Marley Cooling Tower Design Guide
Marley Cooling Tower Design Guide
engineering data
C O O LI N G TOW E R
NC Steel Cooling Tower — Sound Control 2
VELOCITY RECOVERY
CYLINDER INCREASES MODEL
PERFORMANCE. REFER TO
DATA TABLE AND UPDATE FOR
ADDITIONAL INFORMATION.
FAN GUARD NOT REQUIRED.
PLAN NOT AVAILABLE ON NC8401 A MIN
CL CL
MODELS.
3 1/2"
W MIN
B
INSTALLED
HEIGHT
H
INSTALLED
HEIGHT
HINGED ACCESS
DOOR L
CASED SIDE ELEVATION AIR INLET ELEVATION
NC Steel Cooling Tower — Schematic Data 5
Nominal Design
Nominal Shipping Dimensions
Model Tons with Motor Operating
Tons Weight
note 2 VR Cylinder hp Weight
note 3 lb L W H B A
note 3 lb
NC8401G-1 101 – 2
NC8401H-1 117 – 3
NC8401K-1 139 – 5
7810 3983 6'-61 ⁄4" 12'-10" 10'-21 ⁄2" – 6'-9 3 ⁄4"
NC8401M-1 159 – 7.5
NC8401N-1 175 – 10
NC8401P-1 198 – 15
NC8402H-1 156 168 3
NC8402K-1 186 199 5
NC8402M-1 212 228 7.5
10171 4748 8'-43 ⁄4" 14'-2" 10'-3" 14'-9" 8'-81 ⁄4"
NC8402N-1 236 252 10
NC8402P-1 265 283 15
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current 4 Standard overflow is a 4" dia. standpipe in the collection basin floor.
drawings from your Marley sales representative. All table data is per The standpipe removes for flush-out and draining. See page 20 for
cell. side overflow option.
2 Last numeral of model number indicates number of cells. Change as 5 Outlet sizes vary according to gpm and arrangement. See pages 20
appropriate for your selection. and 21 for outlet sizes and details.
3 Nominal tons are based upon 95°F HW, 85°F CW, 78°F WB, 6 Makeup water connection may be 1" or 2" dia., depending upon
3 gpm/ton and standard low sound fans. The UPDATE web-based tower heat load, water pressure, and desired connections. See page
selection software provides NC model recommendations based on 15 for additional information.
specific design requirements.
NC Steel Cooling Tower — Schematic 6
NC8407 NC8409
VELOCITY RECOVERY
CYLINDER INCREASES MODEL
PERFORMANCE. REFER TO
DATA TABLE AND UPDATE FOR
A MIN
PLAN CL CL
ADDITIONAL INFORMATION.
FAN GUARD NOT REQUIRED. 3 1/2" MIN
16'-5 3/4"
INSTALLED
HEIGHT
11'-11 3/4"
INSTALLED
HEIGHT
HINGED ACCESS
DOOR L
CASED SIDE ELEVATION AIR INLET ELEVATION
NC Steel Cooling Tower — Schematic Data 7
NC8407 NC8409
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current 4 Standard overflow is a 4" dia. standpipe in the collection basin floor.
drawings from your Marley sales representative. All table data is per The standpipe removes for flush-out and draining. See page 20 for
cell. side overflow option.
2 Last numeral of model number indicates number of cells. Change as 5 Outlet sizes vary according to gpm and arrangement. See pages 20
appropriate for your selection. and 21 for outlet sizes and details.
3 Nominal tons are based upon 95°F HW, 85°F CW, 78°F WB, 6 Makeup water connection may be 1" or 2" dia., depending upon
3 gpm/ton and standard low sound fans. The UPDATE web-based tower heat load, water pressure, and desired connections. See page
selection software provides NC model recommendations based on 15 for additional information.
specific design requirements.
