Technical Specification 34
Technical Specification 34
W.O. No 83002
CUSTOMER POWER GRID CORPORATION OF INDIA LIMITED
PROJECT 400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu
and Abhishekpatty substation
Cover Sheet 01
Enclosures:
00 First Issue
Rev. Date Altered Checked Approved REVISION DETAILS
Distribution CUSTOMER TBMM O/C
- 4 1
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
SECTION 1
SCOPE, SPECIFIC TECHNICAL REQUIREMENTS AND QUANTITIES
1.1 SCOPE
This technical specification covers the requirements of design, manufacture,
testing at works, packing and dispatch and erection & commissioning
supervision of Circuit Breakers complete with accessories as listed under this
specification.
This section covers the specific technical requirements of Circuit Breakers. This
constitutes minimum technical parameters for the above item as specified by
the customer (POWERGRID). The offered equipment shall also comply with the
General Technical Requirements for the project as detailed under section-3 of
this specification.
Section 1 : Page 1 of 6
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
Corona extinction voltage (kVrms) with circuit 320(min)
breaker in all positions
Max. radio interference Voltage (microvolts) for 1000
frequency between 0.5 MHz and 2 MHz at 266
kVrms (for 400kV) & 156kVrms (for 245kV)
Minimum creepage distance:
Phase to ground (mm) 10500*
Between CB terminals (mm) 10500*
System neutral earthing Effectively Earthed
Seismic acceleration 0.3g horizontal( it is
coming under zone –III
Thermal rating of auxiliary contacts 10 A at 220 V DC
Breaking capacity of auxiliary contacts 2 A DC with circuit time
constant of not less than
20 ms
Phase to phase spacing (mm) 6000
Rated continuous current at design Ambient 3150A
temperature
Section 1 : Page 2 of 6
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
opening of main contacts
at rated air/gas pressure ,
where the PIR contacts
remains closed
No. of trip coil 2 per pole
No. of closing coil 1 per pole
Total break time as per IEC (ms) 45
Rated break time as per IEC (ms) 40
Total closing time (ms) Max. 150
Rated operating duty cycle O-0.3 sec.-CO-3 min-CO
* 25mm/kV for Karaikudi, Pagular & Abhishekpatty station and 31mm/kV for
Kalivanthapattu station
The offered circuit breakers shall be as per POWERGRID approved standard
drawing as per POWERGRID standard specification C/ENGG/SPEC/SWGR/R9-
Sep 2010
1.3 QUANTITIES
Section 1 : Page 3 of 6
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
1.3.1 MAIN QUANTITY
Section 1 : Page 4 of 6
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
6 Terminal pads Nos. 2 2 2 2
7 Corona rings Nos. 1 1 1 1
Relays, Power contactors, switch
8 fuse units, limit switches, push Set 1 1 1 1
buttons, timers & MCBs etc.
9 Pressure switches Set 1 1 1 1
10 Aux. switch assembly Set 1 1 1 1
Bidder shall submit valid type test reports ( as per relevant IEC/IS standard) for
the tests carried out within last ten years from the date of bid opening
(17.05.13). The reports should have been conducted on identical or similar
equipment/components to those offered. In case type test reports are more than
10 years old or if any type report is found to be technically unacceptable , such
type test(s) shall be conducted by the vendor without cost and delivery
implication to BHEL.
Section 1 : Page 5 of 6
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
1.6 Note:-
Following additional requirements shall be met for Kalivanthapattu substion
extension:
1) All switchgears/ equipments, insulator strings, bushings, BPIs shall be designed for
minimum creepage distance of 31mm/kV instead of 25mm/kV for other three
stations.
2) The rate of zinc coating for galvanized lattice and pipe structures (excluding
foundation bolts and fasteners) shall not be less than 900gm/sq. m instead of
610gm/sq. m for other three stations.
3) Outdoor atmosphere around the substation is highly polluted coupled with coastal
pollution. Suitable paint and corresponding primers etc. as recommended by paint
manufacturer shall be used to withstand the outdoor atmospheric condition.
4) Kalivanthapattu substation falls under high wind zone and basic wind speed shall
be considered as 50m/sec.
--xx--
Section 1 : Page 6 of 6
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
SECTION-2
GENERAL EQUIPMENT SPECIFICATION
1.0 GENERAL
1.1 The circuit breakers and accessories shall conform to IEC: 62271-100, IEC:
62271-01 and other relevant IEC standards except to the extent explicitly modi-
fied in the specification and shall also be in accordance with require-
ments specified in Section-3 of this technical specification.
1.3 The circuit breaker shall be complete with terminal connectors, operating
mechanism, control cabinets, piping, interpole cable, cable accessories like
glands, terminal blocks, marking ferrules, lugs, pressure gauges, density moni-
tors (with graduated scale), galvanised support structure for CB and control
cabinets, their foundation bolts and all other circuit breaker accessories
required for carrying out all the functions the CB is required to perform.
All necessary parts to provide a complete and operable circuit breaker in-
stallation such as main equipment, terminals, control parts, connectors and other
devices whether specifically called for herein or not shall be provided.
1.4 Painting shall be done in line with Section –3. Shade- 697 as per IS-5 or RAL-
7032 or similar shades can be used for painting. The support structure of circuit
breaker shall be hot dip galvanised. Exposed hardware items shall be hot dip
galvanised or Electro-galvanised.
1.5 The circuit breakers shall be designed for use in the geographic and mete-
orological conditions as given in Section--3.
2.1 The circuit breakers shall be capable of performing their duties without opening
resistors.
2.2 The circuit breaker shall meet the duty requirements for any type of fault or fault
location also for line switching when used on a 800/420/245/145 kV effectively
grounded system, and perform make and break operations as per the stipulated
duty cycles satisfactorily.
800/420 kV circuit breakers wherever specified shall be provided with single step
preinsertion closing resistors to limit the switching surges to a value of less than
1.9 p.u for 800 kV and 2.3 p.u. for 420 kV respectively. The value of the pre-
insertion resistor and the duration of pre-insertion time shall be as given in clause
17.0 of this chapter. the resistor shall have thermal rating for the following duties:
Page 1 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
i) TERMINAL FAULT
Close .... 1 Min ........ Open Close open…… 2 min ........ close ....... 1 Min
........ open close open.
Duty same as under (i) above. The first, third and fourth closures are to be on
deenergised line while second closing is to be made with lines against trapped
charge of 1.2 p.u. of opposite polarity.
One closing operation under phase opposition that is with twice the voltage across
the terminals.
iv) No allowance shall be made for heat dissipation of resistor during time inter-
val between successive closing operations. The resistors and resis-
tor supports shall perform all these duties without deterioration. Calcula-
tions and test reports of resistors proving thermal rating for duties speci-
fied above shall be furnished during detailed engineering. The calculations
shall take care of adverse tolerances on resistance values and time set-
tings.
