
Nc = 60.512821 kip
Ic = 4218.75 in4
Ig = 7717.5 in4
Ac = 225 sq-in.
h = 10 ft
H = 105 ft
L = 14 ft
B= 37.5 ft
E= 3000 ksi.

A max = Ac+Ag+A'c
Ac=HVch2/12EIc = 0.708468 in 36.779555 %

Ag=HVgL2/12EIg = 1.0069333 in 52.274149 %

A'c=2NcH2/3EAcB = 0.2108536 in 10.946296 %

A max = Ac+Ag+A'c = 1.9262549 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 23.561065 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FJ

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 19 ft
Total frame width B = 56.75 ft
Total no. of storied = 10 .+ Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 39.986445 kip
Axial column forces for exterior column
above 3rd floor N4 = 19.593358 kip
Axial column forces for exterior column
above 4th floor N5 = 14.39512 kip
Girder lateral load shear at 4th floor
level vg4 = 5.1982379 kip

Shear for a typical exterior column

v1 = 7.5974246 kip
v4 = 5.3181972 kip
v5 = 4.5584548 kip
Column size above 3rd
floor level = b = 15 in.
h = 15 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FJ

Vc = 5.3181972 kip
Vg = 5.1982379 kip
Nc = 39.986445 kip
Ic = 4218.75 in4
Ig = 7717.5 in4
Ac = 225 sq-in.
h = 10 ft
H = 105 ft
L = 19 ft
B= 56.75 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.6353473 in 32.533079 %

Ag=HVgL2/12EIg = 1.2255111 in 62.752529 %

A'c=2NcH2/3EAcB = 0.0920686 in 4.7143924 %

A max = Ac+Ag+A'c = 1.952927 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 23.239278 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FK

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 15 ft
Total frame width B = 83.75 ft
Total no. of storied = 10 .+ Basement
Total base shear in the short direction
of the building = 590 kip
No. of frame = 13 nos
Shear at base in each frame
V1 = 45.384615 kip
Shear above 3rd floor in each frame
V4 = 31.769231 kip
Shear above 4th floor in each frame
V5 = 27.230769 kip
Axial column forces for exterior column
at base N1 = 27.095293 kip
Axial column forces for exterior column
above 3rd floor N4 = 13.276693 kip
Axial column forces for exterior column
above 4th floor N5 = 9.7543054 kip
Girder lateral load shear at 4th floor
level vg4 = 3.5223881 kip

Shear for a typical exterior column

v1 = 4.0642939 kip
v4 = 2.8450057 kip
v5 = 2.4385763 kip

Column size above 3rd


floor level = b = 15 in.
h = 15 in.
Beam size above 3rd
floor level = b = 10 in.
h = 21 in.

A max for Interior Frame type - FK

Vc = 2.8450057 kip
Vg = 3.5223881 kip
Nc = 27.095293 kip
Ic = 4218.75 in4
Ig = 7717.5 in4
Ac = 225 sq-in.
h = 10 ft
H = 105 ft
L = 15 ft
B= 83.75 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.3398834 in 37.776033 %

Ag=HVgL2/12EIg = 0.5175754 in 57.525456 %


A'c=2NcH2/3EAcB = 0.042274 in 4.6985115 %

A max = Ac+Ag+A'c = 0.8997328 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 50.442327 k/in.

IN THE LONG DIRECTION OF THE BUILDING

No. of frame

KfA = 12.863426 1
KfB = 21.348979 1
KfC = 19.560872 1
KfD = 42.957872 1
KfE = 7.3804967 2
KfF = 12.280145 1
KfG = 16.801666 2
KfH = 26.862373 1
KfI = 23.561065 1
KfJ = 23.239278 1
KfK = 50.442327 1
-----------------------------------------
Ekf = 281.48066

Lateral load carrid


by frame = 590 kip
Lateral load carrid
by frame FA = 26.962497 kip
Deflection A fA = 2.0960587 in. < 2.52 in.
Lateral load carrid
by frame FB = 44.748714 kip
Deflection A fB = 2.0960587 in. < 2.52 in.
Lateral load carrid
by frame FC = 41.000737 kip
Deflection A fC = 2.0960587 in. < 2.52 in.
Lateral load carrid
by frame FD = 90.042222 kip
Deflection A fD = 2.0960587 in. < 2.52 in.
Lateral load carrid
by frame FE = 15.469955 kip
Deflection A fE = 2.0960587 in. < 2.52 in.
Lateral load carrid
by frame FF = 25.739905 kip
Deflection A fF = 2.0960587 in. < 2.52 in.
Lateral load carrid
by frame FG = 35.217278 kip
Deflection A fG = 2.0960587 in. < 2.52 in.
Lateral load carrid
by frame FH = 56.305111 kip
Deflection A fH = 2.0960587 in. < 2.52 in.
Lateral load carrid
by frame FI = 49.385375 kip
Deflection A fI = 2.0960587 in. < 2.52 in.
Lateral load carrid
by frame FJ = 48.710893 kip
Deflection A fJ = 2.0960587 in. < 2.52 in.
Lateral load carrid
by frame FK = 105.73008 kip
Deflection A fK = 2.0960587 in. < 2.52 in.

STIFFNESS OF SHEAR WALL

Area of Shear Wall

----------------------------------------------------------------------------
no.of wall b h Area =A
( ft ) ( ft ) ( sq-ft )
----------------------------------------------------------------------------
3 0.833 11.833 29.570667
1 0.833 10.417 8.677361
1 0.833 12.5 10.4125
1 0.833 34.5 28.7385

----------------------------------------------------------------------------
A = 77.399028

---
C.G of Area X
---------------------------------------------------------------------------------------------------
No. b h A=bxh X AxX
wall (ft) (ft) (sq-ft) (ft) (cu-ft)
---------------------------------------------------------------------------------------------------
3 0.833 11.833 29.570667 5.9167 174.96077
1 0.833 10.417 8.677361 6.625 57.487517
1 0.833 12.5 10.4125 1.833 19.086113
1 0.833 34.5 28.7385 12.25 352.04663

---------------------------------------------------------------------------------------------------
EA = 77.399028 E A x X = 603.58102
---
X = 7.7983023
---
C.G of Area Y
---------------------------------------------------------------------------------------------------
No. b h A=bxh Y AxY
wall (ft) (ft) (sq-ft) (ft) (cu-ft)
---------------------------------------------------------------------------------------------------
1 0.833 11.833 9.856889 0.417 4.1103227
1 0.833 11.833 9.856889 8.25 81.319334
1 0.833 11.833 9.856889 34.083 335.95235
1 0.833 10.417 8.677361 21.583 187.28348
1 0.833 12.5 10.4125 14.9167 155.32014
1 0.833 34.5 28.7385 17.25 495.73913
---------------------------------------------------------------------------------------------------
EA = 77.399028 E A x Y = 1259.7248
---
Y = 16.275718

Moment of Inertia (in the long direction) = I x-x


------------------------------------------------------------------------------------------
No. b&A h&y I x-x
wall (ft & sq-ft) (ft) (ft4)
------------------------------------------------------------------------------------------
b x h3/12 = 1 11.833 0.833 0.5699656
A x y2 = 1 9.856889 15.833 2470.9633
b x h3/12 = 1 11.833 0.833 0.5699656
A x y2 = 1 9.856889 8 630.8409
b x h3/12 = 1 10.583 0.833 0.5097562
A x y2 = 1 8.815639 5.33 250.44261
b x h3/12 = 1 11.833 0.833 0.5699656
A x y2 = 1 9.856889 17.833 3134.6473
b x h3/3 = 1 0.833 4.9167 33.002351
b x h3/3 = 1 0.833 7.583 121.07289
b x h3/3 = 1 0.833 16.25 1191.472
b x h3/3 = 1 0.833 18.25 1687.7665
------------------------------------------------------------------------------------------
I x-x = 9522.4275

Moment of Inertia (in the short direction) = I y-y


------------------------------------------------------------------------------------------
No. b&A h&y Iy-y
wall (ft & sq-ft) (ft) (ft4)
------------------------------------------------------------------------------------------
b x h3/3 = 3 0.833 7.75 387.74848
b x h3/3 = 3 0.833 4.083 56.700011
b x h3/3 = 1 0.833 4.083 18.900004
b x h3/3 = 1 0.833 5.5 46.196792
b x h3/12 = 1 12.5 0.833 0.6020933
A x y2 = 1 10.4125 5.9167 364.51392
b x h3/12 = 1 34.5 0.833 1.6617774
A x y2 = 1 28.7385 4.5 581.95463
------------------------------------------------------------------------------------------
I y-y = 1458.2777

WALL STIFFNESS Kw

H = 185 ft
I x-x(long)= 9522.4275 ft4
I y-y(short)= 1458.2777 ft4

K w(long) = 162.42626 k/in > Ekf = 0 k/in.


K w(short)= 24.874182 k/in < Ekf = #REF! k/in.
IN THE LONG DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE SHEAR WALL.

Total building ht. H = 185 ft


I y-y (short direction) = #REF! ft4

Assuming that the wind is carried by the


concrete walls only = 773 kip

Aw = #REF! in > 4.44 in.

Kw = #REF! k/in.

No. of frame

Kf1 = 42.533078 2
Kf2 = 56.373941 2
Kf3 = 39.286934 2
-----------------------------------------
Ekf = 276.38791

Lateral load carrid


by shear wall = #REF! kip
Deflection Aw = #REF! in. < 4.44 in.
Lateral load carrid
by frame = #REF! kip
Lateral load carrid
by frame F1 = #REF! kip
Deflection A f1 = #REF! in. < 4.44 in.
Lateral load carrid
by frame F2 = #REF! kip
Deflection A f2 = #REF! in. < 4.44 in.
Lateral load carrid
by frame F3 = #REF! kip
Deflection A f1 = #REF! in. < 4.44 in.
G + 8-STORIED (WITH BASEMENT) APARTMENT BUILDING
AT PLOT NO. 2 / B, GOLDEN STREET, MOHAMMADPUR,
RING ROAD, DHAKA.

SEL SOBHAN PALACE

DESIGN PARAMETERS:-

1. f'c = 3000 psi


2. fy = 60000 psi
3. Live Load = 40 psf
4. Partition Load = 5" Brick wall
5. Wind Velocity = 120 mph
6. Seismic Factor - Moderate Damage.
7. Code Follows - B.N.B.C.

Design by :- Md. Masud Sheikh


B.Sc. Engg.(civil) M.I.E.B.

WIND LOAD ANALYSIS :-


Ref. ANSI Standard A58.1-1982.

P1 = qz Gh Cp
V = 120 MPH
I = 1
qz = 0.0025 Kz(IV)2
qz = 36 Kz
Gh = 0.65 + 3.65 Tz
2.35(Do)1/2
Tz = --------------------
(Z/30)1/L
Bldg Ht. Z = 105 ft
Do = 0.01 For Exposure B.
L = 4.5 For Exposure B.
Tz = 0.177895
Gh = 1.2993169
Cp = .8+.5 = 1.3
P1 = 60.808032 Kz psf

P1 =
HT. in ft Kz 60.808032 Kz psf
---------------------------------------------------------------------------------
0 0 0 0
15 0.37 22.498972 0.3374846
20 0.42 25.539373 0.1276969
25 0.46 27.971695 0.1398585
30 0.5 30.404016 0.1520201
40 0.57 34.660578 0.3466058
50 0.63 38.30906 0.3830906
60 0.68 41.349462 0.4134946
70 0.73 44.389863 0.4438986
80 0.77 46.822184 0.4682218
90 0.82 49.862586 0.4986259
100 0.86 52.294907 0.5229491
105 0.93 56.551469 0.2827573
130 0.99 60.199951
160 1.05 63.848433
180 1.11 67.496915
185 1.16 70.537317
250 1.28 77.834281
---------------------------------------------------------------------------------
V = 4.1167037
Length of Building = 95.5
Width of Building = 27
Total Base Shear in the Short
direction of the Bldg. = 393.14521
Total Base Shear in the Long
direction of the Bldg. = 111.151
SEISMIC LOAD ANALYSIS :-

No. of storied with Basement = 11


Length of Building = 95.5 ft
Width of Building = 27 ft
Total Shear Wall = 0 rft
Shear Wall Thickness= 0 in
Total 10" Wall = 250 rft
10" Wall Thickness= 7 in
Total 5" Wall = 145 rft
5" Wall Thickness= 4 in
No of Column = 18 nos
Column Size = 15 in
20 in
Total Beam = 385 rft
Beam Weight per ft. = 0.2 k/ft
Slab Thickness = 4.5 in
Floor to Floor Height = 10 ft
Floor Finish Load = 20 psf
Partition Wall Load = 0 psf
Lime Terracing Load = 40 psf
Parapet Wall Height = 4 ft
Parapet Wall Thickness = 5 in
Total Building Area per Floor = 2578.5 sft
Total Shear Wall Area per Floor = 0 sft
Total Column Area per Floor = 37.5 sft
Total 10" Wall Area per Floor = 145.83333 sft
Total 5" Wall Area per Floor = 48.333333 sft
Lift core & void area = 230 sft
Net Floor Area per Floor = 2116.8333 sft

1. Self Weight of Slab per Floor = 119.07188 kip


2. Col.&S.Wall Weight per Floor = 56.25 kip
3. Floor Finish Weight per Floor = 42.336667 kip
4. Partition Wall Weight per Floor = 0 kip
5. 10" Wall Weight per Floor = 144.375 kip
5. 5" Wall Weight per Floor = 50.75 kip
6. Beam Weight per Floor = 77 kip
7. Lime Terracing wt. at Roof = 103.14 kip
8. Parapet wt.. at Roof = 61.25 kip
9. Live Load per Floor = 40 psf
10. Live Load at Roof = 40 psf

Floor Dead Load 25% L.L Total Load

Roof 360.46188 25.785 386.24688 kip


15 th kip
14 th kip
13 th kip
12 th kip
11 th kip
10 th kip
9 th 489.78354 21.168333 510.95188 kip
8 th 489.78354 21.168333 510.95188 kip
7 th 489.78354 21.168333 510.95188 kip
6 th 489.78354 21.168333 510.95188 kip
5 th 489.78354 21.168333 510.95188 kip
4 th 489.78354 21.168333 510.95188 kip
3 rd 489.78354 21.168333 510.95188 kip
2nd 489.78354 21.168333 510.95188 kip
1 st 489.78354 21.168333 510.95188 kip
Gr. 489.78354 21.168333 510.95188 kip
------------------------------------------------------------------------
W= 5258.2973 237.46833 5495.7656 kip

Therefore Load = 0.1937619 ksf per floor

Z= 0.15 (BNBC)
I = 1
Ct = 0.073
hn = 32.012195 meter
T = 0.9824477
S = 1.5
C = 1.8972665
R = 8
Vshort = 0.0355737 W
Vshort = 187.05733 kip < 393.14521

Vlong = 0.0355737 W
Vlong = 187.05733 kip > 111.151

In the short direction of the building wind load


governed the design and in the long direction
of the building seismic load governed the design.

CHECK FOR OVERTURNING


-------------------------------------------------
Overturning Moment in the Short direction
due to Wind Load Mo = 23800.674 k-ft

Registing Moment in the Short direction


due to Dead Load Mr = 70987.013 k-ft

F.S.against overturning= 2.9825632 > 3 O.K.


IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FA

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 16 ft
Total frame width B = 27 ft
Total no. of storied = 10 + Basement
Total base shear in the short direction
of the building = 390 kip
No. of frame = 5 nos
Shear at base in each frame
V1 = 78 kip
Shear above 3rd floor in each frame
V4 = 54.6 kip
Shear above 4th floor in each frame
V5 = 46.8 kip
Axial column forces for exterior column
at base N1 = 144.44444 kip
Axial column forces for exterior column
above 3rd floor N4 = 70.777778 kip
Axial column forces for exterior column
above 4th floor N5 = 52 kip
Girder lateral load shear at 4th floor
level vg4 = 18.777778 kip

Shear for a typical exterior column

v1 = 23.111111 kip
v4 = 16.177778 kip
v5 = 13.866667 kip

Column size above 3rd


floor level = 15 in.
20 in.
Beam size above 3rd
floor level = 12 in.
21 in.
A max for Exterior Frame type - FA

Vc = 16.177778 kip
Vg = 18.777778 kip
Nc = 144.44444 kip
Ic = 10000 in4
Ig = 9261 in4
Ac = 300 sq-in.
h = 10 ft
H = 105 ft
L = 16 ft
B= 27 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.81536 in 20.611996 %

Ag=HVgL2/12EIg = 2.6161149 in 66.134406 %

A'c=2NcH2/3EAcB = 0.5242798 in 13.253598 %

A max = Ac+Ag+A'c = 3.9557547 in. < 2.52 in.

Flexural stiffness of the


frame is KfA = 19.718108 k/in.

IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FB

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 16 ft
Total frame width B = 27 ft
Total no. of storied = 10 Basement
Total base shear in the short direction
of the building = 390 kip
No. of frame = 5 nos
Shear at base in each frame
V1 = 78 kip
Shear above 3rd floor in each frame
V4 = 54.6 kip
Shear above 4th floor in each frame
V5 = 46.8 kip
Axial column forces for exterior column
at base N1 = 144.44444 kip
Axial column forces for exterior column
above 3rd floor N4 = 70.777778 kip
Axial column forces for exterior column
above 4th floor N5 = 52 kip
Girder lateral load shear at 4th floor
level vg4 = 18.777778 kip

Shear for a typical exterior column

v1 = 23.111111 kip
v4 = 16.177778 kip
v5 = 13.866667 kip

Column size above 3rd


floor level = b = 15 in.
h = 20 in.
Beam size above 3rd
floor level = b = 12 in.
h = 21 in.

A max for Interior Frame type - FB

Vc = 16.177778 kip
Vg = 18.777778 kip
Nc = 144.44444 kip
Ic = 10000 in4
Ig = 9261 in4
Ac = 300 sq-in.
h = 10 ft
H = 105 ft
L = 16 ft
B= 27 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.81536 in 20.611996 %

Ag=HVgL2/12EIg = 2.6161149 in 66.134406 %

A'c=2NcH2/3EAcB = 0.5242798 in 13.253598 %

A max = Ac+Ag+A'c = 3.9557547 in. < 2.52 in.

Flexural stiffness of the


frame is KfB = 19.718108 k/in.
IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE FRAME TYPE - FC

Total building ht. H = 105 ft


Floor to floor ht. h = 10 ft
Beam span L = 16 ft
Total frame width B = 27 ft
Total no. of storied = 10 Basement
Total base shear in the short direction
of the building = 390 kip
No. of frame = 5 nos
Shear at base in each frame
V1 = 78 kip
Shear above 3rd floor in each frame
V4 = 54.6 kip
Shear above 4th floor in each frame
V5 = 46.8 kip
Axial column forces for exterior column
at base N1 = 144.44444 kip
Axial column forces for exterior column
above 3rd floor N4 = 70.777778 kip
Axial column forces for exterior column
above 4th floor N5 = 52 kip
Girder lateral load shear at 4th floor
level vg4 = 18.777778 kip

Shear for a typical exterior column

v1 = 23.111111 kip
v4 = 16.177778 kip
v5 = 13.866667 kip

Column size above 3rd


floor level = b = 15 in.
h = 20 in.
Beam size above 3rd
floor level = b = 12 in.
h = 21 in.

A max for Interior Frame type - FC


Vc = 16.177778 kip
Vg = 18.777778 kip
Nc = 144.44444 kip
Ic = 10000 in4
Ig = 9261 in4
Ac = 300 sq-in.
h = 10 ft
H = 105 ft
L = 16 ft
B= 27 ft
E= 3000 ksi.

A max = Ac+Ag+A'c

Ac=HVch2/12EIc = 0.81536 in 20.611996 %

Ag=HVgL2/12EIg = 2.6161149 in 66.134406 %

A'c=2NcH2/3EAcB = 0.5242798 in 13.253598 %

A max = Ac+Ag+A'c = 3.9557547 in. < 2.52 in.

Flexural stiffness of the


frame is KfC = 19.718108 k/in.

IN THE LONG DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE SHEAR WALL.

Total building ht. H = 105 ft


I y-y (short direction) = 172.5 ft4

Assuming that the wind is carried by the


concrete walls only = 390 kip

Aw = 9.0876359 in > 2.52 in.


Kw = 42.915452 k/in.

Kw = 42.915452 2
-----------------------------------------
Ekw = 85.830904
No. of frame
Kf1 = 19.718108 2
Kf2 = 19.718108 1
Kf3 = 19.718108 2
-----------------------------------------
Ekf = 98.590541

Lateral load carrid


by shear wall = 90.75423 kip
Deflection Aw = 2.1147215 in. < 2.52 in.
Lateral load carrid
by frame = 208.49154 kip
Lateral load carrid
by frame F1 = 41.698308 kip
Deflection A f1 = 2.1147215 in. < 2.52 in.
Lateral load carrid
by frame F2 = 41.698308 kip
Deflection A f2 = 2.1147215 in. < 2.52 in.
Lateral load carrid
by frame F3 = 41.698308 kip
Deflection A f1 = 2.1147215 in. < 2.52 in.
IN THE SHORT DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE SHEAR WALL.

Total building ht. H = 185 ft


I y-y (short direction) = 0 ft4

Assuming that the wind is carried by the


concrete walls only = 773 kip

Aw = #DIV/0! in > 4.44 in.

Kw = #DIV/0! k/in.

No. of frame

Kf1 = 2.1147215 2
Kf2 = 0 2
Kf3 = 0 2
-----------------------------------------
Ekf = 4.2294431

Lateral load carrid


by shear wall = #DIV/0! kip
Deflection Aw = #DIV/0! in. < 4.44 in.
Lateral load carrid
by frame = #DIV/0! kip
Lateral load carrid
by frame F1 = #DIV/0! kip
Deflection A f1 = #DIV/0! in. < 4.44 in.
Lateral load carrid
by frame F2 = #DIV/0! kip
Deflection A f2 = #DIV/0! in. < 4.44 in.
Lateral load carrid
by frame F3 = #DIV/0! kip
Deflection A f1 = #DIV/0! in. < 4.44 in.

STIFFNESS OF SHEAR WALL

Area of Shear Wall

----------------------------------------------------------------------------
no.of wall b h Area =A
( ft ) ( ft ) ( sq-ft )
----------------------------------------------------------------------------
1 1.25 2.0833 2.604125
1 1.25 1.25 1.5625
1 0.833 8.5 7.0805
1

----------------------------------------------------------------------------
A = 11.247125

---
C.G of Area X
---------------------------------------------------------------------------------------------------
No. b h A=bxh X AxX
wall (ft) (ft) (sq-ft) (ft) (cu-ft)
---------------------------------------------------------------------------------------------------
1 1.25 2.0833 2.604125 10.791 28.101113
1 1.25 1.25 1.5625 0.625 0.9765625
1 0.833 8.5 7.0805 5.5 38.94275

---------------------------------------------------------------------------------------------------
EA = 11.247125 E A x X = 68.020425
---
X = 6.0478056

---
C.G of Area Y
---------------------------------------------------------------------------------------------------
No. b h A=bxh Y AxY
wall (ft) (ft) (sq-ft) (ft) (cu-ft)
---------------------------------------------------------------------------------------------------
1 11.833 1.25 14.79125 0.625 9.2445313

---------------------------------------------------------------------------------------------------
EA = 14.79125 E A x Y = 9.2445313
---
Y = 0.625

Moment of Inertia (in the long direction) = I x-x


------------------------------------------------------------------------------------------
No. b&A h&y I x-x
wall (ft & sq-ft) (ft) (ft4)
------------------------------------------------------------------------------------------
b x h3/12 = 1 11.833 0.833 0.5699656
A x y2 = 1 9.856889 15.833 2470.9633
b x h3/12 = 1 11.833 0.833 0.5699656
A x y2 = 1 9.856889 8 630.8409
b x h3/12 = 1 10.583 0.833 0.5097562
A x y2 = 1 8.815639 5.33 250.44261
b x h3/12 = 1 11.833 0.833 0.5699656
A x y2 = 1 9.856889 17.833 3134.6473
b x h3/3 = 1 0.833 4.9167 33.002351
b x h3/3 = 1 0.833 7.583 121.07289
b x h3/3 = 1 0.833 16.25 1191.472
b x h3/3 = 1 0.833 18.25 1687.7665
------------------------------------------------------------------------------------------
I x-x = 9522.4275

Moment of Inertia (in the short direction) = I y-y


------------------------------------------------------------------------------------------
No. b&A h&y Iy-y
wall (ft & sq-ft) (ft) (ft4)
------------------------------------------------------------------------------------------
b x h3/3 = 3 0.833 7.75 387.74848
b x h3/3 = 3 0.833 4.083 56.700011
b x h3/3 = 1 0.833 4.083 18.900004
b x h3/3 = 1 0.833 5.5 46.196792
b x h3/12 = 1 12.5 0.833 0.6020933
A x y2 = 1 10.4125 5.9167 364.51392
b x h3/12 = 1 34.5 0.833 1.6617774
A x y2 = 1 28.7385 4.5 581.95463
------------------------------------------------------------------------------------------
I y-y = 1458.2777

WALL STIFFNESS Kw

H = 185 ft
I x-x(long)= 9522.4275 ft4
I y-y(short)= 1458.2777 ft4

K w(long) = 162.42626 k/in > Ekf = #VALUE! k/in.


K w(short)= 24.874182 k/in < Ekf = 0 k/in.
IN THE LONG DIRECTION OF THE BUILDING

DETERMINATION OF THE APPROXIMATE LATERAL


SWAY OF THE SHEAR WALL.

Total building ht. H = 185 ft


I y-y (short direction) = 1657 ft4

Assuming that the wind is carried by the


concrete walls only = 773 kip

Aw = 10.256039 in > 4.44 in.

Kw = 75.370225 k/in.

No. of frame

Kf1 = #REF! 2
Kf2 = #REF! 2
Kf3 = #REF! 2
-----------------------------------------
Ekf = #REF!

Lateral load carrid


by shear wall = #REF! kip
Deflection Aw = #REF! in. < 4.44 in.
Lateral load carrid
by frame = #REF! kip
Lateral load carrid
by frame F1 = #REF! kip
Deflection A f1 = #REF! in. < 4.44 in.
Lateral load carrid
by frame F2 = #REF! kip
Deflection A f2 = #REF! in. < 4.44 in.
Lateral load carrid
by frame F3 = #REF! kip
Deflection A f1 = #REF! in. < 4.44 in.
DESIGN OF FOUNDATION :- MAT FOUNDAT

ARTMENT BUILDING DETERMINATION OF SOIL PRESSURE

No. of storied incl. Basement


Length of Building
Width of Building
Total Shear Wall
Shear Wall Thickness
Total 10" Wall
10" Wall Thickness
Total 5" Wall
5" Wall Thickness
No of Column
Column Size

Total Beam
Beam Weight per ft.
Slab Thickness
gg.(civil) M.I.E.B. Floor to Floor Height
Floor Finish Load
Partition Wall Load
Lime Terracing Load
Parapet Wall Height
Parapet Wall Thickness
Total Building Area per Floor
Total Shear Wall Area per Floor
Total Column Area per Floor
Total 10" Wall Area per Floor
Total 5" Wall Area per Floor
Lift core & void area
Net Floor Area per Floor

1. Self Weight of Slab


2. Col.&S.Wall Weight
3. Floor Finish Weight
4. Partition Wall Weight
5. 10" Wall Weight
5. 5" Wall Weight
6. Beam Weight
7. Lime Terracing wt. at Roof
8. Parapet wt.. at Roof
----------------------------------------------------------------
TOTAL DEAD LOAD
DL

---------------------------------------------------------------
k/ft Avg. Live Load per Floor
k/ft 2.5595819 ----------------------------------------------------------------
k/ft 2.259811 TOTAL LIVE LOAD
k/ft 3.1821829
k/ft 4.2275376 ----------------------------------------------------------------
k/ft 12.267546 f TOTAL BUILDING LOAD
k/ft 17.432828 TOTAL LOAD
k/ft 22.997805
k/ft 29.177696
k/ft 35.511316 MAT AREA
k/ft 66.18018 Length
k/ft 0 Width
k/ft 0 ----------------------------------------------------------------
k/ft 0 MAT AREA
k/ft 0
k/ft 0
k/ft 0 Net Soil Pressure
k/ft
---------------------------------------------------------------
k/ft Mo = 195.79648 k-ft/ft
ft
ft Allowable Bearing capacity of soil
at 8 ft depth from E.G.L.
kip

kip

Soil pressure due to lateral load moment

In the short direction of the bldg.

Total lateral load moment due to wind


Ic of mat
Soil pressure
In the long direction of the bldg.

Base shear due to EQ.


Total lateral load moment due to EQ.
Ic of mat
Soil pressure
ksf per floor
k-ft/ft
k-ft/ft
MENT BUILDING
AMMADPUR,

gg.(civil) M.I.E.B.
---------------------------------------------------------------
k/ft
k/ft 2.5311343
k/ft 2.2346952
k/ft 3.1468156
k/ft 4.1805522
k/ft 12.131202
k/ft 17.239077
k/ft 22.742204
k/ft 28.853411
k/ft 35.116638
k/ft 42.383198
k/ft 49.680162
k/ft 28.982628
k/ft 0
k/ft 0
k/ft 0
k/ft 0
k/ft
---------------------------------------------------------------
k/ft Mo = 249.22172
ft
ft

kip

kip
ksf per floor
MENT BUILDING
AMMADPUR,

gg.(civil) M.I.E.B.
---------------------------------------------------------------
k/ft
k/ft 2.5311343
k/ft 2.2346952
k/ft 3.1468156
k/ft 4.1805522
k/ft 12.131202
k/ft 17.239077
k/ft 22.742204
k/ft 28.853411
k/ft 35.116638
k/ft 42.383198
k/ft 49.680162
k/ft 28.982628
k/ft 0
k/ft 0
k/ft 0
k/ft 0
k/ft
---------------------------------------------------------------
k/ft Mo = 249.22172
ft
ft

kip

kip
ksf per floor
--------------------------------

--------------------------------

--------------------------------

ft
--------------------------------

--------------------------------

--------------------------------

ft

-----------------------------

-----------------------------
-----------------------------
ft4

-----------------------------

-----------------------------

-----------------------------
ft4
MENT BUILDING
AMMADPUR,

gg.(civil) M.I.E.B.
---------------------------------------------------------------
k/ft
k/ft 2.5311343
k/ft 2.2346952
k/ft 3.1468156
k/ft 4.1805522
k/ft 12.131202
k/ft 17.239077
k/ft 22.742204
k/ft 28.853411
k/ft 35.116638
k/ft 42.383198
k/ft 49.680162
k/ft 28.982628
k/ft 0
k/ft 0
k/ft 0
k/ft 0
k/ft
---------------------------------------------------------------
k/ft Mo = 249.22172 k-ft/ft
ft
ft

kip

kip
ksf per floor
--------------------------------

--------------------------------

--------------------------------
ft

--------------------------------

--------------------------------

--------------------------------

ft

-----------------------------

-----------------------------
-----------------------------
ft4

-----------------------------

-----------------------------

-----------------------------
ft4
TION :- MAT FOUNDATION

SOIL PRESSURE

= 10
= 79 ft
= 65 ft
= 0 rft
= 0 in
= 0 rft
= 0 in
= 1000 rft
= 4 in
= 40 nos
= 15 in
= 20 in
= 865 rft
= 0.2 k/ft
= 4.5 in
= 10 ft
= 20 psf
= 20 psf
= 40 psf
= 4 ft
= 5 in
= 5135 sft
= 0 sft
= 83.333333 sft
= 0 sft
= 333.33333 sft
= 171.71289 sft
= 4546.6204 sft

= 2557.474 kip
= 1250 kip
= 909.32409 kip
= 909.32409 kip
= 0 kip
= 3850 kip
= 1730 kip
= 205.4 kip
= 72 kip
--------------------------------------
= 11483.522 kip
= 0.2236324 ksf / floor

= 50 psf
--------------------------------------
= 2273.3102 kip

--------------------------------------
= 13756.832 kip
= 0.2679033 ksf / floor

= 90 ft
= 38 ft
--------------------------------------
= 3420 sft

= 4.0224656 ksf

2.5 Tsf
5.6 ksf > 4.0224656

ateral load moment

= 15467.922 k-ft
= 411540 ft4
= 4.0224656 ksf + 0.7141238 ksf
= 4.7365894 ksf > 7.448 ksf
= 3.3083418 ksf
372.21248 kip
= 23573.457 k-ft
= 2308500 ft4
= 4.0224656 ksf + 0.4595216 ksf
= 4.4819872 ksf < 7.448 ksf
= 3.562944 ksf
BENDING MOMENT ON SHEAR WALL DUE TO EQ.

IN THE LONG DIRECTION OF THE BLDG.

Triangular load on wall W1= 275


Point load at Top = 0
Building height = 95
=

0 17416.667
10.5 14540.925
21.5 11605.11
32.5 8827.8364
43.5 6290.2162
54.5 4073.3632

BENDING MOMENT ON COLUMN IN THE


LONG DIRECTION OF THE BUILDING.

Triangular load (Total) = 252


No. of Frame = 4
Base Shear per Frame = 63
No. of Column per Frame = 4
Shear in each Column = 15.75
Point load at Top = 0
Building height = 95
=

0 15960
10.5 13324.775
21.5 10634.501
32.5 8089.5083
43.5 5764.1254
54.5 3732.6819
BENDING MOMENT ON COLUMN IN THE
LONG DIRECTION OF THE BUILDING.

Base Shear per Frame = 57


No. of Column per Frame = 4
Shear in each Column = 14.25
Point load at Top = 11.4
Building height = 95
=

0 -1083
10.5 -963.3
21.5 -837.9
32.5 -712.5
43.5 -587.1
54.5 -461.7
HEAR WALL DUE TO EQ. DETERMINATION OF PILE VALUE : - FOR

OF THE BLDG.
Dia of Pile = 16
kip -------------------------------------------
kip Depth in ft Skin friction
ft ksf
-----------------------------------------------------------
0 0
k-ft 5 0.01
k-ft 10 0.04
k-ft 15 0.05
k-ft 20 0.07
k-ft 25 0.09
k-ft 30 0.28
35 0.3
40 0.31
45 0.32
50 0.32
55 0.32
60 0.32
65

OLUMN IN THE

DETERMINATION OF PILE VALUE : - FOR


kip
Nos Dia of Pile = 18
kip
Nos Depth in ft Skin friction
kip Tsf
kip -----------------------------------------------------------
ft 0 0
5 0.02
10 0.03
k-ft 15 0.05
k-ft 20 0.11
k-ft 25 0.24
k-ft 30 0.25
k-ft 35 0.27
k-ft 40 0.29
45 0.3
50 0.32
55 0
60 0
OLUMN IN THE 65 0

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 18
kip
Nos Depth in ft Skin friction
kip Tsf
kip -----------------------------------------------------------
ft 0 0
5 0.02
10 0.03
k-ft 15 0.05
k-ft 20 0.11
k-ft 25 0.24
k-ft 30 0.25
k-ft 35 0.27
k-ft 40 0.29
45 0.3
50 0.32
55 0
60 0
65 0

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 18

Depth in ft Skin friction


Tsf
-----------------------------------------------------------
0 0
5 0.02
10 0.03
15 0.05
20 0.11
25 0.24
30 0.25
35 0.27
40 0.29
45 0.3
50 0.32
55 0
60 0
65 0

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 18

Depth in ft Skin friction


Tsf
-----------------------------------------------------------
0 0
5 0.02
10 0.03
15 0.05
20 0.11
25 0.24
30 0.25
35 0.27
40 0.29
45 0.3
50 0.32
55 0
60 0
65 0
70 0
75 0
80 0
85 0
90 0
95 0
100 0
110 0
DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 18

Skin friction End bearing Depth in ft Skin friction


Ton / sq.m Ton / sq.m Ksf
-----------------------------------------------------------
0 0 0 0
0.77 0 5 0.143143
1.33 24.2 10 0.247247
1.96 26.5 15 0.364364
1.83 301 20 0.340197
1.99 398 25 0.369941
2.85 570 30 0.529815
3.23 645 35 0.600457
3.55 710 40 0.659945
3.92 785 45 0.728728
50 0
55 0
60 0
65 0

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 18

Skin friction End bearing Depth in ft Skin friction


Ton / sq.m Ton / sq.m Ksf
-----------------------------------------------------------
0 0 0 0
1.84 0 5 0.342056
1.84 21.8 10 0.342056
1.37 86 15 0.254683
0.77 155 20 0.143143
1.05 323 25 0.195195
2.42 484 30 0.449878
2.58 516 35 0.479622
2.91 581 40 0.540969
3.23 645 45 0.600457
50 0
55 0
60 0
65 0
70
75
80
85
90

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 18

Skin friction End bearing Depth in ft Skin friction


Ton / sq.m Ton / sq.m Ksf
-----------------------------------------------------------
0 0 0 0
1.02 0 5 0.189618
1.07 69 10 0.198913
0.34 69 15 0.063206
0.69 279 20 0.128271
2.37 473 25 0.440583
2.53 505 30 0.470327
2.74 548 35 0.509366
2.91 581 40 0.540969
2.85 570 45 0.529815
50 0
55 0
60 0
65 0
DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 18

Skin friction End bearing Depth in ft Skin friction


Ton / sq.m Ton / sq.m Ksf
-----------------------------------------------------------
0 0 0 0
1.44 0 5 0.267696
1.46 77 10 0.271414
0.5 150 15 0.09295
1.51 301 20 0.280709
2.37 473 25 0.440583
2.47 495 30 0.459173
2.58 516 35 0.479622
2.85 570 40 0.529815
2.91 581 45 0.540969
50 0
55 0
60 0
65 0

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 18

Skin friction End bearing Depth in ft Skin friction


Ton / sq.m Ton / sq.m Ksf
-----------------------------------------------------------
0 0 0 0
0.27 0 5 0.050193
0.84 26.5 10 0.156156
1.52 112 15 0.282568
0.95 344 20 0.176605
2.21 441 25 0.410839
2.74 548 30 0.509366
2.9 581 35 0.53911
3.01 602 40 0.559559
3.23 645 45 0.600457
50 0
55 0
60 0
65 0
DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 20

Skin friction End bearing Depth in ft Skin friction


Ton / sq.m Ton / sq.m Ksf
-----------------------------------------------------------
0 0 0 0
0.77 0 5 0.143143
1.33 24.2 10 0.247247
1.96 26.5 15 0.364364
1.83 301 20 0.340197
1.99 398 25 0.369941
2.85 570 30 0.529815
3.23 645 35 0.600457
3.55 710 40 0.659945
3.92 785 45 0.728728
50 0
55 0
60 0
65 0

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 20

Skin friction End bearing Depth in ft Skin friction


Ton / sq.m Ton / sq.m Ksf
-----------------------------------------------------------
0 0 0 0
1.84 0 5 0.342056
1.84 21.8 10 0.342056
1.37 86 15 0.254683
0.77 155 20 0.143143
1.05 323 25 0.195195
2.42 484 30 0.449878
2.58 516 35 0.479622
2.91 581 40 0.540969
3.23 645 45 0.600457
50 0
55 0
60 0
65 0
70
75
80
85
90

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 20

Skin friction End bearing Depth in ft Skin friction


Ton / sq.m Ton / sq.m Ksf
-----------------------------------------------------------
0 0 0 0
1.02 0 5 0.189618
1.07 69 10 0.198913
0.34 69 15 0.063206
0.69 279 20 0.128271
2.37 473 25 0.440583
2.53 505 30 0.470327
2.74 548 35 0.509366
2.91 581 40 0.540969
2.85 570 45 0.529815
50 0
55 0
60 0
65 0

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 20

Skin friction End bearing Depth in ft Skin friction


Ton / sq.m Ton / sq.m Ksf
-----------------------------------------------------------
0 0 0 0
1.44 0 5 0.267696
1.46 77 10 0.271414
0.5 150 15 0.09295
1.51 301 20 0.280709
2.37 473 25 0.440583
2.47 495 30 0.459173
2.58 516 35 0.479622
2.85 570 40 0.529815
2.91 581 45 0.540969
50 0
55 0
60 0
65 0

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 20

Skin friction End bearing Depth in ft Skin friction


Ton / sq.m Ton / sq.m Ksf
-----------------------------------------------------------
0 0 0 0
0.27 0 5 0.050193
0.84 26.5 10 0.156156
1.52 112 15 0.282568
0.95 344 20 0.176605
2.21 441 25 0.410839
2.74 548 30 0.509366
2.9 581 35 0.53911
3.01 602 40 0.559559
3.23 645 45 0.600457
50 0
55 0
60 0
65 0

Dia of Pile = 16
Depth in ft
From E.G.L. BH - 1

25 125
30 175
35 205
40 235
45 270

Dia of Pile = 18

Depth in ft
From E.G.L. BH - 1

25 155
30 220
35 255
40 290
45 330

Dia of Pile = 20

Depth in ft
From E.G.L. BH - 1

25 185
30 265
35 310
40 355
45 400

DESIGN CAPACITY OF PILES


Depth in ft 16 in dia.
From E.G.L.
25 105
30 150
35 170
40 190
45 200
DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 16

Depth in ft Skin friction


Tsf
-----------------------------------------------------------
0 0
5 0
10 0
15 0
20 0
25 0.054
30 0.09
35 0.108
40 0.136
45 0.21
50 0.216
55 0
60 0
65 0

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 18

Depth in ft Skin friction


Tsf
-----------------------------------------------------------
0 0
5 0.375
10 0.375
15 0.3867
20 0.3938
25 0.3664
30 0.1704
35 0.2169
40 0.2943
45 0.3563
50 0.4027
55 0.4337
60 0.4802
65 0

DETERMINATION OF PILE VALUE : - FOR

Dia of Pile = 16

Depth in ft Skin friction


Tsf
-----------------------------------------------------------
0 0
5 0
10 0
15 0
20 0.06
25 0.066
30 0.078
35 0.096
40 0.12
45 0.166
50 0.172
55 0
60 0
65 0
MINATION OF PILE VALUE : - FOR BORING NO - 1

in.
-------------------------------
End bearing Pile Value Pile Value Pile Value
ksf Ps, kip Pe, kip Ps + Pe,kip
-------------------------------------------------------------------------------------------------
0 0
0 0 0
0.2093333 0 0.2093333
0.8373333 0 1.0466667
1.0466667 0 2.0933333
4.28 1.4653333 5.9729778 9.5316444
17.3 1.884 24.143111 29.585778
21.8 5.8613333 30.423111 41.727111
27.4 6.28 38.238222 55.822222
35 6.4893333 48.844444 72.917778
38.9 6.6986667 54.287111 85.059111
42.8 6.6986667 59.729778 97.200444
46.7 6.6986667 65.172444 109.34178

MINATION OF PILE VALUE : - FOR BH - 1

in.

End bearing Pile Value Pile Value Pile Value


Tsf Ps, Ton Pe, Ton Ps + Pe,Ton
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
0 0.471 0 0.471
0 0.7065 0 1.1775
0 1.1775 0 2.355
11.3 2.5905 19.958625 24.904125
14 5.652 24.7275 35.325
18.5 5.8875 32.675625 49.160625
24.3 6.3585 42.919875 65.763375
29.4 6.8295 51.92775 81.60075
36.6 7.065 64.64475 101.38275
0 7.536 0 44.274
0 0 0 44.274
0

MINATION OF PILE VALUE : - FOR BH - 2

in.

End bearing Pile Value Pile Value Pile Value


Tsf Ps, Ton Pe, Ton Ps + Pe,Ton
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
0 0.471 0 0.471
0 0.7065 0 1.1775
0 1.1775 0 2.355
11.3 2.5905 19.958625 24.904125
14 5.652 24.7275 35.325
18.5 5.8875 32.675625 49.160625
24.3 6.3585 42.919875 65.763375
29.4 6.8295 51.92775 81.60075
36.6 7.065 64.64475 101.38275
0 7.536 0 44.274
0 0 0 44.274
0

MINATION OF PILE VALUE : - FOR BH - 3

in.

End bearing Pile Value Pile Value Pile Value


Tsf Ps, Ton Pe, Ton Ps + Pe,Ton
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
0 0.471 0 0.471
0 0.7065 0 1.1775
0 1.1775 0 2.355
11.3 2.5905 19.958625 24.904125
14 5.652 24.7275 35.325
18.5 5.8875 32.675625 49.160625
24.3 6.3585 42.919875 65.763375
29.4 6.8295 51.92775 81.60075
36.6 7.065 64.64475 101.38275
0 7.536 0 44.274
0 0 0 44.274
0

MINATION OF PILE VALUE : - FOR BH - 4

in.

End bearing Pile Value Pile Value Pile Value


Tsf Ps, Ton Pe, Ton Ps + Pe,Ton
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
0 0.471 0 0.471
0 0.7065 0 1.1775
0 1.1775 0 2.355
11.3 2.5905 19.958625 24.904125
14 5.652 24.7275 35.325
18.5 5.8875 32.675625 49.160625
24.3 6.3585 42.919875 65.763375
29.4 6.8295 51.92775 81.60075
36.6 7.065 64.64475 101.38275
0 7.536 0 44.274
0 0 0 44.274
0 0 0 44.274
0 0 0 44.274
0 0 0 43.803
0 0 0 43.0965
0 0 0 41.919
0 0 0 39.3285
0 0 0 33.6765
0 0 0 27.789
0 0 0 21.4305
MINATION OF PILE VALUE : - FOR BH - 1

in.

End bearing Pile Value Pile Value Pile Value


ksf Ps, kip Pe, kip Ps + Pe,kip
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
4.49878 3.3710177 7.9459702 11.316988
4.92635 5.8226669 8.7011657 17.89485
55.9559 8.5807722 98.832108 116.60657
73.9882 8.0116394 130.68166 156.46775
105.963 8.7121106 187.15715 221.65536
119.9055 12.477143 211.78309 258.75844
131.989 14.140762 233.12557 294.24168
145.9315 15.541705 257.75151 334.40933
0 17.161544 0 93.819361
0 0 0 93.819361
0 0 0 93.819361
0

MINATION OF PILE VALUE : - FOR BH - 2

in.

End bearing Pile Value Pile Value Pile Value


ksf Ps, kip Pe, kip Ps + Pe,kip
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
4.05262 8.0554188 7.1579401 15.213359
15.9874 8.0554188 28.237745 44.348583
28.8145 5.9977847 50.893611 73.002233
60.0457 3.3710177 106.05572 131.53536
89.9756 4.5968423 158.9194 188.99589
95.9244 10.594627 169.42647 210.09758
108.0079 11.295098 190.76895 242.73516
119.9055 12.73982 211.78309 276.48912
0 14.140762 0 78.846789
0 0 0 78.846789
0 0 0 78.846789
0
0 0 78.846789
0 0 78.846789

MINATION OF PILE VALUE : - FOR BH - 3

in.

End bearing Pile Value Pile Value Pile Value


ksf Ps, kip Pe, kip Ps + Pe,kip
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
12.8271 4.4655039 22.655865 27.121369
12.8271 4.6844012 22.655865 31.80577
51.8661 1.4885013 91.608499 102.24691
87.9307 3.0207821 155.3076 168.96679
93.8795 10.37573 165.81467 189.84958
101.8732 11.076201 179.93354 215.04466
108.0079 11.995569 190.76895 237.87564
105.963 12.73982 187.15715 247.00366
0 12.477143 0 72.323651
0 0 0 72.323651
0 0 0 72.323651
0
MINATION OF PILE VALUE : - FOR BH - 4

in.

End bearing Pile Value Pile Value Pile Value


ksf Ps, kip Pe, kip Ps + Pe,kip
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
14.3143 6.3042408 25.282632 31.586873
27.885 6.3917997 49.251881 61.947922
55.9559 2.1889725 98.832108 113.71712
87.9307 6.610697 155.3076 176.80331
92.0205 10.37573 162.53121 194.40265
95.9244 10.813524 169.42647 212.11144
105.963 11.295098 187.15715 241.13721
108.0079 12.477143 190.76895 257.22616
0 12.73982 0 79.197025
0 0 0 79.197025
0 0 0 79.197025
0

MINATION OF PILE VALUE : - FOR BH - 5

in.

End bearing Pile Value Pile Value Pile Value


ksf Ps, kip Pe, kip Ps + Pe,kip
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
4.92635 1.1820452 8.7011657 9.8832108
20.8208 3.6774738 36.774738 41.634257
63.9496 6.6544764 112.95098 124.46498
81.9819 4.1590478 144.80053 160.47357
101.8732 9.6752585 179.93354 205.28184
108.0079 11.995569 190.76895 228.11282
111.9118 12.696041 197.66422 247.70413
119.9055 13.177614 211.78309 275.00062
0 14.140762 0 77.358288
0 0 0 77.358288
0 0 0 77.358288
0
MINATION OF PILE VALUE : - FOR BH - 1

in.

End bearing Pile Value Pile Value Pile Value


ksf Ps, kip Pe, kip Ps + Pe,kip
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
4.49878 3.7455752 9.8098397 13.555415
4.92635 6.4696298 10.74218 20.957385
55.9559 9.5341913 122.01495 141.76434
73.9882 8.9018215 161.33538 189.9866
105.963 9.6801228 231.05821 269.38955
119.9055 13.863493 261.4606 313.65544
131.989 15.711958 287.80935 355.71614
145.9315 17.268561 318.21174 403.3871
0 19.068383 0 104.24373
0 0 0 104.24373
0 0 0 104.24373
0

MINATION OF PILE VALUE : - FOR BH - 2

in.

End bearing Pile Value Pile Value Pile Value


ksf Ps, kip Pe, kip Ps + Pe,kip
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
4.05262 8.9504653 8.8369631 17.787428
15.9874 8.9504653 34.861414 52.762345
28.8145 6.6642052 62.831618 87.396754
60.0457 3.7455752 130.93298 159.2437
89.9756 5.1076025 196.19679 229.61511
95.9244 11.771808 209.16848 254.3586
108.0079 12.550109 235.51723 293.25746
119.9055 14.155356 261.4606 333.35619
0 15.711958 0 87.607544
0 0 0 87.607544
0 0 0 87.607544
0
0 0 87.607544
0 0 87.607544

MINATION OF PILE VALUE : - FOR BH - 3

in.

End bearing Pile Value Pile Value Pile Value


ksf Ps, kip Pe, kip Ps + Pe,kip
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
12.8271 4.961671 27.970204 32.931875
12.8271 5.2048902 27.970204 38.136765
51.8661 1.6538903 113.09691 124.91736
87.9307 3.3564245 191.73778 206.91465
93.8795 11.528589 204.70947 231.41493
101.8732 12.30689 222.14017 261.15253
108.0079 13.32841 235.51723 287.85799
105.963 14.155356 231.05821 297.55433
0 13.863493 0 80.359613
0 0 0 80.359613
0 0 0 80.359613
0

MINATION OF PILE VALUE : - FOR BH - 4

in.

End bearing Pile Value Pile Value Pile Value


ksf Ps, kip Pe, kip Ps + Pe,kip
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
14.3143 7.004712 31.213126 38.217838
27.885 7.1019997 60.804792 74.911503
55.9559 2.4321917 122.01495 138.55385
87.9307 7.3452188 191.73778 215.6219
92.0205 11.528589 200.65581 236.06852
95.9244 12.015027 209.16848 256.59622
105.963 12.550109 231.05821 291.03605
108.0079 13.863493 235.51723 309.35857
0 14.155356 0 87.996695
0 0 0 87.996695
0 0 0 87.996695
0

MINATION OF PILE VALUE : - FOR BH - 5

in.

End bearing Pile Value Pile Value Pile Value


ksf Ps, kip Pe, kip Ps + Pe,kip
----------------------------------------------------------------------------------
0 0 0
0 0 0 0
4.92635 1.3133835 10.74218 12.055563
20.8208 4.086082 45.400911 50.800377
63.9496 7.3938627 139.44566 152.23898
81.9819 4.6211642 178.76609 196.18058
101.8732 10.750287 222.14017 250.30495
108.0079 13.32841 235.51723 277.01042
111.9118 14.106712 244.0299 299.6298
119.9055 14.641794 261.4606 331.7023
0 15.711958 0 85.953654
0 0 0 85.953654
0 0 0 85.953654
0

in.
(All values are in Kip) Design
BH - 2 BH - 3 BH - 4 BH - 5 Capacity

105 130 140 125 105


150 150 155 160 150
170 170 170 180 170
195 190 195 200 190
220 200 205 220 200

in.

(All values are in Kip) Design


BH - 2 BH - 3 BH - 4 BH - 5 Capacity

130 165 175 160 130


185 185 190 205 185
210 215 210 225 210
240 235 240 245 235
275 245 255 275 245

in.