NC Steel Cooling Tower — Schematic 8
PLAN
A MIN
CL CL
22' 5" 3 1/2" MIN
B
INSTALLED
HEIGHT
H
INSTALLED
HEIGHT
HINGED ACCESS
DOOR L
CASED SIDE ELEVATION AIR INLET ELEVATION
NC Steel Cooling Tower — Schematic Data 9
NC8410S-1 708 744 30 33594 16311 11'-10 3 ⁄4" 16'-0" 20'-6" 12'-21 ⁄4"
NC8411S-1 756 797 30 37334 17608 11'-10 3 ⁄4" 18'-10" 23'-4" 12'-21 ⁄4"
NC8412T-1 926 971 40 42915 19757 13'-10 3 ⁄4" 18'-10" 23'-4" 14'-21 ⁄4"
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current 4 Standard overflow is a 4" dia. standpipe in the collection basin floor.
drawings from your Marley sales representative. All table data is per The standpipe removes for flush-out and draining. See page 20 for
cell. side overflow option.
2 Last numeral of model number indicates number of cells. Change as 5 Outlet sizes vary according to gpm and arrangement. See pages 20
appropriate for your selection. and 21 for outlet sizes and details.
3 Nominal tons are based upon 95°F HW, 85°F CW, 78°F WB, 6 Makeup water connection may be 1" or 2" dia., depending upon
3 gpm/ton and standard low sound fans. The UPDATE web-based tower heat load, water pressure, and desired connections. See page
selection software provides NC model recommendations based on 15 for additional information.
specific design requirements.
NC Steel Cooling Tower — Schematic 10
NC8413 NC8414
PLAN
A MIN
CL CL
22' 5" 3 1/2" MIN
27'-1 3/16"
INSTALLED
HEIGHT
22'-7 3/16"
INSTALLED
HEIGHT
HINGED ACCESS
DOOR L
CASED SIDE ELEVATION AIR INLET ELEVATION
NC Steel Cooling Tower — Schematic Data 11
NC8413 NC8414
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current 4 Standard overflow is a 4" dia. standpipe in the collection basin floor.
drawings from your Marley sales representative. All table data is per The standpipe removes for flush-out and draining. See page 20 for
cell. side overflow option.
2 Last numeral of model number indicates number of cells. Change as 5 Outlet sizes vary according to gpm and arrangement. See pages 20
appropriate for your selection. and 21 for outlet sizes and details.
3 Nominal tons are based upon 95°F HW, 85°F CW, 78°F WB, 6 Makeup water connection may be 1" or 2" dia., depending upon
3 gpm/ton and standard low sound fans. The UPDATE web-based tower heat load, water pressure, and desired connections. See page
selection software provides NC model recommendations based on 15 for additional information.
specific design requirements.
NC Steel Cooling Tower — Schematic Data 12
NC8422
Use this data for preliminary layouts only.
Obtain current drawing from your local Marley
sales representative.
NC8422W-1 1810 75
NC8422X-1 1967 100
NC8422Y-1 2080 125
NC8422Z-1 2189 150
27'-1 3/16"
INSTALLED
HEIGHT
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current drawings 4 Standard overflow is a 4" dia. standpipe in the collection basin floor.
from your Marley sales representative. All table data is per cell. The standpipe removes for flush-out and draining.
2 Last numeral of model number indicates number of cells. Change as 5 Outlet sizes vary according to gpm and arrangement. See pages 23
appropriate for your selection. for outlet sizes and details.
3 Nominal tons are based upon 95°F HW, 85°F CW, 78°F WB, 6 Makeup water connection may be 1" or 2" dia., depending upon
3 gpm/ton and standard low sound fans. The UPDATE web-based tower heat load, water pressure, and desired connections. See page
selection software provides NC model recommendations based on 15 for additional information.
specific design requirements.