2.3 The breaker shall be capable of interrupting the steady state and transient mag-
netising current corresponding of power transformers.
ii) Clearing short line fault (Kilometric faults) with source impedance behind
the bus equivalent to symmetrical fault current specified.
iii) Breaking 25% of the rated fault current at twice rated voltage under phase
opposition condition.
iv) 400kV breakers shall be able to switch in and out the 400kV shunt reactor for any
value from 50MVAR and above, without giving rise to overvoltage more than 2.3
p.u. Laboratory test and / or field test reports in support of the same shall be fur-
nished during detailed engineering.
2.5 The Breaker shall satisfactorily withstand the high stresses imposed on them
during fault clearing, load rejection and re-energisation of lines with trapped
charges. The breaker shall also withstand the voltages specified under
Clause 17 of this section.
Page 2 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
The Circuit Breaker shall be equipped with controlled switching with conse-
quent optimization of switching behavior, when used in:
a. for 800 kV
Switching of transformer
The controller shall be provided in Circuit breaker of switchable line reactor and in
Main & Tie circuit breakers of Transformers and Bus reactors.
b. for 400 kV
The controller shall be provided in Circuit breaker of switchable line reactor and in
Main & Tie circuit breakers of Bus reactors.
The controlling relay shall also record and monitor the switching operations and
make adjustments to the switching instants to optimize the switching behavior as
necessary. It shall provide self diagnostic facilities, signaling of alarms and enable
downloading of data captured from the switching events.
Page 3 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
switching etc. Window based software for this purpose shall be supplied by
the contractor to be used on the owner’s PC.
h) The controller shall have self-monitoring facility.
i) The controller shall be suitable for current input of 1 amp from the secon-
dary of the CTs. and 110 V (Ph to Ph) from the CVTs. The controller shall also
take care of transient and dynamic state values of the current from the sec-
ondary of the CTs and CVTs.
j) The controller shall have time setting resolution of 0.1 ms or better.
k) The controller shall have sufficient number of output/input potential free con-
tacts for connecting the monitoring equipment and annunciation system
available in the control room. Necessary details shall be worked out during
engineering the scheme.
3.1 The total break time as specified under this section shall not be exceeded under
any of the following duties:
i) Test duties T10, T30, T60, T100a, T100s (TRV as per IEC: 62271-100)
3.2 The Bidder may please note that total break time of the breaker shall not be ex-
ceeded under any duty conditions specified such as with the combined varia-
tion of the trip coil voltage, (70-110%), pneumatic/hydraulic pressure and arc ex-
tinguishing medium pressure etc. While furnishing the proof of the total break time
of complete circuit breaker, the Bidders may specificallybring out the effect of
non-simultaneity between contacts within a pole or between poles and show how
it is covered in the guaranteed total break time.
3.3 The values guaranteed shall be supported with the type test reports.
4.1 Contacts
4.1.1 The gap between the open contacts shall be such that it can withstand atleast the
rated phase to ground voltage for 8 hours at zero gauge pressure of SF6 gas due
to the leakage. The breaker should be able to withstand all dielectric stresses im-
posed on it in open condition at lock out pressure continuously (i.e.2 p.u. across
the breaker continuously, for validation of which a power frequency dielectric
with stand test conducted for a duration of at least 15 minutes is acceptable).
4.2 If multibreak interrupters are used, these shall be so designed and augmented that
a uniform voltage distribution is developed across them. Calculations/ test reports
in support of the same shall be furnished. The thermal and voltage withstand of the
Page 4 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
grading elements shall be adequate for the service conditions and duty specified.
4.3 The SF6 Circuit Breaker shall meet the following additional require-
ments:
a) The circuit breaker shall be single pressure type. The design and con-
struction of the circuit breaker shall be such that there is a minimum possibility
of gas leakage and entry of moisture. There should not be any condensa-
tion of SF6 gas on the internal insulating surfaces of the circuit breaker.
d) Each pole shall form an enclosure filled with SF6 gas independent of two
other poles (for 800, 420 & 245 kV CBs) and the SF6 density of each pole
shall be monitored. For CBs of voltage class of 145 kV or less, a common
SF6 scheme/density monitor shall be acceptable.
e) The dial type SF6 density monitor shall be adequately temperature com-
pensated to model the pressure changes due to variations in ambient
temperature within the body of circuit breaker as a whole. The density monitor
shall have graduated scale and shall meet the following requirements:
g) Sufficient SF6 gas including that will be required for gas analysis during
filling shall be provided to fill all the circuit breakers installed.
In addition spare gas shall be supplied in separate unused cylinders as per
requirement specified in Section--- 1.
4.4 Provisions shall be made for attaching an operational analyser to record con-
tact travel, speed and making measurement of operating timings, preinser-
tion timings of closing resisters if used, synchronisation of contacts in one pole.
Page 5 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
a) The SF6 gas shall comply with IEC 60376, 60376A and 60376B and shall
be suitable in all respects for use in the switchgear under the operating
conditions.
b) The high pressure cylinders in which the SF6 gas is shipped and stored
at site shall comply with requirements of the relevant standards and regula-
tions.
c) Test: SF6 gas shall be tested for purity, dew point, air, hydrolysable fluo-
rides and water content as per IEC 60376, 60376A and 60376B and test cer-
tificates shall be furnished to Employer indicating all the tests as per IEC
60376 for each lot of SF6 gas in stipulated copies as indicated in section-3.
Gas bottles should be tested for leakage during receipt at site.
6.0 INSULATORS:
c) All hollow insulators shall conform to IEC-62155. All routine and sample
tests shall be conducted on the hollow column insulators as per these stan-
dards with requirements and procedures modified as under:
iii) Bending load test as a sample test on each lot. iv) Burst
The bidder shall include in his proposal spare parts and maintenance
equipment in accordance with Section-1 alongwith the equipment. Calibration certifi-
cate of each maintenance equipment shall be supplied along with the equipment.
Page 6 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
8.1.1 Circuit breaker shall be operated by pneumatic mechanism (for 400 kV & 800 kV rat-
ings only) or spring charged mechanism or hydraulic mechanism or a combination
of these. The mechanism shall be housed in a weather proof and dust proof control
cabinet as stipulated in Section-3.
8.1.2 The operating mechanism shall be strong, rigid, not subject to rebound.
8.1.3 The mechanism shall be antipumping and trip free (as per IEC definition)
under every method of closing.
8.1.4 The mechanism shall be such that the failure of any auxiliary spring will not prevent
tripping and will not cause trip or closing operation of the power operating de-
vices.
8.1.5 A mechanical indicator shall be provided to show open and close position of the
breaker. It shall be located in a position where it will be visible to a man standing
on the ground level with the mechanism housing closed. An operation counter
shall also be provided in the central control cabinet.
8.1.6 Working parts of the mechanism shall be corrosion resisting material, bear-
ings which require grease shall be equipped with pressure type grease fittings.