(All values are in Kip) Design


BH - 2 BH - 3 BH - 4 BH - 5 Capacity

155 205 215 195 155


225 230 235 250 225
250 260 255 275 250
290 285 290 295 285
330 295 305 330 295

CAPACITY OF PILES
18 in dia. 20 in dia.
(All values are in Kip)
130 155
185 225
210 250
235 285
245 295
MINATION OF PILE VALUE : - FOR BH - 1

in.
Allowable
End bearing Pile Value Pile Value Pile Value Pile Value
Tsf Ps, ton Pe, Ton Ps + Pe,TonPs + Pe,Ton
----------------------------------------------------------------------------------
0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
10.8 0 15.072 15.072 10.048
18 1.1304 25.12 26.2504 17.500267
21.6 1.884 30.144 33.1584 22.1056
27.6 2.2608 38.517333 43.792533 29.195022
42 2.8469333 58.613333 66.735467 44.490311
43.2 4.396 60.288 72.806133 48.537422
0 4.5216 0 17.039733 11.359822
0 0 0 17.039733 11.359822
0

MINATION OF PILE VALUE : - FOR BH - 2

in.
Allowable
End bearing Pile Value Pile Value Pile Value Pile Value
Tsf Ps, ton Pe, Ton Ps + Pe,TonPs + Pe,Ton
----------------------------------------------------------------------------------
0 0 0 0
4.5 0 7.948125 7.948125 3.17925
6.8 8.83125 12.0105 20.84175 8.3367
6.2 8.83125 10.95075 28.61325 11.4453
5.1 9.106785 9.007875 35.77716 14.310864
3.9 9.27399 6.888375 42.93165 17.17266
6.6 8.62872 11.65725 56.329245 22.531698
8.4 4.01292 14.8365 63.521415 25.408566
11.4 5.107995 20.13525 73.92816 29.571264
13.8 6.930765 24.37425 85.097925 34.03917
15.6 8.390865 27.5535 96.66804 38.667216
16.8 9.483585 29.673 108.27113 43.30845
18.6 10.213635 32.85225 121.66401 48.665604
0
0

MINATION OF PILE VALUE : - FOR BH - 3

in.
Allowable
End bearing Pile Value Pile Value Pile Value Pile Value
Tsf Ps, ton Pe, Ton Ps + Pe,TonPs + Pe,Ton
----------------------------------------------------------------------------------
0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
12.2 0 17.025778 17.025778 11.350519
13.2 1.256 18.421333 19.677333 13.118222
15.6 1.3816 21.770667 24.408267 16.272178
19.2 1.6328 26.794667 31.065067 20.710044
24 2.0096 33.493333 39.773333 26.515556
33.6 2.512 46.890667 55.682667 37.121778
34.8 3.4749333 48.565333 60.832267 40.554844
0 3.6005333 0 15.867467 10.578311
0 0 0 15.867467 10.578311
0
DETERMINATION OF PILE VALUE

BORE HOLE - 1

Pile Size = 7 in-sq


-------------------------------------------
Depth in ft Skin friction End bearing Pile Value Pile Value Pile Value
ksf ksf Ps, kip Pe, kip Ps + Pe,kip
-------------------------------------------------------------------------------------------------------------
0 0 0 0
5 0 0 0 0
10 0.392 4.94 0 1.6809722 1.6809722
15 0.392 4.94 4.5733333 1.6809722 6.2543056
20 0.56 4.04 4.5733333 1.3747222 10.521389
25 0.56 4.04 6.5333333 1.3747222 17.054722
30 0.642 3.16 6.5333333 1.0752778 23.288611
35 0.642 3.16 7.49 1.0752778 30.778611
40 0.672 4.96 7.49 1.6877778 38.881111
45 0.672 4.96 7.84 1.6877778 46.721111
50 0 0 7.84 0 52.873333
55 0 0 52.873333
60 0 0 52.873333
65

DETERMINATION OF PILE VALUE


--------------------------------------------------------

Pile Size = 7 in-sq


-------------------------------------------
Depth in ft Skin friction End bearing Pile Value Pile Value Pile Value
ksf ksf Ps, kip Pe, kip Ps + Pe,kip
-------------------------------------------------------------------------------------------------------------
0 0 0 0
11 0.16 0 0 0
18 1.2 2.24 0 2.24
24 0.4 42 0 44.24
39 1.1 21 0 65.24
61.5 1.88 -80.85 0 -15.61
30 0.29 21.933333 0 6.3233333
35 0.2 46 3.3833333 15.652778 25.359444
40 0.2 40 2.3333333 13.611111 25.651111
45 0.33 90 2.3333333 30.625 44.998333
50 0.49 98 3.85 33.347222 51.570556
55 5.7166667 0 23.94
60 0 0 23.94
65

DETERMINATION OF PILE VALUE

BORE HOLE - 1

Pile Size = 7 in-sq


-------------------------------------------
Depth in ft Skin friction End bearing Pile Value Pile Value Pile Value
ksf ksf Ps, kip Pe, kip Ps + Pe,kip
-------------------------------------------------------------------------------------------------------------
0 0 0 0
5 0 0 0 0
10 0.392 4.94 0 1.6809722 1.6809722
15 0.392 4.94 4.5733333 1.6809722 6.2543056
20 0.56 4.04 4.5733333 1.3747222 10.521389
25 0.56 4.04 6.5333333 1.3747222 17.054722
30 0.642 3.16 6.5333333 1.0752778 23.288611
35 0.642 3.16 7.49 1.0752778 30.778611
40 0.672 4.96 7.49 1.6877778 38.881111
45 0.672 4.96 7.84 1.6877778 46.721111
50 0 0 7.84 0 52.873333
55 0 0 52.873333
60 0 0 52.873333
65

DETERMINATION OF PILE VALUE

BORE HOLE - 2

Pile Size = 7 in-sq


-------------------------------------------
Depth in ft Skin friction End bearing Pile Value Pile Value Pile Value
ksf ksf Ps, kip Pe, kip Ps + Pe,kip
-------------------------------------------------------------------------------------------------------------
0 0 0 0
5 0 0 0 0
10 0.448 4.5 0 1.53125 1.53125
15 0.448 4.5 5.2266667 1.53125 6.7579167
20 0.504 4.04 5.2266667 1.3747222 11.828056
25 0.504 4.04 5.88 1.3747222 17.708056
30 0.348 22.04 5.88 7.4997222 29.713056
35 0.348 22.04 4.06 7.4997222 33.773056
40 0.7 5.4 4.06 1.8375 32.170833
45 0.7 5.4 8.1666667 1.8375 40.3375
50 0 0 8.1666667 0 46.666667
55 0 0 46.666667
60 0 0 46.666667
65

DETERMINATION OF PILE VALUE

BORE HOLE - 3

Pile Size = 7 in-sq


-------------------------------------------
Depth in ft Skin friction End bearing Pile Value Pile Value Pile Value
ksf ksf Ps, kip Pe, kip Ps + Pe,kip
-------------------------------------------------------------------------------------------------------------
0 0 0 0
5 0 0 0 0
10 0.28 4.5 0 1.53125 1.53125
15 0.28 4.5 3.2666667 1.53125 4.7979167
20 0.392 3.16 3.2666667 1.0752778 7.6086111
25 0.309 21.12 4.5733333 7.1866667 18.293333
30 0.309 21.12 3.605 7.1866667 21.898333
35 0.504 4.04 3.605 1.3747222 19.691389
40 0.616 4.94 5.88 1.6809722 25.877639
45 0.616 4.94 7.1866667 1.6809722 33.064306
50 0.7 7.2 7.1866667 2.45 41.02
55 0.617 45.6 8.1666667 15.516667 62.253333
60 0.658 45.5 7.1983333 15.482639 69.417639
65 0.7 60.2 0 0 53.935

DETERMINATION OF PILE VALUE

BORE HOLE - 4

Pile Size = 7 in-sq


-------------------------------------------
Depth in ft Skin friction End bearing Pile Value Pile Value Pile Value
ksf ksf Ps, kip Pe, kip Ps + Pe,kip
-------------------------------------------------------------------------------------------------------------
0 0 0 0
5 0 0 0 0
10 0.498 4.04 0 1.3747222 1.3747222
15 0.498 4.04 5.81 1.3747222 7.1847222
20 0.672 5.4 5.81 1.8375 13.4575
25 0.264 2.4 7.84 0.8166667 20.276667
30 0.328 17.76 3.08 6.0433333 28.583333
35 0.672 5.4 3.8266667 1.8375 28.204167
40 0.672 5.4 7.84 1.8375 36.044167
45 0.7 5.84 7.84 1.9872222 44.033889
50 0.7 5.84 8.1666667 1.9872222 52.200556
55 8.1666667 0 58.38
60 0 0 58.38
65 0 0 58.38

DETERMINATION OF PILE VALUE

BORE HOLE - 5

Pile Size = 7 in-sq


-------------------------------------------
Depth in ft Skin friction End bearing Pile Value Pile Value Pile Value
ksf ksf Ps, kip Pe, kip Ps + Pe,kip
-------------------------------------------------------------------------------------------------------------
0 0 0 0
5 0 0 0 0
10 0.616 6.3 0 2.14375 2.14375
15 0.616 6.3 7.1866667 2.14375 9.3304167
20 0.56 4.04 7.1866667 1.3747222 15.748056
25 0.272 11.4 6.5333333 3.8791667 24.785833
30 0.328 17.76 3.1733333 6.0433333 30.123333
35 0.448 3.6 3.8266667 1.225 29.131667
40 0.672 5.4 5.2266667 1.8375 34.970833
45 0.672 5.4 7.84 1.8375 42.810833
50 0.7 9 7.84 3.0625 51.875833
55 0.7 9 8.1666667 3.0625 60.0425
60 8.1666667 0 65.146667
65 0 0 65.146667
CALCULATION OF AVG

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Avg Live Load/Floor =


OK
CALCULATION OF AVG. LIVE LOAD

Gr. Floor 100 psf


st. Floor 40 psf
nd. Floor 36 psf
rd. Floor 32 psf
th. Floor 28 psf
th. Floor 24 psf
th. Floor 20 psf
th. Floor 20 psf
th. Floor 20 psf
th. Floor 20 psf
th. Floor 20 psf
th. Floor 20 psf
th. Floor psf
th. Floor psf
th. Floor psf
th. Floor psf
th. Floor psf
Roof 40 psf
-------------------------------------------
Avg Live Load/Floor = 32.308 psf

Column Load at (B2)1

Slab = 0.08 X 12 X 9X 10 = 86.4 kip


Slab = 0 X 0 X 5.25 X 10 = 0 kip
Wall,Beam = 0.65 X 7 X 1X 9.5 = 43.23 kip
Wall,Beam = 0.65 X 10 X 1X 9.5 = 61.75 kip
Wall,Beam = 0 X 5 X 1X 9.5 = 0 kip
Column = 15 X 15 X 10 X 10 = 23.44 kip
----------------------------------------
D.L. = 214.8 kip
Live Load = 0.03 X 12 X 9X 10 = 32.4 kip
Live Load = 0.03 X 0X 5.25 X 10 = 0 kip
----------------------------------------
Total Column Load = 247.2 kip
0.229 ksf/floor

Column Load at (B1)1

Slab = 0.08 X 10 X 8X 10 = 64 kip


Slab = 0.08 X 0X 5.25 X 2= 0 kip
Wall,Beam = 0.65 X 0 X 1X 8= 0 kip
Wall,Beam = 0.65 X 10 X 1X 9.5 = 61.75 kip
Wall,Beam = 0.6 X 0 X 1X 9.5 = 0 kip
Column = 15 X 15 X 10 X 10 = 23.44 kip
----------------------------------------
D.L. = 149.2 kip
Live Load = 0.03 X 10 X 8X 10 = 24 kip
Live Load = 0.03 X 0X 5.25 X 2= 0 kip
----------------------------------------
Total Column Load = 173.2 kip
0.216 ksf/floor

Column Load at B2

Slab = 0.08 X 11 X 7X 10 = 61.6 kip


Slab = 0.08 X 5 X 5.5 X 10 = 22 kip
Wall,Beam = 0.65 X 11 X 1X 9.5 = 67.93 kip
Wall,Beam = 1 X 5.5 X 1X 9.5 = 52.25 kip
Wall,Beam = 0 X 0 X 1X 10 = 0 kip
Column = 15 X 18 X 10 X 10 = 28.13 kip
----------------------------------------
D.L. = 231.9 kip
Live Load = 0.03 X 11 X 7X 10 = 23.1 kip
Live Load = 0.03 X 5X 5.5 X 10 = 8.25 kip
----------------------------------------
Total Column Load = 263.3 kip
0.252 ksf/floor

Column Load at (B2)2

Slab = 0.08 X 11 X 7.5 X 10 = 66 kip


Slab = 0.08 X 5.5 X 3X 10 = 13.2 kip
Wall,Beam = 0.35 X 0 X 1X 8= 0 kip
Wall,Beam = 0.65 X 17 X 1X 9.5 = 105 kip
Wall,Beam = 0.6 X 0 X 1X 9.5 = 0 kip
Column = 15 X 18 X 10 X 10 = 28.13 kip
----------------------------------------
D.L. = 212.3 kip
Live Load = 0.03 X 11 X 7.5 X 10 = 24.75 kip
Live Load = 0.03 X 5.5 X 3X 10 = 4.95 kip
----------------------------------------
Total Column Load = 242 kip
0.244 ksf/floor
Column Load at B3

Slab = 0.08 X 5.5 X 13.5 X 10 = 59.4 kip


Slab = 0.09 X 11 X 9X 10 = 89.1 kip
Slab = 0.08 X 3.5 X 7.5 X 10 = 21 kip
Wall,Beam = 1 X 5 X 1X 9.5 = 47.5 kip
Wall,Beam = 0.65 X 22 X 1X 9.5 = 135.9 kip
Wall,Beam = 0.2 X 15 X 1X 9= 27 kip
Wall,Beam = 0.4 X 8 X 1X 9= 28.8 kip
Wall,Beam = 0.3 X 7 X 1X 9.5 = 19.95 kip
Column = 15 X 25 X 10 X 10 = 39.06 kip
----------------------------------------
D.L. = 467.7 kip
Live Load = 0.03 X 5.5 X 13.5 X 10 = 22.28 kip
Live Load = 0.03 X 11 X 9X 10 = 29.7 kip
Live Load = 0.03 X 3.5 X 7.5 X 10 = 7.875 kip
----------------------------------------
Total Column Load = 527.5 kip
0.264 ksf/floor

Column Load at (B2)3

Slab = 0.08 X 5.5 X 7.5 X 10 = 33 kip


Slab = 0.08 X 10.5 X 13 X 10 = 109.2 kip
Wall,Beam = 0.65 X 7 X 1X 9.5 = 43.23 kip
Wall,Beam = 0.8 X 8 X 1X 9.5 = 60.8 kip
Wall,Beam = 0.4 X 9 X 1X 9= 32.4 kip
Wall,Beam = 0.45 X 8 X 1X 9= 32.4 kip
Column = 15 X 20 X 10 X 10 = 31.25 kip
----------------------------------------
D.L. = 342.3 kip
Live Load = 0.03 X 5.5 X 7.5 X 10 = 12.38 kip
Live Load = 0.03 X 10.5 X 13 X 10 = 40.95 kip
----------------------------------------
Total Column Load = 395.6 kip
0.223 ksf/floor
Column Load at C3

Slab = 0.08 X 10.5 X 5X 10 = 42 kip


Slab = 0.09 X 6.66 X 15 X 10 = 89.91 kip
Wall,Beam = 0.8 X 7 X 1X 9.5 = 53.2 kip
Wall,Beam = 0.65 X 9 X 1X 9.5 = 55.58 kip
Wall,Beam = 0.05 X 6.67 X 13 X 9 = 39.02 kip
Column = 15 X 18 X 10 X 10 = 28.13 kip
----------------------------------------
D.L. = 307.8 kip
Live Load = 0.03 X 10.5 X 5X 10 = 15.75 kip
Live Load = 0.03 X 6.66 X 15 X 10 = 29.97 kip
----------------------------------------
Total Column Load = 353.5 kip
0.232 ksf/floor

Column Load at D3

Slab = 0.09 X 10.5 X 9.5 X 10 = 89.78 kip


Slab = 0.08 X 10.5 X 5X 10 = 42 kip
Wall,Beam = 0.65 X 14 X 1X 9.5 = 86.45 kip
Wall,Beam = 1 X 9.5 X 1X 9.5 = 90.25 kip
Wall,Beam = 0 X 0 X 1X 9= 0 kip
Column = 15 X 20 X 10 X 10 = 31.25 kip
----------------------------------------
D.L. = 339.7 kip
Live Load = 0.03 X 10.5 X 9.5 X 10 = 29.93 kip
Live Load = 0.03 X 10.5 X 5X 10 = 15.75 kip
----------------------------------------
Total Column Load = 385.4 kip
0.253 ksf/floor

Column Load at E3

Slab = 0.09 X 10.5 X 16.5 X 10 = 155.9 kip


Slab = 0.09 X 0 X 2.5 X 10 = 0 kip
Wall,Beam = 0.65 X 25 X 1X 9.5 = 154.4 kip
Wall,Beam = 0.45 X 8 X 1X 9= 32.4 kip
Wall,Beam = 0.25 X 15 X 1X 9 = 33.75 kip
Column = 15 X 20 X 10 X 10 = 31.25 kip
----------------------------------------
D.L. = 407.7 kip
Live Load = 0.03 X 10.5 X 16.5 X 10 = 51.98 kip
Live Load = 0.03 X 0X 2.5 X 10 = 0 kip
----------------------------------------
Total Column Load = 459.7 kip
0.265 ksf/floor

Column Load at (F2)3

Slab = 0.09 X 10.5 X 7X 10 = 66.15 kip


Slab = 0.08 X 8.5 X 6.5 X 10 = 44.2 kip
Wall,Beam = 0.65 X 22 X 1X 9.5 = 135.9 kip
Wall,Beam = 0.25 X 7 X 1X 9 = 15.75 kip
Wall,Beam = 0.25 X 6.5 X 1X 9 = 14.63 kip
Wall,Beam = 0.25 X 6.5 X 1X 9.5 = 15.44 kip
Wall,Beam = 0 X 5 X 1X 8= 0 kip
Wall,Beam = 0 X 7 X 1X 8= 0 kip
Column = 15 X 20 X 10 X 10 = 31.25 kip
----------------------------------------
D.L. = 323.3 kip
Live Load = 0.03 X 10.5 X 7X 10 = 22.05 kip
Live Load = 0.03 X 8.5 X 6.5 X 10 = 16.58 kip
----------------------------------------
Total Column Load = 361.9 kip
0.281 ksf/floor

Column Load at G3

Slab = 0.08 X 8 X 6.5 X 10 = 41.6 kip


Slab = 0.08 X 4 X 3X 10 = 9.6 kip
Wall,Beam = 0.65 X 13 X 1X 9.5 = 80.28 kip
Wall,Beam = 0 X 12 X 1X 9= 0 kip
Wall,Beam = 0 X 7.5 X 1X 8= 0 kip
Wall,Beam = 0 X 5 X 1X 9= 0 kip
Column = 15 X 15 X 10 X 10 = 23.44 kip
----------------------------------------
D.L. = 154.9 kip
Live Load = 0.03 X 8X 6.5 X 10 = 15.6 kip
Live Load = 0.03 X 4X 3X 10 = 3.6 kip
----------------------------------------
Total Column Load = 174.1 kip
0.272 ksf/floor
Column Load at (A1)4

Slab = 0.08 X 5.5 X 13 X 10 = 57.2 kip


Slab = 0 X 4 X 6X 8= 0 kip
Wall,Beam = 0 X 5 X 5X 1= 0 kip
Wall,Beam = 0.65 X 13 X 1X 9.5 = 80.28 kip
Wall,Beam = 0 X 7.5 X 1X 8= 0 kip
Wall,Beam = 0 X 0 X 1X 9= 0 kip
Column = 15 X 18 X 10 X 10 = 28.13 kip
----------------------------------------
D.L. = 165.6 kip
Live Load = 0.03 X 5.5 X 13 X 10 = 21.45 kip
Live Load = 0.03 X 4X 6X 8= 5.76 kip
----------------------------------------
Total Column Load = 192.8 kip
0.213 ksf/floor

Column Load at G4a

Slab = 0.08 X 7.5 X 10.5 X 10 = 63 kip


Slab = 0 X 0 X 4X 2= 0 kip
Wall,Beam = 0 X 0 X 1X 8= 0 kip
Wall,Beam = 0.65 X 14 X 1X 9.5 = 86.45 kip
Wall,Beam = 0 X 0 X 1X 9.5 = 0 kip
Column = 18 X 18 X 10 X 10 = 33.75 kip
----------------------------------------
D.L. = 183.2 kip
Live Load = 0.03 X 7.5 X 10.5 X 10 = 23.63 kip
Live Load = 0.03 X 0X 4X 2= 0 kip
----------------------------------------
Total Column Load = 206.8 kip
0.263 ksf/floor

Column Load at (A1)5

Slab = 0.08 X 12 X 8X 10 = 76.8 kip


Slab = 0.08 X 5 X 5X 10 = 20 kip
Wall,Beam = 0.65 X 27 X 1X 9.5 = 166.7 kip
Wall,Beam = 0.6 X 0 X 1X 9.5 = 0 kip
Wall,Beam = 0 X 0 X 1X 9.5 = 0 kip
Column = 15 X 18 X 10 X 10 = 28.13 kip
----------------------------------------
D.L. = 291.7 kip
Live Load = 0.03 X 12 X 8X 10 = 28.8 kip
Live Load = 0.03 X 5X 5X 10 = 7.5 kip
----------------------------------------
Total Column Load = 328 kip
0.271 ksf/floor

Column Load at B5

Slab = 0.08 X 7 X 18 X 10 = 100.8 kip


Slab = 0.09 X 11 X 10.5 X 10 = 104 kip
Slab = 0.08 X 7.5 X 8X 10 = 48 kip
Wall,Beam = 0.35 X 7.5 X 1X 9.5 = 24.94 kip
Wall,Beam = 0.65 X 34 X 1X 9.5 = 210 kip
Wall,Beam = 0.25 X 16 X 1X 9= 36 kip
Wall,Beam = 0.35 X 10 X 1X 9= 31.5 kip
Wall,Beam = 0.25 X 5 X 1X 9 = 11.25 kip
Column = 15 X 25 X 10 X 10 = 39.06 kip
----------------------------------------
D.L. = 605.5 kip
Live Load = 0.03 X 7X 18 X 10 = 37.8 kip
Live Load = 0.03 X 11 X 10.5 X 10 = 34.65 kip
Live Load = 0.03 X 7.5 X 8X 10 = 18 kip
----------------------------------------
Total Column Load = 695.9 kip
0.231 ksf/floor

Column Load at C5

Slab = 0.08 X 7 X 15 X 10 = 84 kip


Slab = 0.08 X 10.5 X 5X 10 = 42 kip
Slab = 0.09 X 10.5 X 10 X 10 = 94.5 kip
Wall,Beam = 0.65 X 30 X 1X 9.5 = 185.3 kip
Wall,Beam = 0 X 22 X 1X 9.5 = 0 kip
Wall,Beam = 0.35 X 14 X 1X 9= 44.1 kip
Wall,Beam = 0.25 X 16 X 1X 9= 36 kip
Wall,Beam = 0 X 7 X 1X 9.5 = 0 kip
Column = 15 X 25 X 10 X 10 = 39.06 kip
----------------------------------------
D.L. = 524.9 kip
Live Load = 0.03 X 7X 15 X 10 = 31.5 kip
Live Load = 0.03 X 10.5 X 5X 10 = 15.75 kip
Live Load = 0.03 X 10.5 X 10 X 10 = 31.5 kip
----------------------------------------
Total Column Load = 603.7 kip
0.23 ksf/floor

Column Load at D5

Slab = 0.08 X 17 X 5X 10 = 68 kip


Slab = 0.09 X 10 X 9.5 X 10 = 85.5 kip
Slab = 0.14 X 6 X 7X 10 = 58.8 kip
Wall,Beam = 1 X 6 X 1X 11 = 66 kip
Wall,Beam = 0.65 X 23 X 1X 11 = 164.5 kip
Wall,Beam = 0.5 X 3.5 X 1X 11 = 19.25 kip
Wall,Beam = 0.25 X 18 X 1X 9= 40.5 kip
Wall,Beam = 0.35 X 4.5 X 1X 9 = 14.18 kip
Column = 15 X 25 X 10 X 10 = 39.06 kip
----------------------------------------
D.L. = 555.7 kip
Live Load = 0.03 X 17 X 5X 10 = 25.5 kip
Live Load = 0.03 X 10 X 9.5 X 10 = 28.5 kip
Live Load = 0.05 X 6X 7X 10 = 21 kip
----------------------------------------
Total Column Load = 630.7 kip
0.284 ksf/floor

Column Load at E5

Slab = 0.09 X 10 X 9.5 X 10 = 85.5 kip


Slab = 0.08 X 10 X 7X 10 = 56 kip
Slab = 0.08 X 7 X 6.5 X 10 = 36.4 kip
Slab = 0.14 X 6.5 X 6X 10 = 54.6 kip
Wall,Beam = 1 X 6 X 1X 11 = 66 kip
Wall,Beam = 0.65 X 26 X 1X 11 = 185.9 kip
Wall,Beam = 0.25 X 15 X 1X 9 = 33.75 kip
Wall,Beam = 0.25 X 12 X 1X 9= 27 kip
Column = 15 X 25 X 10 X 10 = 39.06 kip
----------------------------------------
D.L. = 584.2 kip
Live Load = 0.03 X 10 X 9.5 X 10 = 28.5 kip
Live Load = 0.03 X 10 X 7X 10 = 21 kip
Live Load = 0.03 X 7X 6.5 X 10 = 13.65 kip
Live Load = 0.05 X 6.5 X 6X 10 = 19.5 kip
----------------------------------------
Total Column Load = 666.9 kip
0.317 ksf/floor
Column Load at (F2)5

Slab = 0.08 X 10 X 7X 10 = 56 kip


Slab = 0.08 X 7 X 7X 10 = 39.2 kip
Slab = 0.08 X 6.5 X 8X 10 = 41.6 kip
Wall,Beam = 0 X 6 X 1X 11 = 0 kip
Wall,Beam = 0.65 X 28 X 1X 9.5 = 172.9 kip
Wall,Beam = 0 X 3.5 X 1X 11 = 0 kip
Wall,Beam = 0.45 X 7 X 1X 9 = 28.35 kip
Wall,Beam = 0 X 4.5 X 1X 9= 0 kip
Column = 15 X 25 X 10 X 10 = 39.06 kip
----------------------------------------
D.L. = 377.1 kip
Live Load = 0.03 X 10 X 7X 10 = 21 kip
Live Load = 0.03 X 7X 7X 10 = 14.7 kip
Live Load = 0.03 X 6.5 X 8X 10 = 15.6 kip
----------------------------------------
Total Column Load = 428.4 kip
0.251 ksf/floor

Column Load at D5/6

Slab = 0.08 X 7 X 3.5 X 10 = 19.6 kip


Slab = 0.14 X 6 X 6X 10 = 50.4 kip
Wall,Beam = 1 X 6 X 1X 11 = 66 kip
Wall,Beam = 0 X 7 X 1X 9.5 = 0 kip
Wall,Beam = 0.65 X 3 X 1X 11 = 21.45 kip
Column = 15 X 15 X 10 X 11 = 25.78 kip
----------------------------------------
D.L. = 183.2 kip
Live Load = 0.03 X 7X 3.5 X 10 = 7.35 kip
Live Load = 0.05 X 6X 6X 10 = 18 kip
----------------------------------------
Total Column Load = 208.6 kip
0.345 ksf/floor

Column Load at D5/6

Slab = 0.08 X 7X 7X 10 = 39.2 kip


Slab = 0X 0X 6X 10 = 0 kip
Wall,Beam = 1 X 6.5 X 1X 9.5 = 61.75 kip
Wall,Beam = 0.65 X 5 X 1X 9.5 = 30.88 kip
Wall,Beam = 0 X 3 X 1X 11 = 0 kip
Column = 15 X 18 X 10 X 11 = 30.94 kip
----------------------------------------
D.L. = 162.8 kip
Live Load = 0.03 X 7X 7X 10 = 14.7 kip
Live Load = 0X 0X 6X 10 = 0 kip
----------------------------------------
Total Column Load = 177.5 kip
0.362 ksf/floor

Column Load at B6

Slab = 0.08 X 7 X 16 X 10 = 89.6 kip


Slab = 0 X 0 X 14 X 10 = 0 kip
Wall,Beam = 0.65 X 10 X 1X 9.5 = 61.75 kip
Wall,Beam = 0.9 X 9.5 X 1X 9.5 = 81.23 kip
Wall,Beam = 0.25 X 6.5 X 1X 9 = 14.63 kip
Column = 15 X 18 X 10 X 10 = 28.13 kip
----------------------------------------
D.L. = 275.3 kip
Live Load = 0.03 X 7X 16 X 10 = 33.6 kip
Live Load = 0.03 X 0X 14 X 10 = 0 kip
----------------------------------------
Total Column Load = 308.9 kip
0.276 ksf/floor

Column Load at C6

Slab = 0.08 X 7 X 15 X 10 = 84 kip


Slab = 0.08 X 0 X 12.5 X 10 = 0 kip
Wall,Beam = 0.65 X 10 X 1X 9.5 = 61.75 kip
Wall,Beam = 0.9 X 9.5 X 1X 9.5 = 81.23 kip
Wall,Beam = 0.25 X 6.5 X 1X 9 = 14.63 kip
Column = 15 X 18 X 10 X 10 = 28.13 kip
----------------------------------------
D.L. = 269.7 kip
Live Load = 0.03 X 7X 15 X 10 = 31.5 kip
Live Load = 0.03 X 0X 12.5 X 10 = 0 kip
----------------------------------------
Total Column Load = 301.2 kip
0.287 ksf/floor

Column Load at (D1)6

Slab = 0.08 X 7 X 5X 10 = 28 kip


Slab = 0.08 X 7 X 3.5 X 10 = 19.6 kip
Wall,Beam = 1 X 10 X 1X 11 = 110 kip
Wall,Beam = 0.5 X 3 X 1X 11 = 16.5 kip
Wall,Beam = 0.8 X 4.5 X 1X 10 = 36 kip
Column = 15 X 15 X 10 X 10 = 23.44 kip
----------------------------------------
D.L. = 233.5 kip
Live Load = 0.03 X 7X 5X 10 = 10.5 kip
Live Load = 0.03 X 7X 3.5 X 10 = 7.35 kip
----------------------------------------
Total Column Load = 251.4 kip
0.423 ksf/floor

Column Load at (D2)6

Slab = 0.08 X 7 X 3.5 X 10 = 19.6 kip


Slab = 0.14 X 7 X 6X 10 = 58.8 kip
Wall,Beam = 1 X 12 X 1X 11 = 132 kip
Wall,Beam = 0 X 3 X 1X 11 = 0 kip
Wall,Beam = 0 X 4.5 X 1X 10 = 0 kip
Column = 15 X 15 X 10 X 10 = 23.44 kip
----------------------------------------
D.L. = 233.8 kip
Live Load = 0.03 X 7X 3.5 X 10 = 7.35 kip
Live Load = 0.05 X 7X 6X 10 = 21 kip
----------------------------------------
Total Column Load = 262.2 kip
0.394 ksf/floor

Column Load at E6

Slab = 0.08 X 7 X 6 X 10 = 33.6 kip


Slab = 0.14 X 7 X 6 X 10 = 58.8 kip
Wall,Beam = 1 X 16 X 1 X 11 = 176 kip
Wall,Beam = 0 X 3 X 1 X 11 = 0 kip
Wall,Beam = 0 X 4.5 X 1 X 10 = 0 kip
Column = 15 X 15 X 10 X 10 = 23.44 kip
----------------------------------------
D.L. = 291.8 kip
Live Load = 0.03 X 7X 6X 10 = 12.6 kip
Live Load = 0.05 X 7X 6X 10 = 21 kip
----------------------------------------
Total Column Load = 325.4 kip
0.387 ksf/floor

Column Load at (F1)6

Slab = 0.08 X 7 X 7X 10 = 39.2 kip


Slab = 0.14 X 0 X 6X 10 = 0 kip
Wall,Beam = 1 X 11 X 1X 10 = 110 kip
Wall,Beam = 0 X 3 X 1X 11 = 0 kip
Wall,Beam = 0 X 4.5 X 1X 10 = 0 kip
Column = 15 X 20 X 10 X 10 = 31.25 kip
----------------------------------------
D.L. = 180.5 kip
Live Load = 0.03 X 7X 7X 10 = 14.7 kip
Live Load = 0.05 X 0X 6X 10 = 0 kip
----------------------------------------
Total Column Load = 195.2 kip
0.398 ksf/floor
OK
DESIGN OF WALL FOUNDATION (WSD)

f'c = 3 ksi.
fy = 60 ksi.
k = 0.31526
j = 0.89491
R = 0.19044

Wall Thickness = t = 8 in
Wall Load = 22 k/ft
Bearing Capacity = 3.5 ksf
Width of Found(reqd) = 6.6 ft
Width 0f Found.(pro.) = 6.75 ft
Net Pressure = Wu = 3.25926 ksf
M = 15.0769 k-ft/ft
dreq = 8.89775 in < 12 in
d (provided) = 12 in
Vs = 8.28395 kip/ft
v = 57.5274 psi < 60.25 psi
As = 0.62397 sq-in/ft
as = 0.175 sq-in
Spacing of bar = 3.36552 in. c/c
dia. of bar = 0.47215 in
Peremeter of bar = 1.48257 in
Bond Stress = 556.824 psi
Ld (minimum) = 5.72361 in < 33.5 in
As (temp.) = 0.36 sq-in/ft
ast = 0.175 sq-in
Spacing of temp. bar = 5.83333 in. c/c
NOT OK
DESIGN OF WALL FOUNDATION (USD)

f'c 3 ksi.
fy 60 ksi.
k 0.31526
j 0.89491
R 0.19044

Wall Thickness = t = 8 in
Wall Load 22 k/ft
Bearing Capacity = 3.5 ksf
Width of Found(reqd)= 6.6 ft
Width 0f Found.(pro.) = 6.75 ft
Net Pressure = Wu = 3.25926 ksf
M 15.0769 k-ft/ft
dreq 8.89775 in
d (provided) 12 in
Vs 8.28395 kip/ft
v 57.5274 psi < 60.249 psi
As 0.62397 sq-in/ft
as 0.175 sq-in
Spacing of bar = 3.36552 in. c/c
dia. of bar 0.47215 in
Peremeter of bar = 1.48257 in
Bond Stress = 556.824 psi
Ld (minimum) 5.72361 in < 33.5 in
As (temp.) 0.36 sq-in/ft
ast 0.175 sq-in
Spacing of temp. bar= 5.83333 in. c/c
OK (square & rectangle)
DESIGN OF FOOTING - F1 (WSD)

f'c = 3 ksi.
fy = 60 ksi.
k = 0.3152582
j = 0.8949139
R = 0.190437
Column Load (D.L.) = 425 kip
Column Load (L.L.) = 75 kip
Bearing Capacity = 3 ksf
Column Size = 15 in
= 25 in
Area of Found(reqd) = 175 sq-ft
Footing Size(reqd) = 13.228757 ft
Footing Size(prov.) = 12.75 ft
= 13.75 ft
Area of Found(prov) = 175.3125 sq-ft > 175
Wu = 2.8520499 ksf
d (provided) = 27 in
V (punching) = 456.74391 kip
V (punching) = 89.98107 psi < 109.5 psi
M = 47.14795 k-ft/ft
dreq = 15.7346 in
Vs = 9.9821747 kip/ft
v = 30.809181 psi < 60.25 psi
As = 0.8672319 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 4.2895099 in. c/c
dia. of bar = 0.6284142 in
Peremeter of bar = 1.9732207 in
Bond Stress = 418.36548 psi
Ld (minimum) = 10.138973 in < 66 in
M = 48.52446 k-ft/ft
dreq = 15.962637 in
Vs = 13.428402 kip/ft
v = 41.445684 psi < 60.25 psi
As = 0.8925512 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 4.1678279 in. c/c
dia. of bar = 0.6284142 in
Peremeter of bar = 1.9732207 in
Bond Stress = 878.52623 psi
Ld (minimum) = 1.0260157 in < 67 in
As (temp.) = 0.81 sq-in/ft
ast = 0.31 sq-in
Spacing of temp. bar= 4.5925926 in. c/c

DESIGN OF COMBIND FOOTING - F10 (WSD)


FOR 2 NOS. COLUMN(eq. load)
f'c = 2.5 ksi.
fy = 40 ksi.
k = 0.3866667
j = 0.8711111
R = 0.1894667
Column Load = 345 kip
Column Load = 345 kip
Column C/C = 8.833 ft
Bearing Capacity = 3 ksf
Column Size = 10 in
= 20 in
Area of Found(reqd) = 241.5 sq-ft
Footing Size(reqd) = 15.54027 ft
Footing Size(prov.) = 12 ft
= 21 ft
Area of Found(prov) = 252 sq-ft > 241.5
Wu = 2.7380952 ksf
d (provided) = 24 in
V (punching) = 330.77712 kip
V (punching) = 88.348589 psi < 100 psi
M = 36.545966 k-ft/ft
dreq = 13.888435 in < 21 in
Vs = 9.8115079 kip/ft
v = 34.067736 psi < 55 psi
As = 1.1653688 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 3.1921225 in. c/c
dia. of bar = 0.6284142 in
Peremeter of bar = 1.9732207 in
Bond Stress = 381.91369 psi
Ld (minimum) = 7.4044586 in < 64 in
M = 37.736771 k-ft/ft
dreq = 14.11289 in < 20.5 in
Vs = 23.730159 kip/ft
v = 82.396384 psi < 55 psi
As = 1.2033409 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 3.0913933 in. c/c
dia. of bar = 0.6284142 in
Peremeter of bar = 1.9732207 in
Bond Stress = 952.19194 psi
Ld (minimum) = 0.890954 in < 113 in
As (temp.) = 0.72 sq-in/ft
ast = 0.31 sq-in
Spacing of temp. bar= 5.1666667 in. c/c

DESIGN OF COMBIND FOOTING - F10 (WSD)


DESIGN OF FOOTING BEAM - FB1

w = 32.857143 k/ft fy = 60 ksi


L = 8.833 ft f'c = 3 ksi
Beam Size = k = 0.3152581894
= 25 in j = 0.8949139369
= 36 in R = 0.1904370395
d(pro) = 32.5 in
M = 320.44704 k-ft
dreqd = 28.419933 in >< 32.5
M1 = 419.06067 k-ft
M2 = -98.61363 k-ft
As1 = 6.403682 sq-in
As2 = -1.460943 sq-in as no. of bar
As=As1+As2 = 4.9427393 sq-in 0.48 10.297373592 nos.
f's = 18.795546 ksi
As2 = -2.09866 sq-in
V = 145.11357 kip
Vd = 56.125476 kip
vd = 69.077509 psi > 60.2494813256 psi
av = 0.11 sq-in
Stirrup = 26.914279 in. c/c

DESIGN OF COMBIND FOOTING - F11 (WSD)


FOR 4 - NOS. COLUMN
f'c 2.5 ksi.
fy 40 ksi.
k 0.3866667
j 0.8711111
R 0.1894667
Column Load = 150 kip 150 kip
Column Load = 150 kip 150 kip
Column C/C = 8.833 ft 5 ft
Bearing Capacity = 3 ksf
Column Size = 10 in
15 in
Area of Found(reqd) = 210 sq-ft
Footing Size(reqd) = 14.491377 ft
Footing Size(prov.) = 13 ft
17 ft
Area of Found(prov) = 221 sq-ft > 210
Wu 2.7149321 ksf
d (provided) = 15 in
V (punching) 146.46493 kip
V (punching) 88.766626 psi < 100 psi
M 17.430241 k-ft/ft
dreq 9.5914727 in < 12 in
Vs 6.3348416 kip/ft
v 35.193565 psi < 55 psi
As 0.889298 sq-in/ft
as 0.31 sq-in
Spacing of bar = 4.1830746 in. c/c
dia. of bar 0.6284142 in
Peremeter of bar = 1.9732207 in
Bond Stress 381.91369 psi
Ld (minimum) 7.4044586 in < 70 in
M 16.236953 k-ft/ft
dreq 9.2573325 in < 11.5 in
Vs 7.6927602 kip/ft
v 42.737557 psi < 55 psi
As 0.828416 sq-in/ft
as 0.31 sq-in
Spacing of bar = 4.4904976 in. c/c
dia. of bar 0.6284142 in
Peremeter of bar = 1.9732207 in
Bond Stress 919.49642 psi
Ld (minimum) 0.9995208 in < 91.5 in
As (temp.) 0.45 sq-in/ft
ast 0.31 sq-in
Spacing of temp. bar = 8.2666667 in. c/c

DESIGN OF COMBIND FOOTING - F11 (WSD)


DESIGN OF FOOTING BEAM - FB2

w= 17.647059 k/ft fy = 60 ksi


L= 8.833 ft f'c = 3 ksi
Beam Size k = 0.3152581894
12 in j = 0.8949139369
36 in R = 0.1904370395
d(pro) = 32.5 in
M= 172.10711 k-ft
dreqd = 30.062403 in >< 32.5
M1 = 201.14912 k-ft
M2 = -29.04201 k-ft
As1 = 3.0737673 sq-in
As2 = -0.430252 sq-in as no. of bar
As=As1+As2= 2.6435153 sq-in 0.48 5.5073234883 nos.
f's = 18.795546 ksi
As2 = -0.618062 sq-in
V = 77.938235 kip
Vd = 30.144118 kip
vd = 77.292609 psi > 60.2494813256 psi
av = 0.11 sq-in
Stirrup = 29.043964 in. c/c

DESIGN OF COMBIND FOOTING - F11 (WSD)


DESIGN OF FOOTING BEAM - FB3

w= 23.076923 k/ft fy = 60 ksi


L= 5 ft f'c = 3 ksi
Beam Size k = 0.3152581894
20 in j = 0.8949139369
18 in R = 0.1904370395
d(pro) = 14.5 in
M= 72.115385 k-ft
dreqd = 15.073492 in >< 14.5
M1 = 66.732313 k-ft
M2 = 5.383072 k-ft
As1 = 2.2856219 sq-in
As2 = 0.199373 sq-in as no. of bar
As=As1+As2= 2.4849949 sq-in 0.48 5.1770727315 nos.
f's = 11.264972 ksi
As2 = 0.4778593 sq-in
V = 57.692308 kip
Vd = 29.807692 kip
vd = 102.78515 psi > 60.2494813256 psi
av = 0.11 sq-in
Stirrup = 6.9823759 in. c/c

AT - A1,A10
DESIGN OF FOOTING - F1 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 205 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 4.5 ksf
Column Size = 10 in
= 18 in
Area of Found(reqd) = 47.833333 sq-ft
Footing Size(reqd) = 6.9161646 ft
Footing Size(prov.) = 6.75 ft
= 7.5 ft
Area of Found(prov) = 50.625 sq-ft > 47.83
Wu = 4.0493827 ksf
d (provided) = 17 in
V (punching) = 178.42593 kip
V (punching) = 84.64228 psi < 104.9 psi
M = 17.719564 k-ft/ft
dreq = 9.9446118 in
Vs = 6.2427984 kip/ft
v = 30.601953 psi < 57.68 psi
As = 0.5667126 sq-in/ft
as = 0.175 sq-in
Spacing of bar = 3.7055818 in. c/c 7 in. c/c
dia. of bar = 0.4721546 in 13 nos. bar
Peremeter of bar = 1.4825653 in
Bond Stress = 533.11805 psi
Ld (minimum) = 5.4799427 in < 32.5 in
M = 18.222222 k-ft/ft
dreq = 10.084677 in
Vs = 9.2798354 kip/ft
v = 45.489389 psi < 57.68 psi
As = 0.5827888 sq-in/ft
as = 0.175 sq-in
Spacing of bar = 3.6033638 in. c/c 7 in. c/c
dia. of bar = 0.4721546 in 11.71 nos. bar
Peremeter of bar = 1.4825653 in
Bond Stress = 845.45345 psi
Ld (minimum) = 0.4240829 in < 33 in
As (temp.) = 0.51 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 5.7058824 in. c/c

AT - A9, D10
DESIGN OF FOOTING - F2 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 155 kip
Column Load (L.L.) = 75 kip
Bearing Capacity = 3 ksf
Column Size = 12 in
= 20 in
Area of Found(reqd) = 80.5 sq-ft
Footing Size(reqd) = 8.9721792 ft
Footing Size(prov.) = 7.75 ft
= 10.25 ft
Area of Found(prov) = 79.4375 sq-ft > 80.5
Wu = 2.895358 ksf
d (provided) = 18 in
V (punching) = 207.07842 kip
V (punching) = 84.590856 psi < 104.9 psi
M = 16.489969 k-ft/ft
dreq = 9.5933707 in
Vs = 5.4287962 kip/ft
v = 25.133316 psi < 57.68 psi
As = 0.498088 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 5.842341 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 15.63 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 37.5 in
M = 26.663935 k-ft/ft
dreq = 12.198978 in
Vs = 10.254393 kip/ft
v = 47.474041 psi < 57.68 psi
As = 0.8053979 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.6131209 in. c/c 7 in. c/c
dia. of bar = 0.5558032 in 13.43 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 818.02987 psi
Ld (minimum) = 0.5923878 in < 48.5 in
As (temp.) = 0.54 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 5.3888889 in. c/c

AT - D1
DESIGN OF FOOTING - F3 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 190 kip
Column Load (L.L.) = 60 kip
Bearing Capacity = 3 ksf
Column Size = 12 in
= 20 in
Area of Found(reqd) = 87.5 sq-ft
Footing Size(reqd) = 9.3541435 ft
Footing Size(prov.) = 9 ft
= 9.75 ft
Area of Found(prov) = 87.75 sq-ft > 87.5
Wu = 2.8490028 ksf
d (provided) = 19 in
V (punching) = 226.08025 kip
V (punching) = 84.992574 psi < 104.9 psi
M = 22.792023 k-ft/ft
dreq = 11.278536 in
Vs = 6.8850902 kip/ft
v = 30.197764 psi < 57.68 psi
As = 0.6522109 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.4617472 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 14.88 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 45 in
M = 23.26933 k-ft/ft
dreq = 11.396021 in
Vs = 9.2592593 kip/ft
v = 40.610786 psi < 57.68 psi
As = 0.6658694 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.3702266 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 13.75 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 835.26101 psi
Ld (minimum) = 0.6737424 in < 45.5 in
As (temp.) = 0.57 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 5.1052632 in. c/c

AT - A2, A8
DESIGN OF FOOTING - F4 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 190 kip
Column Load (L.L.) = 70 kip
Bearing Capacity = 3 ksf
Column Size = 12 in
= 20 in
Area of Found(reqd) = 91 sq-ft
Footing Size(reqd) = 9.539392 ft
Footing Size(prov.) = 9.25 ft
= 10 ft
Area of Found(prov) = 92.5 sq-ft > 91
Wu = 2.8108108 ksf
d (provided) = 19 in
V (punching) = 236.4009 kip
V (punching) = 88.872519 psi < 104.9 psi
M = 23.913851 k-ft/ft
dreq = 11.552769 in
Vs = 7.1441441 kip/ft
v = 31.333966 psi < 57.68 psi
As = 0.6843128 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.252441 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 15.25 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 46.5 in
M = 24.399399 k-ft/ft
dreq = 11.669463 in
Vs = 9.4864865 kip/ft
v = 41.607397 psi < 57.68 psi
As = 0.6982072 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.1678175 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 14.13 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 843.49117 psi
Ld (minimum) = 0.685701 in < 47 in
As (temp.) = 0.57 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 5.1052632 in. c/c

AT - A3
DESIGN OF FOOTING - F5 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 200 kip
Column Load (L.L.) = 60 kip
Bearing Capacity = 3 ksf
Column Size = 12 in
= 25 in
Area of Found(reqd) = 91 sq-ft
Footing Size(reqd) = 9.539392 ft
Footing Size(prov.) = 9 ft
= 10 ft
Area of Found(prov) = 90 sq-ft > 91
Wu = 2.8888889 ksf
d (provided) = 19 in
V (punching) = 232.6358 kip
V (punching) = 81.626597 psi < 104.9 psi
M = 23.111111 k-ft/ft
dreq = 11.357212 in
Vs = 6.9814815 kip/ft
v = 30.620533 psi < 57.68 psi
As = 0.6613418 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.4001451 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 15.25 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 45 in
M = 22.632137 k-ft/ft
dreq = 11.238908 in
Vs = 9.1481481 kip/ft
v = 40.123457 psi < 57.68 psi
As = 0.6476356 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.4932673 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 13.75 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 843.49117 psi
Ld (minimum) = 0.6671685 in < 44.5 in
As (temp.) = 0.57 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 5.1052632 in. c/c
AT - B10
DESIGN OF FOOTING - F6 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 290 kip
Column Load (L.L.) = 60 kip
Bearing Capacity = 3 ksf
Column Size = 12 in
= 25 in
Area of Found(reqd) = 122.5 sq-ft
Footing Size(reqd) = 11.067972 ft
Footing Size(prov.) = 10.5 ft
= 11.75 ft
Area of Found(prov) = 123.375 sq-ft > 122.5
Wu = 2.8368794 ksf
d (provided) = 22 in
V (punching) = 318.51852 kip
V (punching) = 89.371077 psi < 104.9 psi
M = 32.003546 k-ft/ft
dreq = 13.364735 in
Vs = 8.2742317 kip/ft
v = 31.341787 psi < 57.68 psi
As = 0.790923 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 4.7033658 in. c/c 8.5 in. c/c
dia. of bar = 0.6284142 in 16.88 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 400.55445 psi
Ld (minimum) = 9.7073271 in < 54 in
M = 33.136328 k-ft/ft
dreq = 13.599204 in
Vs = 11.111111 kip/ft
v = 42.087542 psi < 57.68 psi
As = 0.8189181 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 4.5425789 in. c/c 8.5 in. c/c
dia. of bar = 0.6284142 in 15.12 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 803.58023 psi
Ld (minimum) = 0.9237588 in < 55 in
As (temp.) = 0.66 sq-in/ft
ast = 0.31 sq-in
Spacing of temp. bar= 5.6363636 in. c/c

AT - B1
DESIGN OF FOOTING - F7 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 250 kip
Column Load (L.L.) = 70 kip
Bearing Capacity = 3 ksf
Column Size = 15 in
= 18 in
Area of Found(reqd) = 112 sq-ft
Footing Size(reqd) = 10.583005 ft
Footing Size(prov.) = 10.5 ft
= 10.75 ft
Area of Found(prov) = 112.875 sq-ft > 112
Wu = 2.8349945 ksf
d (provided) = 22 in
V (punching) = 290.86256 kip
V (punching) = 85.850814 psi < 104.9 psi
M = 30.321152 k-ft/ft
dreq = 13.008708 in
Vs = 7.9143595 kip/ft
v = 29.978635 psi < 57.68 psi
As = 0.7493449 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 4.9643359 in. c/c 8.5 in. c/c
dia. of bar = 0.6284142 in 15.47 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 400.55445 psi
Ld (minimum) = 9.7073271 in < 52.5 in
M = 30.321152 k-ft/ft
dreq = 13.008708 in
Vs = 10.513104 kip/ft
v = 39.822365 psi < 57.68 psi
As = 0.7667716 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 4.8515101 in. c/c 8.5 in. c/c
dia. of bar = 0.6284142 in 15.12 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 785.77775 psi
Ld (minimum) = 0.9446874 in < 52.5 in
As (temp.) = 0.66 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 4.4090909 in. c/c

AT - D9
DESIGN OF FOOTING - F8 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 300 kip
Column Load (L.L.) = 70 kip
Bearing Capacity = 3 ksf
Column Size = 15 in
= 18 in
Area of Found(reqd) = 129.5 sq-ft
Footing Size(reqd) = 11.379807 ft
Footing Size(prov.) = 11.25 ft
= 11.5 ft
Area of Found(prov) = 129.375 sq-ft > 129.5
Wu = 2.8599034 ksf
d (provided) = 24 in
V (punching) = 337.4686 kip
V (punching) = 86.797479 psi < 104.9 psi
M = 35.748792 k-ft/ft
dreq = 14.125115 in
Vs = 8.5797101 kip/ft
v = 29.79066 psi < 57.68 psi
As = 0.809858 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 4.5933976 in. c/c 8 in. c/c
dia. of bar = 0.6284142 in 17.5 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 400.55445 psi
Ld (minimum) = 9.7073271 in < 57 in
M = 35.748792 k-ft/ft
dreq = 14.125115 in
Vs = 11.439614 kip/ft
v = 39.72088 psi < 57.68 psi
As = 0.8270891 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 4.4977019 in. c/c 8 in. c/c
dia. of bar = 0.6284142 in 17.13 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 814.82184 psi
Ld (minimum) = 0.9760867 in < 57 in
As (temp.) = 0.72 sq-in/ft
ast = 0.31 sq-in
Spacing of temp. bar= 5.1666667 in. c/c

AT - D9
DESIGN OF FOOTING - F9 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 425 kip
Column Load (L.L.) = 75 kip
Bearing Capacity = 3 ksf
Column Size = 15 in
= 25 in
Area of Found(reqd) = 175 sq-ft
Footing Size(reqd) = 13.228757 ft
Footing Size(prov.) = 12.75 ft
= 13.5 ft
Area of Found(prov) = 172.125 sq-ft > 175
Wu = 2.9048656 ksf
d (provided) = 27 in
V (punching) = 455.94287 kip
V (punching) = 89.823261 psi < 104.9 psi
M = 48.02106 k-ft/ft
dreq = 16.371074 in
Vs = 10.16703 kip/ft
v = 31.379722 psi < 57.68 psi
As = 0.9670006 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 3.8469469 in. c/c 7.5 in. c/c
dia. of bar = 0.6284142 in 21.8 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 400.55445 psi
Ld (minimum) = 9.7073271 in < 66 in
M = 47.327624 k-ft/ft
dreq = 16.252444 in
Vs = 13.313968 kip/ft
v = 41.092492 psi < 57.68 psi
As = 0.9530369 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 3.9033117 in. c/c 7.5 in. c/c
dia. of bar = 0.6284142 in 20.6 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 878.52623 psi
Ld (minimum) = 1.0260157 in < 65.5 in
As (temp.) = 0.81 sq-in/ft
ast = 0.31 sq-in
Spacing of temp. bar= 4.5925926 in. c/c

AT - D9
DESIGN OF FOOTING - F10 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 550 kip
Column Load (L.L.) = 90 kip
Bearing Capacity = 3 ksf
Column Size = 22 in
= 22 in
Area of Found(reqd) = 224 sq-ft
Footing Size(reqd) = 14.96663 ft
Footing Size(prov.) = 15 ft
= 15 ft
Area of Found(prov) = 225 sq-ft > 224
Wu = 2.8444444 ksf
d (provided) = 30 in
V (punching) = 586.58765 kip
V (punching) = 94.004432 psi < 104.9 psi
M = 61.639506 k-ft/ft
dreq = 18.547735 in
Vs = 11.614815 kip/ft
v = 32.263374 psi < 57.68 psi
As = 1.1171119 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 3.3300157 in. c/c 6.5 in. c/c
dia. of bar = 0.6284142 in 27.77 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 400.55445 psi
Ld (minimum) = 9.7073271 in < 76 in
M = 61.639506 k-ft/ft
dreq = 18.547735 in
Vs = 15.17037 kip/ft
v = 42.139918 psi < 57.68 psi
As = 1.1171119 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 3.3300157 in. c/c 6.5 in. c/c
dia. of bar = 0.6284142 in 27.77 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 934.45249 psi
Ld (minimum) = 1.1348346 in < 76 in
As (temp.) = 0.9 sq-in/ft
ast = 0.31 sq-in
Spacing of temp. bar= 4.1333333 in. c/c

AT - D9
DESIGN OF FOOTING - F11 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 635 kip
Column Load (L.L.) = 100 kip
Bearing Capacity = 3 ksf
Column Size = 12 in
= 42 in
Area of Found(reqd) = 257.25 sq-ft
Footing Size(reqd) = 16.039015 ft
Footing Size(prov.) = 14.75 ft
= 17.25 ft
Area of Found(prov) = 254.4375 sq-ft > 257.3
Wu = 2.8887251 ksf
d (provided) = 32 in
V (punching) = 669.68272 kip
V (punching) = 88.676207 psi < 104.9 psi
M = 68.268699 k-ft/ft
dreq = 19.519654 in
Vs = 12.156718 kip/ft
v = 31.65812 psi < 57.68 psi
As = 1.1599264 sq-in/ft
as = 0.395 sq-in
Spacing of bar = 4.0864663 in. c/c 7.5 in. c/c
dia. of bar = 0.7093551 in 27.8 nos. bar
Peremeter of bar = 2.2273751 in
Bond Stress = 354.84923 psi
Ld (minimum) = 12.369014 in < 79.5 in
M = 68.268699 k-ft/ft
dreq = 19.519654 in
Vs = 16.008352 kip/ft
v = 41.688416 psi < 57.68 psi
As = 1.1599264 sq-in/ft
as = 0.395 sq-in
Spacing of bar = 4.0864663 in. c/c 7.5 in. c/c
dia. of bar = 0.7093551 in 23.8 nos. bar
Peremeter of bar = 2.2273751 in
Bond Stress = 856.97147 psi
Ld (minimum) = 1.3735419 in < 79.5 in
As (temp.) = 0.96 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 3.03125 in. c/c

AT - D9
DESIGN OF FOOTING - F12 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 160 kip
Column Load (L.L.) = 70 kip
Bearing Capacity = 3 ksf
Column Size = 20 in
= 12 in
Area of Found(reqd) = 80.5 sq-ft
Footing Size(reqd) = 8.9721792 ft
Footing Size(prov.) = 8.5 ft
= 9.25 ft
Area of Found(prov) = 78.625 sq-ft > 80.5
Wu = 2.9252782 ksf
d (provided) = 18 in
V (punching) = 206.84155 kip
V (punching) = 84.494096 psi < 104.9 psi
M = 17.07428 k-ft/ft
dreq = 9.7618586 in
Vs = 5.6067833 kip/ft
v = 25.95733 psi < 57.68 psi
As = 0.5157374 sq-in/ft
as = 0.175 sq-in
Spacing of bar = 4.0718393 in. c/c 7.5 in. c/c
dia. of bar = 0.4721546 in 15 nos. bar
Peremeter of bar = 1.4825653 in
Bond Stress = 533.11805 psi
Ld (minimum) = 5.4799427 in < 38 in
M = 24.887719 k-ft/ft
dreq = 11.785659 in
Vs = 9.872814 kip/ft
v = 45.707472 psi < 57.68 psi
As = 0.7517464 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.8709864 in. c/c 7.5 in. c/c
dia. of bar = 0.5558032 in 13.8 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 818.02987 psi
Ld (minimum) = 0.6497156 in < 46.5 in
As (temp.) = 0.54 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 5.3888889 in. c/c

AT - D9
DESIGN OF FOOTING - F13 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 340 kip
Column Load (L.L.) = 60 kip
Bearing Capacity = 3 ksf
Column Size = 15 in
= 18 in
Area of Found(reqd) = 140 sq-ft
Footing Size(reqd) = 11.83216 ft
Footing Size(prov.) = 9 ft
= 15.5 ft
Area of Found(prov) = 139.5 sq-ft > 140
Wu = 2.8673835 ksf
d (provided) = 26 in
V (punching) = 364.07806 kip
V (punching) = 82.370601 psi < 104.9 psi
M = 21.527778 k-ft/ft
dreq = 10.961271 in
Vs = 4.8984468 kip/ft
v = 15.70015 psi < 57.68 psi
As = 0.4501784 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 8.2633914 in. c/c 8.5 in. c/c
dia. of bar = 0.6284142 in 22.18 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 400.55445 psi
Ld (minimum) = 9.7073271 in < 43.5 in
M = 70.250896 k-ft/ft
dreq = 19.801006 in
Vs = 16.965352 kip/ft
v = 54.37613 psi < 57.68 psi
As = 1.4690524 sq-in/ft
as = 0.48 sq-in
Spacing of bar = 3.9208949 in. c/c 7.5 in. c/c
dia. of bar = 0.7819623 in 14.6 nos. bar
Peremeter of bar = 2.4553615 in
Bond Stress = 667.70935 psi
Ld (minimum) = 1.1857506 in < 81 in
As (temp.) = 0.78 sq-in/ft
ast = 0.31 sq-in
Spacing of temp. bar= 4.7692308 in. c/c

AT - D9
DESIGN OF FOOTING - F14 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 375 kip
Column Load (L.L.) = 60 kip
Bearing Capacity = 3 ksf
Column Size = 20 in
= 15 in
Area of Found(reqd) = 152.25 sq-ft
Footing Size(reqd) = 12.338963 ft
Footing Size(prov.) = 9 ft
= 16.5 ft
Area of Found(prov) = 148.5 sq-ft > 152.3
Wu = 2.9292929 ksf
d (provided) = 27 in
V (punching) = 394.84428 kip
V (punching) = 82.156529 psi < 104.9 psi
M = 19.691358 k-ft/ft
dreq = 10.483327 in
Vs = 4.1498316 kip/ft
v = 12.808122 psi < 57.68 psi
As = 0.3965251 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 9.3814997 in. c/c 7.5 in. c/c
dia. of bar = 0.6284142 in 26.6 nos. bar
Peremeter of bar = 1.9732207 in
Bond Stress = 400.55445 psi
Ld (minimum) = 9.7073271 in < 41 in
M = 85.155461 k-ft/ft
dreq = 21.800556 in
Vs = 19.040404 kip/ft
v = 58.766679 psi < 57.68 psi
As = 1.7471307 sq-in/ft
as = 0.48 sq-in
Spacing of bar = 3.2968341 in. c/c 6.5 in. c/c
dia. of bar = 0.7819623 in 16.69 nos. bar
Peremeter of bar = 2.4553615 in
Bond Stress = 681.85931 psi
Ld (minimum) = 1.1611439 in < 88.5 in
As (temp.) = 0.81 sq-in/ft
ast = 0.31 sq-in
Spacing of temp. bar= 4.5925926 in. c/c

AT - D9
DESIGN OF FOOTING - F15 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 480 kip
Column Load (L.L.) = 80 kip
Bearing Capacity = 3 ksf
Column Size = 27 in
= 15 in
Area of Found(reqd) = 196 sq-ft
Footing Size(reqd) = 14 ft
Footing Size(prov.) = 12.5 ft
= 15.75 ft
Area of Found(prov) = 196.875 sq-ft > 196
Wu = 2.8444444 ksf
d (provided) = 29 in
V (punching) = 511.3284 kip
V (punching) = 88.160068 psi < 104.9 psi
M = 37.355556 k-ft/ft
dreq = 14.43906 in
Vs = 7.7037037 kip/ft
v = 22.13708 psi < 57.68 psi
As = 0.7003513 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.1550574 in. c/c 6.5 in. c/c
dia. of bar = 0.5558032 in 29.15 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 58.5 in
M = 74.755556 k-ft/ft
dreq = 20.425987 in
Vs = 17.185185 kip/ft
v = 49.382716 psi < 57.68 psi
As = 1.4015359 sq-in/ft
as = 0.395 sq-in
Spacing of bar = 3.3820039 in. c/c 6.5 in. c/c
dia. of bar = 0.7093551 in 23.15 nos. bar
Peremeter of bar = 2.2273751 in
Bond Stress = 800.64784 psi
Ld (minimum) = 1.2459044 in < 84 in
As (temp.) = 0.87 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 3.3448276 in. c/c