NC Steel Cooling Tower — Freeze Prevention 13
When the ambient air temperature falls below 32°F, the water STEAM JET BASIN HEATERS
in a cooling tower can freeze. Marley Technical Report #H-003
Penberthy Houdaille bronze steam jet heaters (1⁄4" to 3⁄4") are
“Cooling Towers and Freezing Weather” describes how to prevent
available for freeze protection (installation by others). Injectors
freezing during operation. Available at spxcooling.com or ask your
install in a coupling provided in the side of the collection basin. Live
Marley sales representative for a copy.
steam, as required, is injected directly into the water. Condensed
During shutdown, water collects in the cold water basin and steam adds water to the basin, and the excess will exit the overflow
may freeze solid. You can prevent freezing by adding heat to the of the tower.
water left in the tower—or, you can drain the tower and all exposed
pipework at shutdown. INDOOR STORAGE TANK
ELECTRIC BASIN HEATERS With this type of system, water flows from an indoor tank,
through the load system, and back to the tower, where it is cooled.
An automatic basin water heater system is available consisting The cooled water flows by gravity from the tower to the tank
of the following components: located in a heated space. At shutdown, all exposed water drains
• Stainless steel electric immersion heater(s). into the tank, where it is safe from freezing. Although we do not
produce tanks, many of our representatives offer tanks supplied by
—Threaded couplings are provided in the side of the reputable manufacturers.
collection basin.
The amount of water needed to successfully operate the system
• NEMA 4 enclosure containing: depends on the tower size and gpm and on the volume of water
—Magnetic contactor to energize heater. contained in the piping system to and from the tower. You must
select a tank large enough to contain those combined volumes—
—Transformer to convert power supply to 24 volts for control
plus a level sufficient to maintain a flooded suction on your pump.
circuit.
Control makeup water according to the level where the tank
—Solid state circuit board for temperature and low- stabilizes during operation.
water cutoff.
Enclosure may be mounted on the side of the tower.
• Control probe in the collection basin to monitor water
temperature and level.
Heater components are normally shipped separately for
installation by others.
Note: any exposed piping that is still filled with water at
shutdown—including the makeup water line—should be electrically
traced and insulated (by others).
NC Steel Cooling Tower — Inlet Connection 14
If each cell is to be equipped with an outlet, cased-face Makeup Water Flow Required–gpm
outlet — NC8401 through NC8414 — can be used on end to Maintain Three (3) Concentrations
cells of multicell towers, but not on interior cells. For direct
Cooling “Range” (HW – CW)
outlet from each cell on installations of three or more cells, use Tower gpm
either the depressed sump or bottom outlet on interior cells. 5°F 10°F 15°F 20°F 30°F 40°F
The best choice for a tower used with a remote or indoor 200 2 3 4 5 8 10
storage tank—see page 13—or on a concrete cold water basin is 400 3 5 8 10 15 20
usually a bottom outlet. 600 4 8 12 15 23 30
A cased-face outlet equipped tower — NC8401 through 800 5 10 15 20 30 40
NC8414 — can be installed on a flat concrete slab if a side drain 1000 7 13 19 25 38 50
and overflow are also specified—see page 20. Consult your Marley 1500 10 19 29 38 57 75
sales representative for complete information.
2000 13 25 38 50 75 100
MAKEUP 3000 19 38 57 75 113 150
4000 25 50 75 100 150 200
The amount of water constantly evaporated from a cooling tower
varies directly with the heat load applied. In addition to evaporation, 5000 32 63 94 125 188 250
water is normally lost to the blowdown (bleed-off) necessary to 6000 38 75 113 150 225 300
maintain dissolved solids concentration at an acceptable level in the 8000 50 100 150 200 300 400
circulating water system.
The NC is equipped with one or more float-operated, mechanical NOTE
makeup valves to automatically replenish this lost water. The tables • If circulating water is to be maintained at 2 concentrations
on this page, calculated for a concentration of 3 times normal, instead of 3, multiply table gpm values by 1.36 before sizing
indicate the rate of water loss—and the size of valve(s) required. If makeup valve.
your installation’s cold water basin will drain by gravity to a remote
storage tank—or if you plan a separate means of controlling makeup
water—a price reduction is available for deleting the Marley valve(s).