Bearing pin, bolts, nuts and other parts shall be adequately pinned or locked to pre-
vent loosening or changing adjustment with repeated operation
of the breaker.
8.1.7 The bidder shall furnish detailed operation and maintenance manual of the
mechanism alongwith the operation manual for the circuit breaker. The instruc-
tion manuals shall contain exploded diagrams with complete storage, handling,
erection, commissioning, troubleshooting, servicing and overhauling instructions.
8.2 Control:
8.2.1 The close and trip circuits shall be designed to permit use of momentary contact
switches and push buttons.
8.2.2 Each breaker shall be provided with two (2) independent tripping circuits, pres-
sure switches and coils each to be fed from separate DC sources and con-
nected to a different set of protective relays.
8.2.3 The breaker shall normally be operated by remote electrical control. Elec-
trical tripping shall be performed by shunt trip coils. However, provisions
shall be made for local electrical control.For this purpose a local/remote selec-
tor switch and close and trip control switch/push buttons shall be provided in the
Breaker central control cabinet.
8.2.4 The trip coils shall be suitable for trip circuit supervision during both open and
close position of breaker. The trip circuit supervision relay would be provided on
relay panels.
Page 7 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
8.2.5 Closing coil and associated circuits shall operate correctly at all values of voltage
between 85% and 110% of the rated voltage.Shunt trip coil and associated cir-
cuits shall operate correctly under all operating conditions of the circuit breaker upto
the rated breaking capacity of the circuit breaker and at all values of supply
voltage between 70% and 110% of rated voltage. However, even at 50% of
rated voltage the breaker shall be able to open. If additional elements are int-
duced in the trip coil circuit their successful
operation and reliability for similar applications on outdoor circuit breakers shall be
clearly brought out in the additional information schedules.
8.2.6 Density Monitor contacts and pressure switch contact shall be suitable for
direct use as permissive in closing and tripping circuits. The density monitor shall be
placed suitably inclined in such a way so that the readings are visible from
ground level with or without using binoculars. Separate contacts have to be used
for each of tripping and closing circuits. If contacts are not suitably rated and mul-
tiplying relays are used then fail safe logic/schemes are to be employed. DC sup-
plies for all auxiliary circuits shall be monitored and provision shall be made for
remote annunciations and operation lockout in case of D.C. failures. Density
monitors are to be so mounted that the contacts do not change on vibration during
operation of circuit Breaker.
8.2.7 The auxiliary switch of the breaker shall be positively driven by the breaker operating
rod.
a) Each pneumatic operated breaker shall be equipped with compressed air system
in accordance with Clause 16.0.
b) The breaker local air receivers shall comply with the requirements under
Clause 16.4 and shall have sufficient capacity for atleast two CO operations
of the breaker at the lowest pressure for auto reclosing duty without refilling.
Page 8 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
breaker under all duty conditions with the air pressure immediately before
operation between 85% and 110% of the rated supply pressure.The
make/break time at this supply pressure shall not exceed the specified
make/break time within any value of trip coil supply voltage as specified.
c) After failure of power supply to the motor one close open operation shall be
possible with the energy contained in the operating mechanism.
e) Closing action of circuit breaker shall compress the opening spring ready
for tripping.
h) The spring operating mechanism shall have adequate energy stored in the
operating spring to close and latch the circuit breaker against the rated
making current and also to provide the required energy for the tripping
mechanism in case the tripping energy is derived from the operating
mechanism.
Page 9 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
b) The hydraulic oil used shall be fully compatible for the specified tempera-
ture range.
c) The oil pressure switch controlling the oil pump and pressure in the high
pressure reservoir shall have adequate number of spare contacts to be used
for continuous monitoring of low pressure, high pressure etc.
d) The mechanism shall be suitable for atleast two close open operations after
failure of AC supply to the motor starting at pressure equal to the lowest
pressure of auto reclose duty plus pressure drop for one close open opera-
tion.
g) All hydraulic joints shall have no oil leakage under the site conditions and joints
shall be tested at factory against oil leakage at a minimum of
1.5 times maximum working pressure.
a) The structure design shall be such that during operation of circuit breaker
vibrations are reduced to minimum.
The circuit breaker terminal pads shall be made up of high quality electrolytic copper
or aluminium and shall be conforming to Australian standard AS-2935 for rated cur-
rent. The terminal pad shall have protective covers which shall
be removed before interconnections.
11.1 All cables to be used by contractor shall be armoured and shall be as per IS –
1554/ IEC-502 (1100 Volts Grade). All cables within & between circuit breaker
poles shall be supplied by the CB manufacturer.
11.2 Only stranded conductor shall be used. Minimum size of the conductor for interpole
control wiring shall be 1.5 sq.mm (Copper).
11.3 The cables shall be with oxygen index Min-29 and temp. index as 250oC as
Page 10 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
12.1 Following is a partial list of some of the major fittings and accessories to be fur-
nished by Contractor in the Central Control cabinet. Number and exact location
of these parts shall be indicated in the bid.
vii) The number of terminals provided shall be adequate enough to wire out all con-
tacts and control circuits plus 24 terminals spare for future use.
xi) Rating and diagram plate in accordance with IEC incorporating year of manu-
facture.
xii) Controlled switching equipments like sensors, timers, relays etc.(as applica-
ble)
c) Pressure gauge, spring loaded safety valve and pressure switch with adjust-
able contacts.
e) Stop, non-return and other control valves, pipings and all accessories upto
breaker mechanism housing.
Page 11 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
a) Drawing, showing contacts in close, arc initiation, full arcing, arc extinction
and open position.
b) The temperature v/s pressure curves for each setting of density monitor along-
with details of density monitor.
e) The effect of non-simultaneity between contacts between poles and also show
how it is covered in the guaranteed total break time.
g) Details & type of filters used in interrupter assembly and also the operat-
ing experience with such filters.
i) The test methods used in controlling the quality of gas used in the circuit
breakers particularly purity and moisture content.
ii) Proposed tests to assess the conditions of the SF6 within a circuit
breaker after a period of service particularly with regard to mois-
ture contents of the gas.
i) Clause deleted
j) The bidders shall furnish along with the bid, curves supported by test data
indicating the opening time under close open operation with combined
variation of trip coil voltage and pneumatic/hydraulic pressure.
l) All duty requirements as applicable to 420 kV, 245 kV & 145 kV CBs specified
under Clause 2.0 of this section shall be provided with the support of adequate
test reports.
m) Field test report or laboratory test report in case of CB meant for reactor switch-
ing duty.
Page 12 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
14.0 TESTS:
14.1 In accordance with the requirements stipulated under Section -3 the circuit breaker
alongwith its operating mechanism shall conform to IEC:62271-100.
14.2 The test reports of the type tests and the following additional type tests shall also be
submitted for Purchaser’s review:
iii) Line charging breaking current for proving parameters as per clause no.
17.9 of this section.
In addition to the mechanical and electrical tests specified by IEC, the follow-
ing tests shall also be performed.