AT - D9
DESIGN OF FOOTING - F16 (WSD)
f'c = 2.75 ksi.
fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 200 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 10 in
= 20 in
Area of Found(reqd) = 56 sq-ft
Footing Size(reqd) = 7.4833148 ft
Footing Size(prov.) = 7.25 ft
= 8 ft
Area of Found(prov) = 58 sq-ft > 56
Wu = 3.4482759 ksf
d (provided) = 16 in
V (punching) = 177.58621 kip
V (punching) = 89.509177 psi < 104.9 psi
M = 17.747246 k-ft/ft
dreq = 9.9523765 in
Vs = 6.4655172 kip/ft
v = 33.674569 psi < 57.68 psi
As = 0.6030728 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.8252879 in. c/c 9 in. c/c
dia. of bar = 0.5558032 in 11 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 35.5 in
M = 17.289272 k-ft/ft
dreq = 9.8231249 in
Vs = 8.6206897 kip/ft
v = 44.899425 psi < 57.68 psi
As = 0.5875103 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.9531046 in. c/c 9 in. c/c
dia. of bar = 0.5558032 in 10 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 747.08016 psi
Ld (minimum) = 0.6067983 in < 35 in
As (temp.) = 0.48 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 6.0625 in. c/c
AT - D9
DESIGN OF FOOTING - F17 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 230 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 10 in
= 20 in
Area of Found(reqd) = 64.4 sq-ft
Footing Size(reqd) = 8.0249611 ft
Footing Size(prov.) = 7.75 ft
= 8.5 ft
Area of Found(prov) = 65.875 sq-ft > 64.4
Wu = 3.4914611 ksf
d (provided) = 18 in
V (punching) = 204.20198 kip
V (punching) = 85.943595 psi < 104.9 psi
M = 20.879059 k-ft/ft
dreq = 10.794854 in
Vs = 6.8374447 kip/ft
v = 31.654836 psi < 57.68 psi
As = 0.6306627 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.6141936 in. c/c 8.5 in. c/c
dia. of bar = 0.5558032 in 12.29 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 38.5 in
M = 20.37898 k-ft/ft
dreq = 10.664795 in
Vs = 9.3105629 kip/ft
v = 43.104458 psi < 57.68 psi
As = 0.6155576 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.7274212 in. c/c 8.5 in. c/c
dia. of bar = 0.5558032 in 11.24 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 773.64489 psi
Ld (minimum) = 0.6263738 in < 38 in
As (temp.) = 0.54 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 5.3888889 in. c/c

AT - D9
DESIGN OF FOOTING - F18 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 285 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 10 in
= 25 in
Area of Found(reqd) = 79.8 sq-ft
Footing Size(reqd) = 8.9330846 ft
Footing Size(prov.) = 8.25 ft
= 9.5 ft
Area of Found(prov) = 78.375 sq-ft > 79.8
Wu = 3.6363636 ksf
d (provided) = 20 in
V (punching) = 250.90909 kip
V (punching) = 83.636364 psi < 104.9 psi
M = 25.003157 k-ft/ft
dreq = 11.81296 in
Vs = 7.4242424 kip/ft
v = 30.934343 psi < 57.68 psi
As = 0.6797099 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.2812381 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 14.5 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 41.5 in
M = 25.003157 k-ft/ft
dreq = 11.81296 in
Vs = 10.454545 kip/ft
v = 43.560606 psi < 57.68 psi
As = 0.6797099 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.2812381 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 12.63 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 816.24572 psi
Ld (minimum) = 0.6319847 in < 41.5 in
As (temp.) = 0.6 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 4.85 in. c/c

AT - D9
DESIGN OF FOOTING - F19 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 315 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 10 in
= 25 in
Area of Found(reqd) = 88.2 sq-ft
Footing Size(reqd) = 9.3914855 ft
Footing Size(prov.) = 8.75 ft
= 10 ft
Area of Found(prov) = 87.5 sq-ft > 88.2
Wu = 3.6 ksf
d (provided) = 21 in
V (punching) = 279.35 kip
V (punching) = 86.379097 psi < 104.9 psi
M = 28.203125 k-ft/ft
dreq = 12.546134 in
Vs = 7.95 kip/ft
v = 31.547619 psi < 57.68 psi
As = 0.7301914 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.9852566 in. c/c 7.5 in. c/c
dia. of bar = 0.5558032 in 16.2 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 44.5 in
M = 28.203125 k-ft/ft
dreq = 12.546134 in
Vs = 11.1 kip/ft
v = 44.047619 psi < 57.68 psi
As = 0.7301914 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.9852566 in. c/c 7.5 in. c/c
dia. of bar = 0.5558032 in 14.2 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 836.92654 psi
Ld (minimum) = 0.6537238 in < 44.5 in
As (temp.) = 0.63 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 4.6190476 in. c/c

AT - D9
DESIGN OF FOOTING - F20 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 335 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 15 in
= 15 in
Area of Found(reqd) = 93.8 sq-ft
Footing Size(reqd) = 9.68504 ft
Footing Size(prov.) = 9.75 ft
= 9.75 ft
Area of Found(prov) = 95.0625 sq-ft > 93.8
Wu = 3.5239974 ksf
d (provided) = 22 in
V (punching) = 301.49755 kip
V (punching) = 92.597528 psi < 104.9 psi
M = 31.826101 k-ft/ft
dreq = 13.327633 in
Vs = 8.516327 kip/ft
v = 32.258814 psi < 57.68 psi
As = 0.7865377 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.6997593 in. c/c 7 in. c/c
dia. of bar = 0.5558032 in 16.86 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 48 in
M = 31.826101 k-ft/ft
dreq = 13.327633 in
Vs = 11.746658 kip/ft
v = 44.494916 psi < 57.68 psi
As = 0.7865377 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.6997593 in. c/c 7 in. c/c
dia. of bar = 0.5558032 in 16.86 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 849.90602 psi
Ld (minimum) = 0.7173106 in < 48 in
As (temp.) = 0.66 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 4.4090909 in. c/c

AT - D9
DESIGN OF FOOTING - F21 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 200 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 20 in
= 10 in
Area of Found(reqd) = 56 sq-ft
Footing Size(reqd) = 7.4833148 ft
Footing Size(prov.) = 7.25 ft
= 8 ft
Area of Found(prov) = 58 sq-ft > 56
Wu = 3.4482759 ksf
d (provided) = 16 in
V (punching) = 177.58621 kip
V (punching) = 89.509177 psi < 104.9 psi
M = 13.436901 k-ft/ft
dreq = 8.6598601 in
Vs = 5.0287356 kip/ft
v = 26.191331 psi < 57.68 psi
As = 0.4566021 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 6.3731638 in. c/c 10 in. c/c
dia. of bar = 0.5558032 in 10 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 30.5 in
M = 22.13841 k-ft/ft
dreq = 11.115641 in
Vs = 10.057471 kip/ft
v = 52.382663 psi < 57.68 psi
As = 0.7522899 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.8681899 in. c/c 7.5 in. c/c
dia. of bar = 0.5558032 in 11.8 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 747.08016 psi
Ld (minimum) = 0.6067983 in < 40 in
As (temp.) = 0.48 sq-in/ft
ast = 0.175 sq-in
Spacing of temp. bar= 4.375 in. c/c

AT - D9
DESIGN OF FOOTING - F22 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 315 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 10 in
= 25 in
Area of Found(reqd) = 88.2 sq-ft
Footing Size(reqd) = 9.3914855 ft
Footing Size(prov.) = 9.5 ft
= 9.5 ft
Area of Found(prov) = 90.25 sq-ft > 88.2
Wu = 3.4903047 ksf
d (provided) = 21 in
V (punching) = 280.43629 kip
V (punching) = 86.714993 psi < 104.9 psi
M = 32.770083 k-ft/ft
dreq = 13.523842 in
Vs = 9.0166205 kip/ft
v = 35.78024 psi < 57.68 psi
As = 0.8484319 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.4298567 in. c/c 6.5 in. c/c
dia. of bar = 0.5558032 in 17.62 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 49 in
M = 23.998875 k-ft/ft
dreq = 11.573288 in
Vs = 9.8891967 kip/ft
v = 39.242844 psi < 57.68 psi
As = 0.6213415 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.683415 in. c/c 7.5 in. c/c
dia. of bar = 0.5558032 in 15.4 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 836.92654 psi
Ld (minimum) = 0.7097572 in < 41.5 in
As (temp.) = 0.63 sq-in/ft
ast = 0.175 sq-in
Spacing of temp. bar= 3.3333333 in. c/c

Bond Stress = 452.88354 psi


Ld (minimum) = 7.5936349 in < 43 in
M = 25.709737 k-ft/ft
dreq = 11.978712 in
Vs = 10.351936 kip/ft
v = 41.07911 psi < 57.68 psi
As = 0.6656365 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.3717557 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 13 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 819.80243 psi
Ld (minimum) = 0.6483108 in < 43 in
As (temp.) = 0.63 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 4.6190476 in. c/c

AT - D9
DESIGN OF FOOTING - F12 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 310 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 10 in
= 25 in
Area of Found(reqd) = 86.8 sq-ft
Footing Size(reqd) = 9.3166518 ft
Footing Size(prov.) = 8.75 ft
= 10 ft
Area of Found(prov) = 87.5 sq-ft > 86.8
Wu = 3.5428571 ksf
d (provided) = 21 in
V (punching) = 274.91587 kip
V (punching) = 85.008 psi < 104.9 psi
M = 27.755456 k-ft/ft
dreq = 12.446163 in
Vs = 7.8238095 kip/ft
v = 31.046863 psi < 57.68 psi
As = 0.718601 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.0495349 in. c/c 7.5 in. c/c
dia. of bar = 0.5558032 in 16.2 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 44.5 in
M = 27.755456 k-ft/ft
dreq = 12.446163 in
Vs = 10.92381 kip/ft
v = 43.34845 psi < 57.68 psi
As = 0.718601 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.0495349 in. c/c 7.5 in. c/c
dia. of bar = 0.5558032 in 14.2 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 833.58545 psi
Ld (minimum) = 0.656344 in < 44.5 in
As (temp.) = 0.63 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 4.6190476 in. c/c

AT - D9
DESIGN OF FOOTING - F13 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 370 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 10 in
= 25 in
Area of Found(reqd) = 103.6 sq-ft
Footing Size(reqd) = 10.178409 ft
Footing Size(prov.) = 9.5 ft
= 10.75 ft
Area of Found(prov) = 102.125 sq-ft > 103.6
Wu = 3.623011 ksf
d (provided) = 24 in
V (punching) = 328.08378 kip
V (punching) = 82.350345 psi < 104.9 psi
M = 34.016048 k-ft/ft
dreq = 13.778541 in
Vs = 8.4536924 kip/ft
v = 29.353099 psi < 57.68 psi
As = 0.7706042 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.7762576 in. c/c 7 in. c/c
dia. of bar = 0.5558032 in 18.57 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 49 in
M = 34.016048 k-ft/ft
dreq = 13.778541 in
Vs = 12.076703 kip/ft
v = 41.932998 psi < 57.68 psi
As = 0.7706042 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.7762576 in. c/c 7 in. c/c
dia. of bar = 0.5558032 in 16.43 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 871.28479 psi
Ld (minimum) = 0.6817687 in < 49 in
As (temp.) = 0.72 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 4.0416667 in. c/c

AT - D9
DESIGN OF FOOTING - F14 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 140 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 20 in
= 10 in
Area of Found(reqd) = 39.2 sq-ft
Footing Size(reqd) = 6.2609903 ft
Footing Size(prov.) = 5 ft
= 8.5 ft
Area of Found(prov) = 42.5 sq-ft > 39.2
Wu = 3.2941176 ksf
d (provided) = 16 in
V (punching) = 118.58824 kip
V (punching) = 59.772296 psi < 104.9 psi
M = 4.5751634 k-ft/ft
dreq = 5.0531782 in
Vs = 1.0980392 kip/ft
v = 5.7189542 psi < 57.68 psi
As = 0.1554696 sq-in/ft
as = 0.175 sq-in
Spacing of bar = 13.507467 in. c/c 3.75 in. c/c
dia. of bar = 0.4721546 in 26.6 nos. bar
Peremeter of bar = 1.4825653 in
Bond Stress = 533.11805 psi
Ld (minimum) = 5.4799427 in < 17 in
M = 24.202614 k-ft/ft
dreq = 11.62231 in
Vs = 10.431373 kip/ft
v = 54.330065 psi < 57.68 psi
As = 0.822434 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.5382778 in. c/c 7 in. c/c
dia. of bar = 0.5558032 in 8.714 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 683.34766 psi
Ld (minimum) = 0.4575113 in < 43 in
As (temp.) = 0.48 sq-in/ft
ast = 0.175 sq-in
Spacing of temp. bar= 4.375 in. c/c

AT - D9
DESIGN OF FOOTING - F15 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 180 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 20 in
= 10 in
Area of Found(reqd) = 50.4 sq-ft
Footing Size(reqd) = 7.0992957 ft
Footing Size(prov.) = 6 ft
= 8.5 ft
Area of Found(prov) = 51 sq-ft > 50.4
Wu = 3.5294118 ksf
d (provided) = 17 in
V (punching) = 155.51471 kip
V (punching) = 71.468155 psi < 104.9 psi
M = 8.2843137 k-ft/ft
dreq = 6.7996973 in
Vs = 2.6470588 kip/ft
v = 12.975779 psi < 57.68 psi
As = 0.2649515 sq-in/ft
as = 0.175 sq-in
Spacing of bar = 7.9259789 in. c/c 7.5 in. c/c
dia. of bar = 0.4721546 in 13.8 nos. bar
Peremeter of bar = 1.4825653 in
Bond Stress = 533.11805 psi
Ld (minimum) = 5.4799427 in < 23 in
M = 25.931373 k-ft/ft
dreq = 12.030234 in
Vs = 11.029412 kip/ft
v = 54.065744 psi < 57.68 psi
As = 0.8293452 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.5087921 in. c/c 6.75 in. c/c
dia. of bar = 0.5558032 in 10.78 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 727.65887 psi
Ld (minimum) = 0.5155811 in < 43 in
As (temp.) = 0.51 sq-in/ft
ast = 0.175 sq-in
Spacing of temp. bar= 4.1176471 in. c/c

AT - D9
DESIGN OF FOOTING - F16 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 215 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 20 in
= 10 in
Area of Found(reqd) = 60.2 sq-ft
Footing Size(reqd) = 7.7588659 ft
Footing Size(prov.) = 6.75 ft
= 9 ft
Area of Found(prov) = 60.75 sq-ft > 60.2
Wu = 3.5390947 ksf
d (provided) = 18 in
V (punching) = 188.85002 kip
V (punching) = 79.482333 psi < 104.9 psi
M = 11.431399 k-ft/ft
dreq = 7.9875023 in
Vs = 3.6865569 kip/ft
v = 17.067393 psi < 57.68 psi
As = 0.3452913 sq-in/ft
as = 0.175 sq-in
Spacing of bar = 6.0818215 in. c/c 3.5 in. c/c
dia. of bar = 0.4721546 in 30.14 nos. bar
Peremeter of bar = 1.4825653 in
Bond Stress = 533.11805 psi
Ld (minimum) = 5.4799427 in < 27.5 in
M = 29.504744 k-ft/ft
dreq = 12.832381 in
Vs = 11.796982 kip/ft
v = 54.615658 psi < 57.68 psi
As = 0.891206 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.2652383 in. c/c 6.5 in. c/c
dia. of bar = 0.5558032 in 12.54 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 760.71034 psi
Ld (minimum) = 0.5548276 in < 46 in
As (temp.) = 0.54 sq-in/ft
ast = 0.175 sq-in
Spacing of temp. bar= 3.8888889 in. c/c

AT - D9
DESIGN OF FOOTING - F17 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 220 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 20 in
= 10 in
Area of Found(reqd) = 61.6 sq-ft
Footing Size(reqd) = 7.8485667 ft
Footing Size(prov.) = 7.5 ft
= 8.25 ft
Area of Found(prov) = 61.875 sq-ft > 61.6
Wu = 3.5555556 ksf
d (provided) = 18 in
V (punching) = 193.7284 kip
V (punching) = 81.53552 psi < 104.9 psi
M = 15.123457 k-ft/ft
dreq = 9.1872778 in
Vs = 5.037037 kip/ft
v = 23.319616 psi < 57.68 psi
As = 0.4568118 sq-in/ft
as = 0.175 sq-in
Spacing of bar = 4.597079 in. c/c 7.5 in. c/c
dia. of bar = 0.4721546 in 13.4 nos. bar
Peremeter of bar = 1.4825653 in
Bond Stress = 533.11805 psi
Ld (minimum) = 5.4799427 in < 32 in
M = 24.447531 k-ft/ft
dreq = 11.680967 in
Vs = 10.518519 kip/ft
v = 48.696845 psi < 57.68 psi
As = 0.7384503 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 3.9406851 in. c/c 7 in. c/c
dia. of bar = 0.5558032 in 13 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 765.09502 psi
Ld (minimum) = 0.6129421 in < 41.5 in
As (temp.) = 0.54 sq-in/ft
ast = 0.175 sq-in
Spacing of temp. bar= 3.8888889 in. c/c

AT - D9
DESIGN OF FOOTING - F18 (WSD)

f'c = 2.75 ksi.


fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load (D.L.) = 260 kip
Column Load (L.L.) = 0 kip
Bearing Capacity = 3.75 ksf
Column Size = 20 in
= 10 in
Area of Found(reqd) = 72.8 sq-ft
Footing Size(reqd) = 8.5322916 ft
Footing Size(prov.) = 6.5 ft
= 11.5 ft
Area of Found(prov) = 74.75 sq-ft > 72.8
Wu = 3.4782609 ksf
d (provided) = 21 in
V (punching) = 229.29952 kip
V (punching) = 75.82656 psi < 104.9 psi
M = 10.157005 k-ft/ft
dreq = 7.5291187 in
Vs = 2.3188406 kip/ft
v = 9.2017483 psi < 57.68 psi
As = 0.2629693 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 11.065929 in. c/c 8 in. c/c
dia. of bar = 0.5558032 in 17.5 nos. bar
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 26 in
M = 49.468599 k-ft/ft
dreq = 16.615986 in
Vs = 15.507246 kip/ft
v = 61.536692 psi < 57.68 psi
As = 1.2807639 sq-in/ft
as = 0.395 sq-in
Spacing of bar = 3.7009163 in. c/c 7 in. c/c
dia. of bar = 0.7093551 in 11.29 nos. bar
Peremeter of bar = 2.2273751 in
Bond Stress = 625.04367 psi
Ld (minimum) = 0.8298875 in < 61 in
As (temp.) = 0.63 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 4.6190476 in. c/c
DESIGN OF COMBIND FOOTING - F19 (WSD)
FOR 2 NOS. COLUMN(eq. load)
f'c = 2.75 ksi.
fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load = 230 kip
Column Load = 230 kip
Column C/C = 6.833 ft
Bearing Capacity = 3.75 ksf
Column Size = 10 in
= 20 in
Area of Found(reqd) = 128.8 sq-ft
Footing Size(reqd) = 11.349009 ft
Footing Size(prov.) = 8.75 ft
= 15 ft
Area of Found(prov) = 131.25 sq-ft > 128.8
Wu = 3.5047619 ksf
d (provided) = 19 in
V (punching) = 216.23651 kip
V (punching) = 83.682859 psi < 104.9 psi
M = 21.98082 k-ft/ft
dreq = 11.076008 in < 16 in
Vs = 8.3238095 kip/ft
v = 36.507937 psi < 57.68 psi
As = 0.6289977 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.626408 in. c/c
dia. of bar = 0.5558032 in
Peremeter of bar = 1.745222 in
Bond Stress = 452.88354 psi
Ld (minimum) = 7.5936349 in < 44.5 in
M = 23.56193 k-ft/ft
dreq = 11.467447 in < 15.5 in
Vs = 20.590476 kip/ft
v = 90.309106 psi < 57.68 psi
As = 0.6742424 sq-in/ft
as = 0.2425 sq-in
Spacing of bar = 4.3159555 in. c/c
dia. of bar = 0.5558032 in
Peremeter of bar = 1.745222 in
Bond Stress = 920.02401 psi
Ld (minimum) = 0.5946788 in < 77 in
As (temp.) = 0.57 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 5.1052632 in. c/c
DESIGN OF COMBIND FOOTING - F10 (WSD)
DESIGN OF FOOTING BEAM - FB1

w = 30.666667 k/ft fy = 40 ksi


L = 6.833 ft f'c = 2.5 ksi
Beam Size = k = 0.3866666667
= 20 in j = 0.8711111111
= 24 in R = 0.1894666667
d(pro) = 20.5 in
M = 178.97791 k-ft
dreqd = 23.807233 in >< 20.5
M1 = 132.70561 k-ft
M2 = 46.272297 k-ft
As1 = 4.9541667 sq-in
As2 = 1.7137888 sq-in as no. of bar
As=As1+As2 = 6.6679554 sq-in 0.58 11.4964748865 nos.
f's = 15.537646 ksi
As2 = 1.9853843 sq-in
V = 104.77267 kip
Vd = 52.383778 kip
vd = 127.76531 psi > 55 psi
av = 0.11 sq-in
Stirrup = 2.7210768 in. c/c

Wu = 28.002765 ksf
d (provided) = 27 in
V (punching) = -734.3685 kip
V (punching) = -84.59556 psi < 846.1 psi
M = 0.010762 k-ft/ft
dreq = 0.0466081 in
Vs = -63.78258 kip/ft
v = -196.8598 psi < 465.4 psi
As = 9.649E-06 sq-in/ft
as = 0.48 sq-in
Spacing of bar = 596972 in. c/c 5 in. c/c
dia. of bar = 0.7819623 in 6.331 nos. bar
Peremeter of bar = 2.4553615 in
Bond Stress = 2596.8996 psi
Ld (minimum) = 0.8064772 in < -3.333 in
M = 126.43194 k-ft/ft
dreq = 5.0517645 in
Vs = -115.6511 kip/ft
v = -356.9479 psi < 465.4 psi
As = 0.1133527 sq-in/ft
as = 0.48 sq-in
Spacing of bar = 50.814855 in. c/c 5 in. c/c
dia. of bar = 0.7819623 in 0.064 nos. bar
Peremeter of bar = 2.4553615 in
Bond Stress = 2194.1278 psi
Ld (minimum) = 0.0044103 in < -39.06 in
As (temp.) = 0.81 sq-in/ft
ast = 0.48 sq-in
Spacing of temp. bar= 7.1111111 in. c/c

DESIGN OF COMBIND FOOTING - F20 (WSD)


FOR 2 NOS. COLUMN(eq. load)
f'c = 2.75 ksi.
fy = 55 ksi.
k = 0.3247244
j = 0.8917585
R = 0.179175
Column Load = 290 kip
Column Load = 290 kip
Column C/C = 6.833 ft
Bearing Capacity = 3.75 ksf
Column Size = 10 in
= 20 in
Area of Found(reqd) = 162.4 sq-ft
Footing Size(reqd) = 12.743626 ft
Footing Size(prov.) = 10.25 ft
= 16.25 ft
Area of Found(prov) = 166.5625 sq-ft > 162.4
Wu = 3.4821764 ksf
d (provided) = 21 in
V (punching) = 274.63248 kip
V (punching) = 90.817619 psi < 104.9 psi
M = 32.068063 k-ft/ft
dreq = 13.3782 in < 18 in
Vs = 10.301438 kip/ft
v = 40.878724 psi < 57.68 psi
As = 0.8302563 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 4.4805439 in. c/c
dia. of bar = 0.6284142 in
Peremeter of bar = 1.9732207 in
Bond Stress = 400.55445 psi
Ld (minimum) = 9.7073271 in < 53.5 in
M = 32.070554 k-ft/ft
dreq = 13.378719 in < 17.5 in
Vs = 22.343965 kip/ft
v = 88.666528 psi < 57.68 psi
As = 0.8303208 sq-in/ft
as = 0.31 sq-in
Spacing of bar = 4.4801959 in. c/c
dia. of bar = 0.6284142 in
Peremeter of bar = 1.9732207 in
Bond Stress = 862.26692 psi
Ld (minimum) = 0.8403896 in < 84.5 in
As (temp.) = 0.63 sq-in/ft
ast = 0.2425 sq-in
Spacing of temp. bar= 4.6190476 in. c/c

DESIGN OF COMBIND FOOTING - F10 (WSD)


DESIGN OF FOOTING BEAM - FB1

w = 35.692308 k/ft fy = 40 ksi


L = 6.833 ft f'c = 2.5 ksi
Beam Size = k = 0.3866666667
= 20 in j = 0.8711111111
= 24 in R = 0.1894666667
d(pro) = 20.5 in
M = 208.30874 k-ft
dreqd = 25.684018 in >< 20.5
M1 = 132.70561 k-ft
M2 = 75.603124 k-ft
As1 = 4.9541667 sq-in
As2 = 2.8001157 sq-in as no. of bar
As=As1+As2 = 7.7542824 sq-in 0.58 13.36945239 nos.
f's = 15.537646 ksi
As2 = 3.2438687 sq-in
V = 121.94277 kip
Vd = 60.96841 kip
vd = 148.70344 psi > 55 psi
av = 0.11 sq-in
Stirrup = 2.1130494 in. c/c

Wu = 45.40787 ksf
d (provided) = 27 in
V (punching) = -1409.894 kip
V (punching) = -145.7092 psi < 912.8 psi
M = 0.1458913 k-ft/ft
dreq = 0.1716048 in
Vs = -105.8077 kip/ft
v = -326.5668 psi < 502 psi
As = 7.42E-05 sq-in/ft
as = 0.48 sq-in
Spacing of bar = 77623.051 in. c/c 5 in. c/c
dia. of bar = 0.7819623 in 4.871 nos. bar
Peremeter of bar = 2.4553615 in
Bond Stress = 2801.6197 psi
Ld (minimum) = 0.8064772 in < -3.962 in
M = 367.71267 k-ft/ft
dreq = 8.6152719 in
Vs = -233.8244 kip/ft
v = -721.6802 psi < 502 psi
As = 0.1870298 sq-in/ft
as = 0.48 sq-in
Spacing of bar = 30.797228 in. c/c 5 in. c/c
dia. of bar = 0.7819623 in 0.064 nos. bar
Peremeter of bar = 2.4553615 in
Bond Stress = 2367.0965 psi
Ld (minimum) = 0.004088 in < -51.29 in
As (temp.) = 0.81 sq-in/ft
ast = 0.48 sq-in
Spacing of temp. bar= 7.1111111 in. c/c
OK (square & rectangle) OK
DESIGN OF FOOTING (USD) DESIGN OF PILE CAP - F1(WSD)

f'c 3.5 ksi. f'c


fy 60 ksi. fy
k 0.33213 k
j 0.88929 j
R 0.23259 R
Column Load (D.L.) = 1750 kip Column Load (D.L.) =
Column Load (L.L.) = 150 kip Column Load (L.L.) =
Bearing Capacity = 3.5 ksf No of Pile
Column Size 30 in Column Size
30 in
Area of Found(reqd) = 575.429 sq-ft Pile Value
Footing Size(reqd) = 23.9881 ft Footing Size(prov.) =
Footing Size(prov.) = 24 ft
24 ft Pile c/c distance =
Area of Found(prov) = 576 sq-ft > 575.4 d (provided) =
Wu 4.69618 ksf V (punching)
d (provided) = 45 in V (punching)
V (punching) 2521.56 kip M
V (punching) 186.782 psi < 201.1 psi dreq
Vs (long) 32.8733 kip/ft As
v (long) 60.8764 psi < 100.6 psi as
M (long) 271.351 k-ft/ft No. of bar (reqd) =
a(assumed) 2 in No. of bar (pro) =
As (long) 1.37046 sq-in/ft dia. of bar
a(actual) 2.30329 Peremeter of bar =
as 0.6 sq-in Bond Stress (allow) =
Spacing of bar = 5.25371 in. c/c Ld (minimum)
dia. of bar 0.87426 in Bond Stress (reqd) =
Peremeter of bar = 2.74518 in Vs
Bond Stress = 642.861 psi v
Ld (minimum) 20.3993 in < 126 in av
Vs (short) 32.8733 kip/ft No. of leg (pro) =
v (short) 60.8764 psi < 100.6 psi Stirrup (spacing) =
M (short) 271.351 k-ft/ft As (temp.)
a(assumed) 2 in ast
As (short) 1.37046 sq-in/ft Spacing of temp. bar=
a(actual) 2.30329
as 0.6 sq-in
Spacing of bar = 5.25371 in. c/c
dia. of bar 0.87426 in
Peremeter of bar = 2.74518 in
Bond Stress = 642.861 psi DESIGN OF PILE CAP - F2(WSD)
Ld (minimum) 20.3993 in < 126 in
As (temp.) 1.8 sq-in/ft f'c
ast 0.175 sq-in fy
Spacing of temp. bar= 1.16667 in. c/c k
Bear stress at the inter- j
face of column&footing 3.00556 ksi < 2.494 ksi R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size

Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=

DESIGN OF PILE CAP - F3(WSD)

f'c
fy
k
j
R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size

Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=

DESIGN OF PILE CAP - F4(WSD)

f'c
fy
k
j
R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size

Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=

DESIGN OF PILE CAP - F5(WSD)

f'c
fy
k
j
R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size

Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=

DESIGN OF PILE CAP - F6(WSD)

f'c
fy
k
j
R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size
Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=

DESIGN OF PILE CAP - F7(WSD)

f'c
fy
k
j
R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size

Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=

DESIGN OF PILE CAP - F8(WSD)

f'c
fy
k
j
R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size

Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=

DESIGN OF PILE CAP - F9(WSD)

f'c
fy
k
j
R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size

Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=

DESIGN OF PILE CAP - F10(WSD)

f'c
fy
k
j
R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size

Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=

DESIGN OF PILE CAP - F11(WSD)

f'c
fy
k
j
R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size

Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=

DESIGN OF PILE CAP - F10(WSD)

f'c
fy
k
j
R
Column Load (D.L.) =
Column Load (L.L.) =
No of Pile
Column Size

Pile Value
Footing Size(prov.) =

Pile c/c distance =


d (provided) =
V (punching)
V (punching)
M
dreq
As
as
No. of bar (reqd) =
No. of bar (pro) =
dia. of bar
Peremeter of bar =
Bond Stress (allow) =
Ld (minimum)
Bond Stress (reqd) =
Vs
v
av
No. of leg (pro) =
Stirrup (spacing) =
As (temp.)
ast
Spacing of temp. bar=
NOT OK
N OF PILE CAP - F1(WSD) DESIGN OF PILE CAP (USD)

2.75 ksi. f'c 2.5 ksi.


55 ksi. & 45 ksi. fy 40 ksi.
0.32472 k 0.38667
0.89176 j 0.87111
0.17917 R 0.18947
165 kip Column Load (D.L.) 80 kip
70 kip Column Load (L.L.) 20 kip
2 nos No of Pile 2 nos
15 in Column Size 10 in
18 in 15 in
117.5 kip Pile Value 50 kip
3.5 ft Footing Size(prov.) = 3 ft
7.5 ft 7 ft
4 ft Pile c/c distance 4 ft
24 in d (provided) 15 in
235 kip V (punching) 100 kip
67.7789 psi < 104.9 psi V (punching) 69.5733 psi < 100
185.65 k-ft M 100 k-ft
17.2058 in < 24 in dreq 13.264 in < 15
4.20574 sq-in/ft As 5.10204 sq-in/ft
0.48 sq-in as 0.58 sq-in
8.76196 nos. No. of bar (reqd) 8.79662 nos.
10 nos. No. of bar (pro) 9 nos.
0.78196 in dia. of bar 0.85957 in
2.45536 in Peremeter of bar 2.69904 in
321.901 psi Bond Stress (allow) = 279.211 psi
15.0307 in < 34.5 in Ld (minimum) 13.8535 in < 34
223.596 psi < 321.9 psi Bond Stress (reqd) = 157.527 psi < 279.211
117.5 kip Vs 50 kip
116.567 psi > 57.68 psi v 92.5926 psi > 55
0.12 sq-in av 0.175 sq-in
4 nos. No. of leg (pro) 4 nos.
3.93031 in c/c Stirrup (spacing) 9.31034 in c/c
0.72 sq-in/ft As (temp.) 0.45 sq-in/ft
0.12 sq-in ast 0.175 sq-in
2 in. c/c Spacing of temp. bar= 4.66667 in. c/c
N OF PILE CAP - F2(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
185 kip
70 kip
2 nos
15 in
18 in
127.5 kip
3.5 ft
7.5 ft
4 ft
26 in
255 kip
64.695 psi < 104.9 psi
191.25 k-ft
17.4634 in < 26 in
3.99933 sq-in/ft
0.48 sq-in
8.33193 nos.
10 nos.
0.78196 in
2.45536 in
321.901 psi
15.0307 in < 34.5 in
223.962 psi < 321.9 psi
127.5 kip
116.758 psi > 57.68 psi
0.12 sq-in
4 nos.
3.91762 in c/c
0.78 sq-in/ft
0.175 sq-in
2.69231 in. c/c

N OF PILE CAP - F3(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
235 kip
70 kip
2 nos
15 in
18 in
152.5 kip
3.5 ft
7.5 ft
4 ft
30 in
305 kip
61.2941 psi < 104.9 psi
228.75 k-ft
19.0989 in < 30 in
4.14571 sq-in/ft
0.48 sq-in
8.63689 nos.
10 nos.
0.78196 in
2.45536 in
321.901 psi
15.0307 in < 34.5 in
232.159 psi < 321.9 psi
152.5 kip
121.032 psi > 57.68 psi
0.12 sq-in
4 nos.
3.65333 in c/c
0.9 sq-in/ft
0.175 sq-in
2.33333 in. c/c

N OF PILE CAP - F4(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
295 kip
70 kip
3 nos
15 in
20 in
121.667 kip
3.5 ft
7.5 ft
4 ft
30 in
365 kip
71.8077 psi < 104.9 psi
182.5 k-ft
17.0592 in < 30 in
3.3075 sq-in/ft
0.48 sq-in
6.89063 nos.
8 nos.
0.78196 in
2.45536 in
321.901 psi
15.0307 in < 34.5 in
231.525 psi < 321.9 psi
121.667 kip
96.5608 psi > 57.68 psi
0.12 sq-in
3 nos.
4.4647 in c/c
0.9 sq-in/ft
0.175 sq-in
2.33333 in. c/c

N OF PILE CAP - F5(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
340 kip
70 kip
3 nos
15 in
20 in
136.667 kip
3.5 ft
7.5 ft
4 ft
33 in
410 kip
68.9718 psi < 104.9 psi
205 k-ft
18.0802 in < 33 in
3.37753 sq-in/ft
0.48 sq-in
7.03651 nos.
8 nos.
0.78196 in
2.45536 in
321.901 psi
15.0307 in < 34.5 in
236.426 psi < 321.9 psi
136.667 kip
98.6051 psi > 57.68 psi
0.12 sq-in
3 nos.
4.24166 in c/c
0.99 sq-in/ft
0.175 sq-in
2.12121 in. c/c

N OF PILE CAP - F6(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
380 kip
70 kip
3 nos
15 in
20 in
150 kip
3.5 ft
7.5 ft
4 ft
36 in
450 kip
65.5012 psi < 104.9 psi
225 k-ft
18.9417 in < 36 in
3.39812 sq-in/ft
0.48 sq-in
7.07942 nos.
8 nos.
0.78196 in
2.45536 in
321.901 psi
15.0307 in < 34.5 in
237.868 psi < 321.9 psi
150 kip
99.2063 psi > 57.68 psi
0.12 sq-in
3 nos.
4.18024 in c/c
1.08 sq-in/ft
0.175 sq-in
1.94444 in. c/c

N OF PILE CAP - F7(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
410 kip
70 kip
4 nos
15 in
25 in
120 kip
7.5 ft
7.5 ft
4 ft
36 in
480 kip
66.7488 psi < 104.9 psi
360 k-ft
16.3675 in < 36 in
5.43699 sq-in/ft
0.31 sq-in
17.5387 nos.
24 nos.
0.62841 in
1.97322 in
400.554 psi
9.70733 in < 34.5 in
78.9304 psi < 400.6 psi
120 kip
37.037 psi > 57.68 psi
0.12 sq-in
2 nos.
-2.61534 in c/c
1.08 sq-in/ft
0.175 sq-in
1.94444 in. c/c

N OF PILE CAP - F8(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
470 kip
70 kip
4 nos
15 in
20 in
135 kip
7.5 ft
7.5 ft
4 ft
36 in
540 kip
78.6014 psi < 104.9 psi
405 k-ft
17.3603 in < 36 in
6.11662 sq-in/ft
0.31 sq-in
19.731 nos.
22 nos.
0.62841 in
1.97322 in
400.554 psi
9.70733 in < 34.5 in
96.8692 psi < 400.6 psi
135 kip
41.6667 psi > 57.68 psi
0.12 sq-in
2 nos.
-3.37125 in c/c
1.08 sq-in/ft
0.31 sq-in
3.44444 in. c/c

N OF PILE CAP - F9(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
525 kip
80 kip
4 nos
18 in
25 in
151.25 kip
7.5 ft
7.5 ft
4 ft
37 in
605 kip
78.3593 psi < 104.9 psi
453.75 k-ft
18.3755 in < 37 in
6.66766 sq-in/ft
0.31 sq-in
21.5086 nos.
22 nos.
0.62841 in
1.97322 in
400.554 psi
9.70733 in < 33 in
105.596 psi < 400.6 psi
151.25 kip
45.4204 psi > 57.68 psi
0.12 sq-in
2 nos.
-4.40311 in c/c
1.11 sq-in/ft
0.31 sq-in
3.35135 in. c/c

N OF PILE CAP - F10(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
565 kip
75 kip
5 nos
18 in
27 in
128 kip
9.5 ft
9.5 ft
6 ft
37 in
640 kip
81.4993 psi < 104.9 psi
640 k-ft
19.3905 in < 37 in
9.40453 sq-in/ft
0.48 sq-in
19.5928 nos.
22 nos.
0.78196 in
2.45536 in
321.901 psi
15.0307 in < 45 in
71.8163 psi < 321.9 psi
128 kip
30.3461 psi > 57.68 psi
0.12 sq-in
2 nos.
-1.55941 in c/c
1.11 sq-in/ft
0.48 sq-in
5.18919 in. c/c

N OF PILE CAP - F11(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
605 kip
90 kip
5 nos
18 in
27 in
139 kip
9.5 ft
9.5 ft
6 ft
38 in
695 kip
84.7498 psi < 104.9 psi
695 k-ft
20.2065 in < 38 in
9.94397 sq-in/ft
0.48 sq-in
20.7166 nos.
22 nos.
0.78196 in
2.45536 in
321.901 psi
15.0307 in < 45 in
75.9357 psi < 321.9 psi
139 kip
32.0868 psi > 57.68 psi
0.12 sq-in
2 nos.
-1.66545 in c/c
1.14 sq-in/ft
0.48 sq-in
5.05263 in. c/c

N OF PILE CAP - F10(WSD)

2.75 ksi.
55 ksi. & 45 ksi.
0.32472
0.89176
0.17917
460 kip
75 kip
5 nos
15 in
25 in
107 kip
9 ft
9 ft
6 ft
27 in
535 kip
118.191 psi < 104.9 psi
535 k-ft
18.2145 in < 27 in
10.7733 sq-in/ft
0.48 sq-in
22.4444 nos.
18 nos.
0.78196 in
2.45536 in
321.901 psi
15.0307 in < 43.5 in
100.551 psi < 321.9 psi
107 kip
36.6941 psi > 57.68 psi
0.12 sq-in
2 nos.
-2.14384 in c/c
0.81 sq-in/ft
0.175 sq-in
2.59259 in. c/c
OK
DESIGN OF SLAB (WSD) - S1

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 12 ft m = 0.8571
LB = 14 ft case = 5
Thickness (reqd) = 3.466667 in.
Slab Thickness = 4.5 in
Dead Load = 56.25 psf
Floor Finish = 20 psf
Partition Load = 30 psf
-------------------------------------------------
Total Dead Load = 106.25 psf
DL = 0.10625 ksf
Live Load = 40 psf
psi LL = 0.04 ksf W = 0.1463 ksf
CA(-) = 0.083
in CB(-) = 0
CAdl(+ = 0.042
CBdl(+ = 0.017
CAll (+ = 0.046
CBll (+ = 0.022
MA (-) = 1.74798 k-ft
MB (-) = 0 k-ft
MA (+) = 0.90756 k-ft
in MB (+) = 0.526505 k-ft
psi d (reqd= 3.037399 in < 3.5 in
AsA(-) = 0.382211 sq-in.
psi AsB(-) = 0 sq-in.
AsA(+) = 0.198446 sq-in.
Spacin = 4.656177 in.c/c as= 0.077 sq-in
AsB(+) = 0.134313 sq-in. n
Spacin = 6.879479 in c/c as= 0.077 sq-in

DESIGN OF SLAB - S2

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 13.75 ft m = 0.6962
LB = 19.75 ft case 6
Thickness (reqd) = 4.466667 in.
Slab Thickness = 5 in
Dead Load = 62.5 psf
Floor Finish = 20 psf
Partition Load = 40 psf
-------------------------------------------------
Total Dead Load = 122.5 psf
DL = 0.1225 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.1625 ksf
CA(-) = 0.081
CB(-) = 0.019
CAdl(+ = 0.046
CBdl(+ = 0.011
CAll (+ = 0.057
CBll (+ = 0.014
MA (-) = 2.488535 k-ft
MB (-) = 1.204318 k-ft
MA (+) = 1.49643 k-ft
MB (+) = 0.744044 k-ft
d (reqd= 3.624144 in < 4 in
AsA(-) = 0.476123 sq-in.
AsB(-) = 0.230418 sq-in.
AsA(+) = 0.286307 sq-in.
Spacin = 5.029571 in.c/c as= 0.12 sq-in
AsB(+) = 0.142355 sq-in.
Spacin = 6.490797 in c/c as= 0.077 sq-in

DESIGN OF ONE-WAY SLAB - S5

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 11.75 ft m = 0.47
LB = 25 ft
Thickness (reqd) = 5.64 in.
Thickness (reqd) = 4.7 in.
Thickness (reqd) = 4.028571 in.
Slab Thickness = 5.5 in
Dead Load = 68.75 psf
Floor Finish = 20 psf
Partition Load = 12 psf
-------------------------------------------------
Total Dead Load = 100.75 psf
DL = 0.10075 ksf
Live Load = 100 psf
LL = 0.1 ksf W = 0.2008 ksf
w L2/10= MA (-)= 2.771605 k-ft
w L2/14= MA (+= 1.979718 k-ft
w L2/8 = Ma (+ = 3.464506 k-ft
d (reqd= 3.824716 in < 4.5 in
d (reqd= 3.232475 in < 4.5 in
d (reqd= 4.276163 in < 4.5 in
AsA(-) = 0.471361 sq-in.
AsA(+) = 0.336687 sq-in.
Spacin = 4.276974 in.c/c as= 0.12 sq-in
Asa (+)= 0.589202 sq-in.
Spacin = 0 in.c/c as= 0 sq-in

DESIGN OF SLAB - S3

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 18 ft m = 0.9114
LB = 19.75 ft case 1
Thickness (reqd) = 5.033333 in.
Slab Thickness = 5.5 in
Dead Load = 68.75 psf
Floor Finish = 20 psf
Partition Load = 45 psf
-------------------------------------------------
Total Dead Load = 133.75 psf
DL = 0.13375 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.1738 ksf
CA(-) = 0.08
CB(-) = 0
CAdl(+ = 0.029
CBdl(+ = 0.013
CAll (+ = 0.037
CBll (+ = 0.021
MA (-) = 4.5036 k-ft
MB (-) = 0 k-ft
MA (+) = 1.736235 k-ft
MB (+) = 1.005874 k-ft
d (reqd= 4.875436 in < 4.5 in
AsA(-) = 0.765918 sq-in.
AsB(-) = 0 sq-in.
AsA(+) = 0.295278 sq-in.
Spacin = 4.876759 in.c/c as= 0.12 sq-in
AsB(+) = 0.171067 sq-in.
Spacin = 5.401394 in c/c as= 0.077 sq-in

DESIGN OF SLAB -S4

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 13 ft m = 0.6667
LB = 19.5 ft case 1
Thickness (reqd) = 4.333333 in.
Slab Thickness = 4.5 in
Dead Load = 56.25 psf
Floor Finish = 20 psf
Partition Load = 45 psf
-------------------------------------------------
Total Dead Load = 121.25 psf
DL = 0.12125 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.1613 ksf
CA(-) = 0.083
CB(-) = 0.028
CAdl(+ = 0.05
CBdl(+ = 0.011
CAll (+ = 0.06
CBll (+ = 0.013
MA (-) = 2.261854 k-ft
MB (-) = 1.716829 k-ft
MA (+) = 1.430163 k-ft
MB (+) = 0.704888 k-ft
d (reqd= 3.455142 in < 3.5 in
AsA(-) = 0.494574 sq-in.
AsB(-) = 0.3754 sq-in.
AsA(+) = 0.312718 sq-in.
Spacin = 4.604791 in.c/c as= 0.12 sq-in
AsB(+) = 0.15413 sq-in.
Spacin = 5.994934 in c/c as= 0.077 sq-in

DESIGN OF SLAB - S5

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 19.5 ft m = 0.9512
LB = 20.5 ft case 6
Thickness (reqd) = 5.333333 in.
Slab Thickness = 5.5 in
Dead Load = 68.75 psf
Floor Finish = 20 psf
Partition Load = 45 psf
-------------------------------------------------
Total Dead Load = 133.75 psf
DL = 0.13375 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.1738 ksf
CA(-) = 0.055
CB(-) = 0.067
CAdl(+ = 0.031
CBdl(+ = 0.031
CAll (+ = 0.036
CBll (+ = 0.032
MA (-) = 3.633764 k-ft
MB (-) = 4.892235 k-ft
MA (+) = 2.124172 k-ft
MB (+) = 2.280382 k-ft
d (reqd= 4.379373 in < 4.5 in
AsA(-) = 0.617987 sq-in.
AsB(-) = 0.832013 sq-in.
AsA(+) = 0.361254 sq-in.
Spacin = 3.986119 in.c/c as= 0.12 sq-in
AsB(+) = 0.38782 sq-in.
Spacin = 3.713063 in c/c as= 0.12 sq-in
DESIGN OF SLAB - S6

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 19.5 ft m = 0.9512
LB = 20.5 ft case 1 & 2
Thickness (reqd) = 5.333333 in.
Slab Thickness = 5.5 in
Dead Load = 68.75 psf
Floor Finish = 20 psf
Partition Load = 45 psf
-------------------------------------------------
Total Dead Load = 133.75 psf
DL = 0.13375 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.1738 ksf
CA(-) = 0
CB(-) = 0
CAdl(+ = 0.04
CBdl(+ = 0.033
CAll (+ = 0.04
CBll (+ = 0.033
MA (-) = 0 k-ft
MB (-) = 0 k-ft
MA (+) = 2.642738 k-ft
MB (+) = 2.409608 k-ft
d (reqd= 0 in < 4.5 in
AsA(-) = 0 sq-in.
AsB(-) = 0 sq-in.
AsA(+) = 0.449445 sq-in.
Spacin = 3.20395 in.c/c as= 0.12 sq-in
AsB(+) = 0.409797 sq-in.
Spacin = 3.513932 in c/c as= 0.12 sq-in

DESIGN OF SLAB - S7

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 10.75 ft m = 0.7414
LB = 14.5 ft case 1
Thickness (reqd) = 3.366667 in.
Slab Thickness = 4.5 in
Dead Load = 56.25 psf
Floor Finish = 20 psf
Partition Load = 25 psf
-------------------------------------------------
Total Dead Load = 101.25 psf
DL = 0.10125 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.1413 ksf
CA(-) = 0.085
CB(-) = 0
CAdl(+ = 0.033
CBdl(+ = 0.007
CAll (+ = 0.047
CBll (+ = 0.013
MA (-) = 1.387472 k-ft
MB (-) = 0 k-ft
MA (+) = 0.603381 k-ft
MB (+) = 0.258345 k-ft
d (reqd= 2.706112 in < 3.5 in
AsA(-) = 0.303383 sq-in.
AsB(-) = 0 sq-in.
AsA(+) = 0.131935 sq-in.
Spacin = 7.003472 in.c/c as= 0.077 sq-in
AsB(+) = 0.056489 sq-in.
Spacin = 16.35706 in c/c as= 0.077 sq-in

DESIGN OF SLAB - S8

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 10 ft m = 0.6667
LB = 15 ft case 1
Thickness (reqd) = 3.333333 in.
Slab Thickness = 4.5 in
Dead Load = 56.25 psf
Floor Finish = 20 psf
Partition Load = 35 psf
-------------------------------------------------
Total Dead Load = 111.25 psf
DL = 0.11125 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.1513 ksf
CA(-) = 0.093
CB(-) = 0.015
CAdl(+ = 0.054
CBdl(+ = 0.011
CAll (+ = 0.064
CBll (+ = 0.013
MA (-) = 1.406625 k-ft
MB (-) = 0.510469 k-ft
MA (+) = 0.85675 k-ft
MB (+) = 0.392344 k-ft
d (reqd= 2.724726 in < 3.5 in
AsA(-) = 0.307571 sq-in.
AsB(-) = 0.111619 sq-in.
AsA(+) = 0.187336 sq-in.
Spacin = 4.932314 in.c/c as= 0.077 sq-in
AsB(+) = 0.085789 sq-in.
Spacin = 10.77056 in c/c as= 0.077 sq-in

DESIGN OF SLAB - S10

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 13 ft m = 0.9286
LB = 14 ft case 2
Thickness (reqd) = 3.6 in.
Slab Thickness = 4.5 in
Dead Load = 56.25 psf
Floor Finish = 20 psf
Partition Load = 25 psf
-------------------------------------------------
Total Dead Load = 101.25 psf
DL = 0.10125 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.1413 ksf
CA(-) = 0.055
CB(-) = 0.05
CAdl(+ = 0.03
CBdl(+ = 0.027
CAll (+ = 0.035
CBll (+ = 0.032
MA (-) = 1.312919 k-ft
MB (-) = 1.38425 k-ft
MA (+) = 0.749938 k-ft
MB (+) = 0.786695 k-ft
d (reqd= 2.632404 in < 3.5 in
AsA(-) = 0.287081 sq-in.
AsB(-) = 0.302679 sq-in.
AsA(+) = 0.163981 sq-in.
Spacin = 5.634816 in.c/c as= 0.077 sq-in
AsB(+) = 0.172018 sq-in.
Spacin = 5.371535 in c/c as= 0.077 sq-in
DESIGN OF CANT. SLAB

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 3.5 ft
Thickness (reqd) = 3.5 in.
Thickness(pro) = 4.5 in
Dead Load = 56.25 psf
Floor Finish = 20 psf
Partition Load = 0 psf
-------------------------------------------------
Total Dead Load = 76.25 psf
DL = 0.07625 ksf
Live Load = 40 psf
LL = 0.04 ksf
5" wall / drop wall = 0.25 k/ft
MA ( = 1.587031 k-ft/ft
d (reqd= 2.894185 in < 3.5 in
AsA(-) = 0.347018 sq-in.
Spacin = 3.803832 in.c/c as= 0.11 sq-in

DESIGN OF ONE-WAY SLAB - S (FOUNDATION)

f'c = 2.5 ksi


fy = 40 ksi
k = 0.386667
j = 0.871111
R = 0.189467
LA = 11 ft m = 0.4231
LB = 26 ft
Thickness (reqd) = 5.28 in.
Thickness (reqd) = 15 in.
Thickness (reqd) = 3.771429 in.
Slab Thickness = 18 in
Dead Load = 225 psf
Floor Finish = 20 psf
Partition Load = 0 psf
-------------------------------------------------
Total Dead Load = 245 psf
DL = 0.245 ksf
Live Load = 900 psf
LL = 0.9 ksf W = 1.145 ksf
w L2/10= MA (-)= 13.8545 k-ft
w L2/14= MA (+= 9.896071 k-ft
w L2/8 = Ma (+ = 17.31813 k-ft
d (reqd= 8.551239 in < 15 in
d (reqd= 7.227116 in < 17 in
d (reqd= 9.560575 in < 17 in
AsA(-) = 0.706862 sq-in.
AsA(+) = 0.504902 sq-in.
Spacin = 4.159226 in.c/c as= 0.175 sq-in
Asa (+)= 0.779627 sq-in.
Spacin = 0 in.c/c as= 0 sq-in
NOT OK
DESIGN OF SLAB (USD) - S1

f'c = 2.5 ksi


fy = 40 ksi
k = 0.3866667
j = 0.8711111
R = 0.1894667
LA = 30.833 ft m= 1
LB = 30.833 ft case = 1
Thickness (reqd) = 8.2221333 in.
Slab Thickness = 8 in
Dead Load = 100 psf
Floor Finish = 20 psf
Partition Load = 40 psf
-------------------------------------------------
Total Dead Load = 160 psf
DL = 0.16 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.2 ksf
CA(-) = 0
CB(-) = 0
CAdl(+) = 0.036
CBdl(+) = 0.036
CAll (+) = 0.036
CBll (+) = 0.036
MA (-) = 0 k-ft
MB (-) = 0 k-ft
MA (+) = 6.844852 k-ft
MB (+) = 6.844852 k-ft
d (reqd) = 0 in < 7 in
AsA(-) = 0 sq-in.
AsB(-) = 0 sq-in.
AsA(+) = 0.7483439 sq-in.
Spacing = 4.9709767 in.c/c as= 0.31 sq-in
AsB(+) = 0.7483439 sq-in.
Spacing = 4.9709767 in c/c as= 0.31 sq-in

DESIGN OF SLAB S2

f'c = 2.5 ksi


fy = 40 ksi
k = 0.3866667
j = 0.8711111
R = 0.1894667
LA = 23.33 ft m = 0.7566568
LB = 30.833 ft case 1&7
Thickness (reqd) = 7.2217333 in.
Slab Thickness = 8 in
Dead Load = 100 psf
Floor Finish = 20 psf
Partition Load = 0 psf
-------------------------------------------------
Total Dead Load = 120 psf
DL = 0.12 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.16 ksf
CA(-) = 0
CB(-) = 0.046
CAdl(+) = 0.06
CBdl(+) = 0.021
CAll (+) = 0.06
CBll (+) = 0.021
MA (-) = 0 k-ft
MB (-) = 6.9969598 k-ft
MA (+) = 5.2251734 k-ft
MB (+) = 3.1942643 k-ft
d (reqd) = 0 in < 7 in
AsA(-) = 0 sq-in.
AsB(-) = 0.7649737 sq-in.
AsA(+) = 0.5712653 sq-in.
Spacing = 3.6760502 in.c/c as= 0.175 sq-in
AsB(+) = 0.3492271 sq-in.
Spacing = 6.0132783 in c/c as= 0.175 sq-in

DESIGN OF ONE-WAY SLAB

f'c = 2.5 ksi


fy = 40 ksi
k = 0.3866667
j = 0.8711111
R = 0.1894667
LA = 15 ft m = 0.375
LB = 40 ft
Thickness (reqd) = 7.2 in.
Thickness (reqd) = 6 in.
Thickness (reqd) = 5.1428571 in.
Slab Thickness = 6 in
Dead Load = 75 psf
Floor Finish = 20 psf
Partition Load = 40 psf
-------------------------------------------------
Total Dead Load = 135 psf
DL = 0.135 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.175 ksf
w L2/10= MA (-) = 3.9375 k-ft
w L2/14= MA (+) = 2.8125 k-ft
w L2/8 = Ma (+) = 4.921875 k-ft
d (reqd) = 4.5587301 in < 5 in
d (reqd) = 3.8528301 in < 5 in
d (reqd) = 5.0968151 in < 5 in
AsA(-) = 0.6026786 sq-in.
AsA(+) = 0.4304847 sq-in.
Spacing = 4.8782222 in.c/c as= 0.175 sq-in
Asa (+) = 0.7533482 sq-in.
Spacing = 2.7875556 in.c/c as= 0.175 sq-in

DESIGN OF SLAB S3

f'c = 2.5 ksi


fy = 40 ksi
k = 0.3866667
j = 0.8711111
R = 0.1894667
LA = 15 ft m = 0.642949
LB = 23.33 ft case 4,5 & 9
Thickness (reqd) = 5.1106667 in.
Slab Thickness = 5 in
Dead Load = 62.5 psf
Floor Finish = 20 psf
Partition Load = 40 psf
-------------------------------------------------
Total Dead Load = 122.5 psf
DL = 0.1225 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.1625 ksf
CA(-) = 0.087
CB(-) = 0.016
CAdl(+) = 0.05
CBdl(+) = 0.01
CAll (+) = 0.062
CBll (+) = 0.012
MA (-) = 3.1809375 k-ft
MB (-) = 1.4151511 k-ft
MA (+) = 1.936125 k-ft
MB (+) = 0.9280126 k-ft
d (reqd) = 4.0974264 in < 4 in
AsA(-) = 0.6085977 sq-in.
AsB(-) = 0.270756 sq-in.
AsA(+) = 0.3704321 sq-in.
Spacing = 5.6690555 in.c/c as= 0.175 sq-in
AsB(+) = 0.1775534 sq-in.
Spacing = 7.434382 in c/c as= 0.11 sq-in

DESIGN OF SLAB

f'c = 2.5 ksi


fy = 40 ksi
k = 0.3866667
j = 0.8711111
R = 0.1894667
LA = 11.25 ft m = 0.8282412
LB = 13.583 ft case 4
Thickness (reqd) = 3.3110667 in.
Slab Thickness = 4.5 in
Dead Load = 56.25 psf
Floor Finish = 20 psf
Partition Load = 0 psf
-------------------------------------------------
Total Dead Load = 76.25 psf
DL = 0.07625 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.11625 ksf
CA(-) = 0.069
CB(-) = 0.032
CAdl(+) = 0.038
CBdl(+) = 0.018
CAll (+) = 0.046
CBll (+) = 0.022
MA (-) = 1.0151895 k-ft
MB (-) = 0.6863321 k-ft
MA (+) = 0.5995898 k-ft
MB (+) = 0.4155815 k-ft
d (reqd) = 2.3147662 in < 3.5 in
AsA(-) = 0.2219802 sq-in.
AsB(-) = 0.1500726 sq-in.
AsA(+) = 0.1311057 sq-in.
Spacing = 10.068216 in.c/c as= 0.11 sq-in
AsB(+) = 0.0908706 sq-in.
Spacing = 14.526152 in c/c as= 0.11 sq-in