We also offer an optional electronic liquid-level control.
In most instances cooling towers will see the highest water
Makeup Valve Flow Capacities–gpm
usage at design heat load. Off design conditions (99% of the time)
water usage will be less. For a better understanding of how much Pressure at Valve Inlet
1" Diameter Valve 2" Diameter Valve
while flowing–psig
water your application will use throughout the year, consult our
water usage calculator at: 10 56 90
spxcooling.com/watercalc 20 78 120
30 92 143
If too much water is still being consumed consult your Marley
sales representative for water saving alternatives. 40 106 160
50 117 167
NOTE
• If makeup water pressure exceeds 50 psig, use pressure
reducer ahead of valve.
• For flow requirements exceeding the above limitations, use
multiples of the same size valve.
NC Steel Cooling Tower — Dual Inlet Connection 16
NC8401 - NC8409
TOWER CL INLET
CL INLET
CL INLET
K Q
CL INLET
MARLEY HC
BALANCING VALVE
CL INLET
OPTION NOTE 6
CL TOWER
FACE OF VALVE
INLET FLANGE P
PIPING
TOP OF
CL INLET
DISTRIBUTION
BASIN
S J
USE FOR INLET
STATIC LIFT ELEVATION
Dimensions
Model Fan Diameter Inlet Diameter
J K S P Q
NC8401 9'-9" 11'-1" 10'-5 3 ⁄16" 5'-3" 6'-9 3 ⁄4" 72" 2 at 6"
NC8402 9'-9" 12'-5" 10'-5 3 ⁄16" 5'-11" 8'-81 ⁄4" 84" 2 at 6"
NC8403 11'-5 5 ⁄16" 16'-01 ⁄2" 12'-27 ⁄16" 7'-8 3 ⁄4" 8'-81 ⁄4" 84" 2 at 8"
NC8405 11'-5 ⁄16"
5
17'-9 ⁄2"
1
12'-2 ⁄16"
7
8'-7 ⁄4"
1
10'-21 ⁄4" 108" 2 at 8"
NC8407 11'-5 5 ⁄16" 19'-0 7 ⁄8" 12'-27 ⁄16" 9'-215 ⁄16" 12'-21 ⁄4" 120" 2 at 8"
NC8409 11'-5 5 ⁄16" 20'-31 ⁄2" 12'-47 ⁄16" 9'-91 ⁄2" 14'-21 ⁄4" 144" 2 at 10"
NC Steel Cooling Tower — Dual Inlet Connection 17
NC8410 - NC8422
TOWER CL INLET
CL INLET
CL INLET
20'-3 1/2"
Q
CL INLET
MARLEY HC
BALANCING VALVE
CL INLET
OPTION NOTE 6
TOP OF
DISTRIBUTION
BASIN
J
S INLET
USE FOR ELEVATION
STATIC LIFT
Dimensions
Model Fan Diameter Inlet Diameter
J S Q
NC8410 15'-6" 16'-5" 12'-21 ⁄4" 132" 2 at 10"
NC8411 18'-3 5 ⁄8" 19'-23 ⁄4" 12'-21 ⁄4" 132" 2 at 10"
NC8412 18'-3 5 ⁄8" 19'-23 ⁄4" 14'-21 ⁄4" 144" 2 at 10"
NC8413 22'-0 3 ⁄4" 22'-113 ⁄8" 12'-21 ⁄4" 132" 2 at 10"
NC8414 22'-0 3 ⁄4" 22'-113 ⁄8" 14'-21 ⁄4" 144" 2 at 10"
NC8422 22'-0 3 ⁄4" 23'-17 ⁄8" 22'-81 ⁄2" 228" 2 at 14"
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current drawings 4 All piping and supports—and their design—are by others.