1) Speed curves for each breaker shall be obtained with the help of a suit-
able operation analyser to determine the breaker contact movement during
opening, closing, auto-reclosing and trip free operation under normal as
well as limiting operating conditions (control voltage, pneu-
matic/hydraulic pressure etc.). The tests shall show the speed of contacts
directly at various stages of operation, travel of contacts, opening time,
closing time, shortest time between separation and meeting of contacts
at break make operation etc. This test shall also be performed at site for
Page 13 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
15.1 In case dead tank type circuit breaker is offered, the Bidder shall offer bush-
ing type CTs (whose secondary parameters shall be provided during engineering
stage).
15.2 The enclosure shall be made of either Al/Al Alloy or mild steel (suitably hot dip galva-
nised).
The enclosure shall be designed for the mechanical and thermal loads to
which it is subjected in service. The enclosure shall be manufactured and
tested according to the pressure vessel codes {i.e., latest edition of the ASME code
for pressure vessel - Section VIII of BS-5179, IS4379, IS-7311 (as applicable)
and also shall meet Indian Boiler Regulations}.
The maximum temperature of enclosure with CB breaker carrying full load current
shall not exceed the ambient by more than 20 deg C.
15.3 The enclosure has to be tested as a routine test at 1.5 times the design
pressure for one minute. A bursting pressure test shall be carried out at 5 times
the design pressure as type test on the enclosure.
16.1 The unit compressed air system shall meet the following requirements:
a) The compressed air system shall be provided with necessary piping, pip-
ing accessories, control valves, safety valves, filters, reducing valves,
isolating valves, drain ports, automatic condensate drain valve etc. The
Unit compressed air system shall be provided with suitable antivibration
pads wherever required.
b) The compressors or pumps shall be of the air cooled type and mounted
within the operating mechanism housing or a separate weather-proof and
dust-proof housing.
c) The air receiver shall have stored energy for 2 CO operations of the
breaker at the blocking pressure for auto reclosing duty without refill-
Page 14 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
d) The size of the compressor shall be determined by the bidder. The com-
pressor shall be of sufficient capacity for performing all the operations
above mentioned.
a) The air compressor shall be of air cooled type complete with cylinder lubri-
cation, drive motor etc. The compressor shall be rated for the following
duty:
d) The compressor shall be equipped with a Time totaliser and a Pressure gauge.
Intercooler between compressor stage and after cooler at discharge if any of H.P.
cylinder shall be included in Contractor’s scope. They shall be of air cooled type
and shall be designed as per ASME Code of IEMA Standards. The design pres-
sure on the air side of cooler shall be 1.25 times the working pressure. A corrosion
allowance of 3 mm shall be included for all steel parts.
a) Air receiver shall be designed in accordance with the latest edition of the
ASME Code for Pressure Vessel - Section VIII of BS: 5179. If the air re-
ceiver is not fully hot dip galvanised, it shall be coated on the inside face
with antirust medium and a corrosion allowance of 3.0 mm shall be provided
for shell and dished ends.
b) Connections for air inlet and outlet, drain and relief valves shall be
Page 15 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
d) Air receiver shall be offered with atleast 50% spare capacity, calculated on the
basis of total air requirement for 2 CO operations.
Compressed air used shall be dry and free of dust particles and fully com-
patible with the materials used in the pneumatic operating mechanism. Arrange-
ment for conditioning the compressed air if required shall be provided as
an integral part of air compressor system.
If situation warrants, because of the severe ambient conditions, the supplier may of-
fer centralised compressed air system.
a) The flow capacity of all valves shall be at least 20% greater than the total
compressor capacity.
b) The high pressure pipe and air system shall be such that after one O-0.3 sec-
CO-operation the breaker shall be capable of performing one CO operation
within 3 minutes.
Page 16 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
d) All joints and connections in the piping system shall be brazed or flared
as necessary.
e) All compressed air piping shall be carried out in accordance with BS:
162.
f) Compressed air piping system shall be complete with Saddle clamps to sup-
port the piping system at suitable intervals. Necessary bolts, nuts, pipe fix-
ing clamps etc shall be included in the scope of Contractor.
16.8 Tests:
Page 17 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
(The breaker shall be able to interrupt the rated line charging current with test volt-
age immediately before opening equal to the product of U/ 3 & 1.4 as per IEC:
62271-100).
The above shall be at rated control voltage and rated operating and quenching media
pressures.
A17.15 Trip coil and closing 220 V DC with variation as specified coil volt-
age
A17.17 Rated terminal load As per IEC or as per the value calculated by
Section-3 whichever is higher.
Page 18 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
iii) Opening of PIR contacts a) PIR Contacts should open immediately after
closing of main circuits.
OR
18.1 An indicative list of tests is given below. All routine tests except power frequency
voltage dry withstand test on main circuit breaker shall be repeated on the
completely assembled breaker at site. Pre-commissioning tests, procedures and
formats for circuit breakers, Doc.No.: MR/CF/CB/05/R-2, Dated 01/04/08 under
POWERGRID Document no. D-2-01-03-01-02 will be the reference document.
This document will be available at respective sites and shall be referred by the
supplier. Supplier shall perform any additional test based on specialties of the
items as per the field Q.P./instructions of the equipment Supplier or Powergrid with-
out any extra cost to the BHEL The supplier shall arrange all instruments re-
quired for conducting these tests alongwith calibration certificates and shall fur-
nish the list of instruments to BHEL/POWERGRID for approval.
Page 19 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
(n) Operation check of pressure switches and gas density monitor during gas fill-
ing.
18.2 The supplier shall ensure that erection, testing and commissioning of circuit breaker shall
be carried out under his supervision . The commissioning report shall be signed by the
manufacturers representative, BHEL and Powergrid.
19 Applicable Standards
The circuit breakers shall strictly conform to the following Indian and International stan-
dards as appropriate:
IEC 60056 (1987) Specification for high voltage alternating-current circuit breaker.
Page 20 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
IEC 62271-100 High voltage Switchgear and control gear, HV-AC Circuit
Breaker
IS 13947 (Part 1):1993 Low voltage switchgear and control gear, General rules
IS 13947 (Part 2): 1993 Low voltage switchgear and control gear, Circuit Breakers.
IS 2629: 1985 Recommended practices for hot dip galvanizing on iron and
steel.
IEC 60 (Part 1) 1989 High voltage test techniques, General definition and test re-
quirement.
IEC 60694: 1980/ 1996 Common clauses for high voltage switchgear and controlgear
standards
IEC 71 (Part 1): 1993 Insulation coordination, Definition Principle and rules
CIGRE WG Report No. Switching over-voltage in EHV and UHV systems with
13-02-1973 special reference to closing and re-closing transmission lines
IS 2633 : 1986 Method for Testing Uniformity of coating on zinc coated arti-
cles.
IS 2544 : 1973 Specification for Porcelain Post Insulators for systems with
nominal voltages greater than 1000 volts.