DESIGN OF SLAB

f'c = 2.5 ksi


fy = 40 ksi
k = 0.3866667
j = 0.8711111
R = 0.1894667
LA = 12.5 ft m = 0.8021562
LB = 15.583 ft case 4&9
Thickness (reqd) = 3.7444 in.
Slab Thickness = 4.5 in
Dead Load = 56.25 psf
Floor Finish = 20 psf
Partition Load = 0 psf
-------------------------------------------------
Total Dead Load = 76.25 psf
DL = 0.07625 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.11625 ksf
CA(-) = 0.075
CB(-) = 0.029
CAdl(+) = 0.039
CBdl(+) = 0.016
CAll (+) = 0.048
CBll (+) = 0.02
MA (-) = 1.3623047 k-ft
MB (-) = 0.8186403 k-ft
MA (+) = 0.7646484 k-ft
MB (+) = 0.4905164 k-ft
d (reqd) = 2.6814563 in < 3.5 in
AsA(-) = 0.29788 sq-in.
AsB(-) = 0.179003 sq-in.
AsA(+) = 0.1671972 sq-in.
Spacing = 7.89487 in.c/c as= 0.11 sq-in
AsB(+) = 0.1072558 sq-in.
Spacing = 12.307031 in c/c as= 0.11 sq-in
DESIGN OF SLAB

f'c = 2.5 ksi


fy = 40 ksi
k = 0.3866667
j = 0.8711111
R = 0.1894667
LA = 12.75 ft m = 0.8052801
LB = 15.833 ft case 4&9
Thickness (reqd) = 3.8110667 in.
Slab Thickness = 4.5 in
Dead Load = 56.25 psf
Floor Finish = 20 psf
Partition Load = 0 psf
-------------------------------------------------
Total Dead Load = 76.25 psf
DL = 0.07625 ksf
Live Load = 40 psf
LL = 0.04 ksf W = 0.11625 ksf
CA(-) = 0.075
CB(-) = 0.029
CAdl(+) = 0.039
CBdl(+) = 0.016
CAll (+) = 0.048
CBll (+) = 0.02
MA (-) = 1.4173418 k-ft
MB (-) = 0.8451181 k-ft
MA (+) = 0.7955402 k-ft
MB (+) = 0.5063815 k-ft
d (reqd) = 2.7350854 in < 3.5 in
AsA(-) = 0.3099144 sq-in.
AsB(-) = 0.1847926 sq-in.
AsA(+) = 0.1739519 sq-in.
Spacing = 7.5883026 in.c/c as= 0.11 sq-in
AsB(+) = 0.1107248 sq-in.
Spacing = 11.921448 in c/c as= 0.11 sq-in

DESIGN OF CANT. SLAB

f'c = 2.5 ksi


fy = 40 ksi
k = 0.3866667
j = 0.8711111
R = 0.1894667
LA = 3.5 ft
Thickness (reqd) = 3.5 in.
Thickness(pro) = 4.5 in
Dead Load = 56.25 psf
Floor Finish = 20 psf
Partition Load = 0 psf
-------------------------------------------------
Total Dead Load = 76.25 psf
DL = 0.07625 ksf
Live Load = 40 psf
LL = 0.04 ksf
5" wall / drop wall = 0.25 k/ft
MA (-) = 1.5870313 k-ft/ft
d (reqd) = 2.8941853 in < 3.5 in
AsA(-) = 0.3470185 sq-in.
Spacing = 3.8038318 in.c/c as= 0.11 sq-in
OK NOT OK
DESIGN OF COLUMN -C1(WSD) DESIGN OF COLUMN (USD)

f'c 3 ksi. f'c 2.5 ksi.


fy 55 ksi. fy 40 ksi.
k 0.334 k 0.39
j 0.889 j 0.87
R 0.201 R 0.19
Column Load (D.L.) = 245 kip Column Lo150 kip
Column Load (L.L.) = 70 kip Column Lo 0 kip
Column Size 10 in Column Siz 10 in
30 in 20 in
Pc 191.3 kip Pc 106 kip
Ps 123.8 kip Ps 43.8 kip
As 5.882 As 2.86
as 0.48 as 0.31
No of Bar (reqd) = 12.25 No of Bar 9.22
No of Bar (pro) = 18 No of Bar 10
Ps (pro) 181.8 Ps (pro) 47.4
P(pro)=Pc+Ps = 373 P(pro)=Pc+154
P(pro)/P(actual) = 1.184 P(pro)/P(a1.02
% of steel 2.88 % % of steel1.55 %
P(pro) B.S. code = 476.1 P(pro) B.S 203
P(pro B.S.)/P(actual) = 1.511 P(pro B.S 1.36

DESIGN OF CIRCULAR COLUMN (WSDDESIGN OF CIRCULAR COLUMN (WSD)

f'c 3 ksi. f'c 4 ksi.


fy 60 ksi. fy 60 ksi.
k 0.315 k 0.35
j 0.895 j 0.88
R 0.19 R 0.28

Column Load (D.L.) = 250 kip Column Lo480 kip


Column Load (L.L.) = 40 kip Column Lo 0 kip
Dia. of Column 20 in Dia. of Co 20 in
0 in 0 in
Pc 0 kip Pc 0 kip
Ps 290 kip Ps 480 kip
As 12.64 As 20.9
as 0.48 as 0.48
No of Bar (reqd) = 26.33 No of Bar 43.6
No of Bar (pro) = 14 No of Bar 14
Ps (pro) 154.2 Ps (pro) 154
P(pro)=Pc+Ps = 154.2 P(pro)=Pc+154
P(pro)/P(actual) = 0.532 P(pro)/P(a0.32
% of steel ### % % of steel ### %
P(pro) B.S. code = 175.4 P(pro) B.S 173
P(pro B.S.)/P(actual) = 0.605 P(pro B.S 0.36

COMPRESION PLUS BENDING

DESIGN OF COLUMN -C2(WSD) DESIGN OF COLUMN -C1(USD)


AT - A1, A6, E1, E6.
f'c 3 ksi. 3.5 ksi
fy 60 ksi. 60 ksi
k 0.315
j 0.895
R 0.19 Dead Loa 150 kip
Column Load (D.L.) = 245 kip Live Load 20 kip
Column Load (L.L.) = 0 kip EQ. Load 70 kip
Column Size 10 in M (D.L.) 0 k-ft
20 in M (L.L.) 0 k-ft
Pc 127.5 kip M (EQ.) 35 k-ft
Ps 117.5 kip
As 5.12 Pu 281 kip
as 0.48 235 kip
No of Bar (reqd) = 10.67 244 kip
No of Bar (pro) = 12 Mu 49.1 k-ft
Ps (pro) 132.2 50.1 k-ft
P(pro)=Pc+Ps = 259.7 0 k-ft
P(pro)/P(actual) = 1.06
% of steel 2.88 % Pu (Desi 281 kip
P(pro) B.S. code = 330.3 Mu (Desi 50.1 k-ft
P(pro B.S.)/P(actual) = 1.348 Column S 12 in
20 in
0.67 (within 0.6-0.9)
e =Mu 2.14 in.
e/h 0.18
Pu/f'c b h 0.33
Pu/f'c b 0.06
Pt 0.2
Ast 2.38
a 0.48
no.of bar 4.96
no.of bar 8

P 661
Pu(pro)/P2.35

P (B.S. 340 kip > ###


P(pro)/P 1.55

% of stee 1.6 %

CORRECTED DESIGN

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C2(WSD) DESIGN OF COLUMN -C2(USD)
D5/H1 D5/H1
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 55
n = 8.525034 Dead Load = 160
k = 0.351703 Live Load = 25
j = 0.882766 EQ. Load = 75
R = 0.244496 M (D.L.) = 0
Dead Load = 160 kip M (L.L.) = 0
Live Load = 25 kip M (EQ.) = 50
EQ. Load = 75 kip Pu = 305.06
M (D.L.) = 0 k-ft = 251.25
M (L.L.) = 0 k-ft = 266.5
M (EQ.) = 50 k-ft Mu = 70.125
P = 195 kip = 71.5
= 235 kip = 0
= 185 kip Pu (Design) = 305.06
M = 37.5 k-ft Mu (Design) = 71.5
= 50 k-ft Column Size, b = 20
= 0 k-ft h = 12
P (Design) = 235 kip g = 0.75
M (Design) = 50 k-ft e =Mu/P = 2.8125
Column Size, b = 20 in e/h = 0.2344
h = 12 in Pu/f'c b h = 0.4237
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0.0993
No of Bar (pro) = 10 Ptm = 0.4
No of Bar in each face = 4 Ast = 4.4509
m = 18.48739 as = 0.48
pg = 0.02 no.of bar(reqd) = 9.2727
pgm = 0.369748 no.of bar(pro) = 10
bh3/12 = 2880 cu-inch. % of steel = 2
2x(2n-1)xAs/2x(t/2-d')2 = 754.9952 cu-inch. Pu = 490.56
Sut = 605.8325 cu-inch. Pu(pro)/Pu = 1.6081
Fa = 1.63 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 317.28
fa = 0.979167 ksi. P(pro)/P = 1.3501
fb = 0.990373 ksi.
fa/Fa+fb/Fb = 1.229524
% of steel = 2 %
Pc = 178.5 kip
Ps (pro) = 100.98
P(pro)=Pc+Ps = 279.48 kip > 235 kip
P(pro)/P(actual) = 1.189277
P(pro) B.S. code = 365.76 kip > 235 kip
P(pro B.S.)/P(actual) = 1.556426

REVISED COLUMN DESIGN FOR BUNDLE BAR


COLUMN C4

b = 12 in
h = 20 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 10
As = 4.8 sq-in.
B = 13
C = -1.2
t = 0.091661 in
Z = 190.577 cu-in
As' = 3.388036
No of Bar (reqd) = 7.058409

REVISED COLUMN DESIGN FOR BUNDLE BAR


COLUMN C4

b = 20 in
h = 12 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 10
As = 4.8 sq-in.
B = 13
C = -1.2
t = 0.091661 in
Z = 72.30005 cu-in
As' = 5.141337
No of Bar (reqd) = 10.71112

CORRECTED DESIGN
BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C3(WSD) DESIGN OF COLUMN -C3(USD)
A4/G1 A4/G1
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 55
n = 8.525034 Dead Load = 190
k = 0.351703 Live Load = 30
j = 0.882766 EQ. Load = 75
R = 0.244496 M (D.L.) = 0
Dead Load = 190 kip M (L.L.) = 0
Live Load = 30 kip M (EQ.) = 50
EQ. Load = 75 kip Pu = 342.94
M (D.L.) = 0 k-ft = 278.25
M (L.L.) = 0 k-ft = 317
M (EQ.) = 50 k-ft Mu = 70.125
P = 221.25 kip = 71.5
= 265 kip = 0
= 220 kip Pu (Design) = 342.94
M = 37.5 k-ft Mu (Design) = 71.5
= 50 k-ft Column Size, b = 20
= 0 k-ft h = 12
P (Design) = 265 kip g = 0.75
M (Design) = 50 k-ft e =Mu/P = 2.5019
Column Size, b = 20 in e/h = 0.2085
h = 12 in Pu/f'c b h = 0.4763
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0.0993
No of Bar (pro) = 12 Ptm = 0.5
No of Bar in each face = 4 Ast = 5.5636
m = 18.48739 as = 0.48
pg = 0.024 no.of bar(reqd) = 11.591
pgm = 0.443697 no.of bar(pro) = 12
bh3/12 = 2880 cu-inch. % of steel = 2.4
2x(2n-1)xAs/2x(t/2-d')2 = 754.9952 cu-inch. Pu = 520.13
Sut = 605.8325 cu-inch. Pu(pro)/Pu = 1.5167
Fa = 1.718 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 337.54
fa = 1.104167 ksi. P(pro)/P = 1.2737
fb = 0.990373 ksi.
fa/Fa+fb/Fb = 1.271513
% of steel = 2.4 %
Pc = 178.5 kip
Ps (pro) = 121.176
P(pro)=Pc+Ps = 299.676 kip > 265 kip
P(pro)/P(actual) = 1.130853
P(pro) B.S. code = 388.512 kip > 265 kip
P(pro B.S.)/P(actual) = 1.466083

REVISED COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 20 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 12
As = 5.76 sq-in.
B = 13
C = -1.44
t = 0.109841 in
Z = 227.5081 cu-in
As' = 4.044589
No of Bar (reqd) = 8.426227

REVISED COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 20 in
h = 12 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 12
As = 5.76 sq-in.
B = 13
C = -1.44
t = 0.109841 in
Z = 86.18307 cu-in
As' = 6.128574
No of Bar (reqd) = 12.76786
CORRECTED DESIGN
BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C4(WSD) DESIGN OF COLUMN -C4(USD)
D1/E1 D1/E1
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 55
n = 8.525034 Dead Load = 210
k = 0.351703 Live Load = 30
j = 0.882766 EQ. Load = 75
R = 0.244496 M (D.L.) = 0
Dead Load = 210 kip M (L.L.) = 0
Live Load = 30 kip M (EQ.) = 50
EQ. Load = 75 kip Pu = 363.94
M (D.L.) = 0 k-ft = 296.25
M (L.L.) = 0 k-ft = 345
M (EQ.) = 50 k-ft Mu = 70.125
P = 236.25 kip = 71.5
= 285 kip = 0
= 240 kip Pu (Design) = 363.94
M = 37.5 k-ft Mu (Design) = 71.5
= 50 k-ft Column Size, b = 20
= 0 k-ft h = 12
P (Design) = 285 kip g = 0.75
M (Design) = 50 k-ft e =Mu/P = 2.3575
Column Size, b = 20 in e/h = 0.1965
h = 12 in Pu/f'c b h = 0.5055
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0.0993
No of Bar (pro) = 14 Ptm = 0.5
No of Bar in each face = 5 Ast = 5.5636
m = 18.48739 as = 0.48
pg = 0.028 no.of bar(reqd) = 11.591
pgm = 0.517647 no.of bar(pro) = 14
bh3/12 = 2880 cu-inch. % of steel = 2.8
2x(2n-1)xAs/2x(t/2-d')2 = 943.744 cu-inch. Pu = 549.7
Sut = 637.2907 cu-inch. Pu(pro)/Pu = 1.5104
Fa = 1.806 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 357.79
fa = 1.1875 ksi. P(pro)/P = 1.2554
fb = 0.941486 ksi.
fa/Fa+fb/Fb = 1.255299
% of steel = 2.8 %
Pc = 178.5 kip
Ps (pro) = 141.372
P(pro)=Pc+Ps = 319.872 kip > 285 kip
P(pro)/P(actual) = 1.122358
P(pro) B.S. code = 411.264 kip > 285 kip
P(pro B.S.)/P(actual) = 1.443032

REVISED COLUMN DESIGN FOR BUNDLE BAR


COLUMN C2

b = 12 in
h = 20 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 14
As = 6.72 sq-in.
B = 13
C = -1.68
t = 0.127971 in
Z = 264.0552 cu-in
As' = 4.694315
No of Bar (reqd) = 9.779824

REVISED COLUMN DESIGN FOR BUNDLE BAR


COLUMN C2

b = 20 in
h = 12 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 14
As = 6.72 sq-in.
B = 13
C = -1.68
t = 0.127971 in
Z = 99.87968 cu-in
As' = 7.102555
No of Bar (reqd) = 14.79699

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C5(WSD) DESIGN OF COLUMN -C5(USD)
H5 H5
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 55
n = 8.525034 Dead Load = 200
k = 0.351703 Live Load = 25
j = 0.882766 EQ. Load = 75
R = 0.244496 M (D.L.) = 0
Dead Load = 200 kip M (L.L.) = 0
Live Load = 25 kip M (EQ.) = 60
EQ. Load = 75 kip Pu = 347.06
M (D.L.) = 0 k-ft = 287.25
M (L.L.) = 0 k-ft = 322.5
M (EQ.) = 60 k-ft Mu = 84.15
P = 225 kip = 85.8
= 275 kip = 0
= 225 kip Pu (Design) = 347.06
M = 45 k-ft Mu (Design) = 85.8
= 60 k-ft Column Size, b = 25
= 0 k-ft h = 12
P (Design) = 275 kip g = 0.8
M (Design) = 60 k-ft e =Mu/P = 2.9666
Column Size, b = 25 in e/h = 0.2472
h = 12 in Pu/f'c b h = 0.3856
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0.0953
No of Bar (pro) = 12 Ptm = 0.35
No of Bar in each face = 4 Ast = 4.8682
m = 18.48739 as = 0.48
pg = 0.0192 no.of bar(reqd) = 10.142
pgm = 0.354958 no.of bar(pro) = 12
bh3/12 = 3600 cu-inch. % of steel = 1.92
2x(2n-1)xAs/2x(t/2-d')2 = 754.9952 cu-inch. Pu = 605.81
Sut = 725.8325 cu-inch. Pu(pro)/Pu = 1.7455
Fa = 1.6124 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 391.54
fa = 0.916667 ksi. P(pro)/P = 1.4238
fb = 0.991964 ksi.
fa/Fa+fb/Fb = 1.198329
% of steel = 1.92 %
Pc = 223.125 kip
Ps (pro) = 121.176
P(pro)=Pc+Ps = 344.301 kip > 275 kip
P(pro)/P(actual) = 1.252004
P(pro) B.S. code = 451.512 kip > 275 kip
P(pro B.S.)/P(actual) = 1.641862

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 25 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 12
As = 5.76 sq-in.
B = 15.5
C = -1.44
t = 0.092353 in
Z = 359.2618 cu-in
As' = 3.592618
No of Bar (reqd) = 7.48462

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 25 in
h = 12 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 12
As = 5.76 sq-in.
B = 15.5
C = -1.44
t = 0.092353 in
Z = 91.15053 cu-in
As' = 6.481816
No of Bar (reqd) = 13.50378

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C6(WSD) DESIGN OF COLUMN -C6(USD)
A3/F5 A3/F5
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 55
n = 8.525034 Dead Load = 280
k = 0.351703 Live Load = 40
j = 0.882766 EQ. Load = 75
R = 0.244496 M (D.L.) = 0
Dead Load = 280 kip M (L.L.) = 0
Live Load = 40 kip M (EQ.) = 75
EQ. Load = 75 kip Pu = 450.19
M (D.L.) = 0 k-ft = 359.25
M (L.L.) = 0 k-ft = 460
M (EQ.) = 75 k-ft Mu = 105.19
P = 296.25 kip = 107.25
= 355 kip = 0
= 320 kip Pu (Design) = 460
M = 56.25 k-ft Mu (Design) = 107.25
= 75 k-ft Column Size, b = 25
= 0 k-ft h = 12
P (Design) = 355 kip g = 0.8
M (Design) = 75 k-ft e =Mu/P = 2.7978
Column Size, b = 25 in e/h = 0.2332
h = 12 in Pu/f'c b h = 0.5111
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.1192
No of Bar (pro) = 16 Ptm = 0.55
No of Bar in each face = 6 Ast = 7.65
m = 18.48739 as = 0.58
pg = 0.030933 no.of bar(reqd) = 13.19
pgm = 0.571877 no.of bar(pro) = 16
bh3/12 = 3600 cu-inch. % of steel = 3.0933
2x(2n-1)xAs/2x(t/2-d')2 = 1368.429 cu-inch. Pu = 714.22
Sut = 828.0715 cu-inch. Pu(pro)/Pu = 1.5527
Fa = 1.870533 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 465.81
fa = 1.183333 ksi. P(pro)/P = 1.3121
fb = 1.086863 ksi.
fa/Fa+fb/Fb = 1.32269
% of steel = 3.093333 %
Pc = 223.125 kip
Ps (pro) = 195.228
P(pro)=Pc+Ps = 418.353 kip > 355 kip
P(pro)/P(actual) = 1.178459
P(pro) B.S. code = 534.936 kip > 355 kip
P(pro B.S.)/P(actual) = 1.506862

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 25 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 16
As = 9.28 sq-in.
B = 15.5
C = -2.32
t = 0.148259 in
Z = 571.1863 cu-in
As' = 5.711863
No of Bar (reqd) = 9.848039

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 25 in
h = 12 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 16
As = 9.28 sq-in.
B = 15.5
C = -2.32
t = 0.148259 in
Z = 144.0739 cu-in
As' = 10.24526
No of Bar (reqd) = 17.66424

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C7(WSD) DESIGN OF COLUMN -C7(USD)
A3 A3
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 55
n = 8.525034 Dead Load = 290
k = 0.351703 Live Load = 40
j = 0.882766 EQ. Load = 60
R = 0.244496 M (D.L.) = 0
Dead Load = 290 kip M (L.L.) = 0
Live Load = 40 kip M (EQ.) = 100
EQ. Load = 60 kip Pu = 439.65
M (D.L.) = 0 k-ft = 346.8
M (L.L.) = 0 k-ft = 474
M (EQ.) = 100 k-ft Mu = 140.25
P = 292.5 kip = 143
= 350 kip = 0
= 330 kip Pu (Design) = 474
M = 75 k-ft Mu (Design) = 143
= 100 k-ft Column Size, b = 12
= 0 k-ft h = 25
P (Design) = 350 kip g = 0.5833
M (Design) = 100 k-ft e =Mu/P = 3.6203
Column Size, b = 12 in e/h = 0.1448
h = 25 in Pu/f'c b h = 0.5267
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.0763
No of Bar (pro) = 14 Ptm = 0.4
No of Bar in each face = 4 Ast = 5.5636
m = 18.48739 as = 0.58
pg = 0.027067 no.of bar(reqd) = 9.5925
pgm = 0.500392 no.of bar(pro) = 14
bh3/12 = 15625 cu-inch. % of steel = 2.7067
2x(2n-1)xAs/2x(t/2-d')2 = 7447.232 cu-inch. Pu = 678.5
Sut = 1845.779 cu-inch. Pu(pro)/Pu = 1.4314
Fa = 1.785467 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 441.33
fa = 1.166667 ksi. P(pro)/P = 1.2609
fb = 0.650132 ksi.
fa/Fa+fb/Fb = 1.066206
% of steel = 2.706667 %
Pc = 223.125 kip
Ps (pro) = 170.8245
P(pro)=Pc+Ps = 393.9495 kip > 350 kip
P(pro)/P(actual) = 1.12557
P(pro) B.S. code = 507.444 kip > 350 kip
P(pro B.S.)/P(actual) = 1.44984

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 25 in
h = 12 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 14
As = 8.12 sq-in.
B = 15.5
C = -2.03
t = 0.129879 in
Z = 126.8598 cu-in
As' = 10.3559
No of Bar (reqd) = 17.85501

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 25 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 14
As = 8.12 sq-in.
B = 15.5
C = -2.03
t = 0.129879 in
Z = 501.9717 cu-in
As' = 4.777839
No of Bar (reqd) = 8.237653

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C8(WSD) DESIGN OF COLUMN -C8(USD)
C1 C1
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 55
n = 8.525034 Dead Load = 235
k = 0.351703 Live Load = 30
j = 0.882766 EQ. Load = 75
R = 0.244496 M (D.L.) = 0
Dead Load = 235 kip M (L.L.) = 0
Live Load = 30 kip M (EQ.) = 50
EQ. Load = 75 kip Pu = 390.19
M (D.L.) = 0 k-ft = 318.75
M (L.L.) = 0 k-ft = 380
M (EQ.) = 50 k-ft Mu = 70.125
P = 255 kip = 71.5
= 310 kip = 0
= 265 kip Pu (Design) = 390.19
M = 37.5 k-ft Mu (Design) = 71.5
= 50 k-ft Column Size, b = 26
= 0 k-ft h = 12
P (Design) = 310 kip g = 0.8077
M (Design) = 50 k-ft e =Mu/P = 2.1989
Column Size, b = 26 in e/h = 0.1832
h = 12 in Pu/f'c b h = 0.4169
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0.0764
No of Bar (pro) = 12 Ptm = 0.35
No of Bar in each face = 4 Ast = 5.0629
m = 18.48739 as = 0.48
pg = 0.018462 no.of bar(reqd) = 10.548
pgm = 0.341306 no.of bar(pro) = 12
bh3/12 = 3744 cu-inch. % of steel = 1.8462
2x(2n-1)xAs/2x(t/2-d')2 = 754.9952 cu-inch. Pu = 622.94
Sut = 749.8325 cu-inch. Pu(pro)/Pu = 1.5965
Fa = 1.596154 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 402.34
fa = 0.99359 ksi. P(pro)/P = 1.2979
fb = 0.800179 ksi.
fa/Fa+fb/Fb = 1.13054
% of steel = 1.846154 %
Pc = 232.05 kip
Ps (pro) = 121.176
P(pro)=Pc+Ps = 353.226 kip > 310 kip
P(pro)/P(actual) = 1.139439
P(pro) B.S. code = 464.112 kip > 310 kip
P(pro B.S.)/P(actual) = 1.497135

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 26 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 12
As = 5.76 sq-in.
B = 16
C = -1.44
t = 0.089499 in
Z = 388.6837 cu-in
As' = 3.525476
No of Bar (reqd) = 7.344741
COLUMN DESIGN FOR BUNDLE BAR
COLUMN C1

b = 26 in
h = 12 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 12
As = 5.76 sq-in.
B = 16
C = -1.44
t = 0.089499 in
Z = 91.957 cu-in
As' = 6.539164
No of Bar (reqd) = 13.62326

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C9(WSD) DESIGN OF COLUMN -C9(USD)
E3/F3 E3/F3
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 55
n = 8.525034 Dead Load = 635
k = 0.351703 Live Load = 100
j = 0.882766 EQ. Load = 0
R = 0.244496 M (D.L.) = 0
Dead Load = 635 kip M (L.L.) = 0
Live Load = 100 kip M (EQ.) = 75
EQ. Load = 0 kip Pu = 794.25
M (D.L.) = 0 k-ft = 571.5
M (L.L.) = 0 k-ft = 1059
M (EQ.) = 75 k-ft Mu = 105.19
P = 551.25 kip = 107.25
= 635 kip = 0
= 735 kip Pu (Design) = 1059
M = 56.25 k-ft Mu (Design) = 107.25
= 75 k-ft Column Size, b = 42
= 0 k-ft h = 12
P (Design) = 735 kip g = 0.881
M (Design) = 75 k-ft e =Mu/P = 1.2153
Column Size, b = 42 in e/h = 0.1013
h = 12 in Pu/f'c b h = 0.7004
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.0709
No of Bar (pro) = 30 Ptm = 0.65
No of Bar in each face = 12 Ast = 15.189
m = 18.48739 as = 0.58
pg = 0.034524 no.of bar(reqd) = 26.187
pgm = 0.638255 no.of bar(pro) = 30
bh3/12 = 6048 cu-inch. % of steel = 3.4524
2x(2n-1)xAs/2x(t/2-d')2 = 2736.858 cu-inch. Pu = 1255.6
Sut = 1464.143 cu-inch. Pu(pro)/Pu = 1.1857
Fa = 1.949524 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 820.74
fa = 1.458333 ksi. P(pro)/P = 1.2925
fb = 0.614694 ksi.
fa/Fa+fb/Fb = 1.138328
% of steel = 3.452381 %
Pc = 374.85 kip
Ps (pro) = 366.0525
P(pro)=Pc+Ps = 740.9025 kip > 735 kip
P(pro)/P(actual) = 1.008031
P(pro) B.S. code = 941.58 kip > 735 kip
P(pro B.S.)/P(actual) = 1.281061

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 42 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 30
As = 17.4 sq-in.
B = 24
C = -4.35
t = 0.179901 in
Z = 2949.825 cu-in
As' = 8.618917
No of Bar (reqd) = 14.8602

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1
b = 42 in
h = 12 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 30
As = 17.4 sq-in.
B = 24
C = -4.35
t = 0.179901 in
Z = 292.2482 cu-in
As' = 20.7821
No of Bar (reqd) = 35.8312

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C10(WSD) DESIGN OF COLUMN -C10(USD)
A2 A2
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 55
n = 8.525034 Dead Load = 155
k = 0.351703 Live Load = 20
j = 0.882766 EQ. Load = 75
R = 0.244496 M (D.L.) = 0
Dead Load = 155 kip M (L.L.) = 0
Live Load = 20 kip M (EQ.) = 60
EQ. Load = 75 kip Pu = 293.44
M (D.L.) = 0 k-ft = 246.75
M (L.L.) = 0 k-ft = 251
M (EQ.) = 60 k-ft Mu = 84.15
P = 187.5 kip = 85.8
= 230 kip = 0
= 175 kip Pu (Design) = 293.44
M = 45 k-ft Mu (Design) = 85.8
= 60 k-ft Column Size, b = 15
= 0 k-ft h = 15
P (Design) = 230 kip g = 0.6667
M (Design) = 60 k-ft e =Mu/P = 3.5088
Column Size, b = 15 in e/h = 0.2339
h = 15 in Pu/f'c b h = 0.4347
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0.1017
No of Bar (pro) = 10 Ptm = 0.45
No of Bar in each face = 4 Ast = 4.6943
m = 18.48739 as = 0.48
pg = 0.021333 no.of bar(reqd) = 9.7798
pgm = 0.394398 no.of bar(pro) = 10
bh3/12 = 4218.75 cu-inch. % of steel = 2.1333
2x(2n-1)xAs/2x(t/2-d')2 = 1540.807 cu-inch. Pu = 469.14
Sut = 767.9409 cu-inch. Pu(pro)/Pu = 1.5988
Fa = 1.659333 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 303.78
fa = 1.022222 ksi. P(pro)/P = 1.3208
fb = 0.937572 ksi.
fa/Fa+fb/Fb = 1.211328
% of steel = 2.133333 %
Pc = 167.3438 kip
Ps (pro) = 100.98
P(pro)=Pc+Ps = 268.3238 kip > 230 kip
P(pro)/P(actual) = 1.166625
P(pro) B.S. code = 350.01 kip > 230 kip
P(pro B.S.)/P(actual) = 1.521783

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 15 in
h = 15 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 10
As = 4.8 sq-in.
B = 12
C = -1.2
t = 0.09918 in
Z = 111.4519 cu-in
As' = 4.458075
No of Bar (reqd) = 9.287656

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 15 in
h = 15 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 10
As = 4.8 sq-in.
B = 12
C = -1.2
t = 0.09918 in
Z = 111.4519 cu-in
As' = 4.043605
No of Bar (reqd) = 8.424178

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
B2 B2
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 250
k = 0.351703 Live Load = 35
j = 0.882766 EQ. Load = 75
R = 0.244496 M (D.L.) = 0
Dead Load = 250 kip M (L.L.) = 0
Live Load = 35 kip M (EQ.) = 75
EQ. Load = 75 kip Pu = 412.31
M (D.L.) = 0 k-ft = 332.25
M (L.L.) = 0 k-ft = 409.5
M (EQ.) = 75 k-ft Mu = 105.19
P = 270 kip = 107.25
= 325 kip = 0
= 285 kip Pu (Design) = 412.31
M = 56.25 k-ft Mu (Design) = 107.25
= 75 k-ft Column Size, b = 18
= 0 k-ft h = 15
P (Design) = 325 kip g = 0.7222
M (Design) = 75 k-ft e =Mu/P = 3.1214
Column Size, b = 18 in e/h = 0.2081
h = 15 in Pu/f'c b h = 0.509
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.1059
No of Bar (pro) = 12 Ptm = 0.55
No of Bar in each face = 4 Ast = 6.3113
m = 18.48739 as = 0.58
pg = 0.025778 no.of bar(reqd) = 10.881
pgm = 0.476564 no.of bar(pro) = 12
bh3/12 = 5062.5 cu-inch. % of steel = 2.5778
2x(2n-1)xAs/2x(t/2-d')2 = 1861.808 cu-inch. Pu = 619.42
Sut = 923.2411 cu-inch. Pu(pro)/Pu = 1.5023
Fa = 1.757111 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 403.78
fa = 1.203704 ksi. P(pro)/P = 1.2424
fb = 0.974827 ksi.
fa/Fa+fb/Fb = 1.303985
% of steel = 2.577778 %
Pc = 200.8125 kip
Ps (pro) = 146.421
P(pro)=Pc+Ps = 347.2335 kip > 325 kip
P(pro)/P(actual) = 1.068411
P(pro) B.S. code = 448.452 kip > 325 kip
P(pro B.S.)/P(actual) = 1.379852

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 15 in
h = 18 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 12
As = 6.96 sq-in.
B = 13.5
C = -1.74
t = 0.127681 in
Z = 237.6626 cu-in
As' = 5.625151
No of Bar (reqd) = 9.698536

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 18 in
h = 15 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 12
As = 6.96 sq-in.
B = 13.5
C = -1.74
t = 0.127681 in
Z = 169.4513 cu-in
As' = 6.147893
No of Bar (reqd) = 10.59982

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
B4 B4
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 300
k = 0.351703 Live Load = 60
j = 0.882766 EQ. Load = 75
R = 0.244496 M (D.L.) = 0
Dead Load = 300 kip M (L.L.) = 0
Live Load = 60 kip M (EQ.) = 75
EQ. Load = 75 kip Pu = 496.69
M (D.L.) = 0 k-ft = 377.25
M (L.L.) = 0 k-ft = 522
M (EQ.) = 75 k-ft Mu = 105.19
P = 326.25 kip = 107.25
= 375 kip = 0
= 360 kip Pu (Design) = 522
M = 56.25 k-ft Mu (Design) = 107.25
= 75 k-ft Column Size, b = 18
= 0 k-ft h = 15
P (Design) = 375 kip g = 0.7222
M (Design) = 75 k-ft e =Mu/P = 2.4655
Column Size, b = 18 in e/h = 0.1644
h = 15 in Pu/f'c b h = 0.6444
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.1059
No of Bar (pro) = 14 Ptm = 0.65
No of Bar in each face = 5 Ast = 7.4588
m = 18.48739 as = 0.58
pg = 0.030074 no.of bar(reqd) = 12.86
pgm = 0.555991 no.of bar(pro) = 14
bh3/12 = 5062.5 cu-inch. % of steel = 3.0074
2x(2n-1)xAs/2x(t/2-d')2 = 2327.26 cu-inch. Pu = 658.39
Sut = 985.3013 cu-inch. Pu(pro)/Pu = 1.2613
Fa = 1.85163 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 430.57
fa = 1.388889 ksi. P(pro)/P = 1.1482
fb = 0.913426 ksi.
fa/Fa+fb/Fb = 1.330043
% of steel = 3.007407 %
Pc = 200.8125 kip
Ps (pro) = 170.8245
P(pro)=Pc+Ps = 371.637 kip > 375 kip
P(pro)/P(actual) = 0.991032
P(pro) B.S. code = 475.944 kip > 375 kip
P(pro B.S.)/P(actual) = 1.269184

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 15 in
h = 18 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 14
As = 8.12 sq-in.
B = 13.5
C = -2.03
t = 0.148732 in
Z = 275.6084 cu-in
As' = 6.523276
No of Bar (reqd) = 11.24703

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 18 in
h = 15 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 14
As = 8.12 sq-in.
B = 13.5
C = -2.03
t = 0.148732 in
Z = 196.401 cu-in
As' = 7.125658
No of Bar (reqd) = 12.28562
CORRECTED DESIGN REVISED
BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
H4 H4
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 375
k = 0.351703 Live Load = 50
j = 0.882766 EQ. Load = 60
R = 0.244496 M (D.L.) = 0
Dead Load = 375 kip M (L.L.) = 0
Live Load = 50 kip M (EQ.) = 100
EQ. Load = 60 kip Pu = 541.65
M (D.L.) = 0 k-ft = 423.3
M (L.L.) = 0 k-ft = 610
M (EQ.) = 100 k-ft Mu = 140.25
P = 363.75 kip = 143
= 435 kip = 0
= 425 kip Pu (Design) = 610
M = 75 k-ft Mu (Design) = 143
= 100 k-ft Column Size, b = 20
= 0 k-ft h = 15
P (Design) = 435 kip g = 0.75
M (Design) = 100 k-ft e =Mu/P = 2.8131
Column Size, b = 20 in e/h = 0.1875
h = 15 in Pu/f'c b h = 0.6778
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.1271
No of Bar (pro) = 20 Ptm = 0.9
No of Bar in each face = 6 Ast = 11.475
m = 18.48739 as = 0.58
pg = 0.038667 no.of bar(reqd) = 19.784
pgm = 0.714846 no.of bar(pro) = 20
bh3/12 = 5625 cu-inch. % of steel = 3.8667
2x(2n-1)xAs/2x(t/2-d')2 = 2792.712 cu-inch. Pu = 818.16
Sut = 1122.362 cu-inch. Pu(pro)/Pu = 1.3412
Fa = 2.040667 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 537.96
fa = 1.45 ksi. P(pro)/P = 1.2367
fb = 1.069174 ksi.
fa/Fa+fb/Fb = 1.389393
% of steel = 3.866667 %
Pc = 223.125 kip
Ps (pro) = 244.035
P(pro)=Pc+Ps = 467.16 kip > 435 kip
P(pro)/P(actual) = 1.073931
P(pro) B.S. code = 589.92 kip > 435 kip
P(pro B.S.)/P(actual) = 1.356138

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 15 in
h = 20 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 20
As = 11.6 sq-in.
B = 14.5
C = -2.9
t = 0.197315 in
Z = 484.8239 cu-in
As' = 8.619091
No of Bar (reqd) = 14.8605

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 20 in
h = 15 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 20
As = 11.6 sq-in.
B = 14.5
C = -2.9
t = 0.197315 in
Z = 285.0396 cu-in
As' = 10.34157
No of Bar (reqd) = 17.8303

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
B3 B3
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 425
k = 0.351703 Live Load = 75
j = 0.882766 EQ. Load = 0
R = 0.244496 M (D.L.) = 0
Dead Load = 425 kip M (L.L.) = 0
Live Load = 75 kip M (EQ.) = 125
EQ. Load = 0 kip Pu = 541.88
M (D.L.) = 0 k-ft = 382.5
M (L.L.) = 0 k-ft = 722.5
M (EQ.) = 125 k-ft Mu = 175.31
P = 375 kip = 178.75
= 425 kip = 0
= 500 kip Pu (Design) = 722.5
M = 93.75 k-ft Mu (Design) = 178.75
= 125 k-ft Column Size, b = 15
= 0 k-ft h = 25
P (Design) = 500 kip g = 0.6667
M (Design) = 125 k-ft e =Mu/P = 2.9689
Column Size, b = 15 in e/h = 0.1188
h = 25 in Pu/f'c b h = 0.6422
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.0763
No of Bar (pro) = 18 Ptm = 0.5
No of Bar in each face = 5 Ast = 7.9688
m = 18.48739 as = 0.58
pg = 0.02784 no.of bar(reqd) = 13.739
pgm = 0.514689 no.of bar(pro) = 18
bh3/12 = 19531.25 cu-inch. % of steel = 2.784
2x(2n-1)xAs/2x(t/2-d')2 = 9309.04 cu-inch. Pu = 886.28
Sut = 2307.223 cu-inch. Pu(pro)/Pu = 1.2267
Fa = 1.80248 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 578.66
fa = 1.333333 ksi. P(pro)/P = 1.3616
fb = 0.650132 ksi.
fa/Fa+fb/Fb = 1.152504
% of steel = 2.784 %
Pc = 278.9063 kip
Ps (pro) = 219.6315
P(pro)=Pc+Ps = 498.5378 kip > 500 kip
P(pro)/P(actual) = 0.997076
P(pro) B.S. code = 641.178 kip > 500 kip
P(pro B.S.)/P(actual) = 1.282356

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1
b = 25 in
h = 15 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 18
As = 10.44 sq-in.
B = 17
C = -2.61
t = 0.152167 in
Z = 275.5329 cu-in
As' = 11.02132
No of Bar (reqd) = 19.00227

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 15 in
h = 25 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 18
As = 10.44 sq-in.
B = 17
C = -2.61
t = 0.152167 in
Z = 694.7961 cu-in
As' = 6.613169
No of Bar (reqd) = 11.40202

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
F4 F4
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 480
k = 0.351703 Live Load = 80
j = 0.882766 EQ. Load = 0
R = 0.244496 M (D.L.) = 0
Dead Load = 480 kip M (L.L.) = 0
Live Load = 80 kip M (EQ.) = 125
EQ. Load = 0 kip Pu = 606
M (D.L.) = 0 k-ft = 432
M (L.L.) = 0 k-ft = 808
M (EQ.) = 125 k-ft Mu = 175.31
P = 420 kip = 178.75
= 480 kip = 0
= 560 kip Pu (Design) = 808
M = 93.75 k-ft Mu (Design) = 178.75
= 125 k-ft Column Size, b = 27
= 0 k-ft h = 15
P (Design) = 560 kip g = 0.8148
M (Design) = 125 k-ft e =Mu/P = 2.6547
Column Size, b = 27 in e/h = 0.177
h = 15 in Pu/f'c b h = 0.665
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.1177
No of Bar (pro) = 24 Ptm = 0.85
No of Bar in each face = 8 Ast = 14.631
m = 18.48739 as = 0.58
pg = 0.03437 no.of bar(reqd) = 25.225
pgm = 0.635419 no.of bar(pro) = 24
bh3/12 = 7593.75 cu-inch. % of steel = 3.437
2x(2n-1)xAs/2x(t/2-d')2 = 3723.616 cu-inch. Pu = 1046.1
Sut = 1508.982 cu-inch. Pu(pro)/Pu = 1.2946
Fa = 1.946148 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 686.05
fa = 1.382716 ksi. P(pro)/P = 1.4293
fb = 0.994048 ksi.
fa/Fa+fb/Fb = 1.34163
% of steel = 3.437037 %
Pc = 301.2188 kip
Ps (pro) = 292.842
P(pro)=Pc+Ps = 594.0608 kip > 560 kip
P(pro)/P(actual) = 1.060823
P(pro) B.S. code = 755.154 kip > 560 kip
P(pro B.S.)/P(actual) = 1.348489

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 15 in
h = 27 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 24
As = 13.92 sq-in.
B = 18
C = -3.48
t = 0.1913 in
Z = 1070.647 cu-in
As' = 8.848325
No of Bar (reqd) = 15.25573

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 27 in
h = 15 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 24
As = 13.92 sq-in.
B = 18
C = -3.48
t = 0.1913 in
Z = 370.1026 cu-in
As' = 13.42776
No of Bar (reqd) = 23.15131

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
C3 C3
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 550
k = 0.351703 Live Load = 90
j = 0.882766 EQ. Load = 0
R = 0.244496 M (D.L.) = 0
Dead Load = 550 kip M (L.L.) = 0
Live Load = 90 kip M (EQ.) = 125
EQ. Load = 0 kip Pu = 692.25
M (D.L.) = 0 k-ft = 495
M (L.L.) = 0 k-ft = 923
M (EQ.) = 125 k-ft Mu = 175.31
P = 480 kip = 178.75
= 550 kip = 0
= 640 kip Pu (Design) = 923
M = 93.75 k-ft Mu (Design) = 178.75
= 125 k-ft Column Size, b = 12
= 0 k-ft h = 38
P (Design) = 640 kip g = 0.5833
M (Design) = 125 k-ft e =Mu/P = 2.3239
Column Size, b = 12 in e/h = 0.0612
h = 38 in Pu/f'c b h = 0.6747
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.0413
No of Bar (pro) = 26 Ptm = 0.65
No of Bar in each face = 5 Ast = 12.597
m = 18.48739 as = 0.58
pg = 0.03307 no.of bar(reqd) = 21.719
pgm = 0.611381 no.of bar(pro) = 26
bh3/12 = 54872 cu-inch. % of steel = 3.307
2x(2n-1)xAs/2x(t/2-d')2 = 25343.86 cu-inch. Pu = 1157.9
Sut = 4221.887 cu-inch. Pu(pro)/Pu = 1.2544
Fa = 1.917544 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 758.75
fa = 1.403509 ksi. P(pro)/P = 1.3795
fb = 0.355291 ksi.
fa/Fa+fb/Fb = 0.957512
% of steel = 3.307018 %
Pc = 339.15 kip
Ps (pro) = 317.2455
P(pro)=Pc+Ps = 656.3955 kip > 640 kip
P(pro)/P(actual) = 1.025618
P(pro) B.S. code = 836.196 kip > 640 kip
P(pro B.S.)/P(actual) = 1.306556

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 38 in
h = 12 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 26
As = 15.08 sq-in.
B = 22
C = -3.77
t = 0.170049 in
Z = 250.4285 cu-in
As' = 20.44314
No of Bar (reqd) = 35.24679
COLUMN DESIGN FOR BUNDLE BAR
COLUMN C1

b = 12 in
h = 38 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 26
As = 15.08 sq-in.
B = 22
C = -3.77
t = 0.170049 in
Z = 2108.374 cu-in
As' = 7.514809
No of Bar (reqd) = 12.95657

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
B4. B4.
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 425
k = 0.351703 Live Load = 75
j = 0.882766 EQ. Load = 0
R = 0.244496 M (D.L.) = 0
Dead Load = 425 kip M (L.L.) = 0
Live Load = 75 kip M (EQ.) = 120
EQ. Load = 0 kip Pu = 541.88
M (D.L.) = 0 k-ft = 382.5
M (L.L.) = 0 k-ft = 722.5
M (EQ.) = 120 k-ft Mu = 168.3
P = 375 kip = 171.6
= 425 kip = 0
= 500 kip Pu (Design) = 722.5
M = 90 k-ft Mu (Design) = 171.6
= 120 k-ft Column Size, b = 15
= 0 k-ft h = 25
P (Design) = 500 kip g = 0.6667
M (Design) = 120 k-ft e =Mu/P = 2.8501
Column Size, b = 15 in e/h = 0.114
h = 25 in Pu/f'c b h = 0.6422
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.0732
No of Bar (pro) = 20 Ptm = 0.5
No of Bar in each face = 5 Ast = 7.9688
m = 18.48739 as = 0.58
pg = 0.030933 no.of bar(reqd) = 13.739
pgm = 0.571877 no.of bar(pro) = 20
bh3/12 = 19531.25 cu-inch. % of steel = 3.0933
2x(2n-1)xAs/2x(t/2-d')2 = 9309.04 cu-inch. Pu = 925.26
Sut = 2307.223 cu-inch. Pu(pro)/Pu = 1.2806
Fa = 1.870533 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 605.46
fa = 1.333333 ksi. P(pro)/P = 1.4246
fb = 0.624127 ksi.
fa/Fa+fb/Fb = 1.10908
% of steel = 3.093333 %
Pc = 278.9063 kip
Ps (pro) = 244.035
P(pro)=Pc+Ps = 522.9413 kip > 500 kip
P(pro)/P(actual) = 1.045883
P(pro) B.S. code = 668.67 kip > 500 kip
P(pro B.S.)/P(actual) = 1.33734

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 25 in
h = 15 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 20
As = 11.6 sq-in.
B = 17
C = -2.9
t = 0.16891 in
Z = 304.7268 cu-in
As' = 12.18907
No of Bar (reqd) = 21.01564

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1
b = 15 in
h = 25 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 20
As = 11.6 sq-in.
B = 17
C = -2.9
t = 0.16891 in
Z = 769.1727 cu-in
As' = 7.321096
No of Bar (reqd) = 12.62258

CORRECTED DESIGN REVISED


BASEMENT & GR. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
F5. F5.
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 480
k = 0.351703 Live Load = 80
j = 0.882766 EQ. Load = 0
R = 0.244496 M (D.L.) = 0
Dead Load = 480 kip M (L.L.) = 0
Live Load = 80 kip M (EQ.) = 100
EQ. Load = 0 kip Pu = 606
M (D.L.) = 0 k-ft = 432
M (L.L.) = 0 k-ft = 808
M (EQ.) = 100 k-ft Mu = 140.25
P = 420 kip = 143
= 480 kip = 0
= 560 kip Pu (Design) = 808
M = 75 k-ft Mu (Design) = 143
= 100 k-ft Column Size, b = 18
= 0 k-ft h = 18
P (Design) = 560 kip g = 0.7222
M (Design) = 100 k-ft e =Mu/P = 2.1238
Column Size, b = 27 in e/h = 0.118
h = 15 in Pu/f'c b h = 0.8313
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.0981
No of Bar (pro) = 22 Ptm = 0.9
No of Bar in each face = 7 Ast = 12.393
m = 18.48739 as = 0.58
pg = 0.031506 no.of bar(reqd) = 21.367
pgm = 0.582467 no.of bar(pro) = 22
bh3/12 = 7593.75 cu-inch. % of steel = 3.9383
2x(2n-1)xAs/2x(t/2-d')2 = 3258.164 cu-inch. Pu = 891.41
Sut = 1446.922 cu-inch. Pu(pro)/Pu = 1.1032
Fa = 1.883136 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 586.36
fa = 1.382716 ksi. P(pro)/P = 1.2216
fb = 0.829347 ksi.
fa/Fa+fb/Fb = 1.260832
% of steel = 3.150617 %
Pc = 301.2188 kip
Ps (pro) = 268.4385
P(pro)=Pc+Ps = 569.6573 kip > 560 kip
P(pro)/P(actual) = 1.017245
P(pro) B.S. code = 727.662 kip > 560 kip
P(pro B.S.)/P(actual) = 1.299396

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 15 in
h = 27 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 22
As = 12.76 sq-in.
B = 18
C = -3.19
t = 0.175511 in
Z = 984.619 cu-in
As' = 8.137347
No of Bar (reqd) = 14.02991

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 27 in
h = 15 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 22
As = 12.76 sq-in.
B = 18
C = -3.19
t = 0.175511 in
Z = 340.7163 cu-in
As' = 12.36159
No of Bar (reqd) = 21.31308

CORRECTED DESIGN REVISED


1ST & 2ND. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
D1 D1
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 205
k = 0.351703 Live Load = 25
j = 0.882766 EQ. Load = 70
R = 0.244496 M (D.L.) = 0
Dead Load = 205 kip M (L.L.) = 0
Live Load = 25 kip M (EQ.) = 45
EQ. Load = 70 kip Pu = 345.3
M (D.L.) = 0 k-ft = 284.6
M (L.L.) = 0 k-ft = 329.5
M (EQ.) = 45 k-ft Mu = 63.113
P = 225 kip = 64.35
= 275 kip = 0
= 230 kip Pu (Design) = 345.3
M = 33.75 k-ft Mu (Design) = 64.35
= 45 k-ft Column Size, b = 20
= 0 k-ft h = 12
P (Design) = 275 kip g = 0.75
M (Design) = 45 k-ft e =Mu/P = 2.2363
Column Size, b = 20 in e/h = 0.1864
h = 12 in Pu/f'c b h = 0.4796
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0.0894
No of Bar (pro) = 14 Ptm = 0.4
No of Bar in each face = 5 Ast = 4.08
m = 18.48739 as = 0.48
pg = 0.028 no.of bar(reqd) = 8.5
pgm = 0.517647 no.of bar(pro) = 14
bh3/12 = 2880 cu-inch. % of steel = 2.8
2x(2n-1)xAs/2x(t/2-d')2 = 943.744 cu-inch. Pu = 568.51
Sut = 637.2907 cu-inch. Pu(pro)/Pu = 1.6464
Fa = 1.806 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 371.23
fa = 1.145833 ksi. P(pro)/P = 1.3499
fb = 0.847337 ksi.
fa/Fa+fb/Fb = 1.172451
% of steel = 2.8 %
Pc = 178.5 kip
Ps (pro) = 141.372
P(pro)=Pc+Ps = 319.872 kip > 275 kip
P(pro)/P(actual) = 1.163171
P(pro) B.S. code = 411.264 kip > 275 kip
P(pro B.S.)/P(actual) = 1.495505

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 20 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 14
As = 6.72 sq-in.
B = 13
C = -1.68
t = 0.127971 in
Z = 264.0552 cu-in
As' = 4.694315
No of Bar (reqd) = 9.779824
COLUMN DESIGN FOR BUNDLE BAR
COLUMN C1

b = 20 in
h = 12 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 14
As = 6.72 sq-in.
B = 13
C = -1.68
t = 0.127971 in
Z = 99.87968 cu-in
As' = 7.102555
No of Bar (reqd) = 14.79699

CORRECTED DESIGN REVISED


1ST & 2ND. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
D3 D3
f'c = 3 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 9.208089 Dead Load = 170
k = 0.334336 Live Load = 25
j = 0.888555 EQ. Load = 0
R = 0.200526 M (D.L.) = 0
Dead Load = 170 kip M (L.L.) = 0
Live Load = 25 kip M (EQ.) = 0
EQ. Load = 0 kip Pu = 210.38
M (D.L.) = 0 k-ft = 153
M (L.L.) = 0 k-ft = 280.5
M (EQ.) = 0 k-ft Mu = 0
P = 146.25 kip = 0
= 170 kip = 0
= 195 kip Pu (Design) = 280.5
M = 0 k-ft Mu (Design) = 0
= 0 k-ft Column Size, b = 20
= 0 k-ft h = 12
P (Design) = 195 kip g = 0.75
M (Design) = 0 k-ft e =Mu/P = 0
Column Size, b = 20 in e/h = 0
h = 12 in Pu/f'c b h = 0.3896
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0
No of Bar (pro) = 8 Ptm = 0.4
No of Bar in each face = 3 Ast = 4.08
m = 21.56863 as = 0.48
pg = 0.016 no.of bar(reqd) = 8.5
pgm = 0.345098 no.of bar(pro) = 8
bh3/12 = 2880 cu-inch. % of steel = 1.6
2x(2n-1)xAs/2x(t/2-d')2 = 614.4428 cu-inch. Pu = 471.74
Sut = 582.4071 cu-inch. Pu(pro)/Pu = 1.6818
Fa = 1.372 ksi. =
Fb = 1.35 ksi. P (B.S. code) = 304.7
fa = 0.8125 ksi. P(pro)/P = 1.7924
fb = 0 ksi.
fa/Fa+fb/Fb = 0.592201
% of steel = 1.6 %
Pc = 153 kip
Ps (pro) = 80.784
P(pro)=Pc+Ps = 233.784 kip > 195 kip
P(pro)/P(actual) = 1.198892
P(pro) B.S. code = 307.584 kip > 195 kip
P(pro B.S.)/P(actual) = 1.577354

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 20 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 8
As = 3.84 sq-in.
B = 13
C = -0.96
t = 0.073431 in
Z = 153.2574 cu-in
As' = 2.724577
No of Bar (reqd) = 5.676201

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 20 in
h = 12 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 8
As = 3.84 sq-in.
B = 13
C = -0.96
t = 0.073431 in
Z = 58.22811 cu-in
As' = 4.140665
No of Bar (reqd) = 8.626386

CORRECTED DESIGN REVISED


1ST & 2ND. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
A4 A4
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 290
k = 0.351703 Live Load = 40
j = 0.882766 EQ. Load = 70
R = 0.244496 M (D.L.) = 0
Dead Load = 290 kip M (L.L.) = 0
Live Load = 40 kip M (EQ.) = 90
EQ. Load = 70 kip Pu = 453.68
M (D.L.) = 0 k-ft = 361.1
M (L.L.) = 0 k-ft = 474
M (EQ.) = 90 k-ft Mu = 126.23
P = 300 kip = 128.7
= 360 kip = 0
= 330 kip Pu (Design) = 474
M = 67.5 k-ft Mu (Design) = 128.7
= 90 k-ft Column Size, b = 12
= 0 k-ft h = 25
P (Design) = 360 kip g = 0.5833
M (Design) = 90 k-ft e =Mu/P = 3.2582
Column Size, b = 12 in e/h = 0.1303
h = 25 in Pu/f'c b h = 0.5267
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0.0686
No of Bar (pro) = 16 Ptm = 0.3
No of Bar in each face = 5 Ast = 3.825
m = 18.48739 as = 0.48
pg = 0.0256 no.of bar(reqd) = 7.9688
pgm = 0.473277 no.of bar(pro) = 16
bh3/12 = 15625 cu-inch. % of steel = 2.56
2x(2n-1)xAs/2x(t/2-d')2 = 7704.033 cu-inch. Pu = 686.45
Sut = 1866.323 cu-inch. Pu(pro)/Pu = 1.4482
Fa = 1.7532 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 447.41
fa = 1.2 ksi. P(pro)/P = 1.2428
fb = 0.578678 ksi.
fa/Fa+fb/Fb = 1.051877
% of steel = 2.56 %
Pc = 223.125 kip
Ps (pro) = 161.568
P(pro)=Pc+Ps = 384.693 kip > 360 kip
P(pro)/P(actual) = 1.068592
P(pro) B.S. code = 497.016 kip > 360 kip
P(pro B.S.)/P(actual) = 1.3806

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 25 in
h = 12 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 16
As = 7.68 sq-in.
B = 15.5
C = -1.92
t = 0.122897 in
Z = 120.2725 cu-in
As' = 9.81816
No of Bar (reqd) = 20.4545

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 25 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 16
As = 7.68 sq-in.
B = 15.5
C = -1.92
t = 0.122897 in
Z = 475.5582 cu-in
As' = 4.526432
No of Bar (reqd) = 9.430066