from your Marley sales representative. 5 Allow adequate clearance for entry to tower access doors and safe
2 Pumping head contributed by the tower is static lift “S”. Add your use of optional ladder. Refer to appropriate Marley drawings.
system dynamic pipe losses for total. 6 You may choose to use 90° short radius flanged elbows in place
3 The tower will support the vertical weight of piping shown within of HC balancing valves on single-cell towers where inlet piping is
the plan area of the tower only. All piping loads, including thrust balanced for equal flow. Pipe elevation remains as shown.
and lateral loads of riser and horizontal piping must be supported
independent of the tower. See inlet piping drawings for details.
NC Steel Cooling Tower — Single Inlet Connection 18
NC8401 - NC8409
CL TOWER CELL
C
FACE OF SIDE
INLET CONNECTION
SINGLE SIDE
INLET NOTE 5
SIDE INLET CL TOWER
CL INLET
6 3/8"
Dimensions
Model Inlet Diameter
B C D E
NC8401 7'-6 7 ⁄16" 3'-3 1⁄16" na na 6"
NC8402 7'-6 5 ⁄8" 5'-013 ⁄16" 2'-41 ⁄8" 2'-0" 8"
NC8403 9'-3 9 ⁄16" 5'-011 ⁄16" 2'-43 ⁄16" 2'-5" 8"
NC8405 9'-2 ⁄16"
9
5'-11 ⁄8"
7
2'-711 ⁄16" 3'-01 ⁄4" 10"
NC8407 9'-111 ⁄16" 7'-01 ⁄16" 2'-10 5 ⁄8" 4'-2" 10"
NC8409 9'-2 ⁄8"
1
8'-0" 2'-10 7 ⁄8" 4'-8" 10"
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current drawings 4 Allow adequate clearance for entry to tower access doors and safe
from your Marley sales representative. use of optional ladder. Refer to appropriate Marley drawings.
2 All external piping loads, including weight, thrust and lateral loads 5 You may choose either a bottom inlet connection or a side inlet
of riser and horizontal piping plus the weight of water in the internal connection. The bottom inlet connects at the tower collection basin
riser must be supported independent of the tower. Internal riser adds floor. Refer to appropriate Marley drawings.
additional vertical operating loads to external piping at the bottom 6 Contact your Marley sales representative for the required pump head
inlet flange. for single-inlet applications.
3 All piping and supports beyond the inlet connection—and their 7. Weight of internal piping must be added to tower weights. Contact
design—are by others. your Marley sales representative for combined tower weight
information.
NC Steel Cooling Tower — Single Inlet Connection 19
NC8410 - NC8414
CL TOWER CELL
C
FACE OF SIDE
INLET CONNECTION
SINGLE SIDE
SIDE INLET CL TOWER INLET NOTE 5
CL INLET
6 3/8"
CLINLET CL TOWER
CL TOP OF FACE OF
INLET SUPPORT BOTTOM INLET
2'-7 5/8" CONNECTION E
SINGLE BOTTOM SINGLE BOTTOM
INLET NOTE 5 INLET NOTE 5
Dimensions
Model Inlet Diameter
B C E
NC8410 13'-31 ⁄2" 7'-37 ⁄16" 4'-6" 10"
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current drawings 4 Allow adequate clearance for entry to tower access doors and safe
from your Marley sales representative. use of optional ladder. Refer to appropriate Marley drawings.
2 All external piping loads, including weight, thrust and lateral loads 5 You may choose either a bottom inlet connection or a side inlet
of riser and horizontal piping plus the weight of water in the internal connection. The bottom inlet connects at the tower collection basin
riser must be supported independent of the tower. Internal riser adds floor. Refer to appropriate Marley drawings.
additional vertical operating loads to external piping at the bottom 6 Contact your Marley sales representative for the required pump head
inlet flange. for single-inlet applications.