IEC 233 : 1974 Tests on hollow insulators for use in Electrical Equipment.
IS 4379 : 1981 Identification of contents & industrial gas cylinders.
IS 7285 : 1988 Seamless steel cylinders for permanent and high pressure
liquifiable gases.
IEC 427(1989) Synthetic testing of High Voltage alternating current Circuit
Breaker required to be submitted by the specification.
Page 21 of 21
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
SECTION-3
Particular Details
a) Customer Power Grid Corporation of India Limited
a) Altitude above sea Less than Less than Less than Less than
level 1000m 1000m 1000m 1000m
b) Ambient air temp.
50°C 50°C 50°C 50°C
(Max)
c) Special corrosion Yes
conditions No No See note No
below
d) Snow fall Nil Nil Nil Nil
e) Seismic zone As per IS 1893
f) Wind zone As per IS 875 (also see note below)
g) Pollution Severity High High Very High High
Pollution Pollution Pollution Pollution
level level level level
(25mm/kV) (25mm/kV) (31mm/kV) (25mm/kV)
Note:-
Following additional requirements shall be met for Kalivanthapattu substion
extension:
1) All switchgears/ equipments, insulator strings, bushings, BPIs shall be designed for
minimum creepage distance of 31mm/kV instead of 25mm/kV for other three
stations.
2) The rate of zinc coating for galvanized lattice and pipe structures (excluding
foundation bolts and fasteners) shall not be less than 900gm/sq. m instead of
610gm/sq. m for other three stations.
3) Outdoor atmosphere around the substation is highly polluted coupled with coastal
pollution. Suitable paint and corresponding primers etc. as recommended by paint
manufacturer shall be used to withstand the outdoor atmospheric condition.
4) Kalivanthapattu substation falls under high wind zone and basic wind speed shall
___________________________________________________________________
Page 1 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
be considered as 50m/sec.
1.0 GENERAL
f) The Bidder shall clearly indicate in the bid, the specific standards in
___________________________________________________________________
Page 2 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
g) The equipment must be new, of highest grade, the best quality of their
kind, to best engineering practice and latest state of art, and in accordance
with purpose for which they are intended and ensure satisfactory
performance throughout the service life.
h) All similar parts of the equipment shall be made to gauge and shall be
interchangeable with and shall be made of same materials and
workmanship as the corresponding parts of the equipment. Where
feasible, common components, units shall be employed in different pieces
of equipment in order to optimize the spare part stock-up and utilization.
a) The equipment furnished under this specification shall perform all its
functions and operate satisfactorily without showing undue strain, restrike
etc.
b) The equipment shall be able to withstand forces due to wind load, short
circuit, system over voltages, fluctuations, frequency variations etc., all
forces considered together.
a) The support structures should be hot dip galvanised with minimum 610
gram/m2 net of zinc.
4.0 STANDARDS
___________________________________________________________________
Page 3 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
5.1 The furnishing of engineering data by the Contractor shall be in accordance with
the Schedule for each set of equipment as specified in this Technical
Specification and the data furnished under the Schedule of Data Requirements
(DRS). The review of these data by the Employer will cover only general
conformance of the data to the specifications and documents, interfaces with the
equipment provided under the specifications, external connections and of the
dimensions which might affect overall layout. This review by the Employer may
not indicate a thorough review of all dimensions, quantities and details of the
equipment, materials, any devices or items indicated or the accuracy of the
information submitted. This review and/or approval by the Employer shall not be
considered by the Contractor, as limiting any of his responsibilities and liabilities
for mistakes and deviations from the requirements, specified under these
specifications and documents.
5.2 All engineering data submitted by the Contractor after final process including
review and approval by the Employer shall form part of the Contract Document
and the entire works performed under these specifications shall be performed in
strict conformity, unless otherwise explicitly requested by the Employer in Writing.
b) The reports for all type tests and additional type tests as per technical
specification shall be furnished by the Contractor alongwith equipment /
material drawings. The type tests conducted earlier should have either been
conducted in accredited laboratory (accredited based on ISO / IEC Guide 25
/ 17025 or EN 45001 by the national accredition body of the country where
laboratory is located ) or witnessed by the representative(s) of
POWERGRID or Utility. The test reports submitted shall be of the tests
conducted within last 5 (five) years prior to the date of bid opening. In case
the test reports are of the test conducted earlier than 5 (five) years prior to
___________________________________________________________________
Page 4 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
the date of bid opening, the contractor shall repeat these test(s) at no extra
cost to the purchaser.
In the event of any discrepancy in the test reports i.e. any test report
not acceptable due to any design / manufacturing changes (including
substitution of components) or due to non-compliance with the requirement
stipulated in the Technical Specification or any/all additional type tests not
carried out, same shall be carried out without any additional cost implication
to the Purchaser.
c) The Purchaser intends to repeat the type tests and additional type tests on
Capacitors for which test charges shall be payable as per provision of
contract. The price of conducting type tests and additional type tests shall
be included in Bid price and break up of these shall be given in the relevant
schedule of Bid Proposal Sheets. These Type test charges would be
considered in bid evaluation. In case Bidder does not indicate charges for
any of the type tests or does not mention the name of any test in the price
schedules, it will be presumed that the particular test has been offered free
of charge. Further, in case any Bidder indicates that he shall not carry out a
particular test, his offer shall be considered incomplete and shall be liable to
be rejected.
d) Four (4) copies of all test reports shall be submitted for approval before
shipment of equipment. The reports shall indicate clearly the standard
values specified for each test, to facilitate checking of the test reports. Six
(6) bound copies of test reports shall be submitted after approval of test
results.
f) 1 RTF and 8 copies of all drawings for each substation plus 6 copies and
one RTF of each drawing for corporate office shall be furnished after
approval of drgs. 6 copies of instruction/operation manuals for each
substation and corporate centre shall also be furnished after approval of
manuals.
___________________________________________________________________
Page 5 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
NOTE : The contractor may please note that all resubmissions must
incorporate all comments given in the prior submission by the
Employer failing which the submission of documents is likely to be
returned.
i) All exposed ferrous parts shall be hot dip galvanised as per IS : 2633 & IS :
4579.
j) All current making and breaking contact surfaces shall preferably be silver
plated.
l) Each drawing submitted by the Contractor shall be clearly marked with the
name of the Employer, the unit designation, the specifications title, the
specification number and the name of the Project. If standard catalogue
pages are submitted, the applicable items shall be indicated therein. All
titles, notings, markings and writings on the drawing shall be in English.
All the dimensions should be in metric units.
SYSTEM PARAMETERS
___________________________________________________________________
Page 6 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
6.1 The Employer or the Contractor may propose changes in the specification of the
equipment or quality thereof and if the parties agree upon any such changes,
the specification shall be modified accordingly.
___________________________________________________________________
Page 7 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
6.2 The Bidder should however note that changes proposed by him will have to be
supported with applicable type test reports.