CORRECTED DESIGN REVISED


1ST & 2ND. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
C1 C1
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 225
k = 0.351703 Live Load = 30
j = 0.882766 EQ. Load = 70
R = 0.244496 M (D.L.) = 0
Dead Load = 225 kip M (L.L.) = 0
Live Load = 30 kip M (EQ.) = 45
EQ. Load = 70 kip Pu = 372.68
M (D.L.) = 0 k-ft = 302.6
M (L.L.) = 0 k-ft = 366
M (EQ.) = 45 k-ft Mu = 63.113
P = 243.75 kip = 64.35
= 295 kip = 0
= 255 kip Pu (Design) = 372.68
M = 33.75 k-ft Mu (Design) = 64.35
= 45 k-ft Column Size, b = 26
= 0 k-ft h = 12
P (Design) = 295 kip g = 0.8077
M (Design) = 45 k-ft e =Mu/P = 2.072
Column Size, b = 26 in e/h = 0.1727
h = 12 in Pu/f'c b h = 0.3982
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0.0688
No of Bar (pro) = 12 Ptm = 0.4
No of Bar in each face = 4 Ast = 5.304
m = 18.48739 as = 0.48
pg = 0.018462 no.of bar(reqd) = 11.05
pgm = 0.341306 no.of bar(pro) = 12
bh3/12 = 3744 cu-inch. % of steel = 1.8462
2x(2n-1)xAs/2x(t/2-d')2 = 754.9952 cu-inch. Pu = 639.07
Sut = 749.8325 cu-inch. Pu(pro)/Pu = 1.7148
Fa = 1.596154 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 413.86
fa = 0.945513 ksi. P(pro)/P = 1.4029
fb = 0.720161 ksi.
fa/Fa+fb/Fb = 1.049614
% of steel = 1.846154 %
Pc = 232.05 kip
Ps (pro) = 121.176
P(pro)=Pc+Ps = 353.226 kip > 295 kip
P(pro)/P(actual) = 1.197376
P(pro) B.S. code = 464.112 kip > 295 kip
P(pro B.S.)/P(actual) = 1.573261

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 26 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 12
As = 5.76 sq-in.
B = 16
C = -1.44
t = 0.089499 in
Z = 388.6837 cu-in
As' = 3.525476
No of Bar (reqd) = 7.344741

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 26 in
h = 12 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 12
As = 5.76 sq-in.
B = 16
C = -1.44
t = 0.089499 in
Z = 91.957 cu-in
As' = 6.539164
No of Bar (reqd) = 13.62326
CORRECTED DESIGN REVISED
1ST & 2ND. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
E4/F4 E4/F4
f'c = 3 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 9.208089 Dead Load = 460
k = 0.334336 Live Load = 70
j = 0.888555 EQ. Load = 0
R = 0.200526 M (D.L.) = 0
Dead Load = 460 kip M (L.L.) = 0
Live Load = 70 kip M (EQ.) = 50
EQ. Load = 0 kip Pu = 572.25
M (D.L.) = 0 k-ft = 414
M (L.L.) = 0 k-ft = 763
M (EQ.) = 50 k-ft Mu = 70.125
P = 397.5 kip = 71.5
= 460 kip = 0
= 530 kip Pu (Design) = 763
M = 37.5 k-ft Mu (Design) = 71.5
= 50 k-ft Column Size, b = 42
= 0 k-ft h = 12
P (Design) = 530 kip g = 0.881
M (Design) = 50 k-ft e =Mu/P = 1.1245
Column Size, b = 42 in e/h = 0.0937
h = 12 in Pu/f'c b h = 0.5046
as = 0.48 sq-inch. Pu/f'c b hxe/h = 0.0473
No of Bar (pro) = 22 Ptm = 0.4
No of Bar in each face = 6 Ast = 8.568
m = 21.56863 as = 0.48
pg = 0.020952 no.of bar(reqd) = 17.85
pgm = 0.451914 no.of bar(pro) = 22
bh3/12 = 6048 cu-inch. % of steel = 2.0952
2x(2n-1)xAs/2x(t/2-d')2 = 1228.886 cu-inch. Pu = 1074.5
Sut = 1212.814 cu-inch. Pu(pro)/Pu = 1.4083
Fa = 1.480952 ksi. =
Fb = 1.35 ksi. P (B.S. code) = 697.54
fa = 1.051587 ksi. P(pro)/P = 1.5164
fb = 0.494717 ksi.
fa/Fa+fb/Fb = 1.076532
% of steel = 2.095238 %
Pc = 321.3 kip
Ps (pro) = 222.156
P(pro)=Pc+Ps = 543.456 kip > 530 kip
P(pro)/P(actual) = 1.025389
P(pro) B.S. code = 705.456 kip > 530 kip
P(pro B.S.)/P(actual) = 1.331049

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 12 in
h = 42 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 22
As = 10.56 sq-in.
B = 24
C = -2.64
t = 0.1095 in
Z = 1809.713 cu-in
As' = 5.287695
No of Bar (reqd) = 11.01603

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 42 in
h = 12 in
c = 1.5 in
as = 0.48 sq-in.
No of Bar (pro) = 22
As = 10.56 sq-in.
B = 24
C = -2.64
t = 0.1095 in
Z = 181.1295 cu-in
As' = 12.88032
No of Bar (reqd) = 26.83399
CORRECTED DESIGN REVISED
1ST & 2ND. FLOOR

COMPRESION PLUS BENDING (WSD) COMPRESION PLUS BENDING (USD)


DESIGN OF COLUMN - C1(WSD) DESIGN OF COLUMN -C1(USD)
C4 C4
f'c = 3.5 ksi. f'c = 3
fy = 55 ksi. fy = 60
n = 8.525034 Dead Load = 465
k = 0.351703 Live Load = 90
j = 0.882766 EQ. Load = 0
R = 0.244496 M (D.L.) = 0
Dead Load = 465 kip M (L.L.) = 0
Live Load = 90 kip M (EQ.) = 120
EQ. Load = 0 kip Pu = 603
M (D.L.) = 0 k-ft = 418.5
M (L.L.) = 0 k-ft = 804
M (EQ.) = 120 k-ft Mu = 168.3
P = 416.25 kip = 171.6
= 465 kip = 0
= 555 kip Pu (Design) = 804
M = 90 k-ft Mu (Design) = 171.6
= 120 k-ft Column Size, b = 20
= 0 k-ft h = 20
P (Design) = 555 kip g = 0.75
M (Design) = 120 k-ft e =Mu/P = 2.5612
Column Size, b = 20 in e/h = 0.1281
h = 20 in Pu/f'c b h = 0.67
as = 0.58 sq-inch. Pu/f'c b hxe/h = 0.0858
No of Bar (pro) = 22 Ptm = 0.7
No of Bar in each face = 5 Ast = 11.9
m = 18.48739 as = 0.58
pg = 0.0319 no.of bar(reqd) = 20.517
pgm = 0.589748 no.of bar(pro) = 22
bh3/12 = 13333.33 cu-inch. % of steel = 3.19
2x(2n-1)xAs/2x(t/2-d')2 = 5236.335 cu-inch. Pu = 999.94
Sut = 1856.967 cu-inch. Pu(pro)/Pu = 1.2437
Fa = 1.8918 ksi. =
Fb = 1.575 ksi. P (B.S. code) = 654.76
fa = 1.3875 ksi. P(pro)/P = 1.4081
fb = 0.775458 ksi.
fa/Fa+fb/Fb = 1.225783
% of steel = 3.19 %
Pc = 297.5 kip
Ps (pro) = 268.4385
P(pro)=Pc+Ps = 565.9385 kip > 555 kip
P(pro)/P(actual) = 1.019709
P(pro) B.S. code = 722.412 kip > 555 kip
P(pro B.S.)/P(actual) = 1.301643

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 20 in
h = 20 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 22
As = 12.76 sq-in.
B = 17
C = -3.19
t = 0.18562 in
Z = 588.324 cu-in
As' = 10.45909
No of Bar (reqd) = 18.03292

COLUMN DESIGN FOR BUNDLE BAR


COLUMN C1

b = 20 in
h = 20 in
c = 1.5 in
as = 0.58 sq-in.
No of Bar (pro) = 22
As = 12.76 sq-in.
B = 17
C = -3.19
t = 0.18562 in
Z = 588.324 cu-in
As' = 9.795197
No of Bar (reqd) = 16.88827
DESIGN OF BEAM B3 (Single Span)

w 1 k/ft fy = 50
L = 17 ft f = 2.75
Beam Size k = 0.346
10 in j = 0.8847
clear 20 in R = 0.1894
cover = 3.5
d(pro)= 16.5
M = 36.125 k-ft
dreqd = 15.13 in >< 16.5
As = 1.3199
M1 = 42.965
M2 = -6.8402
As1 = 1.5698
As2 = -0.2606 as no. of bar
As=As1+As 1.3092 0.31 4.2233
f's = 13.379 as no. of bar
As' = -0.4382 0.31 -1.4137
V = 8.5 kip
Vd = 7.125 kip
vd = 43.182 psi > 57.684
av = 0.077 sq-in (2 - leg)
Stirrup= -23.892 in. c/c

DESIGN OF BEAM (FOR 2-SPAN)

w1 = 1 k/ft w2 =
L1 = 19.5 ft L2 =

!------------------------------------- !----------------------------------
! 1 0.371 ! 0.629
!------------------------------------- !----------------------------------
! -31.688 31.688 ! -6.6125
! 31.688 15.844 ! -3.3063
! -13.953 ! -23.659
!------------------------------------- !----------------------------------
! M (-) = 33.578 ! -33.578
M (+) = 30.742
31.688

M = 33.578 k-ft fy = 40
b = 5 in. f'c = 2.5
h = 21 in. k = 0.3867
d(pro)= 17.5 j = 0.8711
dreqd = 20.624 in. R = 0.1895
M1 = 24.177 k-ft
M2 = 9.4015 k-ft M = 33.578
As1 = 1.0573 sq-in M = 31.688
As2 = 0.4178 sq-in M = 6.6125
As = 1.4751 sq-in
f's = 14.311 ksi as
A's = 0.5256 sq-in 0.31
V = 9.75 kip
Vd = 8.2917 kip
vd = 94.762 psi > 55
av = 0.11 sq-in
Stirrup= 19.919 in. c/c

DESIGN OF BEAM -B7 (FOR 3-SPAN)

w1 = 2 k/ft w2 =
L1 15 ft L2

!------------------------------------- !----------------------------------
! 1 0.4286 ! 0.5714
!------------------------------------- !----------------------------------
! -37.5 37.5 ! -37.5
! 37.5 18.75 !
! -8.0357 ! -10.714
! ! 5.3571
! -2.2959 ! -3.0612
! ! 1.5306
! -0.656 ! -0.8746
! ! 0.4373
! -0.1874 ! -0.2499
! ! 0.1249
! -0.0535 ! -0.0714
! ! 0.0357
! -0.0153 ! -0.0204
!------------------------------------- !----------------------------------
! M (-) = 45.006 ! -45.006
M (+) = 33.747
37.5
M = 45.006 k-ft fy = 40
b = 5 in. f'c= 2.5
h = 18 in. k = 0.3867
d(pro)= 14.5 in j = 0.8711
dreqd = 23.877 in. R= 0.1895
M1 = 16.598 k-ft
M2 = 28.408 k-ft M = 45.006
As1 = 0.876 sq-in M = 45.006
As2 = 1.5782 sq-in M = 37.5
As = 2.4543 sq-in M = 28.125
f's = 12.576 ksi M = 37.5
A's = 2.259 sq-in
V = 15 kip
Vd = 12.583 kip
vd = 173.56 psi > 55
av = 0.11 sq-in
ON PLUS BENDING (USD) Stirrup= 6.68 in. c/c
COLUMN -C2(USD)

ksi
ksi
kip
kip
kip DESIGN OF BEAM - B9 (FOR 4-SPAN)
k-ft
k-ft w1 = 1.6 k/ft w2 =
k-ft L1 = 18 ft L2 =
kip
kip !------------------------------------- !----------------------------------
kip ! 1 0.4286 ! 0.5714
k-ft !------------------------------------- !----------------------------------
k-ft ! -43.2 43.2 ! -43.2
k-ft ! 43.2 21.6 !
kip ! -9.2571 ! -12.343
k-ft ! ! 0
in ! 0! 0
in ! ! 0
(within 0.6-0.9) ! 0! 0
in. ! ! 0
! 0! 0
! ! 0
! 0! 0
! ! 0
! 0! 0
!------------------------------------- !----------------------------------
! M (-) = 55.543 ! -55.543
M (+) = 37.029
% 43.2
kip > 305 kip
M= 37.029 k-ft fy = 55
b = 10 in. f'c= 3
kip > 235 kip h = 18 in. k = 0.3343
d(pro) = 14.5 in j = 0.8886
dreqd = 14.886 in. R= 0.2005
M1 = 35.134 k-ft
M2 = 1.8947 k-ft = 55.543
As1 = 1.3221 sq-in M = 37.029
As2 = 0.0766 sq-in M = 55.543
As = 1.3987 sq-in M = 43.2
f's = 12.041 ksi M= 32.4
A's = 0.1574 sq-in M = 32.4
V = 14.4 kip M= 43.2
Vd = 12.467 kip
vd = 85.977 psi > 60.249
av = 0.11 sq-in
Stirrup = 21.164 in. c/c

DESIGN OF BEAM -B4(FOR 3-SPAN)

w1 = 1.4 k/ft w2 =
L1 8 ft L2
P = 0 kip P =
X L= 2.5 ft X L=
Mf (L) = 0 k-ft Mf (L) =
Mf (R) = 0 k-ft Mf (R) =
R(R) = 13.317 kip R(R) =
R(L) = -2.1174 kip R(L) =

!------------------------------------- !----------------------------------
! 1 0.6279 ! 0.3721
!------------------------------------- !----------------------------------
! -7.4667 7.4667 ! -76.05
! 7.4667 3.7333 !
! 40.72 ! 24.13
! ! -12.457
! 7.8221 ! 4.6353
! ! -2.567
! 1.6119 ! 0.9552
! ! -0.4931
! 0.3096 ! 0.1835
! ! -0.1016
! 0.0638 ! 0.0378
! ! -0.0195
! 0.0123 ! 0.0073
!------------------------------------- !----------------------------------
M (-) = ! 0 61.739 ! -61.739
M (+) = -19.67
47

M = 61.739 k-ft fy = 50
b       10 in. f'c= 2.5
ON PLUS BENDING (USD) h       24 in. k = 0.3353
COLUMN -C3(USD) d(pro)= 20.5 in j = 0.8882
dreqd = 21.031 in. R= 0.1675
ksi M1 = 58.663 k-ft
ksi M2 = 3.0764 k-ft M = 61.739
kip As1 = 1.7182 sq-in M = 59.735
kip As2 = 0.0912 sq-in M = 47
kip As = 1.8094 sq-in M = 76
k-ft f's = 14.44 ksi M = 11.667
k-ft A's = 0.142 sq-in
k-ft V = 5.6 kip
kip Vd = 3.2083 kip
kip vd = 15.65 psi > 55
kip av = 0.11 sq-in
k-ft Stirrup= -12.58 in. c/c
k-ft
k-ft
kip
k-ft
in
in
(within 0.6-0.9)
in.

DESIGN OF BEAM - B2 (FOR 6-SPAN)

w1 = 2.5 k/ft w2 =
L1 18 ft L2
P =
X L=
Mf (L) =
% Mf (R) =
kip > 343 kip R(R) =
R(L) =
kip > 265 kip !------------------------------------- !----------------------------------
! 1 0.4286 ! 0.5714
!------------------------------------- !----------------------------------
! -67.5 67.5 ! -67.5
! 67.5 33.75 !
! -14.464 ! -19.286
! ! 0
! 0! 0
! ! 2.4107
! -1.0332 ! -1.3776
! ! 0
! 0! 0
! ! 0.1722
! -0.0738 ! -0.0984
! ! 0
! 0! 0
!------------------------------------- !----------------------------------
! M (-) = 85.679 ! -85.679
M (+) = 58.411
67.5

M= 62.31 k-ft fy = 60
b = 10 in. f'c= 3
h = 21 in. k = 0.3153
d(pro) = 17.5 in j = 0.8949
dreqd = 19.815 in. R= 0.1904
M1 = 48.601 k-ft
M2 = 13.708 k-ft = 85.679
As1 = 1.3793 sq-in M = 62.31
As2 = 0.4062 sq-in M = 70.083
As = 1.7854 sq-in M = 67.5
f's = 13.596 ksi M= 50.625
A's = 0.8066 sq-in M = 50.625
V = 22.5 kip M= 50.625
Vd = 18.854 kip
vd = 107.74 psi > 60.249
av = 0.11 sq-in
Stirrup = 12.508 in. c/c

DESIGN OF BEAM B-5 (Single Span)

w 5 k/ft fy = 40
L = 11 ft f = 2.5
Beam Size k = 0.3867
7 in j = 0.8711
48 in R = 0.1895
d(pro)= 44.5
M = 75.625 k-ft
dreqd= 26.158 in >< 44.5
ON PLUS BENDING (USD) M1 = 218.86
COLUMN -C4(USD) M2 = -143.24
As1 = 3.764
ksi As2 = -2.2736 as no. of bar
ksi 1.4904 0.31 4.8076
kip f's 19.398 as no. of bar
kip As' = -2.1097 0.31 -6.8056
kip V = 27.5 kip
k-ft Vd = 8.9583 kip
k-ft vd = 28.759 psi > 55
k-ft av = 0.11 sq-in (2 - leg)
kip Stirrup= -21.558 in. c/c
kip
kip
k-ft
k-ft DESIGN OF BEAM B-6 (Single Span)
k-ft
kip w 2.8 k/ft fy = 40
k-ft L = 19 ft f = 3
in Beam Size k = 0.4085
in 10 in j = 0.8638
(within 0.6-0.9) 24 in R = 0.2382
in. d(pro)= 20.5
M = 126.35 k-ft
dreqd= 25.23 in >< 20.5
M1 = 83.416
M2 = 42.934
As1 = 3.1403
As2 = 1.5902 as no. of bar
4.7305 0.48 9.8551
f's 17.44 as no. of bar
% As' = 1.6412 0.31 5.2943
kip > 364 kip V = 26.6 kip
Vd = 21.817 kip
vd = 106.42 psi > 60.249
kip > 285 kip av = 0.11 sq-in (2 - leg)
Stirrup= 8.5764 in. c/c
DESIGN OF BEAM - B7 (FOR 5-SPAN)

w1 = 2.2 k/ft w2 =
L1 21.75 ft L2

!------------------------------------- !----------------------------------
! 1 0.352 ! 0.648
!------------------------------------- !----------------------------------
! -86.728 86.728 ! -28.941
! 86.728 43.364 !
! -35.601 ! -65.551
! ! 2.7664
! -0.9736 ! -1.7928
! ! 9.5077
! -3.3463 ! -6.1614
! ! 0.8731
! -0.3073 ! -0.5658
! ! 1.4017
! -0.4933 ! -0.9084
! ! 0.1725
! -0.0607 ! -0.1118
!------------------------------------- !----------------------------------
! M (-) = 89.31 ! -89.31
M (+) = 85.437
86.728

M= 37.655 k-ft fy = 55
b = 10 in. f'c= 3
h = 18 in. k = 0.3343
d(pro) = 14.5 in j = 0.8886
dreqd = 15.011 in. R= 0.2005
M1 = 35.134 k-ft
M2 = 2.5211 k-ft = 89.31
As1 = 1.3221 sq-in M= 21.38
As2 = 0.1019 sq-in M= 35.209
As = 1.424 sq-in M= 86.728
f's = 12.041 ksi M= 21.705
A's = 0.2094 sq-in M= 29.537
V = 23.925 kip M= 19.52
Vd = 21.267 kip
vd = 146.67 psi > 60.249
ON PLUS BENDING (USD) av = 0.11 sq-in
COLUMN -C5(USD) Stirrup = 6.3008 in. c/c

ksi
ksi
kip
kip
kip DESIGN OF BEAM B8 (FOR 2-SPAN)
k-ft
k-ft w1 = 1.9 k/ft w2 =
k-ft L1 17 ft L2
kip
kip !------------------------------------- !----------------------------------
kip ! 1 0.5952 ! 0.4048
k-ft !------------------------------------- !----------------------------------
k-ft ! -45.758 45.758 ! -112
k-ft ! 45.758 22.879 ! -55.99
kip ! 59.126 ! 40.206
k-ft !------------------------------------- !----------------------------------
in ! M (-) = 127.76 ! -127.76
in M (+) = 4.7559
(within 0.6-0.9) 45.758
in.
M = 127.76 k-ft fy = 60
b = 10 in. f'c = 3
h = 24 in. k = 0.3153
d(pro)= 20.5 j = 0.8949
dreqd= 28.374 in. R = 0.1904
M1 = 66.693 k-ft
M2 = 61.071 k-ft = 127.76
As1 = 1.6157 sq-in M = 45.758
% As2 = 1.5079 sq-in M = 111.98
kip > 347 kip As = 3.1236 sq-in
f's = 15.245 ksi as
A's = 2.6707 sq-in 0.48
kip > 275 kip V = 16.15 kip
Vd = 12.904 kip
vd = 62.947 psi > 60.249
av = 0.11 sq-in
Stirrup= 220.19 in. c/c
DESIGN OF BEAM -B10(FOR 3-SPAN)

w1 = 1.75 k/ft w2 =
L1 8.5 ft L2
P = 0 kip P =
X L= 0 ft X L=
Mf (L) = 0 k-ft Mf (L) =
Mf (R) = 0 k-ft Mf (R) =
R(R) = 10.241 kip R(R) =
R(L) = 4.6343 kip R(L) =

!------------------------------------- !----------------------------------
! 1 0.4286 ! 0.5714
!------------------------------------- !----------------------------------
! -10.536 10.536 ! -29.183
! 10.536 5.2682 !
! 5.7337 ! 7.6449
! ! -3.8225
! 1.6382 ! 2.1843
! ! -1.0921
! 0.4681 ! 0.6241
! ! -0.312
! 0.1337 ! 0.1783
! ! -0.0892
! 0.0382 ! 0.0509
! ! -0.0255
! 0.0109 ! 0.0146
!------------------------------------- !----------------------------------
! 0 23.828 ! -23.828
3.8909
47

M = 23.828 k-ft fy = 60
b       10 in. f'c= 3
h       24 in. k = 0.3153
d(pro)= 20.5 in j = 0.8949
dreqd = 12.253 in. R= 0.1904
M1 = 66.693 k-ft
M2 = -42.865 k-ft M = 23.828
As1 = 1.6157 sq-in M = 23.828
ON PLUS BENDING (USD) As2 = -1.0584 sq-in M = 47
COLUMN -C6(USD) As = 0.5573 sq-in M = 110
f's = 15.245 ksi M = 10.536
ksi A's = -1.8746 sq-in 0.48
ksi V = 7.4375 kip
kip Vd = 4.4479 kip
kip vd = 21.697 psi > 60.249
kip av = 0.11 sq-in
k-ft Stirrup= -15.408 in. c/c
k-ft
k-ft
kip
kip
kip DESIGN OF BEAM B-12(Single Span)
k-ft
k-ft w 1.1 k/ft fy = 40
k-ft L = 24 ft f = 2.5
kip Beam Size k = 0.3867
k-ft 12 in j = 0.8711
in 21 in R = 0.1895
in d(pro)= 17.5
(within 0.6-0.9) M = 79.2 k-ft
in. dreqd= 20.445 in >< 17.5
M1 = 58.024
M2 = 21.176
As1 = 2.5375
As2 = 0.9411 as no. of bar
3.4786 0.58 5.9977
f's 14.311 as no. of bar
As' = 1.1838 0.48 2.4662
V = 13.2 kip
% Vd = 11.596 kip
kip > 460 kip vd = 55.218 psi > 55
av = 0.11 sq-in (2 - leg)
Stirrup= 1512 in. c/c
kip > 355 kip

DESIGN OF BEAM - B13 (FOR 2-SPAN)

w1 = 1.85 k/ft w2 =
L1 15 ft L2

!------------------------------------- !----------------------------------
! 1 0.5489 ! 0.4511
!------------------------------------- !----------------------------------
! -34.688 34.688 ! -55.51
! 34.688 17.344 ! -27.755
! 17.144 ! 14.091
!------------------------------------- !----------------------------------
! M (-) = 69.175 ! -69.175
M (+) = 17.444
34.688

M = 69.175 k-ft fy = 55
b = 10 in. f'c = 2.75
h = 21 in. k = 0.3247
d(pro)= 17.5 j = 0.8918
dreqd= 21.524 in. R = 0.1792
M1 = 45.727 k-ft
M2 = 23.448 k-ft = 69.175
As1 = 1.4207 sq-in M = 34.688
As2 = 0.7579 sq-in M = 55.51
As = 2.1786 sq-in
f's = 13.331 ksi as
A's = 1.4071 sq-in 0.48
V = 13.875 kip
Vd = 11.177 kip
vd = 63.869 psi > 57.684
av = 0.11 sq-in
Stirrup= 88.042 in. c/c

DESIGN OF BEAM - B15 (FOR 6-SPAN)

w1 = 2.15 k/ft w2 =
L1 16.75 ft L2
P =
X L=
Mf (L) =
Mf (R) =
R(R) =
R(L) =
ON PLUS BENDING (USD)
COLUMN -C7(USD) !------------------------------------- !----------------------------------
! 1 0.4212 ! 0.5788
ksi !------------------------------------- !----------------------------------
ksi ! -50.267 50.267 ! -47.311
kip ! 50.267 25.134 !
kip ! -11.831 ! -16.259
kip ! ! 0
k-ft ! 0! 0
k-ft ! ! 3.4826
k-ft ! -1.4667 ! -2.0158
kip ! ! 0.5506
kip ! -0.2319 ! -0.3187
kip ! ! 0.3269
k-ft ! -0.1377 ! -0.1892
k-ft ! ! 0.1542
k-ft ! -0.065 ! -0.0893
kip !------------------------------------- !----------------------------------
k-ft ! M (-) = 61.669 ! -61.669
in M (+) = 44.566
in 50.267
(within 0.6-0.9)
in. M= 20.994 k-ft fy = 60
b = 10 in. f'c= 3
h = 24 in. k = 0.3153
d(pro) = 20.5 in j = 0.8949
dreqd = 11.502 in. R= 0.1904
M1 = 66.693 k-ft
M2 = -45.698 k-ft = 61.669
As1 = 1.6157 sq-in M = 47.033
As2 = -1.1283 sq-in M = 33.96
% As = 0.4873 sq-in M = 50.267
kip > 474 kip f's = 15.245 ksi M= 35.483
A's = -1.9984 sq-in M = 35.483
V = 18.006 kip M= 6.5844
kip > 350 kip Vd = 14.333 kip
vd = 69.919 psi > 60.249
av = 0.11 sq-in
Stirrup = 61.432 in. c/c

DESIGN OF BEAM -B18(FOR 3-SPAN)

w1 = 1.8 k/ft w2 =
L1 17.5 ft L2
P1 = 0 kip P1 =
X L1= 0 ft X L1=
P2 =
X L2=
Mf (L) = 0 k-ft Mf (L) =
Mf (R) = 0 k-ft Mf (R) =
R(R) = 20.451 kip R(R) =
R(L) = 11.049 kip R(L) =

!------------------------------------- !----------------------------------
! 1 0.3913 ! 0.6087
!------------------------------------- !----------------------------------
! -45.938 45.938 ! -88.125
! 45.938 22.969 !
! 7.5204 ! 11.698
! ! -13.227
! 5.1757 ! 8.051
! ! -0.9603
! 0.3758 ! 0.5845
! ! -0.6609
! 0.2586 ! 0.4023
! ! -0.048
! 0.0188 ! 0.0292
! ! -0.033
! 0.0129 ! 0.0201
!------------------------------------- !----------------------------------
! 0 82.268 ! -82.268
27.772
41

M = 68.645 k-ft fy = 60
b       10 in. f'c= 3
h       24 in. k = 0.3153
d(pro)= 20.5 in j = 0.8949
dreqd = 20.798 in. R= 0.1904
M1 = 66.693 k-ft
M2 = 1.9525 k-ft M = 82.268
As1 = 1.6157 sq-in M = 68.645
As2 = 0.0482 sq-in M = 41
As = 1.6639 sq-in M = 80
f's = 15.245 ksi M = 22
A's = 0.0854 sq-in 0.48
ON PLUS BENDING (USD) V = 15.75 kip
COLUMN -C8(USD) Vd = 12.675 kip
vd = 61.829 psi > 60.249
ksi av = 0.11 sq-in
ksi Stirrup= 376 in. c/c
kip
kip
kip
k-ft
k-ft
k-ft
kip
kip
kip
k-ft DESIGN OF BEAM - B21 (FOR 5-SPAN)
k-ft
k-ft w1 = 0 k/ft w2 =
kip L1 0 ft L2
k-ft P =
in X L=
in Mf (L) =
(within 0.6-0.9) Mf (R) =
in. R(R) =
R(L) =

!------------------------------------- !----------------------------------
! 1 1! 0
!------------------------------------- !----------------------------------
! 0 0! -32.76
! 0 0!
! 32.76 ! 0
% ! ! -0.094
kip > 390 kip ! 0.094 ! 0
! ! 0.0486
! -0.0486 ! 0
kip > 310 kip ! ! 2.5952
! -2.5952 ! 0
! ! 0.0082
! -0.0082 ! 0
! ! 0.4355
! -0.4355 ! 0
!------------------------------------- !----------------------------------
! M (-) = 29.767 ! -29.767
M (+) = -14.883
0

M= 121.99 k-ft fy = 40
b = 12 in. f'c= 2.5
h = 21 in. k = 0.3867
d(pro) = 17.5 in j = 0.8711
dreqd = 25.374 in. R = 0.1895
M1 = 58.024 k-ft
M2 = 63.964 k-ft = 29.767
As1 = 2.5375 sq-in M = 27.48
As2 = 2.8428 sq-in M = -0.6201
As = 5.3803 sq-in M = 121.99
f's = 14.311 ksi M= 14.068
A's = 3.5758 sq-in M = 15.844
V = 0 kip M= 76.633
Vd = 0 kip
vd = 0 psi > 55
av = 0.11 sq-in
Stirrup = -6 in. c/c
DESIGN OF BEAM - B23 (FOR 2-SPAN)

w1 = 1.85 k/ft w2 =
L1 13 ft L2
P1 =
X L1=
P2 =
X L2=
Mf (L) =
Mf (R) =
R(R) =
R(L) =

!------------------------------------- !----------------------------------
! 1 0.5 ! 0.5
!------------------------------------- !----------------------------------
! -26.054 26.054 ! -26.054
! 26.054 13.027 ! -13.027
! 0! 0
!------------------------------------- !----------------------------------
! M (-) = 39.081 ! -39.081
ON PLUS BENDING (USD) M (+) = 19.541
COLUMN -C9(USD) 26.054

ksi M = 39.081 k-ft fy = 60


ksi b = 12 in. f'c = 3
kip h = 24 in. k = 0.3153
kip d(pro)= 20.5 j = 0.8949
kip dreqd= 14.325 in. R = 0.1904
k-ft M1 = 80.031 k-ft
k-ft M2 = -40.95 k-ft = 39.081
k-ft As1 = 1.9388 sq-in M = 26.054
kip As2 = -1.0111 sq-in M = 26.054
kip As = 0.9277 sq-in
kip f's = 15.245 ksi as
k-ft A's = -1.7908 sq-in 0.48
k-ft V = 12.025 kip
k-ft Vd = 8.8646 kip
kip vd = 36.035 psi > 60.249
k-ft av = 0.11 sq-in
in Stirrup= -20.442 in. c/c
in
(within 0.6-0.9)
in.

DESIGN OF BEAM B-25(Single Span)

w 1.7 k/ft fy = 60
% L = 24.5 ft f = 3
kip > 1059 kip Beam Size k = 0.3153
10 in j = 0.8949
24 in R = 0.1904
kip > 635 kip d(pro)= 20.5
M = 127.55 k-ft
dreqd= 28.35 in >< 20.5
M1 = 66.693
M2 = 60.86
As1 = 1.6157
As2 = 1.5027 as no. of bar
3.1184 0.58 5.3766
f's 15.245 as no. of bar
As' = 2.6615 0.48 5.5448
V = 20.825 kip
Vd = 17.921 kip
vd = 87.419 psi > 60.249
av = 0.11 sq-in (2 - leg)
Stirrup= 21.863 in. c/c

DESIGN OF BEAM - B26 (FOR 2-SPAN)

w1 = 2.8 k/ft w2 =
L1 14.5 ft L2

!------------------------------------- !----------------------------------
! 1 0.4727 ! 0.5273
!------------------------------------- !----------------------------------
! -49.058 49.058 ! -26.758
! 49.058 24.529 ! -13.379
! -15.813 ! -17.637
!------------------------------------- !----------------------------------
! M (-) = 57.775 ! -57.775
M (+) = 44.7
49.058

M = 57.775 k-ft fy = 60
b = 10 in. f'c = 3
h = 24 in. k = 0.3153
d(pro)= 20.5 j = 0.8949
dreqd= 19.08 in. R = 0.1904
M1 = 66.693 k-ft
M2 = -8.9179 k-ft = 57.775
As1 = 1.6157 sq-in M = 49.058
As2 = -0.2202 sq-in M = 26.758
As = 1.3955 sq-in
f's = 15.245 ksi as
A's = -0.39 sq-in 0.48
V = 20.3 kip
Vd = 15.517 kip
vd = 75.691 psi > 60.249
av = 0.11 sq-in
Stirrup= 38.468 in. c/c

ON PLUS BENDING (USD)


COLUMN -C10(USD)

ksi
ksi
kip
kip
kip
k-ft
k-ft
k-ft
kip
kip
kip
k-ft
k-ft
k-ft
kip
k-ft
in
in
(within 0.6-0.9)
in.
DESIGN OF BEAM -B7 (FOR 3-SPAN)
w1 = 1.6 k/ft w2 =
L1 10.5 ft L2

!------------------------------------- !----------------------------------
! 1 0.5556 ! 0.4444
!------------------------------------- !----------------------------------
% ! -14.7 14.7 ! -61.25
kip > 293 kip ! 14.7 7.35 !
! 21.778 ! 17.422
! ! -8.7111
kip > 230 kip ! 4.8395 ! 3.8716
! ! -1.9358
! 1.0754 ! 0.8604
! ! -0.4302
! 0.239 ! 0.1912
! ! -0.0956
! 0.0531 ! 0.0425
! ! -0.0212
! 0.0118 ! 0.0094
!------------------------------------- !----------------------------------
! M (-) = 50.047 ! -50.047
M (+) = -2.9733
14.7

M = 50.047 k-ft fy = 55
b       10 in. f'c= 3
h       21 in. k = 0.3343
d(pro)= 17.5 in j = 0.8886
dreqd = 17.306 in. R= 0.2005
M1 = 51.176 k-ft
M2 = -1.1293 k-ft M = 50.047
As1 = 1.5957 sq-in M = 50.047
As2 = -0.0365 sq-in M = 14.7
As = 1.5592 sq-in M = 45.938
f's = 14.239 ksi M = 14.7
A's = -0.0635 sq-in
V = 8.4 kip
Vd = 6.0667 kip
vd = 34.667 psi > 60.249
av = 0.11 sq-in
Stirrup= -21.284 in. c/c

DESIGN OF BEAM - B8 (FOR 2-SPAN)


w1 = 2 k/ft w2 =
L1 12.5 ft L2

!------------------------------------- !----------------------------------
! 1 0.5 ! 0.5
!------------------------------------- !----------------------------------
! -26.042 26.042 ! -26.042
! 26.042 13.021 ! -13.021
! 0! 0
!------------------------------------- !----------------------------------
! M (-) = 39.063 ! -39.063
M (+) = 19.531
26.042

M = 39.063 k-ft fy = 40
b = 10 in. f'c = 2.5
ON PLUS BENDING (USD) h = 21 in. k = 0.3867
COLUMN -C1(USD) d(pro)= 17.5 j = 0.8711
dreqd= 15.729 in. R = 0.1895
ksi M1 = 48.353 k-ft
ksi M2 = -9.291 k-ft = 39.063
kip As1 = 2.1146 sq-in M = 26.042
kip As2 = -0.4129 sq-in M = 26.042
kip As = 1.7017 sq-in
k-ft f's = 14.311 ksi as
k-ft A's = -0.5194 sq-in 0.48
k-ft V = 12.5 kip
kip Vd = 9.5833 kip
kip vd = 54.762 psi > 55
kip av = 0.11 sq-in
k-ft Stirrup= -1663.2 in. c/c
k-ft
k-ft
kip
k-ft
in DESIGN OF BEAM -B8 (FOR 3-SPAN)
in
(within 0.6-0.9) w1 = 1.9 k/ft w2 =
in. L1 13 ft L2

!------------------------------------- !----------------------------------
! 1 0.4555 ! 0.5445
!------------------------------------- !----------------------------------
! -26.758 26.758 ! -49.058
! 26.758 13.379 !
! 4.0634 ! 4.8574
! ! -2.4287
% ! 1.1063 ! 1.3224
kip > 412 kip ! ! -0.6612
! 0.3012 ! 0.36
! ! -0.18
kip > 325 kip ! 0.082 ! 0.098
! ! -0.049
! 0.0223 ! 0.0267
! ! -0.0133
! 0.0061 ! 0.0073
!------------------------------------- !----------------------------------
! M (-) = 45.719 ! -45.719
M (+) = 17.278
26.758

M = 45.719 k-ft fy = 40
b       10 in. f'c= 2.5
h       21 in. k = 0.3867
d(pro)= 17.5 in j = 0.8711
dreqd = 17.017 in. R= 0.1895
M1 = 48.353 k-ft
M2 = -2.6347 k-ft M = 45.719
As1 = 2.1146 sq-in M = 45.719
As2 = -0.1171 sq-in M = 26.758
As = 1.9975 sq-in M = 36.794
f's = 14.311 ksi M = 26.758
A's = -0.1473 sq-in
V = 12.35 kip
Vd = 9.5792 kip
vd = 54.738 psi > 55
av = 0.11 sq-in
Stirrup= -1512 in. c/c

DESIGN OF BEAM -B9 (FOR 3-SPAN)

w1 = 1.5 k/ft w2 =
L1 7.5 ft L2

!------------------------------------- !----------------------------------
! 1 0.5833 ! 0.4167
!------------------------------------- !----------------------------------
! -7.0313 7.0313 ! -26.133
! 7.0313 3.5156 !
! 9.0921 ! 6.4944
! ! 11.531
! -6.7262 ! -4.8044
! ! -1.0093
! 0.5887 ! 0.4205
! ! 0.7466
! -0.4355 ! -0.3111
! ! -0.0654
! 0.0381 ! 0.0272
! ! 0.0483
! -0.0282 ! -0.0201
!------------------------------------- !----------------------------------
! M (-) = 13.076 ! -13.076
M (+) = 4.0089
7.0313
ON PLUS BENDING (USD)
COLUMN -C1(USD) M = 49.54 k-ft fy = 40
b       10 in. f'c= 2.5
ksi h       24 in. k = 0.3867
ksi d(pro)= 20.5 in j = 0.8711
kip dreqd = 17.713 in. R= 0.1895
kip M1 = 66.353 k-ft
kip M2 = -16.813 k-ft M = 13.076
k-ft As1 = 2.4771 sq-in M = 49.54
k-ft As2 = -0.6227 sq-in M = 7.0313
k-ft As = 1.8544 sq-in M = 19.6
kip f's = 15.538 ksi M = 42.155
kip A's = -0.7214 sq-in
kip V = 5.625 kip
k-ft Vd = 3.0625 kip
k-ft vd = 14.939 psi > 55
k-ft av = 0.11 sq-in
kip Stirrup= -9.8849 in. c/c
k-ft
in
in
(within 0.6-0.9) DESIGN OF BEAM - B9 (FOR 4-SPAN)
in.
w1 = 2.1 k/ft w2 =
L1 9 ft L2

!------------------------------------- !----------------------------------
! 1 0.4545 ! 0.5455
!------------------------------------- !----------------------------------
! -14.175 14.175 ! -17.5
! 14.175 7.0875 !
% ! -1.7102 ! -2.0523
kip > 522 kip ! ! 26.163
! -11.892 ! -14.27
! ! 4.5986
kip > 375 kip ! -2.0903 ! -2.5083
! ! 3.2139
! -1.4608 ! -1.753
! ! 0.5649
! -0.2568 ! -0.3081
! ! 0.3948
! -0.1795 ! -0.2153
!------------------------------------- !----------------------------------
! M (-) = 3.6729 ! -3.6729
M (+) = 19.426
14.175

M= 77.062 k-ft fy = 50
b = 10 in. f'c= 2.5
h = 24 in. k = 0.3353
d(pro) = 20.5 in j = 0.8882
dreqd = 23.496 in. R= 0.1675
M1 = 58.663 k-ft
M2 = 18.399 k-ft = 3.6729
As1 = 1.7182 sq-in M = 77.062
As2 = 0.5452 sq-in M = 77.851
As = 2.2634 sq-in M = 14.175
f's = 14.44 ksi M= 13.125
A's = 0.8494 sq-in M = 69.431
V = 9.45 kip M= 17.5
Vd = 5.8625 kip
vd = 28.598 psi > 55
av = 0.11 sq-in
Stirrup =-18.748 in. c/c

DESIGN OF BEAM - B10 (FOR 5-SPAN)

w1 = 0 k/ft w2 =
L1 100000 ft L2
P =
X L=
Mf (L) =
Mf (R) =
R(R) =
R(L) =

!------------------------------------- !----------------------------------
! 1 5E-05 ! 1
!------------------------------------- !----------------------------------
! 0 0 ! -31.542
! 0 0!
! 0.0015 ! 31.54
! ! -1.1067
! 5E-05 ! 1.1067
! ! -4.4338
! 0.0002 ! 4.4336
ON PLUS BENDING (USD) ! ! -0.2334
COLUMN -C1(USD) ! 1E-05 ! 0.2334
! ! -0.8419
ksi ! 4E-05 ! 0.8418
ksi ! ! -0.0513
kip ! 2E-06 ! 0.0513
kip !------------------------------------- !----------------------------------
kip ! M (-) = 0.0019 ! -0.0019
k-ft M (+) = -0.0009
k-ft 0
k-ft
kip M= 22.574 k-ft fy = 40
kip b = 12 in. f'c= 2.5
kip h = 24 in. k = 0.3867
k-ft d(pro) = 20.5 in j = 0.8711
k-ft dreqd = 10.915 in. R= 0.1895
k-ft M1 = 79.623 k-ft
kip M2 = -57.05 k-ft = 0.0019
k-ft As1 = 2.9725 sq-in M = 19.53
in As2 = -2.113 sq-in M = 8.2052
in As = 0.8595 sq-in M = 22.574
(within 0.6-0.9) f's = 15.538 ksi M= 5.0172
in. A's = -2.4478 sq-in M = 7.6
V = 0 kip M= 14.29
Vd = 0 kip
vd = 0 psi > 55
av = 0.11 sq-in
Stirrup = -6 in. c/c

% DESIGN OF BEAM - B11 (FOR 2-SPAN)


kip > 610 kip
w1 = 1.45 k/ft w2 =
L1 9 ft L2
kip > 435 kip
!------------------------------------- !----------------------------------
! 1 0.5714 ! 0.4286
!------------------------------------- !----------------------------------
! -9.7875 9.7875 ! -21
! 9.7875 4.8938 ! -10.5
! 9.6107 ! 7.208
!------------------------------------- !----------------------------------
! M (-) = 24.292 ! -24.292
M (+) = 2.5353
9.7875

M = 24.292 k-ft fy = 40
b = 10 in. f'c = 2.5
h = 21 in. k = 0.3867
d(pro)= 17.5 j = 0.8711
dreqd= 12.404 in. R = 0.1895
M1 = 48.353 k-ft
M2 = -24.062 k-ft = 24.292
As1 = 2.1146 sq-in M = 9.7875
As2 = -1.0694 sq-in M = 21
As = 1.0452 sq-in
f's = 14.311 ksi as
A's = -1.3451 sq-in 0.48
V = 6.525 kip
Vd = 4.4104 kip
vd = 25.202 psi > 55
av = 0.11 sq-in
Stirrup= -13.29 in. c/c

DESIGN OF BEAM B-12(Single Span)

w 2.5 k/ft fy = 40
L = 21 ft f = 2.5
Beam Size k = 0.3867
10 in j = 0.8711
24 in R = 0.1895
d(pro)= 20.5
M = 137.81 k-ft
dreqd= 29.544 in >< 20.5
M1 = 66.353
M2 = 71.46
As1 = 2.4771
As2 = 2.6467 as no. of bar
5.1237 0.58 8.834
f's 15.538 as no. of bar
As' = 3.0661 0.48 6.3877
V = 26.25 kip
Vd = 21.979 kip
ON PLUS BENDING (USD) vd = 107.22 psi > 55
COLUMN -C1(USD) av = 0.11 sq-in (2 - leg)
Stirrup= 7.584 in. c/c
ksi
ksi
kip
kip
kip DESIGN OF BEAM B-13(Single Span)
k-ft
k-ft w 2.7 k/ft fy = 40
k-ft L = 22.5 ft f = 2.5
kip Beam Size k = 0.3867
kip 10 in j = 0.8711
kip 30 in R = 0.1895
k-ft d(pro)= 26.5
k-ft M = 170.86 k-ft
k-ft dreqd= 32.896 in >< 26.5
kip M1 = 110.88
k-ft M2 = 59.982
in As1 = 3.2021
in As2 = 1.6662 as no. of bar
(within 0.6-0.9) 4.8682 0.58 8.3935
in. f's 17.158 as no. of bar
As' = 1.7479 0.48 3.6414
V = 30.375 kip
Vd = 24.413 kip
vd = 92.123 psi > 55
av = 0.11 sq-in (2 - leg)
Stirrup= 10.667 in. c/c

%
kip > 722.5 kip

kip > 425 kip


DESIGN OF BEAM -B14 (FOR 3-SPAN)

w1 = 2.2 k/ft w2 =
L1 12 ft L2

!------------------------------------- !----------------------------------
! 1 0.4921 ! 0.5079
!------------------------------------- !----------------------------------
! -26.4 26.4 ! -44.046
! 26.4 13.2 !
! 2.1876 ! 2.2582
! ! 18.659
! -9.1815 ! -9.4777
! ! -0.3467
! 0.1706 ! 0.1761
! ! 1.4551
ON PLUS BENDING (USD) ! -0.716 ! -0.7391
COLUMN -C1(USD) ! ! -0.027
! 0.0133 ! 0.0137
ksi ! ! 0.1135
ksi ! -0.0558 ! -0.0576
kip !------------------------------------- !----------------------------------
kip ! M (-) = 32.018 ! -32.018
kip M (+) = 23.591
k-ft 26.4
k-ft
k-ft M = 79.865 k-ft fy = 40
kip b       10 in. f'c= 2.5
kip h       21 in. k = 0.3867
kip d(pro)= 17.5 in j = 0.8711
k-ft dreqd = 22.491 in. R= 0.1895
k-ft M1 = 48.353 k-ft
k-ft M2 = 31.512 k-ft M = 32.018
kip As1 = 2.1146 sq-in M = 79.865
k-ft As2 = 1.4005 sq-in M = 26.4
in As = 3.5151 sq-in M = 33.034
in f's = 14.311 ksi M = 69.876
(within 0.6-0.9) A's = 1.7616 sq-in
in. V = 13.2 kip
Vd = 9.9917 kip
vd = 57.095 psi > 55
av = 0.11 sq-in
Stirrup= 189 in. c/c

DESIGN OF BEAM - B15 (FOR 4-SPAN)


%
kip > 808 kip w1 = 2 k/ft w2 =
L1 13 ft L2

kip > 480 kip !------------------------------------- !----------------------------------


! 1 0.4721 ! 0.5279
!------------------------------------- !----------------------------------
! -28.167 28.167 ! -43.045
! 28.167 14.083 !
! 0.3752 ! 0.4196
! ! 7.2997
! -3.446 ! -3.8536
! ! 0.8724
! -0.4118 ! -0.4606
! ! 0.9493
! -0.4482 ! -0.5012
! ! 0.1135
! -0.0536 ! -0.0599
! ! 0.1235
! -0.0583 ! -0.0652
!------------------------------------- !----------------------------------
! M (-) = 38.207 ! -38.207
M (+) = 23.146
28.167

M= 66.877 k-ft fy = 40
b = 10 in. f'c= 2.5
h = 21 in. k = 0.3867
d(pro) = 17.5 in j = 0.8711
dreqd = 20.581 in. R= 0.1895
M1 = 48.353 k-ft
M2 = 18.524 k-ft = 38.207
As1 = 2.1146 sq-in M = 59.563
As2 = 0.8233 sq-in M = 66.877
As = 2.9379 sq-in M = 28.167
f's = 14.311 ksi M= 32.284
A's = 1.0355 sq-in M = 52.407
V = 13 kip M= 37.67
Vd = 10.083 kip
vd = 57.619 psi > 55
av = 0.11 sq-in
Stirrup = 151.2 in. c/c

DESIGN OF BEAM -B10 (FOR 3-SPAN)

w1 = 2.4 k/ft w2 =
L1 18.5 ft L2

ON PLUS BENDING (USD) !------------------------------------- !----------------------------------


COLUMN -C1(USD) ! 1 0.4219 ! 0.5781
!------------------------------------- !----------------------------------
ksi ! -68.45 68.45 ! -64.8
ksi ! 68.45 34.225 !
kip ! -15.979 ! -21.896
kip ! ! 1.9442
kip ! -0.8202 ! -1.124
k-ft ! ! 2.9258
k-ft ! -1.2343 ! -1.6915
k-ft ! ! 0.1502
kip ! -0.0634 ! -0.0868
kip ! ! 0.226
kip ! -0.0954 ! -0.1307
k-ft ! ! 0.0116
k-ft ! -0.0049 ! -0.0067
k-ft !------------------------------------- !----------------------------------
kip ! M (-) = 84.478 ! -84.478
k-ft M (+) = 60.436
in 68.45
in
(within 0.6-0.9) M = 84.478 k-ft fy = 40
in. b       10 in. f'c= 2.5
h       24 in. k = 0.3867
d(pro)= 20.5 in j = 0.8711
dreqd = 23.131 in. R= 0.1895
M1 = 66.353 k-ft
M2 = 18.126 k-ft M = 84.478
As1 = 2.4771 sq-in M = 62.886
As2 = 0.6713 sq-in M = 68.45
As = 3.1484 sq-in M = 48.6
% f's = 15.538 ksi M = 48.05
kip > 923 kip A's = 0.7777 sq-in
V = 22.2 kip
Vd = 18.1 kip
kip > 550 kip vd = 88.293 psi > 55
av = 0.11 sq-in
Stirrup= 11.895 in. c/c

DESIGN OF BEAM -B10 (FOR 3-SPAN)

w1 = 2.4 k/ft w2 =
L1 15.5 ft L2

!------------------------------------- !----------------------------------
! 1 0.5267 ! 0.4733
!------------------------------------- !----------------------------------
! -48.05 48.05 ! -130
! 48.05 24.025 !
! 30.534 ! 27.437
! ! 8.9416
! -4.7097 ! -4.2319
! ! -3.7658
! 1.9835 ! 1.7823
! ! 0.5808
! -0.3059 ! -0.2749
! ! -0.2446
! 0.1288 ! 0.1158
! ! 0.0377
! -0.0199 ! -0.0179
!------------------------------------- !----------------------------------
! M (-) = 99.686 ! -99.686
M (+) = 22.232
48.05

M = 153.53 k-ft fy = 40
b       10 in. f'c= 2.5
h       30 in. k = 0.3867
d(pro)= 26.5 in j = 0.8711
dreqd = 31.183 in. R= 0.1895
M1 = 110.88 k-ft
M2 = 42.65 k-ft M = 99.686
As1 = 3.2021 sq-in M = 153.53
As2 = 1.1847 sq-in M = 48.05
As = 4.3868 sq-in M = 97.534
f's = 17.158 ksi M = 108.41
A's = 1.2428 sq-in
V = 18.6 kip
Vd = 13.3 kip
vd = 50.189 psi > 55
av = 0.11 sq-in
Stirrup= -82.306 in. c/c

ON PLUS BENDING (USD)


COLUMN -C1(USD)

ksi
ksi
kip
kip DESIGN OF T - BEAM -B13
kip
k-ft Allowable moment capacity of a given section.
k-ft
k-ft fy = 60
kip f'c = 3
kip n = 9.2081
kip Span = 23.5
k-ft C/C of beam spcing = 18
k-ft Slab thickness , t = 5
k-ft Beam Size b' = 12
kip h = 24
k-ft d = 20
in Effective width of compression flange
in 16xt + b' = 92
(within 0.6-0.9) L/4 = 70.5
in. C/C of beam spcing = = 216
b = 70.5
as = 0.58
no. of bar = 8
p= As/b = 0.0033
pn = 0.0303
t/d = 0.25
k = 0.2196
kd = 4.3918
% j = 0.9301
kip > 722.5 kip
If the allowable moment is gover
the steel stress, then
kip > 425 kip
M = 2330.4
M = 194.2
Checking the concrete extreme f
at that moment,

fc = 804.94

DESIGN OF T - BEAM - B13

Steel Area for a given moment.

M = 193
fy = 60
f'c = 3
n = 9.2081
Span = 23.5
C/C of beam spcing = 18
Slab thickness , t = 5
Beam Size b' = 12
h = 24
d = 20.5
Effective width of compression flange
16xt + b' = 92
L/4 = 70.5
C/C of beam spcing = = 216
b = 70.5

As = 4.7654
p= As/b = 0.0033
pn = 0.0304
t/d = 0.2439
k = 0.2192
kd = 4.4927
j = 0.929

As = 4.5038

fc = 777.78

ON PLUS BENDING (USD)


COLUMN -C1(USD)
DESIGN OF T - BEAM -B14
ksi
ksi Allowable moment capacity of a given section.
kip
kip fy = 55
kip f'c = 2.75
k-ft n = 9.6175
k-ft Span = 18
k-ft C/C of beam spcing = 12
kip Slab thickness , t = 4.5
kip Beam Size b' = 12
kip h = 20
k-ft d = 16.5
k-ft Effective width of compression flange
k-ft 16xt + b' = 84
kip L/4 = 54
k-ft C/C of beam spcing = = 144
in b = 54
in as = 0.48
(within 0.6-0.9) no. of bar = 8
in. p= As/b = 0.0043
pn = 0.0414
t/d = 0.2727
k = 0.2503
kd = 4.13
j = 0.918

If the allowable moment is gover


the steel stress, then
%
kip > 808 kip M = 1439.6
M = 119.97
Checking the concrete extreme f
kip > 480 kip at that moment,

fc = 859.2

DESIGN OF T - BEAM - B14

Steel Area for a given moment.