3 All piping and supports beyond the inlet connection—and their 7. Weight of internal piping must be added to tower weights. Contact
design—are by others. your Marley sales representative for combined tower weight
information.
NC Steel Cooling Tower — Outlet Connection 20
NC8401 - NC8414
WELDING
TOWER CL BEVEL MECHANICAL
COUPLING GROOVE
SUCTION HOOD
REMOVABLE
A TRASH SCREEN
SUCTION CONNECTION
SEE TABLE FOR SIZE TOP OF B
SUPPORT CL TOWER CELL
SECTON
NC8401 - NC8414
BOTTOM OF
COLLECTION
BASIN FLOOR TOP OF
SUPPORT
CL SUMP REMOVABLE
TRASH SCREEN OUTLET
SEE TABLE FOR SIZE TOWER COLLECTION
1 3/8" BASIN FLOOR
REMOVABLE
TRASH SCREEN BOTTOM
OF BASIN
CL OUTLET
pump flow w/ anti-vortex plate or NC8401 thru NC8405 157 355 630 993 1413 1729 2285 2509 3322 4019
gravity flow w/ or w/o anti-vortex plate
Bottom NC8407 thru NC8414 167 380 673 1061 1510 1848 2442 3164 3829 4896
pump flow w/o anti-vortex plate NC8401 thru NC8414 71 162 287 453 644 788 1042 1349 1676 2433
pump flow w/ anti-vortex plate or NC8401 thru NC8405 900 1595 2515 3578 4284
gravity flow w/ or w/o anti-vortex plate
Sump NC8407 thru NC8414 900 1595 2515 3578 4379
pump flow w/o anti-vortex plate NC8401 thru NC8414 630 1116 1761 2505 3065
NOTE
• Flow rate may be limited by the maximum gpm for unit size.
• For gravity-flow situations (as to an indoor tank), use bottom outlet or depressed side outlet sump. Cased-face outlet is not
recommended for gravity flow.
• gpm limits are the outlet capacities per outlet based on the design operating water level—81⁄2" above the top of support on models
NC8401 through NC8405—91⁄w2" on NC8407 thru NC8414.
NC Steel Cooling Tower — Single Inlet Connection 22
NC8422
CL TOWER CELL
12'-6 5/16"
FACE OF SIDE
INLET CONNECTION
16'-7 7/8"
2'-3 11/16"
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current drawings 4 Allow adequate clearance for entry to tower access doors and safe
from your Marley sales representative. use of optional ladder. Refer to appropriate Marley drawings.
2 All external piping loads, including weight, thrust and lateral loads 5 You may choose either a bottom inlet connection or a side inlet
of riser and horizontal piping plus the weight of water in the internal connection. The bottom inlet connects at the tower collection basin
riser must be supported independent of the tower. Internal riser adds floor. Refer to appropriate Marley drawings.
additional vertical operating loads to external piping at the bottom 6 Contact your Marley sales representative for the required pump head
inlet flange. for single-inlet applications.
3 All piping and supports beyond the inlet connection—and their 7. Weight of internal piping must be added to tower weights. Contact
design—are by others. your Marley sales representative for combined tower weight
information.
NC Steel Cooling Tower — Outlet Connection 23
NC8422
BOTTOM OF BOTTOM OF
COLLECTION COLLECTION
BASIN FLOOR TOP OF BASIN FLOOR TOP OF
SUPPORT SUPPORT REMOVABLE
REMOVABLE
CL SUMP TRASH SCREEN CL SUMP TRASH SCREEN
1 3/8" 1 3/8"
4"
CL OUTLET
CL OUTLET
BOTTOM OF
COLLECTION
BASIN FLOOR TOP OF
SUPPORT
REMOVABLE
CL SUMP TRASH SCREEN
1 3/8" OUTLET
SEE TABLE FOR SIZE TOWER COLLECTION
BASIN FLOOR
MECHANICAL
CL OUTLET
Bottom pump flow w/ anti-vortex plate or gravity flow w/ or w/o anti-vortex plate 757 1194 1699 2079 2748 3560 4420 6419
Sump pump flow with anti-vortex plate 900 1595 2515 3578 4379 5787 7746
NOTE
• Flow rate may be limited by the maximum gpm for unit size.