6.3 If any such agreed change is such that it affects the price and schedule of
completion, the parties shall agree in writing as to the extent of any change in
the price and/or schedule of completion before the Contractor proceeds with the
change. Following such agreement, the provision thereof, shall be deemed to
have been amended accordingly.
7.1 To ensure that the equipment and services under the scope of this Contract
whether manufactured or performed within the Contractor’s Works or at his Sub-
contractor’s premises or at the Employer’s site or at any other place of Work are in
accordance with the specifications, the Contractor shall adopt suitable quality
assurance programme to control such activities at all points necessary. Such
programme shall be outlined by the Contractor and shall be finally accepted by
the Employer after discussions before the award of Contract. A quality
assurance programme of the contractor shall generally cover the following :
g) Inspection and test procedure both for manufacture and field activities.
n) A quality plan detailing out the specific quality control measures and
procedure adopted for controlling the quality characteristics relevant to
each item of equipment furnished and /or service rendered.
o) System for various field activities i.e. unloading, receipt at site, proper
storage, erection, testing and commissioning of various equipment and
maintenance of records”. In this regard, the Employer has already prepared
Standard Field Quality Plan for Switchyard Civil Works Document Code No.
CC/QA&I/SFQP/SS/03/970905/Rev.1 which is required to be followed for
associated civil works. Field Quality Plan pertaining to receipt, storage,
erection, testing and commissioning shall be mutually discussed and agreed
upon before placement of order.
The Employer or his duly authorised representative reserves the right to
carry out quality audit and quality surveillance of the system and
procedure of the Contractor/his vendor’s quality management and control
activities.
___________________________________________________________________
Page 9 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
8.1 The Employer, his duly authorised representative and/or outside inspection
agency acting on behalf of the Employer shall have at all reasonable times
access to the Contractor’s premises or Works and shall have the power at all
reasonable times to inspect and examine the materials and workmanship of the
Works during its manufacture or erection and if part of the Works is being
manufactured or assembled at other premises or works, the Contractor shall
obtain for the Employer and for his duly authorised representative permission to
inspect as if the works were manufactured or assembled on the Contractor’s own
premises or works. The equipment if found unsatisfactory as to workmanship or
material is liable to be rejected.
8.2 The Employer reserves the right to witness any or all type, acceptance and
routine tests specified for which at least 30 days notice in advance shall be given
by the Contractor. Contractor shall ensure before giving notice for type test
that all drawings and quality plans have been got approved. The equipment shall
be dispatched to site only after approval of Routine and Acceptance test
results and Issuance of Dispatch Clearance in writing by the Employer.
8.3 The Contractor shall give the Employer/Inspector Twenty one (21) days written
notice of any material being ready for testing far each stage of testing as identified
in the approved quality plan as customer inspection point. Such tests shall be to
the Contractor’s account except for the expenses of the Inspector. The
Employer/inspector, unless witnessing of the tests is waived, will attend such
tests within Twenty one (21) days of the date of which the equipment is notified
as being ready for test/inspection, failing which the Contractor may proceed with
the test which shall be deemed to have been made in the Inspector’s presence and
he shall forthwith forward to the Inspector six copies of tests, duly certified.
8.4 The Employer or Inspector shall, within Twenty (21) days from the date of
inspection as defined herein give notice in writing to the Contractor, of any
objection to any drawings and all or any equipment and workmanship which in
his opinion is not in accordance with the Contract. The Contractor shall give
due consideration to such objections and shall either make the modifications that
may be necessary to meet the said objections or shall confirm in writing to the
Employer/Inspector giving reasons therein, that no modifications are necessary to
comply with the Contract.
8.5 When the factory tests have been completed at the Contractor’s or Sub-
Contractor’s works, the Employer/Inspector shall issue a certificate to this effect
within fifteen (15) days after completion of tests but if the tests are not witnessed
___________________________________________________________________
Page 10 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
by the Employer/Inspector, the certificate shall be issued within fifteen (15) days
of receipt of the Contractor’s Test certificate by the Employer/Inspector.
Failure of the Employer/Inspector to issue such a certificate shall not prevent the
Contractor from proceeding with the Works. The completion of these tests or the
issue of the certificate shall not bind the Employer to accept the equipment should,
it, on further tests after erection, be found not to comply with the Contract.
8.6 In all cases where the Contract provides for tests whether at the premises or
works of the Contractor or of any Sub- Contractor, the Contractor except where
otherwise specified shall provide free of charge such items as labour, materials,
electricity, fuel, water, stores, apparatus and instruments as may be reasonably
demanded by the Employer/Inspector or his authorised representative to carry
out effectively such tests of the equipment in accordance with the Contract and
shall give facilities to the Employer/Inspector or to his authorised representative
to accomplish testing.
8.7 The inspection and acceptance by Employer and issue of Inspection Certificate
thereon shall in no way limit the liabilities and responsibilities of the Contractor in
respect of the agreed quality assurance programme forming a part of the
Contract, or if such equipment is found to be defective at a later stage.
8.8 Material Inspection clearance certificate (MICC) shall be issued by the Employer
after inspection of the equipment. Employer may waive off the presence of
Employer’s inspecting engineer. In that case test will be carried out as per
approved QP and test certificate will be furnished by the supplier for approval.
MICC will be issued only after review and approval of the test reports.
8.9 The Employer will have the right of having at his own expenses any other test(s)
of reasonable nature carried out at Contractor’s premises or at site or in any other
place in addition of aforesaid type and routine tests, to satisfy that the material
comply with the specification.
8.10 The Employer reserves the right for getting any field tests conducted on the
completely assembled equipment at site.
b) The work shall be performed under the direction and supervision of the
Engineer. The scope of the duties of the Engineer, pursuant to the
contract, will include but not be limited to the following :
___________________________________________________________________
Page 11 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
iv) Inspect, accept or reject any equipment, material and work under
the Contract ;
10.0 TESTS
10.1 Charging
___________________________________________________________________
Page 12 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
b) Any special equipment, tools and tackles required for the successful
completion of the Commissioning Tests shall be provided by the
Contractor, free of cost.
The provisions outlines in the IS & IEC codes or other international and Indian
approved equivalents shall generally be used as a guide for all the above test
procedures unless otherwise specified in the Technical Specifications.
___________________________________________________________________
Page 13 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
i) Exposed live parts shall be placed high enough above ground to meet
the requirements of electrical and other statutory safety codes.
Bidder shall confirm in their technical offer that all clearances and spacing
as stated above will invariably be provided. Even though phase to earth
clearance under normal conditions will be as above at certain points
where there can be bird faults (i.e. a bird sitting on the earthed metal part
coming in contact with the HT terminal) adequate clearance as required
shall be provided between the HT terminal and nearest grounded metal
part.