M = 125
fy = 55
f'c = 2.75
n = 9.6175
Span = 18
C/C of beam spcing = 12
Slab thickness , t = 4.5
Beam Size b' = 12
h = 20
d = 16.5
Effective width of compression flange
16xt + b' = 84
L/4 = 54
C/C of beam spcing = = 144
b = 54

As = 4.2531
p= As/b = 0.0048
pn = 0.0459
t/d = 0.2727
k = 0.2608
kd = 4.3031
j = 0.9135

As = 4.0211

fc = 858.4

DESIGN OF BEAM -B10B (FOR 3-SPAN)

w1 = 2.2 k/ft w2 =
L1 4 ft L2

!------------------------------------- !----------------------------------
ON PLUS BENDING (USD) ! 1 0.7895 ! 0.2105
COLUMN -C1(USD) !------------------------------------- !----------------------------------
! -2.9333 2.9333 ! -73.333
ksi ! 2.9333 1.4667 !
ksi ! 54.421 ! 14.512
kip ! ! 4.558
kip ! -3.5984 ! -0.9596
kip ! ! -2.0036
k-ft ! 1.5818 ! 0.4218
k-ft ! ! 0.1325
k-ft ! -0.1046 ! -0.0279
kip ! ! -0.0582
kip ! 0.046 ! 0.0123
kip ! ! 0.0039
k-ft ! -0.003 ! -0.0008
k-ft !------------------------------------- !----------------------------------
k-ft ! M (-) = 56.743 ! -56.743
kip M (+) = -23.971
k-ft 2.9333
in
in M = 85.574 k-ft fy = 55
(within 0.6-0.9) b       12 in. f'c= 2.75
in. h       24 in. k = 0.3247
d(pro)= 20.5 in j = 0.8918
dreqd = 21.854 in. R= 0.1792
M1 = 75.298 k-ft
M2 = 10.276 k-ft M = 56.743
As1 = 1.9971 sq-in M = 85.574
As2 = 0.2768 sq-in M = 2.9333
As = 2.2739 sq-in M = 73.333
f's = 14.864 ksi M = 59.894
% A's = 0.4609 sq-in
kip > 345.3 kip V = 4.4 kip
Vd = 0.6417 kip
vd = 2.6084 psi > 57.684
kip > 275 kip av = 0.11 sq-in
Stirrup= -8.2386 in. c/c

DESIGN OF BEAM - B21 (FOR 4-SPAN)

w1 = 2.1 k/ft w2 =
L1 17 ft L2
!------------------------------------- !----------------------------------
! 1 0.4809 ! 0.5191
!------------------------------------- !----------------------------------
! -50.575 50.575 ! -77.175
! 50.575 25.288 !
! 0.6312 ! 0.6813
! ! -5.95
! 2.8615 ! 3.0885
! ! -3.7935
! 1.8243 ! 1.9691
! ! -0.8474
! 0.4075 ! 0.4399
! ! -0.5403
! 0.2598 ! 0.2805
! ! -0.1207
! 0.058 ! 0.0627
!------------------------------------- !----------------------------------
! M (-) = 81.905 ! -81.905
M (+) = 34.91
50.575

M= 78.4 k-ft fy = 40
b = 10 in. f'c= 2.5
h = 24 in. k = 0.3867
ON PLUS BENDING (USD) d(pro) = 20.5 in j = 0.8711
COLUMN -C1(USD) dreqd = 22.284 in. R= 0.1895
M1 = 66.353 k-ft
ksi M2 = 12.048 k-ft = 81.905
ksi As1 = 2.4771 sq-in M = 57.747
kip As2 = 0.4462 sq-in M = 78.4
kip As = 2.9233 sq-in M = 50.575
kip f's = 15.538 ksi M= 57.881
k-ft A's = 0.5169 sq-in M = 37.931
k-ft V = 17.85 kip M= 70
k-ft Vd = 14.263 kip
kip vd = 69.573 psi > 55
kip av = 0.11 sq-in
kip Stirrup = 27.173 in. c/c
k-ft
k-ft
k-ft
kip
k-ft
in DESIGN OF BEAM - B22 (FOR 2-SPAN)
in
(within 0.6-0.9) w1 = 2.2 k/ft w2 =
in. L1 25 ft L2
!------------------------------------- !----------------------------------
! 1 0.4253 ! 0.5747
!------------------------------------- !----------------------------------
! -114.58 114.58 ! -59.894
! 114.58 57.292 ! -29.947
! -34.888 ! -47.146
!------------------------------------- !----------------------------------
% ! M (-) = 136.99 ! -137
kip > 280.5 kip M (+) = 103.38
114.58

kip > 170 kip M = 136.99 k-ft fy = 55


b = 12 in. f'c = 2.75
h = 25 in. k = 0.3247
d(pro)= 21.5 j = 0.8918
dreqd= 27.65 in. R = 0.1792
M1 = 82.824 k-ft
M2 = 54.163 k-ft = 136.99
As1 = 2.0945 sq-in M = 114.58
As2 = 1.3822 sq-in M = 59.894
As = 3.4766 sq-in
f's = 15.28 ksi as
A's = 2.2388 sq-in 0.48
V = 27.5 kip
Vd = 23.558 kip
vd = 91.311 psi > 57.684
av = 0.11 sq-in
Stirrup= 13.494 in. c/c

DESIGN OF BEAM - B23 (FOR 4-SPAN)

w1 = 1.8 k/ft w2 =
L1 12 ft L2

!------------------------------------- !----------------------------------
! 1 0.5897 ! 0.4103
!------------------------------------- !----------------------------------
! -21.6 21.6 ! -88.167
! 21.6 10.8 !
! 32.888 ! 22.879
! ! 15.017
! -8.8564 ! -6.161
! ! -4.0923
! 2.4134 ! 1.6789
! ! 1.8474
! -1.0895 ! -0.7579
! ! -0.5034
! 0.2969 ! 0.2065
! ! 0.2273
! -0.134 ! -0.0932
!------------------------------------- !----------------------------------
! M (-) = 57.918 ! -57.918
M (+) = 3.4408
21.6

M= 159.2 k-ft fy = 40
b = 12 in. f'c= 2.5
h = 24 in. k = 0.3867
d(pro) = 20.5 in j = 0.8711
dreqd = 28.987 in. R= 0.1895
M1 = 79.623 k-ft
ON PLUS BENDING (USD) M2 = 79.577 k-ft = 57.918
COLUMN -C1(USD) As1 = 2.9725 sq-in M = 121.96
As2 = 2.9473 sq-in M = 159.2
ksi As = 5.9198 sq-in M = 21.6
ksi f's = 15.538 ksi M= 66.125
kip A's = 3.4144 sq-in M = 109.38
kip V = 10.8 kip M= 107.03
kip Vd = 7.725 kip
k-ft vd = 31.402 psi > 55
k-ft av = 0.11 sq-in
k-ft Stirrup =-13.984 in. c/c
kip
kip
kip
k-ft
k-ft
k-ft
kip
k-ft
in
in
(within 0.6-0.9)
in.
DESIGN OF BEAM - B22 (FOR 2-SPAN)

% w1 = 0.19 k/ft w2 =
kip > 474 kip L1 16 ft L2

!------------------------------------- !----------------------------------
kip > 360 kip ! 1 0.5429 ! 0.4571
!------------------------------------- !----------------------------------
! -4.0533 4.0533 ! -5.7158
! 4.0533 2.0267 ! -2.8579
! 1.3538 ! 1.14
!------------------------------------- !----------------------------------
! M (-) = 7.4338 ! -7.4338
M (+) = 2.3631
4.0533

M = 7.4338 k-ft fy = 40
b = 12 in. f'c = 2.5
h = 7 in. k = 0.3867
d(pro)= 6 j = 0.8711
dreqd= 6.2638 in. R = 0.1895
M1 = 6.8208 k-ft
M2 = 0.6129 k-ft = 7.4338
As1 = 0.87 sq-in M = 4.0533
As2 = 0.1168 sq-in M = 5.7158
As = 0.9868 sq-in
f's = -1.7609 ksi as
A's = -1.1935 sq-in 0.48
V = 1.52 kip
Vd = 1.425 kip
vd = 19.792 psi > 55
av = 0.11 sq-in
Stirrup= -9.3728 in. c/c

DESIGN OF BEAM B-22(Single Span)

w 2.6 k/ft fy = 40
L = 23 ft f = 2.5
Beam Size k = 0.3867
12 in j = 0.8711
24 in R = 0.1895
d(pro)= 20.5
M = 137.54 k-ft
dreqd= 26.943 in >< 20.5
M1 = 79.623
M2 = 57.917
As1 = 2.9725
As2 = 2.1451 as no. of bar
5.1176 0.58 8.8234
f's 15.538 as no. of bar
As' = 2.485 0.48 5.1771
V = 29.9 kip
Vd = 25.458 kip
vd = 103.49 psi > 55
av = 0.11 sq-in (2 - leg)
ON PLUS BENDING (USD) Stirrup= 6.8056 in. c/c
COLUMN -C1(USD)

ksi
ksi
kip
kip
kip DESIGN OF BEAM B-24(Single Span)
k-ft
k-ft w 3.3 k/ft fy = 40
k-ft L = 20 ft f = 2.5
kip Beam Size k = 0.3867
kip 12 in j = 0.8711
kip 24 in R = 0.1895
k-ft d(pro)= 20.5
k-ft M = 132 k-ft
k-ft dreqd= 26.395 in >< 20.5
kip M1 = 79.623
k-ft M2 = 52.377
in As1 = 2.9725
in As2 = 1.9399 as no. of bar
(within 0.6-0.9) 4.9124 0.58 8.4696
in. f's 15.538 as no. of bar
As' = 2.2473 0.48 4.6819
V = 33 kip
Vd = 27.363 kip
vd = 111.23 psi > 55
av = 0.11 sq-in (2 - leg)
Stirrup= 5.8688 in. c/c

%
kip > 373 kip
kip > 295 kip DESIGN OF BEAM - B25 (FOR 3-SPAN)

w1 = 1.1 k/ft w2 =
L1 15 ft L2

!------------------------------------- !----------------------------------
! 1 0.2857 ! 0.7143
!------------------------------------- !----------------------------------
! -20.625 20.625 ! -5.8667
! 20.625 10.313 !
! -7.1631 ! -17.908
! ! 8.9539
! -2.5582 ! -6.3956
! ! 3.1978
! -0.9137 ! -2.2842
! ! 1.1421
! -0.3263 ! -0.8158
! ! 0.4079
! -0.1165 ! -0.2913
! ! 0.1457
! -0.0416 ! -0.1041
!------------------------------------- !----------------------------------
! M (-) = 19.818 ! -19.818
M (+) = 21.028
20.625

M = 19.818 k-ft fy = 40
b       12 in. f'c= 2.5
h       21 in. k = 0.3867
d(pro)= 17.5 in j = 0.8711
dreqd = 10.227 in. R= 0.1895
M1 = 58.024 k-ft
M2 = -38.206 k-ft M = 19.818
As1 = 2.5375 sq-in M = 19.818
As2 = -1.6981 sq-in M = 20.625
As = 0.8394 sq-in M = 4.4
f's = 14.311 ksi M = 20.625
A's = -2.1358 sq-in
V = 8.25 kip
Vd = 6.6458 kip
vd = 31.647 psi > 55
av = 0.11 sq-in
Stirrup= -14.131 in. c/c
DESIGN OF BEAM - B29 (FOR 2-SPAN)

w1 = 3.3 k/ft w2 =
L1 20 ft L2

!------------------------------------- !----------------------------------
! 1 0.4286 ! 0.5714
!------------------------------------- !----------------------------------
ON PLUS BENDING (USD) ! -110 110 ! -61.875
COLUMN -C1(USD) ! 110 55 ! -30.938
! -30.938 ! -41.25
ksi !------------------------------------- !----------------------------------
ksi ! M (-) = 134.06 ! -134.06
kip M (+) = 97.969
kip 110
kip
k-ft M = 134.06 k-ft fy = 40
k-ft b = 12 in. f'c = 2.5
k-ft h = 24 in. k = 0.3867
kip d(pro)= 20.5 j = 0.8711
kip dreqd= 26.6 in. R = 0.1895
kip M1 = 79.623 k-ft
k-ft M2 = 54.439 k-ft M = 134.06
k-ft As1 = 2.9725 sq-in M = 110
k-ft As2 = 2.0163 sq-in M = 61.875
kip As = 4.9888 sq-in
k-ft f's = 15.538 ksi as
in A's = 2.3358 sq-in 0.48
in V = 33 kip
(within 0.6-0.9) Vd = 27.363 kip
in. vd = 111.23 psi > 55
av = 0.11 sq-in
Stirrup= 5.8688 in. c/c

% DESIGN OF BEAM - B30 (FOR 2-SPAN)


kip > 763 kip
w1 = 2.2 k/ft w2 =
L1 11 ft L2
kip > 460 kip
!------------------------------------- !----------------------------------
! 1 0.4211 ! 0.5789
!------------------------------------- !----------------------------------
! -22.183 22.183 ! -8.5333
! 22.183 11.092 ! -4.2667
! -8.6211 ! -11.854
!------------------------------------- !----------------------------------
! M (-) = 24.654 ! -24.654
M (+) = 20.948
22.183

M = 24.654 k-ft fy = 40
b = 10 in. f'c = 2.5
h = 18 in. k = 0.3867
d(pro)= 14.5 j = 0.8711
dreqd= 12.496 in. R = 0.1895
M1 = 33.196 k-ft
M2 = -8.5422 k-ft M = 24.654
As1 = 1.7521 sq-in M = 22.183
As2 = -0.4746 sq-in M = 8.5333
As = 1.2775 sq-in
f's = 12.576 ksi as
A's = -0.6793 sq-in 0.48
V = 12.1 kip
Vd = 9.4417 kip
vd = 65.115 psi > 55
av = 0.11 sq-in
Stirrup= 39.15 in. c/c

DETERMINATION OF MAX. DESIGN MOMENT (W

M (DL)= 35 k-ft
M (LL) = 8 k-ft
M (EQ) 90 k-ft

MOMENT COMBINATION (WSD)

ON PLUS BENDING (USD) 99.75 k-ft


COLUMN -C1(USD) 43 k-ft
125 k-ft
ksi M (+EQ) 55 k-ft
ksi
kip DESIGN MOMENT (WSD)
kip
kip M - (DESIGN) = 125 k-ft
k-ft
k-ft M + (DESIGN) = 55 k-ft
k-ft
kip
kip DETERMINATION OF MAX. DESIGN MOMENT (U
kip
k-ft M (DL) 35 k-ft
k-ft M (LL) = 8 k-ft
k-ft M (EQ) 90 k-ft
kip
k-ft MOMENT COMBINATION (USD)
in
in 161.7 k-ft
(within 0.6-0.9) 62.6 k-ft
in. 148.5 k-ft
M (+EQ) 85.5 k-ft

DESIGN MOMENT (USD)

M (DESIGN) = 161.7 k-ft

M + (DESIGN) = 85.5 k-ft

%
kip > 804 kip

kip > 465 kip DESIGN OF BEAM - B5 ( STEEL AREA) USD

f'c = 3 ksi
fy = 55 ksi
Beam depth h = 21 in
M (-) C.S (design) = 161.7 k-ft
Beam Size , b = 12 in
d = 17.5 in
pb = 0.0241
pmax = 0.0181
As -A's = 3.8028 sq-in
a = 6.8352 in
M (max) = 220.91 k-ft <
M1=M(design) - M(max) = -59.207 k-ft
A's = -0.8833 sq- as no. of bar
As = 2.9196 sq- 0.48
OR 2.3611
a (assumed) = 4.5 in
As = 2.5705 sq- 0.48
a = 4.6202 in 2.7553
M (+) C.S (design) = 85.5 k-ft
a (assumed) = 3 in
As = 1.2955 sq- 0.48
a = 2.3284 in 7.0635
M (-) M.S = 80 k-ft
a (assumed) = 2 in
As = 1.1754 sq- 0.48
a = 2.1126 in 4.9005
M (+) M.S = 12 k-ft
a (assumed) = 0.1 in
As = 0.1667 sq- 0.11
a = 0.2996 in 7.9179
As(nominal) M.S. = 0.7636 sq- 0.11
1.7286

DESIGN OF BEAM - B7 (FOR 4-SPAN)

w1 = 1.2 k/ft w2 =
L1 15.5 ft L2
P = 2 kip P =
X L= 13 ft X L=
Mf (L) = 0.6764 k-ft Mf (L) =
Mf (R) = 3.5172 k-ft Mf (R) =
R(R) = ### kip R(R) =
R(L) = ### kip R(L) =

!------------------------------------- !----------------------------------
! 1 0.2791 ! 0.7209
!------------------------------------- !----------------------------------
! -24.701 27.542 ! -6.4
! 24.701 12.351 !
! -9.3468 ! -24.146
! ! -0.75
! 0.2093 ! 0.5407
! ! -1.2049
! 0.3362 ! 0.8686
! ! -0.1449
! 0.0404 ! 0.1045
! ! -0.2328
! 0.065 ! 0.1678
! ! -0.028
! 0.0078 ! 0.0202
!------------------------------------- !----------------------------------
! M (-) = 31.205 ! -31.205
M (+) = 20.435
24.025

M= 0 k-ft fy = 55
b = 10 in. f'c= 3
h = 18 in. k = 0.3343
d(pro) = 14.5 in j = 0.8886
dreqd = 0 in. R = 0.2005
M1 = 35.134 k-ft
M2 = -35.134 k-ft = 31.205
As1 = 1.3221 sq-in M = -9.6432
As2 = -1.4195 sq-in M = 38.441
As = -0.0974 sq-in M = 24.025
f's = 12.041 ksi M= 4.8
A's = -2.9179 sq-in M = 1.875
V = 9.3 kip M= 32.033
Vd = 7.85 kip
vd = 54.138 psi > 60.249
av = 0.11 sq-in
Stirrup =-89.094 in. c/c
DETERMINATION OF MAX. DESIGN MOMENT

M (DL) 38 k-ft
M (LL) = 26 k-ft
M (EQ) 65 k-ft

MOMENT COMBINATION (WSD)

96.75 k-ft
64 k-ft
103 k-ft
M (+EQ) 27 k-ft

DESIGN MOMENT (WSD)

M - (DESIGN) = 103 k-ft

M + (DESIGN) = 27 k-ft

DETERMINATION OF MAX. DESIGN MOMENT (U

M (DL) 38 k-ft
M (LL) = 26 k-ft
M (EQ) 65 k-ft

MOMENT COMBINATION (USD)

155.93 k-ft
97.4 k-ft
118.7 k-ft
M (+EQ) 50.3 k-ft

DESIGN MOMENT (USD)

M (DESIGN) = 155.93 k-ft

M + (DESIGN) = 50.3 k-ft

DESIGN OF BEAM - B5 ( STEEL AREA) USD


f'c = 3 ksi
fy = 55 ksi
Beam depth h = 21 in
M (-) C.S (design) = 155.9 k-ft
Beam Size , b = 10 in
d = 17.5 in
pb = 0.0241
pmax = 0.0181
As -A's = 3.169 sq-in
a = 6.8352 in
M (max) = 184.09 k-ft <
M1=M(design) - M(max) = -28.164 k-ft
A's = -0.4202 sq- as no. of bar
As = 2.7489 sq- 0.48
OR 2.1156
a (assumed) = 5.4 in
As = 2.5541 sq- 0.48
a = 5.5087 in 2.3143
M (+) C.S (design) = 50.3 k-ft
a (assumed) = 2.8 in
As = 0.7574 sq- 0.31
a = 1.6336 in 6.9291
M (-) M.S = 80 k-ft
a (assumed) = 2.6 in
As = 1.1972 sq- 0.48
a = 2.5821 in 4.0095
M (+) M.S = 12 k-ft
a (assumed) = 0.1 in
As = 0.1667 sq- 0.11
a = 0.3596 in 6.5983
As(nominal) M.S. = 0.6364 sq- 0.11
1.7286
DETERMINATION OF MAX. DESIGN MOMENT

M (DL) 42 k-ft
M (LL) = 14 k-ft
M (EQ) 70 k-ft

MOMENT COMBINATION (WSD)

94.5 k-ft
56 k-ft
112 k-ft
M (+EQ) 28 k-ft

DESIGN MOMENT (WSD)

M - (DESIGN) = 112 k-ft

M + (DESIGN) = 28 k-ft

DETERMINATION OF MAX. DESIGN MOMENT (U

M (DL) 42 k-ft
M (LL) = 14 k-ft
M (EQ) 70 k-ft

MOMENT COMBINATION (USD)

151.2 k-ft
82.6 k-ft
128.8 k-ft
M (+EQ) 53.2 k-ft
DESIGN MOMENT (USD)

M (DESIGN) = 151.2 k-ft

M + (DESIGN) = 53.2 k-ft

DESIGN OF BEAM - B5 ( STEEL AREA) USD

f'c = 3 ksi
fy = 55 ksi
Beam depth h = 20 in
M (-) C.S (design) = 151.2 k-ft
Beam Size , b = 10 in
d = 16.5 in
pb = 0.0241
pmax = 0.0181
As -A's = 2.9879 sq-in
a = 6.4446 in
M (max) = 163.65 k-ft <
M1=M(design) - M(max) = -12.451 k-ft
A's = -0.1979 sq- as no. of bar
As = 2.79 sq- 0.48
OR 2.0779
a (assumed) = 6 in
As = 2.7152 sq- 0.48
a = 5.8562 in 2.1475
M (+) C.S (design) = 53.2 k-ft
a (assumed) = 2.2 in
As = 0.8375 sq- 0.58
a = 1.8063 in 22.527
M (-) M.S = 80 k-ft
a (assumed) = 2.6 in
As = 1.2759 sq- 0.48
a = 2.752 in 3.762
M (+) M.S = 12 k-ft
a (assumed) = 0.1 in
As = 0.1768 sq- 0.11
a = 0.3814 in 6.2202
As(nominal) M.S. = 0.6 sq- 0.11
1.8333
DESIGN OF BEAM -B18(FOR 3-SPAN)

w1 = 2.3 k/ft w2 =
L1 18.5 ft L2
P1 = 13 kip P1 =
X L1= 12 ft X L1=
P2 = 0 kip P2 =
X L2= 12 ft X L2=
Mf (L) = 19.258 k-ft Mf (L) =
Mf (R) = 35.553 k-ft Mf (R) =
R(R) = 34.914 kip R(R) =
R(L) = 20.636 kip R(L) =

!------------------------------------- !----------------------------------
! 1 0.3408 ! 0.6592
!------------------------------------- !----------------------------------
! -84.856 101.15 ! -59.089
! 84.856 42.428 !
! -28.79 ! -55.699
! ! 39.283
! -13.386 ! -25.897
! ! 9.1798
! -3.1281 ! -6.0517
! ! 4.2681
! -1.4544 ! -2.8137
! ! 0.9974
! -0.3399 ! -0.6575
! ! 0.4637
! -0.158 ! -0.3057
!------------------------------------- !----------------------------------
! 0 96.322 ! -96.322
50.236
41

M = 122.13 k-ft fy = 60
b       10 in. f'c= 3
h       24 in. k = 0.3153
d(pro)= 20.5 in j = 0.8949
dreqd = 27.741 in. R= 0.1904
M1 = 66.693 k-ft
M2 = 55.438 k-ft M = 96.322
As1 = 1.6157 sq-in M = 122.13
As2 = 1.3688 sq-in M = 41
As = 2.9845 sq-in M = 80
f's = 15.245 ksi M = 22
A's = 2.4244 sq-in 0.48
V = 21.275 kip
Vd = 17.346 kip
vd = 84.614 psi > 60.249
av = 0.11 sq-in
Stirrup= 24.38 in. c/c
3 (Single Span)

ksi
ksi

inch

no. of bar

no. of bar

psi

0.6 k/ft
11.5 ft

!------------------------------------- !
1!
!------------------------------------- !
6.6125 !
-6.6125 !
!
!------------------------------------- !
0!
-6.8704
6.6125

ksi
ksi

as no. of bar
k-ft As= 1.4684 sq-in 0.31 4.7369
k-ft As= 1.3858 sq-in 0.31 4.4702
k-ft As= 0.2892 sq-in 0.31 0.9328

no. of bar
1.6954

psi

B7 (FOR 3-SPAN)

2 k/ft w3 = 2 k/ft
15 ft L3 15 ft

!------------------------------------- !------------------------------------- !
0.5714 ! 0.4286 1!
!------------------------------------- !------------------------------------- !
37.5 ! -37.5 37.5 !
! -18.75 -37.5 !
10.714 ! 8.0357 !
-5.3571 ! !
3.0612 ! 2.2959 !
-1.5306 ! !
0.8746 ! 0.656 !
-0.4373 ! !
0.2499 ! 0.1874 !
-0.1249 ! !
0.0714 ! 0.0535 !
-0.0357 ! !
0.0204 ! 0.0153 !
!------------------------------------- !------------------------------------- !
45.006 ! -45.006 0!
11.244 33.747
28.125 37.5
ksi
ksi

as no. of bar
k-ft As= 2.3754 sq-in 0.48 4.9488
k-ft As= 2.3754 sq-in 0.31 7.6626
k-ft As= 1.9792 sq-in 0.31 6.3846
k-ft As= 1.4844 sq-in 0.31 4.7885
k-ft As= 1.9792 sq-in 0.31 6.3846

psi

B9 (FOR 4-SPAN)

1.6 k/ft w3 = 1.6 k/ft w4 = 1.6 k/ft


18 ft L3 = 18 ft L4 = 18 ft

!------------------------------------- !------------------------------------- !------------------------------------------ !


0.5 ! 0.5 0.5714 ! 0.42857 1!
!------------------------------------- !------------------------------------- !------------------------------------------ !
43.2 ! -43.2 43.2 ! -43.2 43.2 !
! ! -21.6 -43.2 !
0! 0 12.343 ! 9.25714 !
-6.1714 ! 6.1714 0! !
0! 0 0! 0 !
0! 0 0! !
0! 0 0! 0 !
0! 0 0! !
0! 0 0! 0 !
0! 0 0! !
0! 0 0! 0 !
0! 0 0! !
0! 0 0! 0 !
!------------------------------------- !------------------------------------- !------------------------------------------ !
37.029 ! -37.029 55.543 ! -55.5429 0!
18.514 18.514 37.0286
32.4 32.4 43.2

ksi
ksi

as no. of bar
k-ft As= 2.0902 sq-in 0.48 4.35453
k-ft As= 1.3934 sq-in 0.31 4.49499
k-ft As= 2.0902 sq-in 0.31 6.74249
k-ft As= 1.6257 sq-in 0.31 5.24416
k-ft As= 1.2193 sq-in 0.31 3.93312
k-ft As= 1.2193 sq-in 0.31 3.93312
k-ft As= 1.6257 sq-in 0.31 5.24416

psi

B4(FOR 3-SPAN)

1.65 k/ft w3 = 1.4 k/ft


18 ft L3 10 ft
14 kip
9 ft P = 18 kip
31.5 k-ft L = 15 ft
31.5 k-ft X L= 10.5 ft
21.739 kip Mf (L) = 17.01 k-ft
21.961 kip Mf (R) = 39.69 k-ft

!------------------------------------- !------------------------------------- !
0.4255 ! 0.5745 1! P = 23 kip
!------------------------------------- !------------------------------------- ! L = 15.5 ft
76.05 ! -11.667 11.667 ! X L= 7 ft
! -5.8333 -11.667 ! Mf (L) = 48.4173 k-ft
-24.915 ! -33.635 ! Mf (R) = 39.873 k-ft
12.065 ! !
-5.1341 ! -6.931 !
2.3177 ! !
-0.9862 ! -1.3314 !
0.4776 ! !
-0.2032 ! -0.2744 !
0.0917 ! !
-0.039 ! -0.0527 !
0.0189 ! !
-0.008 ! -0.0109 !
!------------------------------------- !------------------------------------- !
59.735 ! -59.735 0!
6.0875 -12.368
76 11.667

ksi
ksi

as no. of bar
k-ft As= 1.8083 sq-in 0.31 5.83327
k-ft As= 1.7496 sq-in 0.31 5.64393
k-ft As= 1.3766 sq-in 0.31 4.44066
k-ft As= 2.226 sq-in 0.31 7.18064
k-ft As= 0.3417 sq-in 0.31 1.10229

psi

B2 (FOR 6-SPAN)

2.5 k/ft w3 = 2.5 k/ft w4 = 2.5 k/ft


18 ft L3 18 ft L4 = 18 ft
0 kip
6 ft
0 k-ft
0 k-ft
21.202 kip
23.798 kip
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
0.5 ! 0.5 0.5 ! 0.5 0.5 !
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
67.5 ! -67.5 67.5 ! -67.5 67.5 !
! ! !
0! 0 0! 0 0!
-9.6429 ! 0 0! 0 0!
4.8214 ! 4.8214 0! 0 -4.82143 !
0! 0 2.4107 ! -2.41071 0!
0! 0 0! 0 0!
-0.6888 ! 0 0! 0 0!
0.3444 ! 0.3444 0! 0 -0.34439 !
0! 0 0.1722 ! -0.17219 0!
0! 0 0! 0 0!
-0.0492 ! 0 0! 0 0!
0.0246 ! 0.0246 0! 0 -0.0246 !
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
62.31 ! -62.31 70.083 ! -70.0829 62.3096 !
27.256 35.054 35.0538
50.625 50.625 50.625

ksi
ksi

as no. of bar
k-ft As= 2.4315 sq-in 0.48 5.06559
k-ft As= 1.7683 sq-in 0.31 5.70416
k-ft As= 1.9889 sq-in 0.31 6.41577
k-ft As= 1.9156 sq-in 0.31 6.17931
k-ft As= 1.4367 sq-in 0.31 4.63449
k-ft As= 1.4367 sq-in 0.31 4.63449
k-ft As= 1.4367 sq-in 0.31 4.63449

psi

-5 (Single Span)

ksi
ksi
inch

no. of bar

no. of bar

psi

-6 (Single Span)

ksi
ksi

inch

no. of bar

no. of bar

psi
B7 (FOR 5-SPAN)

1.4 k/ft w3 = 1.5 k/ft w4 = 1.3 k/ft


15.75 ft L3 17.75 ft L4 = 15.5 ft
P = 0 kip P = 0 kip
X L= 2.5 ft X L= 2.5 ft
Mf (L) = 0 k-ft Mf (L) = 0 k-ft
Mf (R) = 0 k-ft Mf (R) = 0 k-ft
R(R) = 14.092 kip R(R) = 10.2328 kip
R(L) = 12.533 kip R(L) = 9.91722 kip

!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------


0.5299 ! 0.4701 0.4662 ! 0.53383 0.58667 !
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
28.941 ! -39.383 39.383 ! -26.0271 26.0271 !
! ! !
5.5328 ! 4.9094 -6.226 ! -7.12975 15.6765 !
-32.775 ! -3.113 2.4547 ! 7.83826 -3.56488 !
19.015 ! 16.873 -4.7982 ! -5.49474 2.09139 !
-0.8964 ! -2.3991 8.4364 ! 1.0457 -2.74737 !
1.7461 ! 1.5494 -4.4202 ! -5.06189 1.61179 !
-3.0807 ! -2.2101 0.7747 ! 0.80589 -2.53095 !
2.8034 ! 2.4875 -0.7368 ! -0.84377 1.48482 !
-0.2829 ! -0.3684 1.2437 ! 0.74241 -0.42188 !
0.3451 ! 0.3062 -0.9259 ! -1.06028 0.24751 !
-0.4542 ! -0.4629 0.1531 ! 0.12375 -0.53014 !
0.4859 ! 0.4312 -0.1291 ! -0.1478 0.31101 !
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
21.38 ! -21.38 35.209 ! -35.2093 37.6549 !
-11.934 30.78 2.60852
21.705 29.537 19.5203

ksi
ksi

as no. of bar
k-ft As= 3.3609 sq-in 0.48 7.00186
k-ft As= 0.8046 sq-in 0.31 2.59536
k-ft As= 1.325 sq-in 0.31 4.27415
k-ft As= 3.2637 sq-in 0.31 10.5282
k-ft As= 0.8168 sq-in 0.31 2.63488
k-ft As= 1.1115 sq-in 0.31 3.58559
k-ft As= 0.7346 sq-in 0.31 2.36962
psi

8 (FOR 2-SPAN)

2.15 k/ft
25 ft

!------------------------------------- !
1!
!------------------------------------- !
111.98 !
-112 !
!
!------------------------------------- !
0!
104.09
111.98

ksi
ksi

as no. of bar
k-ft As= 3.0952 sq-in 0.48 6.4483
k-ft As= 1.1085 sq-in 0.48 2.3095
k-ft As= 2.7128 sq-in 0.48 5.6517

no. of bar
5.564

psi
B10(FOR 3-SPAN)

2.2 k/ft w3 = 1.75 k/ft


8.5 ft L3 8.5 ft
15 kip
4.25 ft
15.938 k-ft
15.938 k-ft
16.85 kip
16.85 kip

!------------------------------------- !------------------------------------- !
0.5714 ! 0.4286 1!
!------------------------------------- !------------------------------------- !
29.183 ! -10.536 10.536 !
! -5.2682 -10.536 !
-7.6449 ! -5.7337 !
3.8225 ! !
-2.1843 ! -1.6382 !
1.0921 ! !
-0.6241 ! -0.4681 !
0.312 ! !
-0.1783 ! -0.1337 !
0.0892 ! !
-0.0509 ! -0.0382 !
0.0255 ! !
-0.0146 ! -0.0109 !
!------------------------------------- !------------------------------------- !
23.828 ! -23.828 0!
-3.9588 3.8909
110 10.536

ksi
ksi

as no. of bar
k-ft As= 0.5772 sq-in 0.48 1.2026
k-ft As= 0.5772 sq-in 0.48 1.2026
k-ft As= 1.1386 sq-in 0.48 2.37213
k-ft As= 2.6649 sq-in 0.48 5.5518
k-ft As= 0.2553 sq-in 0.48 0.53178
-3.9053
psi

-12(Single Span)

ksi
ksi

inch

no. of bar

no. of bar

psi

B13 (FOR 2-SPAN)

2 k/ft
18.25 ft

!------------------------------------- !
1!
!------------------------------------- !
55.51 !
-55.51 !
!
!------------------------------------- !
0!
48.678
55.51

ksi
ksi

as no. of bar
k-ft As= 2.1492 sq-in 0.48 4.4774
k-ft As= 1.0777 sq-in 0.48 2.2452
k-ft As= 1.7246 sq-in 0.48 3.593

no. of bar
2.9314

psi

B15 (FOR 6-SPAN)

2.15 k/ft w3 = 2.15 k/ft w4 = 2.15 k/ft


16.25 ft L3 16.25 ft L4 = 7 ft
0 kip
6 ft
0 k-ft
0 k-ft
16.568 kip
18.369 kip

!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------


0.5 ! 0.5 0.3011 ! 0.69892 0.70526 !
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
47.311 ! -47.311 47.311 ! -8.77917 8.77917 !
! ! !
0! 0 -11.601 ! -26.931 29.2602 !
-8.1297 ! -5.8005 0! 14.6301 -13.4655 !
6.9651 ! 6.9651 -4.4048 ! -10.2253 -2.98495 !
0 ! -2.2024 3.4826 ! -1.49247 -5.11266 !
1.1012 ! 1.1012 -0.5992 ! -1.39092 4.97813 !
-1.0079 ! -0.2996 0.5506 ! 2.48907 -0.69546 !
0.6537 ! 0.6537 -0.9152 ! -2.12449 0.35048 !
-0.1594 ! -0.4576 0.3269 ! 0.17524 -1.06225 !
0.3085 ! 0.3085 -0.1512 ! -0.35094 0.98265 !
-0.0946 ! -0.0756 0.1542 ! 0.49132 -0.17547 !
0.0851 ! 0.0851 -0.1944 ! -0.4512 0.14019 !
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
47.033 ! -47.033 33.96 ! -33.9598 20.9945 !
16.615 30.47 -14.3084
35.483 35.483 6.58438

ksi
ksi

as no. of bar
k-ft As= 1.494 sq-in 0.48 3.11251
k-ft As= 1.1394 sq-in 0.31 3.67558
k-ft As= 0.8227 sq-in 0.31 2.65391
k-ft As= 1.2178 sq-in 0.31 3.92833
k-ft As= 0.8596 sq-in 0.31 2.77297
k-ft As= 0.8596 sq-in 0.31 2.77297
k-ft As= 0.1595 sq-in 0.31 0.51456

psi

B18(FOR 3-SPAN)

2.2 k/ft w3 = 2 k/ft


15 ft L3 5.5 ft
25 kip P1 = 0 kip
7.5 ft X L1= 0 ft
0 kip
0 ft
46.875 k-ft Mf (L) = 0 k-ft
46.875 k-ft Mf (R) = 0 k-ft
28.092 kip R(R) = -6.9809 kip
29.908 kip R(L) = 17.981 kip

!------------------------------------- !------------------------------------- !
0.3284 ! 0.6716 1!
!------------------------------------- !------------------------------------- !
88.125 ! -5.0417 5.0417 !
! -2.5208 -5.0417 !
-26.453 ! -54.109 !
5.8492 ! !
-1.9206 ! -3.9286 !
4.0255 ! !
-1.3218 ! -2.7037 !
0.2923 ! !
-0.096 ! -0.1963 !
0.2011 ! !
-0.066 ! -0.1351 !
0.0146 ! !
-0.0048 ! -0.0098 !
!------------------------------------- !------------------------------------- !
68.645 ! -68.645 0!
-13.582 -26.76
80 22

ksi
ksi

as no. of bar
k-ft As= 1.993 sq-in 0.48 4.15216
k-ft As= 1.663 sq-in 0.48 3.46458
k-ft As= 0.9933 sq-in 0.48 2.06931
k-ft As= 1.9381 sq-in 0.48 4.03767
k-ft As= 0.533 sq-in 0.48 1.11036
0.1779

psi

B21 (FOR 5-SPAN)


1.5 k/ft w3 = 1.5 k/ft w4 = 1.9 k/ft
12.25 ft L3 13 ft L4 = 8 ft
10 kip P = 10 kip
2 ft X L= 4 ft
14.002 k-ft Mf (L) = 10 k-ft
2.7322 k-ft Mf (R) = 10 k-ft
10.633 kip R(R) = 27.926 kip
17.742 kip R(L) = -2.72601 kip

!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------


0.5149 ! 0.4851 0.381 ! 0.61905 0.78571 !
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
21.49 ! -21.125 21.125 ! -20.1333 20.1333 !
! ! !
-0.1879 ! -0.1771 -0.3778 ! -0.61389 106.033 !
0 ! -0.1889 -0.0885 ! 53.0165 -0.30694 !
0.0972 ! 0.0916 -20.163 ! -32.7649 0.24117 !
0 ! -10.082 0.0458 ! 0.12059 -16.3824 !
5.1905 ! 4.891 -0.0634 ! -0.10301 12.8719 !
0 ! -0.0317 2.4455 ! 6.43596 -0.05151 !
0.0163 ! 0.0154 -3.3834 ! -5.49806 0.04047 !
0 ! -1.6917 0.0077 ! 0.02023 -2.74903 !
0.871 ! 0.8207 -0.0106 ! -0.01729 2.15995 !
0 ! -0.0053 0.4104 ! 1.07998 -0.00864 !
0.0027 ! 0.0026 -0.5677 ! -0.92259 0.00679 !
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
27.48 ! -27.48 -0.6201 ! 0.62014 121.988 !
-0.4866 18.258 -45.4839
14.068 15.844 10

ksi
ksi

as no. of bar
k-ft As= 1.3018 sq-in 0.48 2.71199
k-ft As= 1.2017 sq-in 0.48 2.50363
k-ft As= -0.0271 sq-in 0.48 -0.0565
k-ft As= 5.3348 sq-in 0.48 11.1141
k-ft As= 0.6152 sq-in 0.48 1.28174
k-ft As= 0.6929 sq-in 0.48 1.44349
k-ft As= 3.3513 sq-in 0.48 6.9819

psi
B23 (FOR 2-SPAN)

1.85 k/ft
13 ft
0 kip
0 ft
0 kip
0 ft
0 k-ft
0 k-ft
15.104 kip
8.9459 kip

!------------------------------------- !
1!
!------------------------------------- !
26.054 !
-26.054 !
!
!------------------------------------- !
0!
19.541
26.054

ksi
ksi

as no. of bar
k-ft As= 0.9468 sq-in 0.48 1.9725
k-ft As= 0.6312 sq-in 0.48 1.315
k-ft As= 0.6312 sq-in 0.48 1.315

no. of bar
-3.7308

psi
-25(Single Span)

ksi
ksi

inch

no. of bar

no. of bar

psi

B26 (FOR 2-SPAN)

1.9 k/ft
13 ft

!------------------------------------- !
1!
!------------------------------------- !
26.758 !
-26.758 !
!
!------------------------------------- !
0!
11.25
26.758

ksi
ksi

as no. of bar
k-ft As= 1.3997 sq-in 0.48 2.9159
k-ft As= 1.1885 sq-in 0.48 2.476
k-ft As= 0.6482 sq-in 0.48 1.3505

no. of bar
-0.8125

psi

B7 (FOR 3-SPAN)
2.4 k/ft w3 = 1.6 k/ft
17.5 ft L3 10.5 ft

!------------------------------------- !------------------------------------- !
0.4444 ! 0.5556 1!
!------------------------------------- !------------------------------------- !
61.25 ! -14.7 14.7 !
! -7.35 -14.7 !
-17.422 ! -21.778 !
8.7111 ! !
-3.8716 ! -4.8395 !
1.9358 ! !
-0.8604 ! -1.0754 !
0.4302 ! !
-0.1912 ! -0.239 !
0.0956 ! !
-0.0425 ! -0.0531 !
0.0212 ! !
-0.0094 ! -0.0118 !
!------------------------------------- !------------------------------------- !
50.047 ! -50.047 0!
41.828 -2.9733
45.938 14.7

ksi
ksi

as no. of bar
k-ft As= 1.5605 sq-in 0.48 3.251
k-ft As= 1.5605 sq-in 0.48 3.251
k-ft As= 0.4584 sq-in 0.31 1.4786
k-ft As= 1.4324 sq-in 0.48 2.9841
k-ft As= 0.4584 sq-in 0.31 1.4786

psi

B8 (FOR 2-SPAN)
2 k/ft
12.5 ft

!------------------------------------- !
1!
!------------------------------------- !
26.042 !
-26.042 !
!
!------------------------------------- !
0!
19.531
26.042

ksi
ksi

as no. of bar
k-ft As= 1.7083 sq-in 0.48 3.5589
k-ft As= 1.1388 sq-in 0.48 2.3726
k-ft As= 1.1388 sq-in 0.48 2.3726

no. of bar
-1.0821

psi

B8 (FOR 3-SPAN)

2.8 k/ft w3 = 1.9 k/ft


14.5 ft L3 13 ft

!------------------------------------- !------------------------------------- !
0.5445 ! 0.4555 1!
!------------------------------------- !------------------------------------- !
49.058 ! -26.758 26.758 !
! -13.379 -26.758 !
-4.8574 ! -4.0634 !
2.4287 ! !
-1.3224 ! -1.1063 !
0.6612 ! !
-0.36 ! -0.3012 !
0.18 ! !
-0.098 ! -0.082 !
0.049 ! !
-0.0267 ! -0.0223 !
0.0133 ! !
-0.0073 ! -0.0061 !
!------------------------------------- !------------------------------------- !
45.719 ! -45.719 0!
27.869 17.278
36.794 26.758

ksi
ksi

as no. of bar
k-ft As= 1.9994 sq-in 0.48 4.1653
k-ft As= 1.9994 sq-in 0.31 6.4496
k-ft As= 1.1702 sq-in 0.31 3.7748
k-ft As= 1.6091 sq-in 0.31 5.1905
k-ft As= 1.1702 sq-in 0.31 3.7748

psi

B9 (FOR 3-SPAN)

1.6 k/ft w3 = 1.7 k/ft


14 ft L3 17.25 ft

!------------------------------------- !------------------------------------- !
0.6216 ! 0.3784 1!
!------------------------------------- !------------------------------------- !
26.133 ! -42.155 42.155 !
! -21.077 -42.155 !
23.061 ! 14.037 !
3.2472 ! !
-2.0185 ! -1.2287 !
-2.4022 ! !
1.4933 ! 0.9089 !
0.2103 ! !
-0.1307 ! -0.0796 !
-0.1555 ! !
0.0967 ! 0.0589 !
0.0136 ! !
-0.0085 ! -0.0052 !
!------------------------------------- !------------------------------------- !
49.54 ! -49.54 0!
7.8919 38.462
19.6 42.155

ksi
ksi

as no. of bar
k-ft As= 0.4881 sq-in 0.48 1.017
k-ft As= 1.8494 sq-in 0.48 3.853
k-ft As= 0.2625 sq-in 0.48 0.5469
k-ft As= 0.7317 sq-in 0.48 1.5244
k-ft As= 1.5737 sq-in 0.48 3.2786

psi

B9 (FOR 4-SPAN)

2.1 k/ft w3 = 2.1 k/ft w4 = 2.1 k/ft


10 ft L3 23 ft L4 = 10 ft

!------------------------------------- !------------------------------------- !------------------------------------------ !


0.697 ! 0.303 0.367 ! 0.63303 1!
!------------------------------------- !------------------------------------- !------------------------------------------ !
17.5 ! -92.575 92.575 ! -17.5 17.5 !
! ! -8.75 -17.5 !
52.325 ! 22.75 -24.339 ! -41.9856 !
-1.0261 ! -12.17 11.375 ! !
9.1971 ! 3.9987 -4.1743 ! -7.20069 !
-7.1352 ! -2.0872 1.9994 ! !
6.4277 ! 2.7947 -0.7337 ! -1.26566 !
-1.2542 ! -0.3669 1.3973 ! !
1.1298 ! 0.4912 -0.5128 ! -0.88455 !
-0.8765 ! -0.2564 0.2456 ! !
0.7896 ! 0.3433 -0.0901 ! -0.15548 !
-0.1541 ! -0.0451 0.1717 ! !
0.1388 ! 0.0603 -0.063 ! -0.10866 !
!------------------------------------- !------------------------------------- !------------------------------------------ !
77.062 ! -77.062 77.851 ! -77.8506 0!
-14.117 61.406 -12.6753
13.125 69.431 17.5

ksi
ksi

as no. of bar
k-ft As= 0.1076 sq-in 0.48 0.22412
k-ft As= 2.2571 sq-in 0.31 7.28097
k-ft As= 2.2802 sq-in 0.31 7.35549
k-ft As= 0.4152 sq-in 0.31 1.33928
k-ft As= 0.3844 sq-in 0.31 1.24008
k-ft As= 2.0336 sq-in 0.31 6.56001
k-ft As= 0.5126 sq-in 0.31 1.65344

psi

B10 (FOR 5-SPAN)

1.9 k/ft w3 = 1.9 k/ft w4 = 1.9 k/ft


6.5 ft L3 8 ft L4 = 6.5 ft
28 kip P = 18 kip
1.5 ft X L= 5 ft
24.852 k-ft Mf (L) = 4.7929 k-ft
7.4556 k-ft Mf (R) = 15.9763 k-ft
15.641 kip R(R) = 22.2317 kip
24.709 kip R(L) = 8.11832 kip

!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------


0.5517 ! 0.4483 0.4483 ! 0.55172 0.66087 !
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
14.145 ! -10.133 10.133 ! -11.4825 22.6659 !
! ! !
-2.2134 ! -1.7984 0.6048 ! 0.74436 -0.81389 !
15.77 ! 0.3024 -0.8992 ! -0.40694 0.37218 !
-8.8676 ! -7.2049 0.5855 ! 0.72064 -0.24596 !
0.5533 ! 0.2928 -3.6024 ! -0.12298 0.36032 !
-0.4668 ! -0.3793 1.67 ! 2.05541 -0.23812 !
2.2168 ! 0.835 -0.1896 ! -0.11906 1.0277 !
-1.6837 ! -1.368 0.1384 ! 0.17032 -0.67918 !
0.1167 ! 0.0692 -0.684 ! -0.33959 0.08516 !
-0.1026 ! -0.0833 0.4589 ! 0.56475 -0.05628 !
0.4209 ! 0.2294 -0.0417 ! -0.02814 0.28238 !
-0.3588 ! -0.2915 0.0313 ! 0.03851 -0.18661 !
!------------------------------------- !------------------------------------- !------------------------------------------ !------------------------
19.53 ! -19.53 8.2052 ! -8.20521 22.5736 !
0.2684 1.3324 -5.35503
5.0172 7.6 5.01719

ksi
ksi

as no. of bar
k-ft As= 7E-05 sq-in 0.48 0.00014
k-ft As= 0.7291 sq-in 0.48 1.51895
k-ft As= 0.3063 sq-in 0.785 0.39021
k-ft As= 0.8427 sq-in 0.785 1.07353
k-ft As= 0.1873 sq-in 0.48 0.39021
k-ft As= 0.2837 sq-in 0.48 0.59109
k-ft As= 0.5335 sq-in 0.785 0.67957

psi

B11 (FOR 2-SPAN)

1.75 k/ft
12 ft

!------------------------------------- !
1!
!------------------------------------- !
21 !
-21 !
!
!------------------------------------- !
0!
19.354
21

ksi
ksi

as no. of bar
k-ft As= 1.0623 sq-in 0.48 2.2132
k-ft As= 0.428 sq-in 0.48 0.8917
k-ft As= 0.9184 sq-in 0.48 1.9133

no. of bar
-2.8023

psi

-12(Single Span)

ksi
ksi

inch

no. of bar

no. of bar

psi
-13(Single Span)

ksi
ksi

inch

no. of bar

no. of bar

psi
B14 (FOR 3-SPAN)

2.2 k/ft w3 = 2.45 k/ft


15.5 ft L3 18.5 ft

!------------------------------------- !------------------------------------- !
0.6141 ! 0.3859 1!
!------------------------------------- !------------------------------------- !
44.046 ! -69.876 69.876 !
! -34.938 -69.876 !
37.318 ! 23.45 !
1.1291 ! !
-0.6934 ! -0.4357 !
-4.7388 ! !
2.9101 ! 1.8287 !
0.088 ! !
-0.0541 ! -0.034 !
-0.3695 ! !
0.2269 ! 0.1426 !
0.0069 ! !
-0.0042 ! -0.0026 !
!------------------------------------- !------------------------------------- !
79.865 ! -79.865 0!
10.127 64.881
33.034 69.876
ksi
ksi

as no. of bar
k-ft As= 1.4002 sq-in 0.48 2.9171
k-ft As= 3.4926 sq-in 0.48 7.2763
k-ft As= 1.1545 sq-in 0.31 3.7243
k-ft As= 1.4447 sq-in 0.48 3.0097
k-ft As= 3.0558 sq-in 0.31 9.8574

psi

B15 (FOR 4-SPAN)

2.15 k/ft w3 = 2.45 k/ft w4 = 2.15 k/ft


15.5 ft L3 18.5 ft L4 = 14.5 ft

!------------------------------------- !------------------------------------- !------------------------------------------ !


0.5441 ! 0.4559 0.511 ! 0.48899 1!
!------------------------------------- !------------------------------------- !------------------------------------------ !
43.045 ! -69.876 69.876 ! -37.6698 37.6698 !
! ! -18.8349 -37.6698 !
14.599 ! 12.232 -6.8329 ! -6.53842 !
0.2098 ! -3.4165 6.1159 ! !
1.7448 ! 1.4619 -3.1253 ! -2.99062 !
-1.9268 ! -1.5627 0.7309 ! !
1.8987 ! 1.5908 -0.3735 ! -0.35742 !
-0.2303 ! -0.1868 0.7954 ! !
0.2269 ! 0.1901 -0.4065 ! -0.38894 !
-0.2506 ! -0.2032 0.0951 ! !
0.2469 ! 0.2069 -0.0486 ! -0.04648 !
-0.0299 ! -0.0243 0.1034 ! !
0.0295 ! 0.0247 -0.0529 ! -0.05058 !
!------------------------------------- !------------------------------------- !------------------------------------------ !
59.563 ! -59.563 66.877 ! -66.8771 0!
15.682 41.594 23.0661
32.284 52.407 37.6698

ksi
ksi
as no. of bar
k-ft As= 1.6709 sq-in 0.48 3.48099
k-ft As= 2.6048 sq-in 0.48 5.42667
k-ft As= 2.9247 sq-in 0.48 6.09303
k-ft As= 1.2318 sq-in 0.48 2.56621
k-ft As= 1.4118 sq-in 0.48 2.94129
k-ft As= 2.2919 sq-in 0.48 4.77469
k-ft As= 1.6474 sq-in 0.48 3.43201

psi

B10 (FOR 3-SPAN)

2.4 k/ft w3 = 2.4 k/ft


18 ft L3 15.5 ft

!------------------------------------- !------------------------------------- !
0.5345 ! 0.4655 1!
!------------------------------------- !------------------------------------- !
64.8 ! -48.05 48.05 !
! -24.025 -48.05 !
3.8884 ! 3.3866 !
-10.948 ! !
5.8516 ! 5.0966 !
-0.562 ! !
0.3004 ! 0.2616 !
-0.8457 ! !
0.452 ! 0.3937 !
-0.0434 ! !
0.0232 ! 0.0202 !
-0.0653 ! !
0.0349 ! 0.0304 !
!------------------------------------- !------------------------------------- !
62.886 ! -62.886 0!
23.518 40.632
48.6 48.05

ksi
ksi

as no. of bar
k-ft As= 3.1537 sq-in 0.48 6.5703
k-ft As= 2.3477 sq-in 0.48 4.8909
k-ft As= 2.5554 sq-in 0.48 5.3237
k-ft As= 1.8143 sq-in 0.48 3.7799
k-ft As= 1.7938 sq-in 0.48 3.7371

psi

B10 (FOR 3-SPAN)

2.95 k/ft w3 = 2.95 k/ft


23 ft L3 21 ft

!------------------------------------- !------------------------------------- !
0.549 ! 0.451 1!
!------------------------------------- !------------------------------------- !
130.05 ! -108.41 108.41 !
! -54.206 -108.41 !
17.883 ! 14.69 !
13.718 ! !
-7.5316 ! -6.1867 !
-2.1159 ! !
1.1617 ! 0.9543 !
0.8911 ! !
-0.4893 ! -0.4019 !
-0.1375 ! !
0.0755 ! 0.062 !
0.0579 ! !
-0.0318 ! -0.0261 !
!------------------------------------- !------------------------------------- !
153.53 ! -153.53 0!
68.462 85.855
97.534 108.41

ksi
ksi

as no. of bar
k-ft As= 2.8789 sq-in 0.48 5.9977
k-ft As= 4.4338 sq-in 0.48 9.2371
k-ft As= 1.3877 sq-in 0.31 4.4763
k-ft As= 2.8167 sq-in 0.48 5.8682
k-ft As= 3.1309 sq-in 0.48 6.5227

psi

apacity of a given section.

ksi
ksi

ft
ft
inch
inch
inch
inch
mpression flange
inch
inch
inch
inch
sq-in.
nos

inch > 5 in.

allowable moment is governed by the


teel stress, then

in.- kips
ft - kips
cking the concrete extreme fiber stress

psi. < 1350 psi.

kip - ft.
ksi
ksi

ft
ft
inch
inch
inch
inch
mpression flange
inch
inch
inch
inch

sq-in. 0.58 8.2163

inch > 5 in.

sq-in. 0.58 7.7652

psi. < 1350 psi.

apacity of a given section.

ksi
ksi

ft
ft
inch
inch
inch
inch
mpression flange
inch
inch
inch
inch
sq-in.
nos
inch > 4.5 in.

allowable moment is governed by the


teel stress, then

in.- kips
ft - kips
cking the concrete extreme fiber stress

psi. < 1237.5 psi.

kip - ft.
ksi
ksi

ft
ft
inch
inch
inch
inch
mpression flange
inch
inch
inch
inch

sq-in. 0.48 8.8605


inch > 4.5 in.

sq-in. 0.48 8.3773

psi. < 1237.5 psi.

B10B (FOR 3-SPAN)

2.2 k/ft w3 = 2.1 k/ft


20 ft L3 18.5 ft

!------------------------------------- !------------------------------------- !
0.5522 ! 0.4478 1!
!------------------------------------- !------------------------------------- !
73.333 ! -59.894 59.894 !
! -29.947 -59.894 !
9.116 ! 7.3913 !
7.2561 ! !
-4.0071 ! -3.249 !
-0.4798 ! !
0.265 ! 0.2148 !
0.2109 ! !
-0.1165 ! -0.0944 !
-0.0139 ! !
0.0077 ! 0.0062 !
0.0061 ! !
-0.0034 ! -0.0027 !
!------------------------------------- !------------------------------------- !
85.574 ! -85.574 0!
38.841 47.053
73.333 59.894

ksi
ksi

as no. of bar
k-ft As= 1.5049 sq-in 0.48 3.1353
k-ft As= 2.2696 sq-in 0.48 4.7283
k-ft As= 0.0778 sq-in 0.48 0.1621
k-ft As= 1.9449 sq-in 0.48 4.052
k-ft As= 1.5885 sq-in 0.48 3.3094

psi

B21 (FOR 4-SPAN)

2.1 k/ft w3 = 2.1 k/ft w4 = 2.1 k/ft


21 ft L3 17 ft L4 = 20 ft
!------------------------------------- !------------------------------------- !------------------------------------------ !
0.4474 ! 0.5526 0.6107 ! 0.38931 1!
!------------------------------------- !------------------------------------- !------------------------------------------ !
77.175 ! -50.575 50.575 ! -70 70 !
! ! -35 -70 !
-11.9 ! -14.7 33.237 ! 21.1884 !
0.3406 ! 16.618 -7.35 ! !
-7.5869 ! -9.3721 4.4885 ! 2.86145 !
1.5443 ! 2.2443 -4.686 ! !
-1.6949 ! -2.0937 2.8617 ! 1.82433 !
0.9846 ! 1.4308 -1.0468 ! !
-1.0806 ! -1.3348 0.6393 ! 0.40755 !
0.2199 ! 0.3196 -0.6674 ! !
-0.2414 ! -0.2982 0.4076 ! 0.25983 !
0.1402 ! 0.2038 -0.1491 ! !
-0.1539 ! -0.1901 0.0911 ! 0.05805 !
!------------------------------------- !------------------------------------- !------------------------------------------ !
57.747 ! -57.747 78.4 ! -78.4004 0!
45.937 7.7888 65.7998
57.881 37.931 70

ksi
ksi

0 no. of bar
k-ft As= 3.0577 sq-in 0.48 6.37016
k-ft As= 2.1558 sq-in 0.48 4.49127
k-ft As= 2.9268 sq-in 0.48 6.09759
k-ft As= 1.8881 sq-in 0.48 3.93347
k-ft As= 2.1608 sq-in 0.48 4.50171
k-ft As= 1.416 sq-in 0.48 2.9501
k-ft As= 2.6132 sq-in 0.48 5.44425

psi

B22 (FOR 2-SPAN)

2.1 k/ft
18.5 ft
!------------------------------------- !
1!
!------------------------------------- !
59.894 !
-59.894 !
!
!------------------------------------- !
0!
21.347
59.894

ksi
ksi

as no. of bar
k-ft As= 3.4642 sq-in 0.48 7.217
k-ft As= 2.8976 sq-in 0.48 6.0367
k-ft As= 1.5146 sq-in 0.48 3.1554

no. of bar
4.6642

psi

B23 (FOR 4-SPAN)

2 k/ft w3 = 2.8 k/ft w4 = 1.9 k/ft


23 ft L3 25 ft L4 = 26 ft

!------------------------------------- !------------------------------------- !------------------------------------------ !