• 16" and 18" sumps are only available in stainless steel.
• For gravity-flow situations (as to an indoor tank), use bottom outlet.
• Flow limits are the outlet capacities per outlet based on 115⁄8" design operating water level.
NC Steel Cooling Tower — Support 24
NC8401 - NC8414
L L
OVERALL OF BASIN OVERALL OF BASIN
2 1/4"
1" D 1" 1" D 1"
CL ANCHOR ANCHOR CL 3 1/2" CL ANCHOR ANCHORCL
BOLT BOLT BOLT BOLT
2 1/4" 2 1/4" A
ANCHOR CL
ANCHOR CL
BOLT
BOLT
MODELS NC8407
B THRU NC8414
HOLES FOR
W OVERALL WIDTH OF BASIN
3/4"
DIA. ANCHOR
C
C
HOLES FOR
3/4" DIA. ANCHOR
BOLTS 4 OR 8 REQD
CL ANCHOR
CL ANCHOR
BOLT
BOLT
2 1/4" 2 1/4"
NC8401 12'-10" 6'-61 ⁄4" 12'-51 ⁄ 2" 6'-41 ⁄4" 7810 1952
NC8403 18'-2" 8'-4 3 ⁄4" 17'-91 ⁄ 2" 8'-23 ⁄4" 15812 3953
NC8405 19'-11" 9'-10 3 ⁄4" 19'-61 ⁄ 2" 9'-8 3 ⁄4" 19691 4923
NC8409 22'-5" 13'-10 3 ⁄4" 22'-01 ⁄ 2" 13'-8 3 ⁄4" 30013 7503
NC8410 22'-5" 11'-10 3 ⁄4" 22'-01 ⁄ 2" 11'-8 3 ⁄4" 33594 8399
NC8411 22'-5" 11'-10 3 ⁄4" 22'-01 ⁄ 2" 11'-8 3 ⁄4" 37334 9334
NC8413 22'-5" 11'-10 3 ⁄4" 22'-01 ⁄ 2" 11'-8 3 ⁄4" 41995 10489
NC8414 22'-5" 13'-10 3 ⁄4" 22'-01 ⁄ 2" 13'-8 3 ⁄4" 48355 12089
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current drawings 4 Tower may be placed on a flat concrete slab. Side outlet and optional
from your Marley sales representative for final design. side drain and overflow must be specified. See pages 13 and 18 and
2 Purchaser to provide tower support complete with holes and anchor consult your Marley sales representative.
bolts. Do not use studs! Anchor points must be framed flush and 5 Tower may be supported from piers at each anchor bolt location, as a
level at top. support alternative.
3 Design operating weight occurs with collection basin full to overflow 6. Dimensions between anchor bolts may vary depending on the
level. Actual operating weight varies with gpm and piping scheme. number of cells and options. Dimensions shown are for a standard
two cell arrangement. Obtain current drawings from your Marley
sales representative for final dimension.
NC Steel Cooling Tower — Support 25
NC8401 - NC8414
2 1/4"
ANCHOR CL
BOLT
A
2 1/4"
3 1/2"
HOLES FOR
3/4" DIA. ANCHOR
W OVERALL WIDTH OF BASIN
BOLTS 4 OR 8/CELL
TWO BOLTS REQD.
MODELS NC8407
THRU NC8414
C
CL ANCHOR
BOLT
2 1/4"
TOWER COLLECTION
BASIN
SUPPORTING STEEL
MULTICELL
SUPPORT SUPPORT
BY OTHERS BY OTHERS
1/8"
NORMAL
GAUGE
NORMAL
GAUGE
SECTION B
VIEW A
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current drawings 5 Tower may be supported from piers at each anchor bolt location, as a
from your Marley sales representative for final design. support alternative.