13.0 PROTECTION
All coated surfaces shall be protected against abrasion, impact, discoloration and
any other damages. All exposed threaded portions shall be suitably protected
with protecting device. All ends of equipment connections shall be properly
sealed with suitable devices to protect them from damage. The parts which are
likely to get rusted, due to exposure to weather should also be properly treated
and protected in a suitable manner.
14.1 All exposed metallic surfaces subject to corrosion shall be protected by shop
application of suitable coatings. All surfaces which will not be easily accessible
after the shop assembly, shall beforehand be treated and protected for the life
of the equipment. All surfaces shall be thoroughly cleaned of all mill scale, oxide
and other coatings and prepared in the shop. The surfaces that are to be finish
painted after installation or require corrosion protection until installation, shall be
shop painted with at least two coats of primer. Transformers and other
electrical equipment, if included shall be shop finished with one or more coats of
primer and two coats of high grade resistance enamel. The finished colours
shall be selected and specified by the Employer at a later date.
14.2 Shop primer for all steel surfaces which will be exposed to operating temperature
below 95 deg.C. shall be selected by the Contractor, after obtaining specific
approval of the Employer regarding the quality of primer proposed to be applied.
Special high temperature primer shall be used on surfaces exposed to
temperatures higher than 95 deg.C. and such primers shall also be subject to the
approval of the Employer.
14.3 All other steel surfaces which are not to be painted shall be coated with suitable
dust preventive compound subject to the approval of the Employer.
The Contractor shall be responsible for the selection and design of appropriate
equipment to provide the best coordinated performance of the entire system. The
basic design requirements are detailed out in this Technical Specification. The
design of various components, sub-assemblies and assemblies shall be so done
so that it facilitates easy field assembly and maintenance. All the rotating
components shall be so selected that the natural frequency of the complete unit is
not critical at or close to the operating range of the unit.
___________________________________________________________________
Page 15 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
The Contractor will be called upon to attend design co-ordination meetings with
the Employer, other Contractor’s and the Consultants of the Employer during
the period of Contract. The Contractor shall attend such meetings at his own
cost at New Delhi or at mutually agreed venue as and when required and fully
cooperate with such persons and agencies involved during those discussions.
The post insulators shall conform in general to latest IS:2544, IEC-168 and IEC-
815.
CONSTRUCTIONAL FEATURES
18.1 Post type insulators shall consist of a porcelain part permanently secured in a metal
base to be mounted on the supporting structures. They shall be capable of being
mounted upright. They shall be designed to withstand any shocks to which they
may be subjected to by the operation of the associated equipment. Only solid core
insulators will be acceptable.
18.2 Porcelain used shall be homogeneous, free from lamination, cavities and other
flaws or imperfections that might affect the mechanical or dielectric quality and shall
be thoroughly vitrified, tough and impervious to moisture.
18.3 Glazing of the porcelain shall be of uniform brown in colour, free from blisters, burrs
and other similar defects.
18.4 The insulator shall have alternate long and short sheds with aerodynamic profile.
The shed profile shall also meet the requirements of IEC-815 for the specified
pollution level.
18.5 When operating at normal rated voltage there shall be no electric discharge
between conductor and insulators which would cause corrosion or injury to
conductors or insulators by the formation of substance produced by chemical
action.
18.6 The design of the insulators shall be such that stresses due to expansion and
contraction in any part of the insulator shall not lead to deterioration.
18.7 All ferrous parts shall be hot dip galvanised in accordance with the latest edition of
IS:2633 and IS :4579. The zinc used for galvanising shall be grade Zn 99.95 as
per IS:209. The zinc coating shall be uniform, adherent, smooth, reasonably bright,
continuous and free from imperfections such as flux, ash, rust stains, bulky white
deposits and blisters. The metal parts shall not produce any noise generating
corona under the operating conditions.
___________________________________________________________________
Page 16 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
18.8 If corona extinction voltage is to be achieved with the help of corona ring or any
other similar device, the same shall be deemed to be included in the scope of the
Contractor.
18.9 Tests
The post insulators shall be subject to type, acceptance, sample and routine tests
as per IS:2544 and IEC-168.
___________________________________________________________________
Page 17 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
c) Glazing of the porcelain shall be uniform brown in colour, free from blisters,
burrs and similar other defects.
g) All iron parts shall be hot dip galvanised and all joints shall be air tight.
Surface of joints shall be trued up porcelain parts by grinding and metal
parts by machining. Insulator/bushing design shall be such as to ensure a
uniform compressive pressure on the joints.
h) TESTS :
___________________________________________________________________
Page 18 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
d) Control cabinet/panels, junction boxes, marshaling box & terminal box shall
be provided with padlocking arrangements.
___________________________________________________________________
Page 19 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
e) All doors, removable covers and plates shall be gasketed all around with
neoprene gaskets. The neoprene gasket shall be tested in the presence
of Employer’s representative.
f) All sheet steel work shall be degreased, pickled, phosphated and then
applied with two coats of zinc chromate primer and two coats of finishing
synthetic enamel paint. The colour of finishing paint shall be light
admiralty grey in accordance with shade No. 697 of IS : 5 outside and
inside shall be glossy white.
i) Terminal Block :
The terminal shall be such that maximum contact area is achieved when
a cable is terminated. The terminal shall have a locking characteristic to
prevent cable from escaping from the terminal clamp unless it is done
intentionally. The terminal blocks shall be non- disconnecting stud type
equivalent to Elmex type CAT - M4/CST.
The terminal blocks shall have locking arrangement to prevent its escape
from the mounting rails.
The terminal blocks shall be of 650 V grade and shall be rated to carry
continuously the maximum current that is expected to be carried by the
terminals.
The terminal blocks used for CT circuits shall be fully enclosed with
removable covers of transparent, non-deteriorating type plastic material.
Insulting barriers shall be provided between the terminal blocks. These
barriers shall not hinder the operator from carrying out the wiring without
removing the barriers.
The terminals shall be provided with the marking tags for wiring
identification.
All boxes shall be provided with 20 % spare terminals unless otherwise
specified.
j) There shall be a minimum clearance of 250 mm between the first row of
terminal block and the cable gland plate or side of the box. Also the
clearance between two rows of terminal blocks or side of the box shall be a
minimum of 150 mm.
l) Wiring :
All wiring shall be carried out with 650 V grade, stranded copper wires. The
minimum size of the stranded conductor used for internal wiring shall be as
follows :
i)All circuits except CT circuits – 1.5/ 0.75.00.4 sq.mm (depending on the
device current rating)
ii) CT circuits- 4sq mm; minimum no. of strands shall be 3 per conductor.
___________________________________________________________________
Page 21 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
wires and shall not fall off when the wire is disconnected from terminal
blocks.
All control switches shall be of rotary switch type or push button type and
toggle/piano switches shall not be accepted.
m) Earthing :
19.3 MOTORS :
___________________________________________________________________
Page 22 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
b) All castings shall be free from blow holes, surface blisters, cracks
and cavities. All sharp edges and corners shall be blurred and rounded
off.
d) All ferrous parts shall be hot dip galvanised conforming to IS: 2633.