0.5208 ! 0.4792 0.581 ! 0.41899 1!
!------------------------------------- !------------------------------------- !------------------------------------------ !
88.167 ! -145.83 145.83 ! -107.033 107.033 !
! ! -53.5167 -107.033 !
30.035 ! 27.632 8.5505 ! 6.1662 !
11.439 ! 4.2752 13.816 ! !
-8.1847 ! -7.5299 -8.0272 ! -5.78882 !
-3.0805 ! -4.0136 -3.7649 ! !
3.6948 ! 3.3992 2.1875 ! 1.57749 !
0.8395 ! 1.0937 1.6996 ! !
-1.0069 ! -0.9263 -0.9875 ! -0.71213 !
-0.379 ! -0.4937 -0.4632 ! !
0.4545 ! 0.4182 0.2691 ! 0.19406 !
0.1033 ! 0.1345 0.2091 ! !
-0.1239 ! -0.114 -0.1215 ! -0.08761 !
!------------------------------------- !------------------------------------- !------------------------------------------ !
121.96 ! -122 159.2 ! -159.201 0!
42.312 78.171 80.9496
66.125 109.38 107.033

ksi
ksi

as no. of bar
k-ft As= 2.1622 sq-in 0.48 4.50461
k-ft As= 4.5529 sq-in 0.48 9.48528
k-ft As= 5.9433 sq-in 0.48 12.3818
k-ft As= 0.8064 sq-in 0.48 1.67994
k-ft As= 2.4686 sq-in 0.48 5.14287
k-ft As= 4.0832 sq-in 0.48 8.50664
k-ft As= 3.9958 sq-in 0.48 8.32452

psi
B22 (FOR 2-SPAN)

0.19 k/ft
19 ft

!------------------------------------- !
1!
!------------------------------------- !
5.7158 !
-5.7158 !
!
!------------------------------------- !
0!
4.8569
5.7158

ksi
ksi

as no. of bar
k-ft As= 0.9482 sq-in 0.48 1.9754
k-ft As= 0.517 sq-in 0.48 1.0771
k-ft As= 0.7291 sq-in 0.48 1.5189

no. of bar
-2.4864

psi

-22(Single Span)

ksi
ksi
inch

no. of bar

no. of bar

psi

-24(Single Span)

ksi
ksi

inch

no. of bar

no. of bar

psi
B25 (FOR 3-SPAN)

1.1 k/ft w3 = 1.1 k/ft


8 ft L3 15 ft

!------------------------------------- !------------------------------------- !
0.7143 ! 0.2857 1!
!------------------------------------- !------------------------------------- !
5.8667 ! -20.625 20.625 !
! -10.313 -20.625 !
17.908 ! 7.1631 !
-8.9539 ! !
6.3956 ! 2.5582 !
-3.1978 ! !
2.2842 ! 0.9137 !
-1.1421 ! !
0.8158 ! 0.3263 !
-0.4079 ! !
0.2913 ! 0.1165 !
-0.1457 ! !
0.1041 ! 0.0416 !
!------------------------------------- !------------------------------------- !
19.818 ! -19.818 0!
-11.018 21.028
4.4 20.625

ksi
ksi

as no. of bar
k-ft As= 0.8667 sq-in 0.48 1.8056
k-ft As= 0.8667 sq-in 0.48 1.8056
k-ft As= 0.902 sq-in 0.48 1.8791
k-ft As= 0.1924 sq-in 0.48 0.4009
k-ft As= 0.902 sq-in 0.48 1.8791

psi
B29 (FOR 2-SPAN)

3.3 k/ft
15 ft

!------------------------------------- !
1!
!------------------------------------- !
61.875 !
-61.875 !
!
!------------------------------------- !
0!
25.781
61.875

ksi
ksi

as no. of bar
k-ft As= 5.0048 sq-in 0.48 10.427
k-ft As= 4.1065 sq-in 0.48 8.5553
k-ft As= 2.3099 sq-in 0.48 4.8123

no. of bar
4.8662

psi

B30 (FOR 2-SPAN)

1.6 k/ft
8 ft

!------------------------------------- !
1!
!------------------------------------- !
8.5333 !
-8.5333 !
!
!------------------------------------- !
0!
0.473
8.5333

ksi
ksi

as no. of bar
k-ft As= 1.3012 sq-in 0.48 2.7109
k-ft As= 1.1708 sq-in 0.48 2.4392
k-ft As= 0.4504 sq-in 0.48 0.9383

no. of bar
-1.4151

psi

F MAX. DESIGN MOMENT (WSD)


F MAX. DESIGN MOMENT (USD)

DESIGN OF BEAM - B5 ( STEEL AREA) WSD

M= 60 k-ft fy = 60 ksi
b = 12 in. f'c= 3.5 ksi
h = 22 in. k = 0.33213
d(pro) = 18.5 in j = 0.88929
dreqd = 16.061 in. R= 0.23259
M1 = 79.606 k-ft
M2 = -19.606 k-ft
As1 = 2.1505 sq-in as no. of bar
As2 = -0.5446 sq-in
As = 1.6059 sq-in 0.58 2.76885
161.7 k-ft f's = 15.928 ksi
A's = -0.9232 sq-in 0.48 -1.92331
as no. of bar
6.0824 M (DL & LL) = 46 13 k - ft.
inch c/c
DESIGN OF BEAM -B5 ( STEEL AREA) USD
5.3552 1.4 x D L + 1.7 X L L = 86.5 k-ft
inch c/c M= 86.5 k-ft fy = 60 ksi
b = 12 in. f'c= 3 ksi
h = 21 in. k = 0.31526
2.6989 d(pro) = 17.5 in j = 0.89491
inch c/c R = 0.19044
.145f'cbd2 = 1038 k-in.
dreqd = 14.101 in. < 17.5 in.
2.4487 as no. of bar
inch c/c a (assumed) = 2.3 in
As 1.1757 sq- 0.48 2.44931
a 2.3052 in
1.5155
inch c/c
6.9421
inch c/c

B7 (FOR 4-SPAN)

1.2 k/ft w3 = 1.2 k/ft w4 = 1.6 k/ft


8 ft L3 5 ft L4 = 15.5 ft
0 kip P = 0 kip P = 0 kip
2 ft X L= 2 ft X L= 2 ft
0 k-ft Mf (L) = 0 k-ft Mf (L) = 0 k-ft
0 k-ft Mf (R) = 0 k-ft Mf (R) = 0 k-ft
-0.306 kip R(R) = 12.617 kip R(R) = 9.91994 kip
9.906 kip R(L) = -6.6168 kip R(L) = 14.8801 kip

!------------------------------------- !------------------------------------- !------------------------------------------ !


0.3846 ! 0.6154 0.8052 ! 0.19481 1!
!------------------------------------- !------------------------------------- !------------------------------------------ !
6.4 ! -2.5 2.5 ! -32.0333 32.0333 !
! ! -16.0167 -32.0333 !
-1.5 ! -2.4 36.677 ! 8.87338 !
-12.073 ! 18.338 -1.2 ! 0 !
-2.4097 ! -3.8556 0.9662 ! 0.23377 !
0.2703 ! 0.4831 -1.9278 ! 0 !
-0.2898 ! -0.4637 1.5522 ! 0.37554 !
0.4343 ! 0.7761 -0.2318 ! 0 !
-0.4656 ! -0.7449 0.1867 ! 0.04516 !
0.0522 ! 0.0933 -0.3724 ! 0 !
-0.056 ! -0.0896 0.2999 ! 0.07255 !
0.0839 ! 0.1499 -0.0448 ! 0 !
-0.0899 ! -0.1439 0.0361 ! 0.00873 !
!------------------------------------- !------------------------------------- !------------------------------------------ !
-9.6432 ! 9.6432 38.441 ! -38.4409 0!
-1.1808 -10.649 28.8296
4.8 1.875 32.0333

ksi
ksi

as no. of bar
k-ft As= 1.1743 sq-in 0.48 2.44643
k-ft As= -0.3629 sq-in 0.31 -1.17062
k-ft As= 1.4466 sq-in 0.31 4.66644
k-ft As= 0.9041 sq-in 0.31 2.91646
k-ft As= 0.1806 sq-in 0.31 0.58268
k-ft As= 0.0706 sq-in 0.31 0.22761
k-ft As= 1.2055 sq-in 0.31 3.88861

psi
F MAX. DESIGN MOMENT

F MAX. DESIGN MOMENT (USD)


155.93 k-ft

as no. of bar
5.7268
inch c/c

5.3209
inch c/c

2.4432
inch c/c

2.4941
inch c/c

1.5155
inch c/c
5.7851
inch c/c
F MAX. DESIGN MOMENT

F MAX. DESIGN MOMENT (USD)


151.2 k-ft

as no. of bar
5.8125
inch c/c

5.6566
inch c/c

1.4439
inch c/c

2.6582
inch c/c

1.6077
inch c/c
5.4545
inch c/c
B18(FOR 3-SPAN)

2.3 k/ft w3 = 2.3 k/ft


12.75 ft L3 18.5 ft
11 kip P1 = 13 kip
3.5 ft X L1= 6.5 ft
11 kip P2 = 10 kip
9.25 ft X L2= 9.25 ft
27.931 k-ft Mf (L) = 58.678 k-ft
27.931 k-ft Mf (R) = 42.383 k-ft
27.687 kip R(R) = 24.241 kip
23.638 kip R(L) = 41.309 kip

!------------------------------------- !------------------------------------- !
0.6592 ! 0.3408 1!
!------------------------------------- !------------------------------------- !
59.089 ! -124.28 107.98 !
! -53.99 -108 !
78.567 ! 40.61 !
-27.85 ! !
18.36 ! 9.4899 !
-12.949 ! !
8.5363 ! 4.4123 !
-3.0259 ! !
1.9948 ! 1.0311 !
-1.4069 ! !
0.9275 ! 0.4794 !
-0.3288 ! !
0.2167 ! 0.112 !
!------------------------------------- !------------------------------------- !
122.13 ! -122.13 0!
-62.49 37.331
80 22

ksi
ksi

as no. of bar
k-ft As= 2.3335 sq-in 0.48 4.86145
k-ft As= 2.9588 sq-in 0.48 6.16406
k-ft As= 0.9933 sq-in 0.48 2.06931
k-ft As= 1.9381 sq-in 0.48 4.03767
k-ft As= 0.533 sq-in 0.48 1.11036
5.0508

psi
kip

k-ft
k-ft

kip

k-ft
k-ft
P = 18 kip
L = 15 ft
X L= 10.5 ft
Mf (L) = 17.01 k-ft
Mf (R) = 39.69 k-ft

w5 = 2.5 k/ft w6 = 2.5 k/ft


L5 = 18 ft L6 = 18 ft
!------------------------------------------ !------------------------------------------ !
0.5 0.57143 ! 0.42857 ### !
!------------------------------------------ !------------------------------------------ !
-67.5 67.5 ! -67.5 67.5 !
! -33.75 -67.5 !
0 19.2857 ! 14.4643 !
9.64286 0! !
-4.82143 0! 0 !
0 -2.41071 ! !
0 1.37755 ! 1.03316 !
0.68878 0! !
-0.34439 0! 0 !
0 -0.17219 ! !
0 0.0984 ! 0.0738 !
0.0492 0! !
-0.0246 0! 0 !
!------------------------------------------ !------------------------------------------ !---------------------------------------------
-62.3096 85.6788 ! -85.6788 0!
27.2558 58.4106
50.625 67.5
w5 = 1.55 k/ft
L5 = 16.5 ft

!------------------------------------------ !
0.41333 1!
!------------------------------------------ !
-35.1656 35.1656 !
-17.5828 -35.1656 !
11.0448 !
!
1.47348 !
!
1.13558 !
!
1.04612 !
!
0.17438 !
!
0.21912 !
!------------------------------------------ !
-37.6549 0!
33.921
35.1656
w5 = 2.15 k/ft w6 = 1.75 k/ft
L5 = 16.75 ft L6 = 22 ft

!------------------------------------------ !------------------------------------------ !
0.29474 0.63653 ! 0.36347 1!
!------------------------------------------ !------------------------------------------ !
-50.2674 50.2674 ! -70.5833 70.5833 !
! -35.2917 -70.5833 !
12.2281 35.3958 ! 20.2118 !
17.6979 6.11406 ! !
-1.24744 -3.89177 ! -2.22229 !
-1.94589 -0.62372 ! !
2.08041 0.39702 ! 0.2267 !
0.19851 1.04021 ! !
0.14647 -0.66212 ! -0.37809 !
-0.33106 0.07324 ! !
0.41066 -0.04662 ! -0.02662 !
-0.02331 0.20533 ! !
0.05859 -0.1307 ! -0.07463 !
!------------------------------------------ !------------------------------------------ !---------------------------------------------
-20.9945 88.1381 ! -88.1381 0!
20.8349 61.8059
37.7006 70.5833
w5 = 1.9 k/ft
L5 = 22 ft
P = 10 kip
X L= 7 ft
Mf (L) = 32.5413 k-ft
Mf (R) = 15.186 k-ft
R(R) = 18.5369 kip
R(L) = 33.2631 kip

!------------------------------------------ !
0.21429 1!
!------------------------------------------ !
-109.175 91.8193 !
-45.9096 -91.8193 !
28.9181 !
!
0.06577 !
!
3.51052 !
!
0.01104 !
!
0.58908 !
!
0.00185 !
!------------------------------------------ !
-121.988 0!
53.956
76.6333
w5 = 1.9 k/ft
L5 = 9.5 ft
P = 0 kip
X L= 10.5 ft
Mf (L) = 0 k-ft
Mf (R) = 0 k-ft
R(R) = 6.64883 kip
R(L) = 11.4012 kip

!------------------------------------------ !
0.33913 1!
!------------------------------------------ !
-14.2896 14.2896 !
-7.14479 -14.2896 !
-0.41765 !
!
-0.12622 !
!
-0.1222 !
!
-0.34853 !
!
-0.02888 !
!
-0.09576 !
!------------------------------------------ !
-22.5736 0!
10.1476
14.2896
N. NICE ( 1st & 2nd floor) 100% O.K.

DESIGN OF FLAT PLATE (USD) (N - S DIRECTION)

In the short direction (3 or more span )

f'c = 3 ksi
fy = 40 ksi
Plate thickness = t = 7 in
Dead Load (slab) = 87.5 psf
Floor finish = 20 psf
Partition load = 40 psf
------------------------------------------------------------------
Total Dead Load = 147.5 psf
Total Dead Load = 0.1475 ksf
Live Load = 0.04 ksf
Wu (D.L.+L.L.) = 0.2745 ksf
Add. Load at C.S. = 0 k/ft
Wu (Add. Load) = 0 k/ft
Maxm.Lat. Load Moment = 60 k-ft
Column c/c distance
In the Short dir.of the bldg = 16.5 ft
In the Long dir.of the bldg = 13 ft
Column Size = 20 in
= 12 in

IN THE SHORT DIRECTION OF THE BUILDING :-

Total Static Moment


Mo for D. L & L. L = 98.1461 k-ft
Static Moment for D. L only = 73.8331 k-ft
Additional Moment at C.S. = 0 k-ft
Maxm.Lat. Load Moment = 78 k-ft

INTERIOR SPAN (3 or more span)

M (-) C.S for D. L & L. L = 47.8462 k-ft


M (-) C.S for D. L, L. L & EQ = 145.28 k-ft
M (-) C.S for D. L & EQ = 143.934 k-ft
M (-) C.S (design) = 145.28 k-ft
Beam Size , b = 78 in
d = 5.75 in
pb = 0.03712
pmax = 0.02784
As -A's = 12.4864 sq-in
a = 2.5111 in
M (max) = 168.359 k-ft < 145.28 k-ft
M1=M(design) - M(max) = -23.079 k-ft
A's = -1.7096 sq-in as no. of bar
As = 10.7769 sq-in 0.31 34.764
OR 2.31015 inch c/c
a (assumed) = 2 in
As = 10.1951 sq-in 0.31 32.8873
a = 2.05029 in 2.44611 inch c/c
M (+) C.S. = 20.6107 k-ft
M (+) C.S (due to EQ.) = 68.4784 k-ft
M (+) C.S (design) = 68.4784 k-ft
a (assumed) = 0.86 in
As = 4.29063 sq-in 0.31 13.8407
a = 0.86287 in 6.07442 inch c/c
M (-) M.S = 15.9487 k-ft
a (assumed) = 0.19 in
As = 0.9401 sq-in 0.11 8.54634
a = 0.18906 in 9.12672 inch c/c
M (+) M.S = 13.7405 k-ft
a (assumed) = 0.16 in
As = 0.80779 sq-in 0.11 7.34352
a = 0.16245 in 10.6216 inch c/c
As(nominal) M.S. = 2.2425 sq-in 0.12 18.6875
4.17391 inch c/c

END SPAN
INTERIOR (-) VE

M (-) C.S = 51.5267 k-ft


= 148.04 k-ft
= 157.914 k-ft
M (-) C.S (design) = 157.914 k-ft
pb = 0.03712
pmax = 0.02784
As -A's = 12.4864 sq-in
a = 2.5111 in
M (max) = 168.359 k-ft < 157.914 k-ft
M1=M(design) - M(max) = -10.445 k-ft
A's = -0.7737 sq-in as no. of bar
As = 11.7127 sq-in 0.31 37.783
OR 2.12054 inch c/c
a (assumed) = 2.3 in
As = 11.443 sq-in 0.31 36.9131
a = 2.30127 in 2.17191 inch c/c
M (+) C.S = 30.6216 k-ft
M (+) C.S (due to EQ.) = 65.1659 k-ft
M (+) C.S (design) = 65.1659 k-ft
a (assumed) = 0.81 in
As = 4.06398 sq-in 0.31 13.1096
a = 0.81729 in 6.44116 inch c/c
M (-) M.S = 17.1756 k-ft
a (assumed) = 0.2 in
As = 1.01331 sq-in 0.11 9.21189
a = 0.20378 in 8.46731 inch c/c
M (+) M.S = 20.4144 k-ft
a (assumed) = 0.24 in
As = 1.20867 sq-in 0.11 10.9879
a = 0.24307 in 7.09873 inch c/c

EXTERIOR (-) VE

M (-) C.S = 29.4438 k-ft


= 131.478 k-ft
= 138.039 k-ft
M (-) C.S (design) = 138.039 k-ft
pb = 0.03712
p max = 0.02784
As -A's = 12.4864 sq-in
a = 2.5111 in
M max = 168.359 k-ft < 138.039 k-ft
M1= Mdesign - M max = -30.32 k-ft
A's = -2.2459 sq-in as no. of bar
As = 10.2405 sq-in 0.31 33.034
OR 2.43491 inch c/c
a (assumed) = 2 in
As = 9.68698 sq-in 0.31 31.2483
a = 1.94811 in 2.57866 inch c/c

PUNCHING SHEAR

Punching Area = 500.25 sq-in.


Vc = 93.1594 kip
Vup = 58.3526 kip > 93.1594 kip
Allowable Vc = 46.5797 kip
Vs(reqd) =Vup/Q-Vc = 22.0704 kip
S =Stirrup Spacing = 4 in. c/c
No. of Leg = 8
Since stirrup shall be placed in 4-faces,
use 8-leg in calculating Av
Av =Vs. s / fy. d = 0.38383 sq-in.
dia. of stirrup bar = 0.04798 sq-in.
Length of zone for shear reinf. is given by,
a = 5.12458 in

Check Shear with Lateral Load Moment

Lateral Load Moment on Plates to be


Transfered by Shear = 10 k-ft
Shear Modulus = J/c = 5083.48 cu-in.
Shear Stress = 23.6059 psi
vup (gravity load) = 116.647 psi
vup (design) = 117.583 psi < 116.647 psi

N. NICE ( 1st & 2nd floor) 100% O.K.

DESIGN OF FLAT PLATE (USD) (N - S DIRECTION)

In the short direction (3 or more span )

f'c = 3 ksi
fy = 40 ksi
Plate thickness = t = 7 in
Dead Load (slab) = 87.5 psf
Floor finish = 20 psf
Partition load = 40 psf
------------------------------------------------------------------
Total Dead Load = 147.5 psf
Total Dead Load = 0.1475 ksf
Live Load = 0.04 ksf
Wu (D.L.+L.L.) = 0.2745 ksf
Add. Load at C.S. = 0 k/ft
Wu (Add. Load) = 0 k/ft
Maxm.Lat. Load Moment = 63 k-ft
Column c/c distance
In the Short dir.of the bldg = 12.5 ft
In the Long dir.of the bldg = 13 ft
Column Size = 20 in
= 12 in

IN THE SHORT DIRECTION OF THE BUILDING :-

Total Static Moment


Mo for D. L & L. L = 52.3504 k-ft
Static Moment for D. L only = 39.382 k-ft
Additional Moment at C.S. = 0 k-ft
Maxm.Lat. Load Moment = 81.9 k-ft

INTERIOR SPAN (3 or more span)

M (-) C.S for D. L & L. L = 25.5208 k-ft


M (-) C.S for D. L, L. L & EQ = 134.005 k-ft
M (-) C.S for D. L & EQ = 134.396 k-ft
M (-) C.S (design) = 134.396 k-ft
Beam Size , b = 78 in
d = 5.75 in
pb = 0.03712
pmax = 0.02784
As -A's = 12.4864 sq-in
a = 2.5111 in
M (max) = 168.359 k-ft < 134.396 k-ft
M1=M(design) - M(max) = -33.963 k-ft
A's = -2.5158 sq-in as no. of bar
As = 9.97064 sq-in 0.31 32.1634
OR 2.50294 inch c/c
a (assumed) = 1.8 in
As = 9.23683 sq-in 0.31 29.7962
a = 1.85758 in 2.70869 inch c/c
M (+) C.S. = 10.9936 k-ft
M (+) C.S (due to EQ.) = 94.1483 k-ft
M (+) C.S (design) = 94.1483 k-ft
a (assumed) = 1.12 in
As = 6.04677 sq-in 0.31 19.5057
a = 1.21604 in 4.21491 inch c/c
M (-) M.S = 8.50694 k-ft
a (assumed) = 0.19 in
As = 0.50144 sq-in 0.11 4.55855
a = 0.10084 in 17.1107 inch c/c
M (+) M.S = 7.32905 k-ft
a (assumed) = 0.16 in
As = 0.43087 sq-in 0.11 3.91698
a = 0.08665 in 19.9133 inch c/c
As(nominal) M.S. = 2.2425 sq-in 0.12 18.6875
4.17391 inch c/c

!---------------------------------------------

END SPAN
INTERIOR (-) VE

M (-) C.S = 27.484 k-ft


= 135.478 k-ft
= 141.853 k-ft
M (-) C.S (design) = 141.853 k-ft
pb = 0.03712
pmax = 0.02784
As -A's = 12.4864 sq-in
a = 2.5111 in
M (max) = 168.359 k-ft < 141.853 k-ft
M1=M(design) - M(max) = -26.506 k-ft
A's = -1.9634 sq-in as no. of bar
As = 10.523 sq-in 0.31 33.9451
OR 2.36757 inch c/c
a (assumed) = 1.9 in
As = 9.85087 sq-in 0.31 31.777
a = 1.98107 in 2.53436 inch c/c
M (+) C.S = 16.3333 k-ft
M (+) C.S (due to EQ.) = 92.3814 k-ft
M (+) C.S (design) = 92.3814 k-ft
a (assumed) = 1.1 in
As = 5.92189 sq-in 0.31 19.1029
a = 1.19093 in 4.30871 inch c/c
M (-) M.S = 9.16132 k-ft
a (assumed) = 0.2 in
As = 0.54049 sq-in 0.11 4.91355
a = 0.1087 in 15.8745 inch c/c
M (+) M.S = 10.8889 k-ft
a (assumed) = 0.24 in
As = 0.64469 sq-in 0.11 5.86085
a = 0.12965 in 13.3086 inch c/c

EXTERIOR (-) VE

M (-) C.S = 15.7051 k-ft


= 126.644 k-ft
= 131.252 k-ft
M (-) C.S (design) = 131.252 k-ft
pb = 0.03712
p max = 0.02784
As -A's = 12.4864 sq-in
a = 2.5111 in
M max = 168.359 k-ft < 131.252 k-ft
M1= Mdesign - M max = -37.107 k-ft
A's = -2.7487 sq-in as no. of bar
As = 9.73774 sq-in 0.31 31.4121
OR 2.56477 inch c/c
a (assumed) = 1.7 in
As = 8.92868 sq-in 0.31 28.8022
a = 1.79561 in 2.80553 inch c/c

PUNCHING SHEAR

Punching Area = 500.25 sq-in.


Vc = 93.1594 kip
Vup = 44.0786 kip > 93.1594 kip
Allowable Vc = 46.5797 kip
Vs(reqd) =Vup/Q-Vc = 5.27745 kip
S =Stirrup Spacing = 4 in. c/c
No. of Leg = 8
Since stirrup shall be placed in 4-faces,
use 8-leg in calculating Av
Av =Vs. s / fy. d = 0.09178 sq-in.
dia. of stirrup bar = 0.01147 sq-in.
Length of zone for shear reinf. is given by,
a = 0.41162 in

Check Shear with Lateral Load Moment

Lateral Load Moment on Plates to be


Transfered by Shear = 7 k-ft
Shear Modulus = J/c = 5083.48 cu-in.
Shear Stress = 16.5241 psi
vup (gravity load) = 88.1131 psi
vup (design) = 87.1531 psi < 88.1131 psi
SCHEDULE OF REINFORCEMENT FOR 1ST & 2ND FLOOR SLAB

Bottom Bar

(a) = 16 - D16 mm O @ 6" c/c allthrough (B) (B.B.B) within C.S.


(b) = - D12 mm O @ 6" c/c allthrough (B) (B.B.B) within C.S.
(c) = D10 mm O @ 5" c/c allthrough within C.S.

(k) = 16 - D16 mm O @ 6" c/c allthrough (B) (B.B.B) within C.S.


(L) = - D12 mm O @ 6" c/c allthrough (B) (B.B.B) within C.S.
(m) = D10 mm O @ 5" c/c allthrough within C.S.

Top Bar

(1) = 16 - D16 mm O @ 6" c/c allthrough (T) (A.T.B) within C.S.


(2) = D12 mm O @ 6" c/c allthrough (T) (A.T.B) within C.S.
(3) = 1 - D12 mm O @ 6" c/c (E.T) along with (2) within C.S.
(4) = 1 - D12 mm O @ 6" c/c (E.T) along with (1) within C.S.
(5) = 2 - D16 mm O (bundle) @ 6" c/c (E.T) for middle 7 gap &
1 - D12 mm O @ 6" c/c (E.T) both sides for another 8 gap
along with (1) within C.S.
(6) = 2 - D16 mm O (bundle) @ 6" c/c (E.T) for 3 gap near beam &
1 - D12 mm O @ 6" c/c (E.T) for others gap near M.S. along
with (1) within C.S.
(7) = 2 - D16 mm O (bundle) @ 6" c/c (E.T) for 5 gap near beam &
1 - D12 mm O @ 6" c/c (E.T) for others gap near M.S. along
with (1) within C.S.
(8) = - D10 mm O @ 5" c/c (E.T) within M.S.

Top Bar
(11) = 16 - D16 mm O @ 6" c/c allthrough (T) (A.T.B) within C.S.
(12) = D12 mm O @ 6" c/c allthrough (T) (A.T.B) within C.S.
(13) = 1 - D12 mm O @ 6" c/c (E.T) along with (2) within C.S.
(14) = 1 - D12 mm O @ 6" c/c (E.T) along with (1) within C.S.
(15) = 2 - D16 mm O (bundle) @ 6" c/c (E.T) for middle 7 gap &
1 - D12 mm O @ 6" c/c (E.T) both sides for another 8 gap
along with (1) within C.S.
(16) = 2 - D16 mm O (bundle) @ 6" c/c (E.T) for 3 gap near beam &
1 - D12 mm O @ 6" c/c (E.T) for others gap near M.S. along
with (1) within C.S.
(17) = 2 - D16 mm O (bundle) @ 6" c/c (E.T) for 5 gap near beam &
1 - D12 mm O @ 6" c/c (E.T) for others gap near M.S. along
with (1) within C.S.
(18) = - D10 mm O @ 5" c/c (E.T) within M.S.
!---------------------------------------------
N. NICE ( 1st & 2nd floor) 100% O.K.

DESIGN OF FLAT PLATE (USD) (E - W DIRECTION)

In the long direction (for 2 - span)

f'c = 3 ksi
fy = 55 ksi
Plate thickness = t = 36 in
Dead Load (slab) = 450 psf
Floor finish = 20 psf
Partition load = 40 psf
------------------------------------------------------------------
Total Dead Load = 510 psf
Total Dead Load = 0.51 ksf
Live Load = 0.04 ksf
Wu (D.L.+L.L.) = 0.782 ksf
Add. Load at C.S. = 0 k/ft
Wu (Add. Load) = 0 k/ft
Maxm.Lat. Load Moment = 65 k-ft
Column c/c distance
In the Long dir.of the bldg = 15.5 ft
In the Short dir.of the bldg = 14.5 ft
Column Size = 12 in
= 20 in

IN THE LONG DIRECTION OF THE BUILDING :-

Total Static Moment


Mo for D. L & L. L = 298.00309 k-ft
Static Moment for D. L only = 272.08978 k-ft
Additional Moment at C.S. = 0 k-ft
Maxm.Lat. Load Moment = 84.5 k-ft

INTERIOR SPAN (for 2 - span)

M (-) C.S for D. L & L. L = 178.80186 k-ft


M (-) C.S for D. L, L. L & EQ = 252.61264 k-ft
M (-) C.S for D. L & EQ = 267.76348 k-ft
M (-) C.S (design) = 267.76348 k-ft
Beam Size , b = 87 in
d = 34.75 in
pb = 0.024145
pmax = 0.0181088
As -A's = 54.747293 sq-in
a = 13.572689 in
M (max) = 6315.1045 k-ft > 267.7635 k-ft
M1=M(design) - M(max) = -6047.341 k-ft
A's = -43.76185 sq-in as no. of bar
As = 10.98544 sq-in 0.31 35.4369
OR 2.52636 inch c/c
a (assumed) = 2 in
As = 1.9233292 sq-in 0.31 6.204288
a = 0.4768226 in 16.71699 inch c/c
M (+) C.S. = 107.28111 k-ft
M (+) C.S (due to EQ.) = -40.08667 k-ft
M (+) C.S (design) = 107.28111 k-ft
a (assumed) = 0.6 in
As = 0.7549359 sq-in 0.31 2.435277
a = 0.1871601 in 60.61547 inch c/c
M (-) M.S = 59.600619 k-ft
a (assumed) = 0.22 in
As = 0.4171084 sq-in 0.11 3.791895
a = 0.1034075 in 22.94368 inch c/c
M (+) M.S = 71.520743 k-ft
a (assumed) = 0.27 in
As = 0.5008916 sq-in 0.11 4.55356
a = 0.1241787 in 19.10593 inch c/c
As(nominal) M.S. = 10.993636 sq-in 0.12 91.61364
0.94964 inch c/c

EXTERIOR (-) VE

M (-) C.S = 89.400928 k-ft


= 185.56195 k-ft
= 201.29584 k-ft
M (-) C.S (design) = 201.29584 k-ft
pb = 0.024145
p max = 0.0181088
As -A's = 54.747293 sq-in
a = 13.572689 in
M max = 6315.1045 k-ft < 201.2958 k-ft
M1= Mdesign - M max = -6113.809 k-ft
A's = -44.24285 sq-in as no. of bar
As = 10.504444 sq-in 0.31 33.8853
OR 2.645559 inch c/c
a (assumed) = 1.7 in
As = 1.4394982 sq-in 0.31 4.643543
a = 0.3568736 in 23.87786 inch c/c

PUNCHING SHEAR

Punching Area = 7054.25 sq-in.


Vc = 1313.6824 kip
Vup = 170.99428 kip > 1313.682 kip
Allowable Vc = 656.84121 kip
Vs(reqd) =Vup/Q-Vc = -455.6715 kip
S =Stirrup Spacing = 4 in. c/c
No. of Leg = 8
Since stirrup shall be placed in 4-faces,
use 8-leg in calculating Av
Av =Vs. s / fy. d = -0.953662 sq-in.
dia. of stirrup bar = -0.119208 sq-in.
Length of zone for shear reinf. is given by,
a = 0.8567696 in

Check Shear with Lateral Load Moment

Lateral Load Moment on Plates to be


Transfered by Shear = 5 k-ft
Shear Modulus = J/c = 101264.4 cu-in.
Shear Stress = 0.5925083 psi
vup (gravity load) = 24.239895 psi
vup (design) = 18.935369 psi < 24.23989 psi
N. NICE ( 1st & 2nd floor) 100% O.K.

DESIGN OF FLAT PLATE (USD) (E - W DIRECTION)

In the long direction (for 2 - span)

f'c = 3 ksi
fy = 40 ksi
Plate thickness = t = 7 in
Dead Load (slab) = 87.5 psf
Floor finish = 20 psf
Partition load = 40 psf
------------------------------------------------------------------
Total Dead Load = 147.5 psf
Total Dead Load = 0.1475 ksf
Live Load = 0.04 ksf
Wu (D.L.+L.L.) = 0.2745 ksf
Add. Load at C.S. = 0 k/ft
Wu (Add. Load) = 0 k/ft
Maxm.Lat. Load Moment = 65 k-ft
Column c/c distance
In the Long dir.of the bldg = 10.5 ft
In the Short dir.of the bldg = 14.5 ft
Column Size = 12 in
= 20 in

IN THE LONG DIRECTION OF THE BUILDING :-

Total Static Moment


Mo for D. L & L. L = 44.902195 k-ft
Static Moment for D. L only = 33.778883 k-ft
Additional Moment at C.S. = 0 k-ft
Maxm.Lat. Load Moment = 84.5 k-ft

INTERIOR SPAN (for 2 - span)

M (-) C.S for D. L & L. L = 26.941317 k-ft


M (-) C.S for D. L, L. L & EQ = 138.71724 k-ft
M (-) C.S for D. L & EQ = 139.0756 k-ft
M (-) C.S (design) = 139.0756 k-ft
Beam Size , b = 87 in
d = 5.75 in
pb = 0.0371206
pmax = 0.0278404
As -A's = 13.927174 sq-in
a = 2.5110974 in
M (max) = 187.78502 k-ft > 139.0756 k-ft
M1=M(design) - M(max) = -48.70942 k-ft
A's = -3.608105 sq-in as no. of bar
As = 10.319069 sq-in 0.31 33.28732
OR 2.694556 inch c/c
a (assumed) = 1.7 in
As = 9.4609249 sq-in 0.31 30.51911
a = 1.7058237 in 2.947243 inch c/c
M (+) C.S. = 16.16479 k-ft
M (+) C.S (due to EQ.) = 96.587815 k-ft
M (+) C.S (design) = 96.587815 k-ft
a (assumed) = 1.1 in
As = 6.1915266 sq-in 0.31 19.97267
a = 1.1163447 in 4.585544 inch c/c
M (-) M.S = 8.9804391 k-ft
a (assumed) = 0.09 in
As = 0.5247116 sq-in 0.11 4.770105
a = 0.0946066 in 18.23859 inch c/c
M (+) M.S = 10.776527 k-ft
a (assumed) = 0.11 in
As = 0.6307595 sq-in 0.11 5.734178
a = 0.1137272 in 15.17218 inch c/c
As(nominal) M.S. = 2.50125 sq-in 0.12 20.84375
4.173913 inch c/c

EXTERIOR (-) VE

M (-) C.S = 13.470659 k-ft


= 128.61424 k-ft
= 132.95859 k-ft
M (-) C.S (design) = 132.95859 k-ft
pb = 0.0371206
p max = 0.0278404
As -A's = 13.927174 sq-in
a = 2.5110974 in
M max = 187.78502 k-ft < 132.9586 k-ft
M1= Mdesign - M max = -54.82642 k-ft
A's = -4.061217 sq-in as no. of bar
As = 9.8659575 sq-in 0.31 31.82567
OR 2.822323 inch c/c
a (assumed) = 1.6 in
As = 8.9534406 sq-in 0.31 28.88207
a = 1.6143233 in 3.120285 inch c/c

PUNCHING SHEAR

Punching Area = 500.25 sq-in.


Vc = 93.159391 kip
Vup = 41.158201 kip > 93.15939 kip
Allowable Vc = 46.579696 kip
Vs(reqd) =Vup/Q-Vc = 1.8417175 kip
S =Stirrup Spacing = 4 in. c/c
No. of Leg = 8
Since stirrup shall be placed in 4-faces,
use 8-leg in calculating Av
Av =Vs. s / fy. d = 0.0320299 sq-in.
dia. of stirrup bar = 0.0040037 sq-in.
Length of zone for shear reinf. is given by,
a = 5.1042351 in

Check Shear with Lateral Load Moment

Lateral Load Moment on Plates to be


Transfered by Shear = 5 k-ft
Shear Modulus = J/c = 2415.4792 cu-in.
Shear Stress = 24.839792 psi
vup (gravity load) = 82.275265 psi
vup (design) = 93.377183 psi < 82.27526 psi
DESIGN OF FLAT PLATE (WSD)

In the long direction (3 or more span )

f'c = 2.5
fy = 40
k = 0.3866667
j = 0.8711111
R = 0.1894667
Plate thickness = t = 27
Dead Load (slab) = 337.5
Floor finish = 20
Partition load = 0
------------------------------------------------------------------
Total Dead Load = 357.5
Total Dead Load = 0.3575
Live Load = 1
Wu (D.L.+L.L.) = 1.3575
Add. Load at C.S. = 0
Wu (Add. Load) = 0
Maxm.Lat. Load Moment = 0
Column c/c distance
In the Long dir.of the bldg = 24
In the Short dir.of the bldg = 18
Column Size = 15
= 15

IN THE LONG DIRECTION OF THE BUILDING :-

Total Static Moment Mo = 1580.83


Static Moment for D.L only = 416.31434
Additional Moment at C.S. = 0
Maxm.Lat. Load Moment = 0

INTERIOR SPAN (3 or more span)

M (-) C.S for D. L & L . L. = 770.65461


M (-) C.S for D. L, L . L & EQ.
= 577.99095
M (-) C.S for D. L & EQ. = 202.95324
M (-) C.S (design) = 770.65461
Beam Size , b = 108
d (pro) = 25.75
d (req) = 21.25897
M1 = 1130.6542
M2 = -359.99957
As1 = 33.60375
As2 = -9.7959066
As = 23.807843
f's = 19.846349
A's = -8.8845723

M (+) C.S. = 331.97429


M (+) C.S (due to EQ.) = -770.65461
M (+) C.S (design) = 331.97429
As = 9.8664838

M (-) M.S = 256.88487


As = 7.6347791

M (+) M.S = 221.31619


As = 6.5776559

As(nominal) M.S. = 13.905

END SPAN
INTERIOR (-) VE

M (-) C.S for D. L & L . L. = 829.93573


M (-) C.S for D. L, L . L & EQ.
= 622.4518
M (-) C.S for D. L & EQ. = 218.56503
M (-) C.S (design) = 218.56503

M1 = 1130.6542
M2 = -912.08915
As1 = 33.60375
As2 = -24.818752
As = 8.7849977
f's = 19.846349
A's = -22.50981

M (+) C.S. = 331.97429


M (+) C.S (due to EQ.) = -770.65461
M (+) C.S (design) = 331.97429
As = 9.8664838

M (-) M.S = 256.88487


As = 7.6347791

M (+) M.S = 221.31619


As = 6.5776559

As(nominal) M.S. = 13.905

EXTERIOR (-) VE

M (-) C.S for D. L & L . L. = 474.24899


M (-) C.S for D. L, L . L & EQ.
= 355.68674
M (-) C.S for D. L & EQ. = 124.8943
M (-) C.S (design) = 124.8943

M1 = 1130.6542
M2 = -1005.7599
As1 = 33.60375
As2 = -27.367616
As = 6.2361344
f's = 19.846349
A's = -24.821547

PUNCHING SHEAR

Punching Area = 4197.25


Vc = 713.5325
Vup = 581.15789
Allowable Vc = 356.76625
Vs(reqd) =Vup/Q-Vc = 326.94891
S =Stirrup Spacing = 2.75
No. of Leg = 8
Since stirrup shall be placed in 4-faces,
use 8-leg in calculating Av
Av =Vs. s / fy. d = 0.8729219
dia. of stirrup bar = 0.1091152
Length of zone for shear reinf. is given by,
a = 36.331226

Check Shear with Lateral Load Moment

Lateral Load Moment on Plates to be


Transfered by Shear = 20
Shear Modulus = J/c = 57012.646
Shear Stress = 4.2095924
vup (gravity load) = 138.46158
vup (design) = 109.21342

DESIGN OF FOUNDATION (WSD)

DESIGN OF FLAT PLATE (WSD)

In the long direction (3 or more span )

f'c = 2.5
fy = 40
k = 0.3866667
j = 0.8711111
R = 0.1894667
Plate thickness = t = 27
Dead Load (slab) = 337.5
Floor finish = 20
Partition load = 250
------------------------------------------------------------------
Total Dead Load = 607.5
Total Dead Load = 0.6075
Live Load = 0.6
Wu (D.L.+L.L.) = 1.2075
Add. Load at C.S. = 0
Wu (Add. Load) = 0
Maxm.Lat. Load Moment = 0
Column c/c distance
In the Long dir.of the bldg = 19
In the Short dir.of the bldg = 18
Column Size = 15
= 20

IN THE LONG DIRECTION OF THE BUILDING :-

Total Static Moment Mo = 855.98543


Static Moment for D.L only = 430.65105
Additional Moment at C.S. = 0
Maxm.Lat. Load Moment = 0

INTERIOR SPAN (3 or more span)

M (-) C.S for D. L & L . L. = 417.2929


M (-) C.S for D. L, L . L & EQ.
= 312.96967
M (-) C.S for D. L & EQ. = 209.94239
M (-) C.S (design) = 417.2929
Beam Size , b = 108
d (pro) = 25.75
d (req) = 15.643461
M1 = 1130.6542
M2 = -713.36128
As1 = 33.60375
As2 = -19.411191
As = 14.192559
f's = 19.846349
A's = -17.605326

M (+) C.S. = 179.75694


M (+) C.S (due to EQ.) = -417.2929
M (+) C.S (design) = 179.75694
As = 5.3424888
M (-) M.S = 139.09763
As = 4.1340687

M (+) M.S = 119.83796


As = 3.5616592

As(nominal) M.S. = 13.905

END SPAN
INTERIOR (-) VE

M (-) C.S for D. L & L . L. = 449.39235


M (-) C.S for D. L, L . L & EQ.
= 337.04426
M (-) C.S for D. L & EQ. = 226.0918
M (-) C.S (design) = 226.0918

M1 = 1130.6542
M2 = -904.56237
As1 = 33.60375
As2 = -24.613942
As = 8.9898079
f's = 19.846349
A's = -22.324054

M (+) C.S. = 179.75694


M (+) C.S (due to EQ.) = -417.2929
M (+) C.S (design) = 179.75694
As = 5.3424888

M (-) M.S = 139.09763


As = 4.1340687

M (+) M.S = 119.83796


As = 3.5616592

As(nominal) M.S. = 13.905


EXTERIOR (-) VE

M (-) C.S for D. L & L . L. = 256.79563


M (-) C.S for D. L, L . L & EQ.
= 192.59672
M (-) C.S for D. L & EQ. = 129.19532
M (-) C.S (design) = 129.19532

M1 = 1130.6542
M2 = -1001.4589
As1 = 33.60375
As2 = -27.250581
As = 6.3531688
f's = 19.846349
A's = -24.715401

PUNCHING SHEAR

Punching Area = 4454.75


Vc = 757.3075
Vup = 406.55802
Allowable Vc = 378.65375
Vs(reqd) =Vup/Q-Vc = 99.6498
S =Stirrup Spacing = 2.75
No. of Leg = 8
Since stirrup shall be placed in 4-faces,
use 8-leg in calculating Av
Av =Vs. s / fy. d = 0.2660553
dia. of stirrup bar = 0.0332569
Length of zone for shear reinf. is given by,
a = 22.229484
Check Shear with Lateral Load Moment

Lateral Load Moment on Plates to be


Transfered by Shear = 20
Shear Modulus = J/c = 57012.646
Shear Stress = 4.2095924
vup (gravity load) = 91.263936
vup (design) = 73.815182

DESIGN OF FOUNDATION (WSD)

DESIGN OF FLAT PLATE (WSD)

In the long direction (3 or more span )

f'c = 2.5
fy = 40
k = 0.3866667
j = 0.8711111
R = 0.1894667
Plate thickness = t = 27
Dead Load (slab) = 337.5
Floor finish = 20
Partition load = 250
------------------------------------------------------------------
Total Dead Load = 607.5
Total Dead Load = 0.6075
Live Load = 0.6
Wu (D.L.+L.L.) = 1.2075
Add. Load at C.S. = 0
Wu (Add. Load) = 0
Maxm.Lat. Load Moment = 0
Column c/c distance
In the Long dir.of the bldg = 19
In the Short dir.of the bldg = 18
Column Size = 15
= 20

IN THE LONG DIRECTION OF THE BUILDING :-

Total Static Moment Mo = 855.98543


Static Moment for D.L only = 430.65105
Additional Moment at C.S. = 0
Maxm.Lat. Load Moment = 0

INTERIOR SPAN (3 or more span)

M (-) C.S for D. L & L . L. = 417.2929


M (-) C.S for D. L, L . L & EQ.
= 312.96967
M (-) C.S for D. L & EQ. = 209.94239
M (-) C.S (design) = 417.2929
Beam Size , b = 108
d (pro) = 25.75
d (req) = 15.643461
M1 = 1130.6542
M2 = -713.36128
As1 = 33.60375
As2 = -19.411191
As = 14.192559
f's = 19.846349
A's = -17.605326

M (+) C.S. = 179.75694


M (+) C.S (due to EQ.) = -417.2929
M (+) C.S (design) = 179.75694
As = 5.3424888

M (-) M.S = 139.09763


As = 4.1340687

M (+) M.S = 119.83796


As = 3.5616592

As(nominal) M.S. = 13.905

DESIGN OF FOUNDATION (WSD)

DESIGN OF FLAT PLATE (WSD)


In the long direction (3 or more span )

f'c = 2.5
fy = 40
k = 0.3866667
j = 0.8711111
R = 0.1894667
Plate thickness = t = 27
Dead Load (slab) = 337.5
Floor finish = 20
Partition load = 250
------------------------------------------------------------------
Total Dead Load = 607.5
Total Dead Load = 0.6075
Live Load = 0.6
Wu (D.L.+L.L.) = 1.2075
Add. Load at C.S. = 0
Wu (Add. Load) = 0
Maxm.Lat. Load Moment = 0
Column c/c distance
In the Long dir.of the bldg = 24
In the Short dir.of the bldg = 18
Column Size = 15
= 20

IN THE LONG DIRECTION OF THE BUILDING :-

Total Static Moment Mo = 1406.1526


Static Moment for D.L only = 707.44324
Additional Moment at C.S. = 0
Maxm.Lat. Load Moment = 0

INTERIOR SPAN (3 or more span)

M (-) C.S for D. L & L . L. = 685.4994


M (-) C.S for D. L, L . L & EQ.
= 514.12455
M (-) C.S for D. L & EQ. = 344.87858
M (-) C.S (design) = 685.4994
Beam Size , b = 108
d (pro) = 25.75
d (req) = 20.050069
M1 = 1130.6542
M2 = -445.15477
As1 = 33.60375
As2 = -12.113055
As = 21.490695
f's = 19.846349
A's = -10.986151

M (+) C.S. = 295.29205


M (+) C.S (due to EQ.) = -685.4994
M (+) C.S (design) = 295.29205
As = 8.7762646

M (-) M.S = 228.4998


As = 6.7911571

M (+) M.S = 196.86137


As = 5.8508431

As(nominal) M.S. = 13.905

DESIGN OF FOUNDATION (WSD)

DESIGN OF FLAT PLATE (WSD)

In the long direction (3 or more span )

f'c = 2.5
fy = 40
k = 0.3866667
j = 0.8711111
R = 0.1894667
Plate thickness = t = 27
Dead Load (slab) = 337.5
Floor finish = 20
Partition load = 250
------------------------------------------------------------------
Total Dead Load = 607.5
Total Dead Load = 0.6075
Live Load = 0.6
Wu (D.L.+L.L.) = 1.2075
Add. Load at C.S. = 0
Wu (Add. Load) = 0
Maxm.Lat. Load Moment = 0
Column c/c distance
In the Long dir.of the bldg = 12
In the Short dir.of the bldg = 18
Column Size = 15
= 20

IN THE LONG DIRECTION OF THE BUILDING :-

Total Static Moment Mo = 313.96887


Static Moment for D.L only = 157.95949
Additional Moment at C.S. = 0
Maxm.Lat. Load Moment = 0

INTERIOR SPAN (3 or more span)

M (-) C.S for D. L & L . L. = 153.05982


M (-) C.S for D. L, L . L & EQ.
= 114.79487
M (-) C.S for D. L & EQ. = 77.005252
M (-) C.S (design) = 153.05982
Beam Size , b = 108
d (pro) = 25.75
d (req) = 9.4742086
M1 = 1130.6542
M2 = -977.59435
As1 = 33.60375
As2 = -26.601207
As = 7.0025431
f's = 19.846349
A's = -24.126439

M (+) C.S. = 65.933462


M (+) C.S (due to EQ.) = -153.05982
M (+) C.S (design) = 65.933462
As = 1.9595838

M (-) M.S = 51.019941


As = 1.5163446

M (+) M.S = 43.955641


As = 1.3063892

As(nominal) M.S. = 13.905


DESIGN OF FOUNDATION (WSD)

DESIGN OF FLAT PLATE (WSD)

In the long direction (3 or more span )

f'c = 2.5
fy = 40
k = 0.3866667
j = 0.8711111
R = 0.1894667
Plate thickness = t = 27
Dead Load (slab) = 337.5
Floor finish = 20
Partition load = 250
------------------------------------------------------------------
Total Dead Load = 607.5
Total Dead Load = 0.6075
Live Load = 0.6
Wu (D.L.+L.L.) = 1.2075
Add. Load at C.S. = 0
Wu (Add. Load) = 0
Maxm.Lat. Load Moment = 0
Column c/c distance
In the Long dir.of the bldg = 17
In the Short dir.of the bldg = 12
Column Size = 15
= 20

IN THE LONG DIRECTION OF THE BUILDING :-

Total Static Moment Mo = 449.3032


Static Moment for D.L only = 226.04695
Additional Moment at C.S. = 0
Maxm.Lat. Load Moment = 0

INTERIOR SPAN (3 or more span)

M (-) C.S for D. L & L . L. = 219.03531


M (-) C.S for D. L, L . L & EQ.
= 164.27648
M (-) C.S for D. L & EQ. = 110.19789
M (-) C.S (design) = 219.03531
Beam Size , b = 72
d (pro) = 25.75
d (req) = 13.880817
M1 = 753.76945
M2 = -534.73414
As1 = 22.4025
As2 = -14.550589
As = 7.8519112
f's = 19.846349
A's = -13.196916

M (+) C.S. = 94.353673


M (+) C.S (due to EQ.) = -219.03531
M (+) C.S (design) = 94.353673
As = 2.8042502

M (-) M.S = 73.011771


As = 2.1699555

M (+) M.S = 62.902448


As = 1.8695002

As(nominal) M.S. = 9.27


CHITTAGONG PROJECT
---------------------------------
DESIGN OF BEAM B1
---------------------------------
w = 1 k/ft fy =
L = 14 ft f'c =
ksi Beam Size k =
ksi 10 in j =
18 in R =
d(pro) = 15
M= 36 k-ft
in dreqd = 15 in ><
psf M1 = 33
psf M2 = 2
psf As1 = 2
---------------------------- As2 = 0
psf As=As1+ 2
ksf f's = 13
ksf As2 = 0
ksf
k/ft
k/ft
k-ft DESIGN OF BEAM - B2 (FOR 2-SPAN)
---------------------------------------------------
ft
ft w1 = 1 k/ft
in L1 = 11 ft
in
!---------------------------
OF THE BUILDING :- 1 0.61111 !
!---------------------------
k-ft -11.025 11.025 !
11.025 5.5125 !
k-ft 23.1688 !
k-ft !---------------------------
M (-) = 39.7063 !
M (+) = -3
11

M= 40 k-ft fy =
k-ft b  = 10 in.     f'c =
k-ft h  = 18 in.     k   =  
k-ft d(pro) = 15 j =
k-ft dreqd = 16 in. R =
in M1 = 33 k-ft
in M2 = 7 k-ft =
in. As1 = 2 sq-in M=
k-ft As2 = 0 sq-in M=
k-ft As = 2 sq-in M=
sq-in f's = 13 ksi M=
sq-in as no. of bar A's = 1 sq-in
sq-in 0.31 76.799495 V = 6 kip
ksi 1.42481 inch c/c Vd = 5 kip
sq-in 0.48 -18.509526 vd = 33 psi >
-5.53576 inch c/c av = 0 sq-in
k-ft Stirrup =### in. c/c
k-ft
k-ft
sq-in 0.31 31.827367 L= 15 ft
3.39331 inch c/c KL = 12 ft
k-ft K= 1
sq-in 0.11 69.407083 P= 14 kip
1.55604 inch c/c M f (left) 7 k-ft
k-ft M f(right) 27 k-ft
sq-in 0.11 59.796872
1.80611 inch c/c
sq-in 0.175 79.457143 DESIGN OF BEAM - B3 (FOR 3-SPAN)
1.35922 inch c/c ---------------------------------------------------
w1 = 1 k/ft
L1 = 11 ft

!---------------------------
1 0.53333 !
!---------------------------
-12.8625 12.8625 !
12.8625 6.43125 !
k-ft 10.19 !
k-ft !
k-ft -4.38111 !
k-ft !
0.66046 !
k-ft !
k-ft -0.28396 !
sq-in !
sq-in as no. of bar 0.04281 !
sq-in 0.48 18.302078 !
ksi 12.6323 inch c/c -0.0184 !
sq-in 0.48 -46.895438 !---------------------------
-4.56338 inch c/c M (-) = 25.5035 !
k-ft M (+) = 7
k-ft 13
k-ft
sq-in 0.31 31.827367 M= 56 k-ft fy =
6.8672 inch c/c b  = 10 in.     f'c =
k-ft h  = 21 in.     k   =  
sq-in 0.11 69.407083 d(pro) = 18 j =
3.14903 inch c/c dreqd = 19 in. R =
k-ft M1 = 48 k-ft
sq-in 0.11 59.796872 M2 = 8 k-ft =
3.65512 inch c/c As1 = 2 sq-in M =
sq-in 0.11 126.40909 As2 = 0 sq-in M =
1.72903 inch c/c As = 2 sq-in M =
f's = 14 ksi M=
A's = 0 sq-in
V = 7 kip
Vd = 5 kip
vd = 30 psi >
av = 0 sq-in
Stirrup =### in. c/c

L= 17 ft
k-ft OK KL = 5 ft
k-ft K= 0
k-ft P= 11 kip
k-ft M f (left) 27 k-ft
M f(right) 12 k-ft
k-ft
k-ft DESIGN OF BEAM - B4 (FOR 2-SPAN)
sq-in ---------------------------------------------------
sq-in as no. of bar
sq-in 0.48 12.991947 w1 = 2 k/ft
ksi 10.4148 inch c/c L1 = 11 ft
sq-in 0.48 -51.711557
-2.36939 inch c/c !---------------------------
1 0.61111 !
!---------------------------
-19.2938 19.2938 !
19.2938 9.64688 !
31.3062 !
!---------------------------
M (-) = 60.2469 !
M (+) = -1
19

M= 60 k-ft fy =
sq-in. NOT OK b  = 10 in.     f'c =
kip h  = 21 in.     k   =  
kip > 713.533 kip d(pro) = 18 j =
kip dreqd = 20 in. R =
kip M1 = 48 k-ft
in. c/c M2 = 12 k-ft =
As1 = 2 sq-in M =
As2 = 1 sq-in M =
As = 3 sq-in M =
sq-in. f's = 14 ksi M=
sq-in. A's = 1 sq-in
V = 11 kip
in Vd = 8 kip
vd = 46 psi >
av = 0 sq-in
Stirrup =### in. c/c

k-ft DESIGN OF BEAM B5


cu-in. ---------------------------------
psi
psi w = 2 k/ft fy =
psi < 138.462 psi L = 16 ft f'c =
P = 5 kip k =
a = 11 ft j =
Beam Size R =
10 in
21 in
d(pro) = 18
M= 67 k-ft
dreqd = 21 in ><
M1 = 48
M2 = 18
As1 = 2
As2 = 1
As=As1+ 3
f's = 14
As2 = 1

DESIGN OF BEAM - B6 (FOR 3-SPAN)


ksi ---------------------------------------------------
ksi w1 = 3 k/ft
L1 = 8 ft

!---------------------------
in 1 0.58442 !
psf !---------------------------
psf -13.3333 13.3333 !
psf 13.3333 6.66667 !
---------------------------- 4.20049 !
psf !
ksf -5.06534 !
ksf !
ksf 0.26262 !
k/ft !
k/ft -0.31669 !
k-ft !
0.01642 !
ft !
ft -0.0198 !
in !---------------------------
in M (-) = 19.0777 !
M (+) = 10
OF THE BUILDING :- 13

k-ft M= 44 k-ft fy =
b  = 10 in.     f'c =
k-ft h  = 18 in.     k   =  
k-ft d(pro) = 15 j =
dreqd = 17 in. R =
M1 = 33 k-ft
M2 = 11 k-ft =
As1 = 2 sq-in M =
As2 = 1 sq-in M =
k-ft As = 2 sq-in M =
k-ft f's = 13 ksi M=
k-ft A's = 1 sq-in
k-ft V = 10 kip
in Vd = 7 kip
in vd = 48 psi >
in. av = 0 sq-in
k-ft Stirrup =### in. c/c
k-ft
sq-in
sq-in as no. of bar DESIGN OF BEAM - B7 (FOR 2-SPAN)
sq-in 0.395 35.930529 ---------------------------------------------------
ksi 3.09185 inch c/c
sq-in 0.31 -56.791375 w1 = 1 k/ft
-1.86879 inch c/c L1 = 11 ft
k-ft
k-ft !---------------------------
k-ft 1 0.5 !
sq-in 0.31 17.233835 !---------------------------
6.26674 inch c/c -12.6042 12.6042 !
k-ft 12.6042 6.30208 !
sq-in 0.175 23.62325 0!
4.57177 inch c/c !---------------------------
k-ft M (-) = 18.9063 !
sq-in 0.175 20.352338 M (+) = 9
5.30652 inch c/c 13
sq-in 0.175 79.457143
1.35922 inch c/c M= 19 k-ft fy =
b  = 10 in.     f'c =
h  = 15 in.     k   =  
d(pro) = 12 j =
dreqd = 11 in. R =
M1 = 21 k-ft
M2 = -2 k-ft =
As1 = 1 sq-in M =
As2 = 0 sq-in M =
k-ft As = 1 sq-in M =
k-ft f's = 10 ksi M=
k-ft A's = 0 sq-in
k-ft V = 7 kip
Vd = 6 kip
k-ft vd = 49 psi >
k-ft av = 0 sq-in
sq-in Stirrup =### in. c/c
sq-in as no. of bar
sq-in 0.48 18.728767
ksi 12.7528 inch c/c
sq-in 0.48 -46.508446 DESIGN OF BEAM B8
-4.75898 inch c/c ---------------------------------
k-ft
k-ft w = 1 k/ft fy =
k-ft L = 13 ft f'c =
sq-in 0.31 17.233835 Beam Size k =
13.1191 inch c/c 10 in j =
k-ft 15 in R =
sq-in 0.11 37.582443 d(pro) = 12
6.01589 inch c/c M= 25 k-ft
k-ft dreqd = 13 in ><
sq-in 0.11 32.37872 M1 = 21
6.98273 inch c/c M2 = 5
sq-in 0.11 126.40909 As1 = 1
1.78857 inch c/c As2 = 0
As=As1+ 2
f's = 10
As2 = 1
DESIGN OF BEAM B9
---------------------------------

w = 2 k/ft fy =


L = 16 ft f'c =
Beam Size k =
k-ft OK 10 in j =
k-ft 15 in R =
k-ft d(pro) = 12
k-ft M= 58 k-ft
dreqd = 19 in ><
k-ft M1 = 21
k-ft M2 = 37
sq-in As1 = 1
sq-in as no. of bar As2 = 3
sq-in 0.48 13.235768 As=As1+ 4
ksi 10.5588 inch c/c f's = 10
sq-in 0.48 -51.490418 As2 = 5
-2.46131 inch c/c