2 Purchaser to provide tower support complete with holes and anchor 6. Dimensions between anchor bolts may vary depending on the
bolts. Do not use studs! Anchor points must be framed flush and number of cells and options. Dimensions shown are for a standard
level at top. two cell arrangement. Obtain current drawings from your Marley
3 Design operating weight occurs with collection basin full to overflow sales representative for final dimension.
level. Actual operating weight varies with gpm and piping scheme.
4 Tower may be placed on a flat concrete slab. Side outlet and optional
side drain and overflow must be specified. See pages 13 and 18 and
consult your Marley sales representative.
NC Steel Cooling Tower — Support 26
NC8422
10'-3 1/2"
5 1/2"
HOLES FOR
3/4" DIA. ANCHOR
BOLTS 12 REQD
CL ANCHOR
BOLT
2 1/4"
TOWER COLLECTION
BASIN
SUPPORTING STEEL
SINGLE CELL
SUPPORT
BY OTHERS
NORMAL
GAUGE
VIEW A
NC Steel Cooling Tower — Support 27
NC8422
5 3/4"
1" 22'-2 3/4" 22'-2 3/4" 1"
CL ANCHOR ANCHORCL CL ANCHOR ANCHORCL
BOLT BOLT BOLT BOLT
A
2 1/4"
ANCHOR CL
BOLT
9'-5"
CL ANCHOR
5 1/2"
BOLT
29'-6" OVERALL WIDTH OF BASIN
10'-3 1/2"
HOLES FOR
3/4" DIA. ANCHOR TWO BOLTS REQD.
BOLTS 12 REQD/CELL INTERIOR BEAMS
CL ANCHOR
BOLT
9'-5"
CL ANCHOR
BOLT
2 1/4"
TOWER COLLECTION
BASIN
SUPPORTING STEEL
MULTICELL
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current drawings 4 Tower may be supported from piers at each anchor bolt location, as
from your Marley sales representative for final design. a support alternative. Consult your Marley sales representative for
2 Purchaser to provide tower support complete with holes and anchor additional details.
bolts. Do not use studs! Anchor points must be framed flush and 5. Dimensions between anchor bolts may vary depending on the
level at top. number of cells and options. Dimensions shown are for a standard
3 Design operating weight occurs with collection basin full to overflow two cell arrangement. Obtain current drawings from your Marley
level. Actual operating weight varies with gpm and piping scheme. sales representative for final dimension.
NC Steel Cooling Tower — Hoisting Information 28
NC8401 - NC8414
LIFTING LIFTING
SLING SLING
WIDTH WIDTH
NOTE
• All hoisting clip holes are 11⁄4".
• On multicell tower installations, overall length of shackle pins should not
exceed 51⁄4".
• For overhead lifts or where additional safety is required, add slings beneath
the tower unit.
NC Steel Cooling Tower — Hoisting Information 29
NC8422
LIFTING SLING
11'-6" MIN. LENGTH
10'-0"
6'-6" 10'-0"
NOTE
• All hoisting clip holes are 11⁄4".
• Overall length of shackle pins should not exceed 21⁄2".
• For overhead lifts or where additional safety is required, add slings beneath
the tower unit.
NC Steel Cooling Tower — Sound Attenuators 30
NC8401 - NC8414
W D
NOTE
1 Use this bulletin for preliminary layouts only. Obtain current drawings 3 Attenuators are supported by the tower. Additional support not
from your Marley sales representative. All table data is per cell. required.
2 Attenuators are field installed by others with hardware provided by 4 Discharge attenuators are not available for NC models with velocity
Marley recovery cylinders.
5 Attenuators are not available for NC8422 model.
NC steel
E N G I N E E R I N G DATA