The type test reports or the following tests on auxiliary switch shall be
furnished :
ANNEXURE-A
CORONA AND RADIO INTERFERENCE VOLTAGE (RIV) TEST
___________________________________________________________________
Page 23 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
1. General
Unless otherwise stipulated, all equipment together with its associated connectors, where
applicable, shall be tested for external corona (for 400kV & above) both by observing the
voltage level for the extinction of visible corona under falling power frequency voltage
and by measurement of radio interference voltage (RIV) for
132kV above.
2. Test Levels:
The test voltage levels for measurement of external RIV and for corona extinction voltage
are listed under the relevant clauses of the specification.
___________________________________________________________________
Page 24 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
For recording purpose, modern devices utilizing UV recording methods such as image
intensifier may also be used.
4.1 The test shall be recorded on each photograph. Additional photograph shall be taken
from each camera position with lights on to show the relative position of test object to
facilitate precise corona location from the photographic evidence.
4.2 In addition to photographs of the test object preferably four photographs shall be taken
of the complete test assembly showing relative positions of all the test equipment
and test objects. These four photographs shall be taken from four points equally
spaced around the test arrangement to show its features from all sides. Drawings of
the laboratory and test set up locations shall be provided to indicate camera positions
and angles. The precise location of camera shall be approved by Purchaser’s
inspector, after determining the best camera locations by trial energisation of test object at
a voltage which results in corona.
4.3 The test to determine the visible corona extinction voltage need not be carried out
simultaneously with test to determine RIV levels.
4.4 However, both test shall be carried out with the same test set up and as little time
duration between tests as possible. No modification on treatment of the sample
between tests will be allowed. Simultaneous RIV and visible corona extinction voltage
testing may be permitted at the discretion of Purchaser’s inspector if, in his opinion, it will
not prejudice other test.
5. Test Records:
In addition to the information previously mentioned and the requirements specified as per
CISPR or NEMA 107-1964 the following data shall be included in test report:
a) Background noise before and after test.
b) Detailed procedure of application of test voltage.
c) Measurements of RIV levels expressed in micro volts at each level.
d) Results and observations with regard to location and type of interference
sources detected at each step.
e) Test voltage shall be recorded when measured RIV passes through 100
microvolts in each direction.
f) Onset and extinction of visual corona for each of the four tests required shall be
recorded.
ANNEXURE – B
___________________________________________________________________
Page 25 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420kV CIRCUIT BREAKER
The seismic withstanding test on the complete equipment (for 132kV and above)
shall be carried out alongwith supporting structure.
The Bidder shall arrange to transport the structure from his Contractor’s
premises/POWERGRID sites for the purpose of seismic withstand test only.
The seismic level specified shall be applied at the base of the structure. The
accelerometers shall be provided at the Terminal Pad of the equipment and any other point
as agreed by the Purchaser. The seismic test shall be carried out in all possible
combinations of the equipment. The seismic test procedure shall be furnished for
approval of the Purchaser.
___________________________________________________________________
Page 26 of 26
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
SECTION 4
Bidder shall furnish the technical parameters for each type/voltage class of offered circuit breaker
separately in the below mentioned format.
1. GENERAL
………………………………………
o) Latching Current
Section 4 : Page 1 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
2. GUARANTEED RATINGS
………………………………………
c) (i) Maximum Total break time under any duty
condition for any current upto rated breaking
current with limiting conditions of voltage and
pressure (ms)
………………………………………
ii. Rated break time
………………………………………
d) Closing time (ms)
………………………………………
e) Minimum opening time under any condition with
limiting voltage and pressure (ms)
………………………………………
f) Maximum opening time under any condition with
limiting voltage and pressure (ms)
………………………………………
g) Maximum close open time under any condition
with limiting voltages and pressures (ms)
………………………………………
h) First pole to clear factor
Section 4 : Page 2 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
………………………………………
i) Short time current rating (kA) for 1s
………………………………………
j) Rated operating duty
………………………………………
k) Maximum braking capacity under kilometric faults
and rated TRV characteristic (kAp)
………………………………………
l) Maximum breaking capacity under phase
opposition (kAp)
………………………………………
m) Maximum line charging breaking current with
temporary over voltage upto 1.4 p.u. (A)
………………………………………
n) Maximum over voltage (p.u.) on switching
transformer on no load and corresponding
charging current
r) Pre-insertion resistor
u) Rated voltage & pick up range for trip coil (V) ………………………………………
v) Rated voltage & pick up range for closing coil (V) ………………………………………
Section 4 : Page 3 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
3. DIELECTRIC WITHSTAND OF COMPLETE BREAKER
4. OPERATING MECHANISM
Section 4 : Page 4 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
i. Closing ………………………………………
4.1 Pneumatic operating mechanism
i. Closing ………………………………………
Section 4 : Page 5 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
i. Compressor ………………………………………
o) Safety valve
i. Closing ………………………………………
ii. ………………………………………
iii. ………………………………………
4.2 Hydraulic operating mechanism
Section 4 : Page 6 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
v. 2-CO-operation ………………………………………
v. 2-CO-operation ………………………………………
4.3 Spring charged mechanism
5. TYPE OF BREAKERS
5.1 SF6 Circuit Breakers
Section 4 : Page 7 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
i. Densimeter ………………………………………
p) Densimeter Settings
i. Lockout ………………………………………
Section 4 : Page 8 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
5.2 GENERAL
Section 4 : Page 9 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
7. DETAILED LITERATURE
Section 4 : Page 10 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
Section 4 : Page 11 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
a) Outside ………………………………………
b) Inside ………………………………………
9. Control Wiring
i) Whether aranged
vertical or horizontal
Section 4 : Page 12 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
1. Manufacturer's Name
2. Applicable Standards
3. Type
4. Material of connector
a) Clamp body
c) Spring washers
5. Rated Current
b) Factor of safety
1.Manufacturer's Name
2.Type
3.Applicable Standards
i) Height
Section 4 : Page 13 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
400kV Bay extension at Karaikudi, Pugalur, Kalivanthapattu Rev. 01
and Abhishekpatty substation
Technical Specification for 420 kV CIRCUIT BREAKER
10.Weight (kg)
Section 4 : Page 14 of 14
Bharat Heavy Electricals Limited Doc No. TB-362-316-011
Technical Specification for Circuit Breaker
ANNEXURE - A
SCHEDULE OF TECHNICAL DEVIATIONS
Bidder shall list below all technical deviation clause wise w.r.t. tender specifications:
Any deviation not specifically brought out in this section shall not be admissible for any
commercial implication at later stage. Except to the technical deviations listed in this schedule,
bidder’s offer shall be considered in full compliance to the tender specifications
irrespective of any such deviation indicated / taken elsewhere in the submitted offer.
_____________________________________________________________________________________________________
Page 1 of 1