DESIGN OF BEAM B10


---------------------------------

w = 2 k/ft fy =


L = 7 ft f'c =
Beam Size k =
10 in j =
15 in R =
d(pro) = 12
sq-in. NOT OK M = 9 k-ft
kip dreqd = 8 in ><
kip > 757.308 kip M1 = 21
kip M2 = ###
kip As1 = 1
in. c/c As2 = -1
As=As1+ 1
f's = 10
As2 = -2
sq-in.
sq-in.

in L= 21 ft
KL = 6 ft
K= 0
P= 15 kip
M f (left) 45 k-ft
M f(right) 19 k-ft
k-ft
cu-in. DESIGN OF BEAM - B11 (FOR 2-SPAN)
psi ---------------------------------------------------
psi
psi < 91.2639 psi w1 = 2 k/ft
L1 = 16 ft

!---------------------------
1 0.56164 !
!---------------------------
-40.5333 40.5333 !
40.5333 20.2667 !
93.8184 !
!---------------------------
M (-) = 154.618 !
M (+) = ###
41

ksi M= ### k-ft fy =


ksi b  = 10 in.     f'c =
h  = 30 in.     k   =  
d(pro) = 27 j =
dreqd = 31 in. R =
in M1 = ### k-ft
psf M2 = 44 k-ft =
psf As1 = 3 sq-in M =
psf As2 = 1 sq-in M =
---------------------------- As = 4 sq-in M =
psf f's = 17 ksi M=
ksf A's = 1 sq-in
ksf V = 15 kip
ksf Vd = 11 kip
k/ft vd = 42 psi >
k/ft av = 0 sq-in
k-ft Stirrup =### in. c/c

ft
ft
in
in DESIGN OF BEAM B12 at 2 level per floor
---------------------------------
OF THE BUILDING :-
w = 1 k/ft fy =
k-ft L = 14 ft f'c =
Beam Size k =
k-ft 5 in j =
k-ft 18 in R =
d(pro) = 15
M= 25 k-ft
dreqd = 18 in ><
M1 = 17
M2 = 8
k-ft As1 = 1
k-ft As2 = 0
k-ft As=As1+ 1
k-ft f's = 13
in As2 = 1
in
in.
k-ft
k-ft DESIGN OF BEAM B13 at 2 level per floor
sq-in ---------------------------------
sq-in as no. of bar
sq-in 0.395 35.930529 w = 2 k/ft fy =
ksi 3.09185 inch c/c L = 16 ft f'c =
sq-in 0.31 -56.791375 Beam Size k =
-1.86879 inch c/c 10 in j =
k-ft 21 in R =
k-ft d(pro) = 18
k-ft M= 59 k-ft
sq-in 0.31 17.233835 dreqd = 19 in ><
6.26674 inch c/c M1 = 48
k-ft M2 = 11
sq-in 0.175 23.62325 As1 = 2
4.57177 inch c/c As2 = 0
k-ft As=As1+ 3
sq-in 0.175 20.352338 f's = 14
5.30652 inch c/c As2 = 1
sq-in 0.175 79.457143
1.35922 inch c/c

DESIGN OF BEAM - B14 (FOR 3-SPAN)


---------------------------------------------------
w1 = 3 k/ft
L1 = 16 ft

!------------------------------------------ !---------------------------
! 1 0.21951 !
!------------------------------------------ !---------------------------
! -53.3333 53.3333 !
! 53.3333 26.6667 !
! -16.1122 !
! !
ksi ! -3.92868 !
ksi ! !
! -2.37912 !
! !
! -0.58011 !
in ! !
psf ! -0.3513 !
psf ! !
psf ! -0.08566 !
---------------------------- !------------------------------------------ !---------------------------
psf ! M (-) = 56.5629 !
ksf M (+) = 52
ksf 53
ksf
k/ft M= 57 k-ft fy =
k/ft b  = 10 in.     f'c =
k-ft h  = 21 in.     k   =  
d(pro) = 18 j =
ft dreqd = 19 in. R =
ft M1 = 48 k-ft
in M2 = 8 k-ft =
in As1 = 2 sq-in M =
As2 = 0 sq-in M =
OF THE BUILDING :- As = 2 sq-in M =
f's = 14 ksi M=
k-ft A's = 0 sq-in
V = 20 kip
k-ft Vd = 16 kip
k-ft vd = 93 psi >
av = 0 sq-in
Stirrup = 10 in. c/c

k-ft
k-ft DESIGN OF BEAM - B15 (FOR 3-SPAN)
k-ft ---------------------------------------------------
k-ft w1 = 2 k/ft
in L1 = 16 ft
in
in. !------------------------------------------ !---------------------------
k-ft ! 1 0.21951 !
k-ft !------------------------------------------ !---------------------------
sq-in ! -39.4667 39.4667 !
sq-in as no. of bar ! 39.4667 19.7333 !
sq-in 0.395 54.406823 ! -11.5463 !
ksi 2.02221 inch c/c ! !
sq-in 0.31 -35.439198 ! -5.04789 !
-2.96384 inch c/c ! !
k-ft ! -1.70493 !
k-ft ! !
k-ft ! -0.74537 !
sq-in 0.31 28.310531 ! !
3.81483 inch c/c ! -0.25175 !
k-ft ! !
sq-in 0.175 38.806612 ! -0.11006 !
2.78303 inch c/c !------------------------------------------ !---------------------------
k-ft ! M (-) = 39.7937 !
sq-in 0.175 33.433389 M (+) = 39
3.2303 inch c/c 39
sq-in 0.175 79.457143
1.35922 inch c/c M= 44 k-ft fy =
b  = 10 in.     f'c =
h  = 18 in.     k   =  
d(pro) = 15 j =
dreqd = 17 in. R =
M1 = 33 k-ft
M2 = 11 k-ft =
As1 = 2 sq-in M =
As2 = 1 sq-in M =
As = 2 sq-in M =
f's = 13 ksi M=
A's = 1 sq-in
V = 15 kip
Vd = 13 kip
ksi vd = 87 psi >
ksi av = 0 sq-in
Stirrup = 13 in. c/c

in
psf
psf
psf
----------------------------
psf DESIGN OF BEAM - GB1 (FOR 3-SPAN)
ksf ---------------------------------------------------
ksf w1 = 1 k/ft
ksf L1 = 15 ft
k/ft
k/ft !------------------------------------------ !---------------------------
k-ft ! 1 0.42857 !
!------------------------------------------ !---------------------------
ft ! -23.4375 23.4375 !
ft ! 23.4375 11.7188 !
in ! -5.02232 !
in ! !
! -1.43495 !
OF THE BUILDING :- ! !
! -0.40999 !
k-ft ! !
! -0.11714 !
k-ft ! !
k-ft ! -0.03347 !
! !
! -0.00956 !
!------------------------------------------ !---------------------------
! M (-) = 28.1288 !
M (+) = 21
k-ft 23
k-ft
k-ft M= 28 k-ft fy =
k-ft b  = 10 in.     f'c =
in h  = 16 in.     k   =  
in d(pro) = 13 j =
in. dreqd = 13 in. R =
k-ft M1 = 25 k-ft
k-ft M2 = 3 k-ft =
sq-in As1 = 2 sq-in M =
sq-in as no. of bar As2 = 0 sq-in M =
sq-in 0.2425 28.876467 As = 2 sq-in M =
ksi 3.87424 inch c/c f's = 11 ksi M=
sq-in 0.31 -77.827223 A's = 0 sq-in
-1.37009 inch c/c V = 9 kip
k-ft Vd = 8 kip
k-ft vd = 65 psi >
k-ft av = 0 sq-in
sq-in 0.175 11.197622 Stirrup = 41 in. c/c
9.64491 inch c/c
k-ft
sq-in 0.175 8.6648262
12.4642 inch c/c
k-ft
sq-in 0.175 7.4650811
14.4674 inch c/c
sq-in 0.175 79.457143 DESIGN OF BEAM - GB2 (FOR 4-SPAN)
1.35922 inch c/c ----------------------------------------------------------

w1 = 2 k/ft
L1 = 11 ft

!------------------------------------------ !---------------------------
! 1 0.50562 !
!------------------------------------------ !---------------------------
! -16.1333 16.1333 !
! 16.1333 8.06667 !
! -0.38553 !
! !
! 0!
! !
ksi ! 0!
ksi ! !
! 0!
! !
! 0!
in ! !
psf ! 0!
psf !------------------------------------------ !---------------------------
psf ! M (-) = 23.8145 !
---------------------------- M (+) = 12
psf 16
ksf
ksf M= 24 k-ft fy =
ksf b  = 10 in.     f'c =
k/ft h  = 16 in.     k   =  
k/ft d(pro) = 13 j =
k-ft dreqd = 12 in. R =
M1 = 25 k-ft
ft M2 = -1 k-ft =
ft As1 = 2 sq-in M =
in As2 = 0 sq-in M =
in As = 1 sq-in M =
f's = 11 ksi M=
OF THE BUILDING :- A's = 0 sq-in
V = 9 kip
k-ft Vd = 7 kip
vd = 57 psi >
k-ft av = 0 sq-in
k-ft Stirrup =### in. c/c

DESIGN OF BEAM - GB3 (FOR 4-SPAN)


k-ft ----------------------------------------------------------
k-ft
k-ft w1 = 2 k/ft
k-ft L1 = 11 ft
in
in !------------------------------------------ !---------------------------
in. ! 1 0.42857 !
k-ft !------------------------------------------ !---------------------------
k-ft ! -23.1917 23.1917 !
sq-in ! 23.1917 11.5958 !
sq-in as no. of bar ! -4.96964 !
sq-in 0.31 25.328746 ! !
ksi 2.95946 inch c/c ! -3.2493 !
sq-in 0.31 -42.570697 ! !
-1.65249 inch c/c ! -0.14681 !
k-ft ! !
k-ft ! -0.45433 !
k-ft ! !
sq-in 0.31 9.0459685 ! -0.02053 !
7.95935 inch c/c ! !
k-ft ! -0.06353 !
sq-in 0.175 12.399746 !------------------------------------------ !---------------------------
5.80657 inch c/c ! M (-) = 25.8834 !
k-ft M (+) = 22
sq-in 0.175 10.682858 23
6.73977 inch c/c
sq-in 0.175 52.971429 M= 55 k-ft fy =
1.35922 inch c/c b  = 10 in.     f'c =
h  = 20 in.     k   =  
d(pro) = 17 j =
dreqd = 19 in. R =
M1 = 43 k-ft
M2 = 12 k-ft =
As1 = 2 sq-in M =
As2 = 1 sq-in M =
As = 3 sq-in M =
f's = 14 ksi M=
A's = 1 sq-in
V = 13 kip
Vd = 9 kip
vd = 58 psi >
av = 0 sq-in
Stirrup =### in. c/c

DESIGN OF BEAM - GB5 (FOR 4-SPAN)


----------------------------------------------------------
w1 = 2 k/ft
L1 = 11 ft

!------------------------------------------ !---------------------------
! 1 0.50562 !
!------------------------------------------ !---------------------------
! -16.1333 16.1333 !
! 16.1333 8.06667 !
! -0.38553 !
! !
! -6.17748 !
! !
! -1.07974 !
! !
! -0.75212 !
! !
! -0.13146 !
! !
! -0.09157 !
!------------------------------------------ !---------------------------
! M (-) = 15.5821 !
M (+) = 16
16

M= 56 k-ft fy =
b  = 10 in.     f'c =
h  = 20 in.     k   =  
d(pro) = 17 j =
dreqd = 19 in. R =
M1 = 43 k-ft
M2 = 13 k-ft =
As1 = 2 sq-in M =
As2 = 1 sq-in M =
As = 3 sq-in M =
f's = 14 ksi M=
A's = 1 sq-in
V = 9 kip
Vd = 7 kip
vd = 40 psi >
av = 0 sq-in
Stirrup =### in. c/c

DESIGN OF BEAM - GB6 (FOR 3-SPAN)


---------------------------------------------------
w1 = 1 k/ft
L1 = 15 ft

!------------------------------------------ !---------------------------
! 1 0.52381 !
!------------------------------------------ !---------------------------
! -23.4375 23.4375 !
! 23.4375 11.7188 !
! 15.388 !
! !
! 3.66381 !
! !
! 0.87234 !
! !
! 0.2077 !
! !
! 0.04945 !
! !
! 0.01177 !
!------------------------------------------ !---------------------------
! M (-) = 55.3493 !
M (+) = 7
23

M= 55 k-ft fy =
b  = 10 in.     f'c =
h  = 20 in.     k   =  
d(pro) = 17 j =
dreqd = 19 in. R =
M1 = 43 k-ft
M2 = 12 k-ft =
As1 = 2 sq-in M =
As2 = 1 sq-in M =
As = 3 sq-in M =
f's = 14 ksi M=
A's = 1 sq-in
V = 9 kip
Vd = 8 kip
vd = 46 psi >
av = 0 sq-in
Stirrup =### in. c/c

DESIGN OF BEAM GB7


---------------------------------
w = 1 k/ft fy =
L = 13 ft f'c =
Beam Size k =
5 in j =
20 in R =
d(pro) = 17
M= 21 k-ft
dreqd = 16 in ><
M1 = 21
M2 = 0
As1 = 1
As2 = 0
As=As1+ 1
f's = 14
As2 = 0

DESIGN OF BEAM - GB8 (FOR 4-SPAN)


----------------------------------------------------------

w1 = 2 k/ft
L1 = 16 ft

!------------------------------------------ !---------------------------
! 1 0.38614 !
!------------------------------------------ !---------------------------
! -46.0479 46.0479 !
! 46.0479 23.024 !
! -12.2603 !
! !
! 0!
! !
! 0!
! !
! 0!
! !
! 0!
! !
! 0!
!------------------------------------------ !---------------------------
! M (-) = 56.8116 !
M (+) = 41
46
M= 57 k-ft fy =
b  = 10 in.     f'c =
h  = 20 in.     k   =  
d(pro) = 17 j =
dreqd = 19 in. R =
M1 = 43 k-ft
M2 = 14 k-ft =
As1 = 2 sq-in M =
As2 = 1 sq-in M =
As = 3 sq-in M =
f's = 14 ksi M=
A's = 1 sq-in
V = 18 kip
Vd = 15 kip
vd = 89 psi >
av = 0 sq-in
Stirrup = 12 in. c/c

DESIGN OF BEAM - GB9 (FOR 3-SPAN)


---------------------------------------------------
w1 = 2 k/ft
L1 = 16 ft

!------------------------------------------ !---------------------------
! 1 0.225 !
!------------------------------------------ !---------------------------
! -40.0417 40.0417 !
! 40.0417 20.0208 !
! -12.1641 !
! !
! -1.0944 !
! !
! -1.50834 !
! !
! -0.13571 !
! !
! -0.18703 !
! !
! -0.01683 !
!------------------------------------------ !---------------------------
! M (-) = 44.9561 !
M (+) = 38
40
M= 45 k-ft fy =
b  = 10 in.     f'c =
h  = 20 in.     k   =  
d(pro) = 17 j =
dreqd = 17 in. R =
M1 = 43 k-ft
M2 = 2 k-ft =
As1 = 2 sq-in M =
As2 = 0 sq-in M =
As = 2 sq-in M =
f's = 14 ksi M=
A's = 0 sq-in
V = 16 kip
Vd = 13 kip
vd = 77 psi >
av = 0 sq-in
Stirrup = 18 in. c/c

DESIGN OF BEAM - GB10 (FOR 3-SPAN)


---------------------------------------------------
w1 = 2 k/ft
L1 = 13 ft

!------------------------------------------ !---------------------------
! 1 0.25714 !
!------------------------------------------ !---------------------------
! -32.3917 32.3917 !
! 32.3917 16.1958 !
! -10.7196 !
! !
! -6.19498 !
! !
! -1.54286 !
! !
! -0.89164 !
! !
! -0.22206 !
! !
! -0.12833 !
!------------------------------------------ !---------------------------
! M (-) = 28.888 !
M (+) = 34
32

M= 29 k-ft fy =
b  = 10 in.     f'c =
h  = 20 in.     k   =  
d(pro) = 17 j =
dreqd = 14 in. R =
M1 = 43 k-ft
M2 = ### k-ft =
As1 = 2 sq-in M =
As2 = -1 sq-in M =
As = 1 sq-in M =
f's = 14 ksi M=
A's = -1 sq-in
V = 15 kip
Vd = 12 kip
vd = 71 psi >
av = 0 sq-in
Stirrup = 24 in. c/c
40 ksi
2.5 ksi
0.38667
0.87111
0.18947

14.5

M - B2 (FOR 2-SPAN)
----------------------------

w2 = 2 k/ft
L2 = 17 ft

!--------------------------------------------- !
0.38889 1 !
!--------------------------------------------- !
-36.3 36.3 !
-18.15 -36.3 !
14.7438 !
!--------------------------------------------- !
-39.7063 0 !
35
36

40 ksi
2.5 ksi
0.38667
0.87111
0.18947
11.025 k-ft 0.5818966 sq-in
36.3 k-ft 1.9159043 sq-in

55 psi

M - B3 (FOR 3-SPAN)
----------------------------
w2 = 2 k/ft w3 = 1.7 k/ft
L2 = 16 ft L3 = 15 ft
!14k
!--------------------------------------------- !--------------------------------------------- !
0.46667 0.5555556 ! 0.4444444 1 !
!--------------------------------------------- !--------------------------------------------- !
-38.4 38.4 ! -38.595 58.755 !
! -29.3775 -58.755 !
8.91625 16.429167 ! 13.143333 !
8.21458 4.458125 ! !
-3.83347 -2.4767361 ! -1.9813889 !
-1.23837 -1.9167361 ! !
0.57791 1.0648534 ! 0.8518827 !
0.53243 0.2889525 ! !
-0.24847 -0.1605292 ! -0.1284234 !
-0.08026 -0.1242329 ! !
0.03746 0.0690183 ! 0.0552146 !
0.03451 0.0187284 ! !
-0.0161 -0.0104047 ! -0.0083237 !
!--------------------------------------------- !--------------------------------------------- !
-25.5035 56.040205 ! -56.040205 0 !
17 20
29 32
40 ksi
2.5 ksi
0.38667
0.87111
0.18947

25.5035 k-ft 1.1153153 sq-in


56.0402 k-ft 2.4507378 sq-in
12.8625 k-ft 0.5625 sq-in
28.8 k-ft 1.2594752 sq-in
31.875 k-ft 1.3939504 sq-in

55 psi

M - B4 (FOR 2-SPAN)
----------------------------

w2 = 1 k/ft
L2 = 17 ft
!11k
!--------------------------------------------- !
0.38889 1 !
!--------------------------------------------- !
-58.4797 43.378662 !
-21.6893 -43.378662 !
19.9221 !
!--------------------------------------------- !
-60.2469 0 !
18
32

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

19.2938 k-ft 0.84375 sq-in


31.7625 k-ft 1.3890306 sq-in

55 psi

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

17.5

M - B6 (FOR 3-SPAN)
----------------------------
w2 = 1 k/ft w3 = 1.6 k/ft
L2 = 15 ft L3 = 17 ft

!--------------------------------------------- !--------------------------------------------- !
0.41558 0.6017699 ! 0.3982301 1!
!--------------------------------------------- !--------------------------------------------- !
-27.1875 27.1875 ! -37.329167 37.329167 !
! -18.664583 -37.329167 !
2.98701 17.334735 ! 11.471515 !
8.66737 1.4935065 ! !
-3.60202 -0.8987473 ! -0.5947592 !
-0.44937 -1.8010114 ! !
0.18675 1.0837945 ! 0.7172169 !
0.5419 0.0933763 ! !
-0.2252 -0.0561911 ! -0.0371853 !
-0.0281 -0.112602 ! !
0.01168 0.0677605 ! 0.0448415 !
0.03388 0.005838 ! !
-0.01408 -0.0035132 ! -0.0023249 !
!--------------------------------------------- !--------------------------------------------- !
-19.0777 44.394445 ! -44.394445 0 !
9 34
20 37

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

19.0777 k-ft 1.0069154 sq-in


44.3944 k-ft 2.343127 sq-in
13.3333 k-ft 0.7037298 sq-in
20.3906 k-ft 1.0762117 sq-in
37.3292 k-ft 1.9702234 sq-in

55 psi

M - B7 (FOR 2-SPAN)
----------------------------

w2 = 1 k/ft
L2 = 11 ft

!--------------------------------------------- !
0.5 1!
!--------------------------------------------- !
-12.6042 12.604167 !
-6.30208 -12.604167 !
0 !
!--------------------------------------------- !
-18.9063 0 !
9
13

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

12.6042 k-ft 0.8387866 sq-in


12.6042 k-ft 0.8387866 sq-in

55 psi

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

11.5
40 ksi
2.5 ksi
0.38667
0.87111
0.18947

11.5

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

11.5

L= 21 ft
KL = 13 ft
K= 1
P= 10 kip
M f (left) 17 k-ft
M f(right) 30 k-ft

M - B11 (FOR 2-SPAN)


----------------------------

w2 = 2 k/ft
L2 = 21 ft
!15k !10k
!--------------------------------------------- !
0.43836 1 !
!--------------------------------------------- !
-165.238 125.20853 !
-62.6043 -125.20853 !
73.2241 !
!--------------------------------------------- !
-154.618 0 !
9
58

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

40.5333 k-ft 1.1705814 sq-in


57.7844 k-ft 1.6687825 sq-in

55 psi

M B12 at 2 level per floor

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

14.5

M B13 at 2 level per floor

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

17.5

M - B14 (FOR 3-SPAN)


----------------------------
w2 = 2 k/ft w3 = 2.2 k/ft
L2 = 6 ft L3 = 14 ft

!--------------------------------------------- !--------------------------------------------- !
0.78049 0.7567568 ! 0.2432432 1 !
!--------------------------------------------- !--------------------------------------------- !
-6.6 6.6 ! -35.933333 35.933333 !
! -17.966667 -35.933333 !
-57.2878 35.794595 ! 11.505405 !
17.8973 -28.643902 ! !
-13.9686 21.676467 ! 6.9674357 !
10.8382 -6.9843111 ! !
-8.45911 5.2854246 ! 1.6988865 !
2.64271 -4.2295545 ! !
-2.0626 3.2007439 ! 1.0288105 !
1.60037 -1.0313024 ! !
-1.24907 0.780445 ! 0.2508573 !
0.39022 -0.6245354 ! !
-0.30456 0.4726214 ! 0.151914 !
!--------------------------------------------- !--------------------------------------------- !
-56.5629 32.29669 ! -32.29669 0!
### 38
5 36

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

56.5629 k-ft 2.4735979 sq-in


32.2967 k-ft 1.4123917 sq-in
53.3333 k-ft 2.3323615 sq-in
4.95 k-ft 0.2164723 sq-in
35.9333 k-ft 1.5714286 sq-in

55 psi

M - B15 (FOR 3-SPAN)


----------------------------
w2 = 2 k/ft w3 = 2.8 k/ft
L2 = 6 ft L3 = 14 ft

!--------------------------------------------- !--------------------------------------------- !
0.78049 0.7567568 ! 0.2432432 1 !
!--------------------------------------------- !--------------------------------------------- !
-6.6 6.6 ! -44.916667 44.916667 !
! -22.458333 -44.916667 !
-41.0537 45.991892 ! 14.783108 !
22.9959 -20.526829 ! !
-17.9481 15.533817 ! 4.9930125 !
7.76691 -8.9740277 ! !
-6.06198 6.7911561 ! 2.1828716 !
3.39558 -3.0309886 ! !
-2.65021 2.2937211 ! 0.7372675 !
1.14686 -1.3251036 ! !
-0.89511 1.0027811 ! 0.3223225 !
0.50139 -0.4475553 ! !
-0.39133 0.3386905 ! 0.1088648 !
!--------------------------------------------- !--------------------------------------------- !
-39.7937 44.247553 ! -44.247553 0!
### 45
5 45

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

39.7937 k-ft 2.1002985 sq-in


44.2476 k-ft 2.335374 sq-in
39.4667 k-ft 2.0830401 sq-in
4.95 k-ft 0.2612597 sq-in
44.9167 k-ft 2.3706897 sq-in

55 psi

M - GB1 (FOR 3-SPAN)


----------------------------
w2 = 1 k/ft w3 = 1.3 k/ft
L2 = 15 ft L3 = 15 ft

!--------------------------------------------- !--------------------------------------------- !
0.57143 0.5714286 ! 0.4285714 1!
!--------------------------------------------- !--------------------------------------------- !
-23.4375 23.4375 ! -23.4375 23.4375 !
! -11.71875 -23.4375 !
-6.69643 6.6964286 ! 5.0223214 !
3.34821 -3.3482143 ! !
-1.91327 1.9132653 ! 1.434949 !
0.95663 -0.9566327 ! !
-0.54665 0.5466472 ! 0.4099854 !
0.27332 -0.2733236 ! !
-0.15618 0.1561849 ! 0.1171387 !
0.07809 -0.0780925 ! !
-0.04462 0.0446243 ! 0.0334682 !
0.02231 -0.0223121 ! !
-0.01275 0.0127498 ! 0.0095623 !
!--------------------------------------------- !--------------------------------------------- !
-28.1288 28.128825 ! -28.128825 0 !
7 21
18 23

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

28.1288 k-ft 1.722173 sq-in


28.1288 k-ft 1.722173 sq-in
23.4375 k-ft 1.434949 sq-in
17.5781 k-ft 1.0762117 sq-in
23.4375 k-ft 1.434949 sq-in

55 psi

M - GB2 (FOR 4-SPAN)


-------------------------------------

w2 = 1 k/ft w3 = 1.3 k/ft


L2 = 15 ft L3 = 15 ft

!--------------------------------------------- !--------------------------------------------- !----------------------------------------


0.49438 0.5 ! 0.5 0.494382 !
!--------------------------------------------- !--------------------------------------------- !----------------------------------------
-23.4375 23.4375 ! -23.4375 23.4375 !
! !
-0.37697 0 ! 0 0.3769663 !
0 -0.1884831 ! 0.1884831 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
!--------------------------------------------- !--------------------------------------------- !----------------------------------------
-23.8145 23.249017 ! -23.249017 23.814466 !
12 12
18 18

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

23.8145 k-ft 1.4580285 sq-in


23.249 k-ft 1.4234092 sq-in
16.1333 k-ft 0.9877551 sq-in
17.5781 k-ft 1.0762117 sq-in
17.5781 k-ft 1.0762117 sq-in

55 psi

M - GB3 (FOR 4-SPAN)


-------------------------------------
w2 = 2 k/ft w3 = 2 k/ft
L2 = 11 ft L3 = 17 ft

!--------------------------------------------- !--------------------------------------------- !----------------------------------------


0.57143 0.6071429 ! 0.3928571 0.5405405 !
!--------------------------------------------- !--------------------------------------------- !----------------------------------------
-23.1917 23.191667 ! -48.166667 48.166667 !
! !
-6.62619 15.163393 ! 9.8116071 4.3693694 !
7.5817 -3.3130952 ! 2.1846847 4.9058036 !
-4.3324 0.6851064 ! 0.4433041 -2.6517857 !
0.34255 -2.166199 ! -1.3258929 0.2216521 !
-0.19574 2.1201986 ! 1.3718932 -0.1198119 !
1.0601 -0.0978723 ! -0.059906 0.6859466 !
-0.60577 0.095794 ! 0.0619843 -0.370782 !
0.0479 -0.3028855 ! -0.185391 0.0309922 !
-0.02737 0.2964536 ! 0.1918229 -0.0167525 !
0.14823 -0.0136849 ! -0.0083763 0.0959115 !
-0.0847 0.0133942 ! 0.0086669 -0.051844 !
!--------------------------------------------- !--------------------------------------------- !----------------------------------------
-25.8834 35.672269 ! -35.672269 55.265366 !
4 27
17 36

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

25.8834 k-ft 1.2005273 sq-in


35.6723 k-ft 1.654558 sq-in
23.1917 k-ft 1.0756803 sq-in
17.3938 k-ft 0.8067602 sq-in
36.125 k-ft 1.6755566 sq-in

55 psi

M - GB5 (FOR 4-SPAN)


-------------------------------------
w2 = 1 k/ft w3 = 1.6 k/ft
L2 = 15 ft L3 = 22 ft

!--------------------------------------------- !--------------------------------------------- !----------------------------------------


0.49438 0.5945946 ! 0.4054054 0.4761905 !
!--------------------------------------------- !--------------------------------------------- !----------------------------------------
-23.4375 23.4375 ! -64.533333 64.533333 !
! !
-0.37697 24.43536 ! 16.660473 -13.989087 !
12.2177 -0.1884831 ! -6.9945437 8.3302365 !
-6.0402 4.2709889 ! 2.9120379 -3.9667793 !
2.13549 -3.0201007 ! -1.9833896 1.4560189 !
-1.05575 2.9750483 ! 2.028442 -0.6933424 !
1.48752 -0.527875 ! -0.3466712 1.014221 !
-0.73541 0.5200004 ! 0.3545458 -0.4829624 !
0.26 -0.3677026 ! -0.2414812 0.1772729 !
-0.12854 0.3622174 ! 0.2469664 -0.0844157 !
0.18111 -0.0642697 ! -0.0422078 0.1234832 !
-0.08954 0.063311 ! 0.0431666 -0.0588015 !
!--------------------------------------------- !--------------------------------------------- !----------------------------------------
-15.5821 51.895995 ! -51.895995 56.359177 !
1 43
18 48

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

15.5821 k-ft 0.7227315 sq-in


51.896 k-ft 2.4070499 sq-in
16.1333 k-ft 0.7482993 sq-in
17.5781 k-ft 0.8153119 sq-in
48.4 k-ft 2.244898 sq-in

55 psi

M - GB6 (FOR 3-SPAN)


----------------------------
w2 = 2 k/ft w3 = 1.3 k/ft
L2 = 22 ft L3 = 15 ft

!--------------------------------------------- !--------------------------------------------- !
0.47619 0.4761905 ! 0.5238095 1 !
!--------------------------------------------- !--------------------------------------------- !
-64.5333 64.533333 ! -23.4375 23.4375 !
! -11.71875 -23.4375 !
13.9891 -13.989087 ! -15.387996 !
-6.99454 6.9945437 ! !
3.33074 -3.3307351 ! -3.6638086 !
-1.66537 1.6653675 ! !
0.79303 -0.7930322 ! -0.8723354 !
-0.39652 0.3965161 ! !
0.18882 -0.1888172 ! -0.2076989 !
-0.09441 0.0944086 ! !
0.04496 -0.0449565 ! -0.0494521 !
-0.02248 0.0224782 ! !
0.0107 -0.0107039 ! -0.0117743 !
!--------------------------------------------- !--------------------------------------------- !
-55.3493 55.349315 ! -55.349315 0 !
41 7.5
48 23

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

55.3493 k-ft 2.5672224 sq-in


55.3493 k-ft 2.5672224 sq-in
23.4375 k-ft 1.0870826 sq-in
48.4 k-ft 2.244898 sq-in
23.4375 k-ft 1.0870826 sq-in

55 psi
40 ksi
2.5 ksi
0.38667
0.87111
0.18947

16.5

M - GB8 (FOR 4-SPAN)


-------------------------------------

w2 = 3 k/ft w3 = 2.7 k/ft


L2 = 13 ft L3 = 13 ft

!--------------------------------------------- !--------------------------------------------- !----------------------------------------


0.61386 0.5 ! 0.5 0.6138614 !
!--------------------------------------------- !--------------------------------------------- !----------------------------------------
-37.3208 37.320833 ! -37.320833 37.320833 !
! !
-19.4907 0 ! 0 19.490738 !
0 -9.7453692 ! 9.7453692 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
0 0 ! 0 0 !
!--------------------------------------------- !--------------------------------------------- !----------------------------------------
-56.8116 27.575464 ! -27.575464 56.811572 !
14 14
28 28
40 ksi
2.5 ksi
0.38667
0.87111
0.18947

56.8116 k-ft 2.6350451 sq-in


27.5755 k-ft 1.2790104 sq-in
46.0479 k-ft 2.1358032 sq-in
27.9906 k-ft 1.2982665 sq-in
27.9906 k-ft 1.2982665 sq-in

55 psi

M - GB9 (FOR 3-SPAN)


----------------------------
w2 = 2 k/ft w3 = 2.7 k/ft
L2 = 6 ft L3 = 8 ft

!--------------------------------------------- !--------------------------------------------- !
0.775 0.64 ! 0.36 1 !
!--------------------------------------------- !--------------------------------------------- !
-6 6 ! -14.133333 14.133333 !
! -7.0666667 -14.133333 !
-41.8984 9.728 ! 5.472 !
4.864 -20.949219 ! !
-3.7696 13.4075 ! 7.5417188 !
6.70375 -1.8848 ! !
-5.19541 1.206272 ! 0.678528 !
0.60314 -2.5977031 ! !
-0.46743 1.66253 ! 0.9351731 !
0.83127 -0.2337152 ! !
-0.64423 0.1495777 ! 0.0841375 !
0.07479 -0.3221152 ! !
-0.05796 0.2061537 ! 0.1159615 !
!--------------------------------------------- !--------------------------------------------- !
-44.9561 6.3724812 ! -6.3724812 0 !
### 18
5 14
40 ksi
2.5 ksi
0.38667
0.87111
0.18947

44.9561 k-ft 2.0851635 sq-in


6.37248 k-ft 0.2955696 sq-in
40.0417 k-ft 1.8572202 sq-in
4.5 k-ft 0.2087199 sq-in
14.1333 k-ft 0.6555349 sq-in

55 psi

M - GB10 (FOR 3-SPAN)


----------------------------
w2 = 2 k/ft w3 = 2.3 k/ft
L2 = 6 ft L3 = 16 ft

!--------------------------------------------- !--------------------------------------------- !
0.74286 0.775 ! 0.225 1 !
!--------------------------------------------- !--------------------------------------------- !
-6.9 6.9 ! -46.047917 46.047917 !
! -23.023958 -46.047917 !
-30.9679 48.183203 ! 13.988672 !
24.0916 -15.483929 ! !
-17.8966 12.000045 ! 3.4838839 !
6.00002 -8.9483092 ! !
-4.45716 6.9349396 ! 2.0133696 !
3.46747 -2.2285797 ! !
-2.57583 1.7271493 ! 0.5014304 !
0.86357 -1.2879174 ! !
-0.64151 0.9981359 ! 0.2897814 !
0.49907 -0.3207563 ! !
-0.37074 0.2485861 ! 0.0721702 !
!--------------------------------------------- !--------------------------------------------- !
-28.888 48.722568 ! -48.722568 0 !
### 45
5 46

40 ksi
2.5 ksi
0.38667
0.87111
0.18947

28.888 k-ft 1.3398879 sq-in


48.7226 k-ft 2.2598594 sq-in
32.3917 k-ft 1.5023964 sq-in
5.175 k-ft 0.2400278 sq-in
46.0479 k-ft 2.1358032 sq-in

55 psi
DESIGN OF BEAM B7
---------------------------------
w = 2.5
L = 23.5
Beam Size
10
30
d(pro) = 26.5
M= 172.57813
dreqd = 33.061084
M1 = 110.87747
M2 = 61.700653
As1 = 3.2020833
As2 = 1.713907
As=As1+As 4.9159904
f's = 17.158326
As2 = 1.7979799
V = 29.375
Vd = 23.854167
vd = 90.015723
av = 0.11
Stirrup = 11.309205

DESIGN OF BEAM - B1 (FOR 4-SPA


------------------------------------------------

w1 = 2
L1 = 14

!---------------------------------------------
! 1
!---------------------------------------------
! -32.666667
! 32.666667
!
!
!
!
!
!
!
!
!
!
!
!---------------------------------------------
! M (-) =
M (+) = 28.267857
32.666667

M= 48.714286
b  = 10
h  = 18
d(pro) = 14.5
dreqd = 17.565171
M1 = 33.196139
M2 = 15.518147
As1 = 1.7520833
As2 = 0.8621193
As = 2.6142026
f's = 12.575712
A's = 1.2339776
V = 14
Vd = 11.583333
vd = 79.885057
av = 0.11
Stirrup = 15.913164

DESIGN OF BEAM - B2 (FOR 4-SPA


------------------------------------------------

w1 = 2.7
L1 = 14

!---------------------------------------------
! 1
!---------------------------------------------
! -44.1
! 44.1
!
!
!
!
!
!
!
!
!
!
!
!---------------------------------------------
! M (-) =
M (+) = 37.1875
44.1

M= 57.925
b  = 10
h  = 18
d(pro) = 14.5
dreqd = 19.153901
M1 = 33.196139
M2 = 24.728861
As1 = 1.7520833
As2 = 1.3738256
As = 3.125909
f's = 12.575712
A's = 1.9663985
V = 18.9
Vd = 15.6375
vd = 107.84483
av = 0.11
Stirrup = 7.4936378

DESIGN OF BEAM - B3 (FOR 2-SPA


------------------------------------------------

w1 = 3.25
L1 = 14.75

!---------------------------------------------
! 1
!---------------------------------------------
! -58.923177
! 58.923177
!
!---------------------------------------------
! M (-) =
M (+) = 42.318973
58.923177

M= 92.131585
b  = 10
h  = 24
d(pro) = 20.5
dreqd = 24.156193
M1 = 66.352806
M2 = 25.778779
As1 = 2.4770833
As2 = 0.9547696
As = 3.4318529
f's = 15.537646
A's = 1.1060783
V = 23.96875
Vd = 18.416667
vd = 89.837398
av = 0.11
Stirrup = 11.367095

DESIGN OF BEAM - B4 (FOR 4-SPA


------------------------------------------------

w1 = 3.25
L1 = 14.75

!---------------------------------------------
! 1
!---------------------------------------------
! -58.923177
! 58.923177
!
!
!
!
!
!
!
!
!
!
!
!---------------------------------------------
! M (-) =
M (+) = 52.904001
58.923177

M= 70.96153
b  = 10
h  = 21
d(pro) = 17.5
dreqd = 21.199992
M1 = 48.353472
M2 = 22.608057
As1 = 2.1145833
As2 = 1.0048026
As = 3.1193859
f's = 14.310559
A's = 1.2638532
V = 23.96875
Vd = 19.229167
vd = 109.88095
av = 0.11
Stirrup = 7.2156182

DESIGN OF BEAM - B5 (FOR 4-SPA


------------------------------------------------

w1 = 3
L1 = 23.5

!---------------------------------------------
! 1
!---------------------------------------------
! -138.0625
! 138.0625
!
!
!
!
!
!
!
!
!
!
!
!---------------------------------------------
! M (-) =
M (+) = 128.24043
138.0625

M= 157.70664
b  = 10
h  = 21
d(pro) = 17.5
dreqd = 31.60452
M1 = 48.353472
M2 = 109.35317
As1 = 2.1145833
As2 = 4.8601408
As = 6.9747241
f's = 14.310559
A's = 6.1131458
V = 35.25
Vd = 30.875
vd = 176.42857
av = 0.11
Stirrup = 3.2611765

DESIGN OF BEAM - B6 (FOR 2-SPA


------------------------------------------------

w1 = 2.5
L1 = 23.5

!---------------------------------------------
! 1
!---------------------------------------------
! -115.05208
! 115.05208
!
!---------------------------------------------
! M (-) =
M (+) = 86.289063
115.05208

M= 172.57813
b  = 10
h  = 30
d(pro) = 26.5
dreqd = 33.061084
M1 = 110.87747
M2 = 61.700653
As1 = 3.2020833
As2 = 1.713907
As = 4.9159904
f's = 17.158326
A's = 1.7979799
V = 29.375
Vd = 23.854167
vd = 90.015723
av = 0.11
Stirrup = 11.309205
w4 = 1.6 k/ft
L4 = 11 ft

!--------------------------------------------- !
0.505618 1!
!--------------------------------------------- !
-16.133333 16.133333 !
-8.0666667 -16.133333 !
0.3855337 !
!
0 !
!
0 !
!
0 !
!
0 !
!
0 !
!--------------------------------------------- !
-23.814466 0!
w4 = 2 k/ft
L4 = 15 ft

!--------------------------------------------- !
0.4594595 1 !
!--------------------------------------------- !
-37.5 37.5 !
-18.75 -37.5 !
3.713964 !
!
-2.2540179 !
!
-0.1018401 !
!
-0.3151647 !
!
-0.0142396 !
!
-0.0440674 !
!--------------------------------------------- !
-55.265366 0 !
28.617317
37.5
w4 = 1.25 k/ft
L4 = 15 ft

!--------------------------------------------- !
0.5238095 1 !
!--------------------------------------------- !
-23.4375 23.4375 !
-11.71875 -23.4375 !
-15.387996 !
!
-4.3634572 !
!
-0.7626766 !
!
-0.5312586 !
!
-0.0928572 !
!
-0.0646817 !
!--------------------------------------------- !
-56.359177 0 !
6.9766613
23.4375
w4 = 2.3 k/ft
L4 = 15.5 ft

!--------------------------------------------- !
0.3861386 1!
!--------------------------------------------- !
-46.047917 46.047917 !
-23.023958 -46.047917 !
12.260303 !
!
0 !
!
0 !
!
0 !
!
0 !
!
0 !
!--------------------------------------------- !
-56.811572 0!
40.666089
46.047917
---------------------
k/ft fy = 40 ksi
ft f'c = 2.5 ksi
k = 0.38666667
in j = 0.87111111
in R = 0.18946667

k-ft
in >< 26.5

kip
kip
psi > 55 psi
sq-in
in. c/c

OF BEAM - B1 (FOR 4-SPAN)


------------------------------------------------

k/ft w2 = 2 k/ft w3 =
ft L2 = 14 ft L3 =

!--------------------------------------------- !---------------------------------------------
0.4285714 ! 0.5714286 0.5172414 ! 0.4827586
!--------------------------------------------- !---------------------------------------------
32.666667 ! -32.666667 32.666667 ! -37.5
16.333333 ! !
-7 ! -9.3333333 2.5 ! 2.3333333
! 1.25 -4.6666667 ! 5.3571429
-0.5357143 ! -0.7142857 -0.3571429 ! -0.3333333
! -0.1785714 -0.3571429 ! -0.3333333
0.0765306 ! 0.1020408 0.3571429 ! 0.3333333
! 0.1785714 0.0510204 ! 0.047619
-0.0765306 ! -0.1020408 -0.0510204 ! -0.047619
! -0.0255102 -0.0510204 ! -0.047619
0.0109329 ! 0.0145773 0.0510204 ! 0.047619
! 0.0255102 0.0072886 ! 0.0068027
-0.0109329 ! -0.0145773 -0.0072886 ! -0.0068027
!--------------------------------------------- !---------------------------------------------
41.464286 ! -41.464286 30.142857 ! -30.142857
13.196429
24.5

k-ft fy = 40 ksi
in.     f'c = 2.5 ksi
in.     k   =   0.38666667
j = 0.87111111
in. R = 0.18946667
k-ft
k-ft M = 41.464286 k-ft As = 2.1884739 sq-in
sq-in M = 30.142857 k-ft As = 1.5909319 sq-in
sq-in M = 32.666667 k-ft As = 1.7241379 sq-in
sq-in M = 24.5 k-ft As = 1.2931034 sq-in
ksi M = 28.125 k-ft As = 1.48443 sq-in
sq-in M = 48.714286 k-ft As = 2.571127 sq-in
kip M = 37.5 k-ft As = 1.97924 sq-in
kip
psi > 55 psi
sq-in
in. c/c

OF BEAM - B2 (FOR 4-SPAN)


------------------------------------------------

k/ft w2 = 2.7 k/ft w3 =


ft L2 = 14 ft L3 =

!--------------------------------------------- !---------------------------------------------
0.4285714 ! 0.5714286 0.5 ! 0.5
!--------------------------------------------- !---------------------------------------------
44.1 ! -44.1 44.1 ! -32.666667
22.05 ! !
-9.45 ! -12.6 -5.7166667 ! -5.7166667
! -2.8583333 -6.3 ! 4.6666667
1.225 ! 1.6333333 0.8166667 ! 0.8166667
! 0.4083333 0.8166667 ! 0.8166667
-0.175 ! -0.2333333 -0.8166667 ! -0.8166667
! -0.4083333 -0.1166667 ! -0.1166667
0.175 ! 0.2333333 0.1166667 ! 0.1166667
! 0.0583333 0.1166667 ! 0.1166667
-0.025 ! -0.0333333 -0.1166667 ! -0.1166667
! -0.0583333 -0.0166667 ! -0.0166667
0.025 ! 0.0333333 0.0166667 ! 0.0166667
!--------------------------------------------- !---------------------------------------------
57.925 ! -57.925 32.9 ! -32.9
20.7375
33.075

k-ft fy = 40 ksi
in.     f'c = 2.5 ksi
in.     k   =   0.38666667
j = 0.87111111
in. R = 0.18946667
k-ft
k-ft M = 57.925 k-ft As = 3.057266 sq-in
sq-in M = 32.9 k-ft As = 1.7364532 sq-in
sq-in M = 44.1 k-ft As = 2.3275862 sq-in
sq-in M = 33.075 k-ft As = 1.7456897 sq-in
ksi M = 24.5 k-ft As = 1.2931034 sq-in
sq-in M = 40.775 k-ft As = 2.1520936 sq-in
kip M = 32.666667 k-ft As = 1.7241379 sq-in
kip
psi > 55 psi
sq-in
in. c/c

OF BEAM - B3 (FOR 2-SPAN)


---------------------------------------

k/ft w2 = 3.25 k/ft


ft L2 = 14.75 ft
!11k
!--------------------------------------------- !
0.5 ! 0.5 1 !
!--------------------------------------------- !
58.923177 ! -66.416815 58.923177 !
29.461589 ! -29.461589 -58.923177 !
3.7468189 ! 3.7468189 !
!--------------------------------------------- !
92.131585 ! -92.131585 0 !
42.318973
58.923177

k-ft fy = 40 ksi
in.     f'c = 2.5 ksi
in.     k   =   0.38666667
j = 0.87111111
in. R = 0.18946667
k-ft
k-ft M = 58.923177 k-ft As = 2.1997204 sq-in
sq-in M = 58.923177 k-ft As = 2.1997204 sq-in
sq-in M =
sq-in M =
ksi M =
sq-in
kip
kip
psi > 55 psi
sq-in
in. c/c

OF BEAM - B4 (FOR 4-SPAN)


------------------------------------------------

k/ft w2 = 2.7 k/ft w3 =


ft L2 = 14.75 ft L3 =

!--------------------------------------------- !---------------------------------------------
0.4285714 ! 0.5714286 0.5 ! 0.5
!--------------------------------------------- !---------------------------------------------
58.923177 ! -48.951563 48.951563 ! -48.951563
29.461589 ! !
-16.899944 ! -22.533259 0 ! 0
! 0 -11.266629 ! 6.9930804
0 ! 0 2.1367746 ! 2.1367746
! 1.0683873 0 ! 0
-0.4578803 ! -0.610507 0 ! 0
! 0 -0.3052535 ! -0.3052535
0 ! 0 0.3052535 ! 0.3052535
! 0.1526268 0 ! 0
-0.0654115 ! -0.0872153 0 ! 0
! 0 -0.0436076 ! -0.0436076
0 ! 0 0.0436076 ! 0.0436076
!--------------------------------------------- !---------------------------------------------
70.96153 ! -70.96153 39.821708 ! -39.821708
18.035725
36.713672

k-ft fy = 40 ksi
in.     f'c = 2.5 ksi
in.     k   =   0.38666667
j = 0.87111111
in. R = 0.18946667
k-ft
k-ft M = 70.96153 k-ft As = 3.1032739 sq-in
sq-in M = 39.821708 k-ft As = 1.7414741 sq-in
sq-in M = 58.923177 k-ft As = 2.5768153 sq-in
sq-in M = 36.713672 k-ft As = 1.6055542 sq-in
ksi M = 36.713672 k-ft As = 1.6055542 sq-in
sq-in M = 63.461015 k-ft As = 2.775263 sq-in
kip M = 48.951563 k-ft As = 2.1407389 sq-in
kip
psi > 55 psi
sq-in
in. c/c

OF BEAM - B5 (FOR 4-SPAN)


------------------------------------------------

k/ft w2 = 3.2 k/ft w3 =


ft L2 = 15 ft L3 =

!--------------------------------------------- !---------------------------------------------
0.323741 ! 0.676259 0.5 ! 0.5
!--------------------------------------------- !---------------------------------------------
138.0625 ! -60 60 ! -60
69.03125 ! !
-47.620279 ! -99.473471 0 ! 0
! 0 -49.736736 ! 31.063534
0 ! 0 9.3366007 ! 9.3366007
! 4.6683004 0 ! 0
-1.5113203 ! -3.1569801 0 ! 0
! 0 -1.57849 ! -1.57849
0 ! 0 1.57849 ! 1.57849
! 0.789245 0 ! 0
-0.255511 ! -0.533734 0 ! 0
! 0 -0.266867 ! -0.266867
0 ! 0 0.266867 ! 0.266867
!--------------------------------------------- !---------------------------------------------
157.70664 ! -157.70664 19.599865 ! -19.599865
1.3467475
45

k-ft fy = 40 ksi
in.     f'c = 2.5 ksi
in.     k   =   0.38666667
j = 0.87111111
in. R = 0.18946667
k-ft
k-ft M = 157.70664 k-ft As = 6.8967918 sq-in
sq-in M = 19.599865 k-ft As = 0.857137 sq-in
sq-in M = 138.0625 k-ft As = 6.0377187 sq-in
sq-in M = 45 k-ft As = 1.96793 sq-in
ksi M = 45 k-ft As = 1.96793 sq-in
sq-in M = 123.8939 k-ft As = 5.4181006 sq-in
kip M = 101.24583 k-ft As = 4.4276603 sq-in
kip
psi > 55 psi
sq-in
in. c/c

OF BEAM - B6 (FOR 2-SPAN)


---------------------------------------

k/ft w2 = 2.5 k/ft


ft L2 = 23.5 ft
!11k
!--------------------------------------------- !
0.5 ! 0.5 1 !
!--------------------------------------------- !
115.05208 ! -115.05208 115.05208 !
57.526042 ! -57.526042 -115.05208 !
0 ! 0 !
!--------------------------------------------- !
172.57813 ! -172.57813 0 !
86.289063
115.05208

k-ft fy = 40 ksi
in.     f'c = 2.5 ksi
in.     k   =   0.38666667
j = 0.87111111
in. R = 0.18946667
k-ft
k-ft M = 115.05208 k-ft As = 3.3226439 sq-in
sq-in M = 115.05208 k-ft As = 3.3226439 sq-in
sq-in M =
sq-in M =
ksi M =
sq-in
kip
kip
psi > 55 psi
sq-in
in. c/c
2 k/ft w4 = 2 k/ft
15 ft L4 = 15 ft

---------------------------------- !--------------------------------------------- !
0.5714286 ! 0.4285714 1!
---------------------------------- !--------------------------------------------- !
37.5 ! -37.5 37.5 !
! -18.75 -37.5 !
10.714286 ! 8.0357143 !
1.1666667 ! !
-0.6666667 ! -0.5 !
-0.1666667 ! !
0.0952381 ! 0.0714286 !
0.1666667 ! !
-0.0952381 ! -0.0714286 !
-0.0238095
! !
0.0136054
! 0.0102041 !
0.0238095
! !
-0.0136054
! -0.0102041 !
---------------------------------- !--------------------------------------------- !
48.714286 ! -48.714286 0!
16.821429 31.892857
28.125 37.5

2 k/ft w4 = 2 k/ft
14 ft L4 = 14 ft

---------------------------------- !--------------------------------------------- !
0.5714286 ! 0.4285714 1!
---------------------------------- !--------------------------------------------- !
32.666667 ! -32.666667 32.666667 !
! -16.333333 -32.666667 !
9.3333333 ! 7 !
-2.8583333 ! !
1.6333333 ! 1.225 !
0.4083333 ! !
-0.2333333 ! -0.175 !
-0.4083333 ! !
0.2333333 ! 0.175 !
0.0583333! !
-0.0333333! -0.025 !
-0.0583333! !
0.0333333! 0.025 !
---------------------------------- !--------------------------------------------- !
40.775 ! -40.775 0!
12.1625 28.6125
24.5 32.666667
2.7 k/ft w4 = 2.7 k/ft
14.75 ft L4 = 14.75 ft

---------------------------------- !--------------------------------------------- !
0.5714286 ! 0.4285714 1!
---------------------------------- !--------------------------------------------- !
48.951563 ! -48.951563 48.951563 !
! -24.475781 -48.951563 !
13.986161 ! 10.489621 !
0 ! !
0 ! 0 !
1.0683873 ! !
-0.610507 ! -0.4578803 !
0 ! !
0 ! 0 !
0.1526268 ! !
-0.0872153 ! -0.0654115 !
0 ! !
0 ! 0 !
---------------------------------- !--------------------------------------------- !
63.461015 ! -63.461015 0!
21.785982 41.696836
36.713672 48.951563
3.2 k/ft w4 = 2.2 k/ft
15 ft L4 = 23.5 ft

---------------------------------- !--------------------------------------------- !
0.676259 ! 0.323741 1!
---------------------------------- !--------------------------------------------- !
60 ! -101.24583 101.24583 !
! -50.622917 -101.24583 !
62.127068 ! 29.741682 !
0 ! !
0 ! 0 !
4.6683004 ! !
-3.1569801 ! -1.5113203 !
0 ! !
0 ! 0 !
0.789245 ! !
-0.533734 ! -0.255511 !
0 ! !
0 ! 0 !
---------------------------------- !--------------------------------------------- !
123.8939 ! -123.8939 0!
18.253118 89.9218
45 101.24583
4 2.5 7 12 5.8333333
6 2.5 7 16 11.666667
6 2.5 7 3 2.1875
3.25 3.75 12.5 3 3.1738281
3.25 3.75 9 4 3.046875
3.25 3.75 7 5 2.9622396
3.25 3.75 7.5 1 0.6347656
3.25 3.75 6 1 0.5078125
3.25 3.75 3.5 1 0.296224
3.25 3.75 2.5 1 0.2115885
8 12 6 2 8
38.520833
ULTIMATE MOMENT CAPACITY
--------------------------------------------------
OF A BEAM (USD),singly reinforced
---------------------------------
fy = 60 ksi
f'c = 4 ksi
b  = 12 in.
h  = 20 in.
as = 1 sq-in.
no. of bar = 4 nos.
Actual steel
ratio,p 0.020202
p max = 0.0213801 < 0.020202
failure by yilding is assured.
a = 5.8823529 in.
Mu = 244.05882 k-ft

DESIGN OF BEAM (USD)


---------------------------------------
SIMPLY SUPPORTED BEAM,singly reinforced
------------------------------------------------
D. L . = 1.18 k/ft
L. L . = 2.3 k/ft
L = 13.5 ft
Wu = 5.91 k/ft
Mu = 134.63719 k-ft

fy = 40 ksi
f'c = 3 ksi
b = 11.5 in.
h = 21 in.
Mu = .145 f'c bd2
bd2 = 3714.1293 cu-in.
d = 17.971304 in.> 17.5
a (assum) = 3.9 in
As = 2.8861133 sq-in.
a = 3.9367275 in.
ULTIMATE MOMENT CAPACITY
--------------------------------------------------
OF A BEAM (USD),doubly reinforced
---------------------------------
fy = 50 ksi
f'c = 5 ksi
b  = 12 in.
h  = 21.5 in.
as = 1.265 sq-in.
no. of bar = 6 nos.
a's = 1 sq-in.
no. of bar = 2 nos.
Actual steel
ratio,p 0.0351389
p' = 0.0092593
As-A's = 5.59 sq-in.
p -p' = 0.0258796
p max = 0.034411 < 0.0351389
Analyzed as doubly reinforced.
Checking limits on (p-p')max= .75pb
(p-p')max= 0.034411 > 0.0258796
(p-p')min= 0.0235952 < 0.0258796
M1 = 116.25 k-ft
a = 5.4803922 in.
M2 = 319.88364 k-ft
Mu = 436.13364 k-ft

DESIGN OF BEAM (USD)


---------------------------------------
SIMPLY SUPPORTED BEAM,doubly reinforced
------------------------------------------------
D. L . = 0.98 k/ft
L. L . = 2.33 k/ft
L = 18 ft
Wu = 5.664 k/ft
Mu = 229.392 k-ft

fy = 40 ksi
f'c = 3 ksi
b = 10 in.
h = 19.5 in.
p max = 0.0278404
As = 4.4544685 sq-in.
a = 6.9874016 in.
M max = 167.12675 k-ft< 229.392
M1 = 62.265252 k-ft
A's = 1.5374136 sq-in.
As-A's = 4.4544685 sq-in.
As = 5.9918821 sq-in.

T - BEAM (USD)

ULTIMATE MOMENT CAPACITY


OF T - BEAM (USD).

fy = 60 ksi
f'c = 4 ksi
b  = 12 in.
h  = 20 in.
as = 1 sq-in.
no. of bar = 4 nos.
Actual steel
ratio,p 0.020202
p max = 0.0213801 < 0.020202
failure by yilding is assured.
a = 5.8823529 in.
Mu = 244.05882 k-ft
DESIGN OF BEAM (USD)
---------------------------------------
SIMPLY SUPPORTED BEAM,singly reinforced
------------------------------------------------
D. L . = 1.18 k/ft
L. L . = 2.3 k/ft
L = 13.5 ft
Wu = 5.91 k/ft
Mu = 134.63719 k-ft

fy = 40 ksi
f'c = 3 ksi
b = 11.5 in.
h = 21 in.
Mu = .145 f'c bd2
bd2 = 3714.1293 cu-in.
d = 17.971304 in.> 17.5
a (assum) = 3.9 in
As = 2.8861133 sq-in.
a = 3.9367275 in.
A' ! ! B'
! !
! 12"x20" 12"x20" !
! !
! w = 2 k/ft !
A !- ! B
! 12" x 24" !
! !
! !
! 12"x20" 12"x20" !
! !
A" ! ! B"
C0L. HT= 9 ft
BEAM. SPAN= 65

C0L. SIZE= 20 25

26041.666667 2893.518519

BEAM SIZE= 20 54

262440 2018.769231

AA" AA' AB
------------------ ------------------ ------------------
0.370687975 0.370687975 0.25862405
---------------------------------------------------------------
-1232.29166667
456.7957025 456.7957025 318.7002616578
---------------------------------------------------------------
456.7957025 456.7957025 -913.591405009

934.846095