Abb Eurotrafo l2v2
Abb Eurotrafo l2v2
100 TWh annually.
This corresponds
40 Mt of CO2 emissions.
Are manufacturers allowed to produce transformers with to be non-compliant and thus cannot be delivered to the
lower efficiency than required in the regulation? European market.
Transformers not compliant with the regulation may no longer
be placed in the European market (EU28-countries and Iceland, For the verification measurements conducted by the
Liechtenstein, Norway) as of July 1, 2015. Switzerland is expected surveillance authorities, there is a 5 percent tolerance.
to adopt the same requirements. By then all new transformers However, this tolerance shall not be used by the manufacturer
need to meet the “Tier 1” minimum efficiency requirements of the of importer as an allowed tolerance.
regulation (except the specific special transformers / installations
which are exempted from the regulation). How can I be sure that a transformer is compliant?
All the transformers will have to bear a CE-marking as a sign
However, the regulations do not apply outside Europe. of compliancy with the prevailing directives. An easy way
Therefore, it will be possible for manufacturers in Europe to verify the compliancy is by checking whether the transformer
to produce low efficiency transformers with high energy losses has the appropriate marking on the main rating plate.
for markets that do not have minimum efficiency requirements. The manufacturers will also have a responsibility of making a
duly signed EC Declaration of Conformity document available.
Do I, as a customer, have to specify in my inquiry documents
that the transformer needs to meet the minimum efficiency As a customer, I have been utilizing capitalization values for
requirements? the transformer losses in my inquiry and tender evaluations.
No, this is not necessary. It is primarily the manufacturer’s Should I continue to do so despite the regulation?
responsibility to ensure that the transformers are compliant Yes, you should continue to do so. The regulation is only for
with the regulation. Producing or importing a non-compliant setting a minimum floor level for the transformer efficiency.
transformer into European market is illegal beginning July 1, Total Cost of Ownership method (TCO) is used to minimize
2015. However, especially during the transition period, it may the investment required to obtain the greatest energy savings
be recommended to make reference to the regulation as the for the least cost. This results in the selection of transformers
minimum required efficiency level. whose losses are economically optimal for the given need /
case.
Is there a tolerance for exceeding the MEPS values?
No, there is no tolerance. If the loss values exceed the The regulation will only define a constraint for the losses.
requirements of the regulation, the transformer is considered The manufacturer should provide an offer with optimized loss
Timeline
October 21, 2009 June 11, 2014 July 1, 2015 2017 July 1, 2021
EU adopted revised EU commission adopted Transformers need Mid-term assessment Transformers need
“Ecodesign Directive” a regulation to apply to be compliant with of the regulation to be compliant
(2009/125/EC) for the defined ecodesing the efficiency by the European with the efficiency
Energy-related products – requirements on requirements of „Tier 1” Commission requirements of „Tier 2”
establishing a framework transformers and the – level of the regulation – level of the regulation
to be complemented regulation 548/2014
by “implementing entered into force
measures” (E.Q.
regulations on individual
products and systems)
Markings and documentation Our technologies are used along the entire energy value chain
Beginning July 1, 2015, the following product information in both the utility and the industrial sectors. ABB enables
requirements for transformers not exempted from the scope customers to maximize the value of energy used to improve
of the regulation must be shown on the rating plate in addition their competitiveness while reducing environmental impact
to the EN 60076-1 requirements: and enhancing sustainability. Solutions from ABB can help
– The values and the name of the classes of no load loss and customers achieve:
load loss for transformers ≤ 3150 kVA – Reduced energy costs
– For transformers > 3150 kVA the PEI – Reduced greenhouse gas emissions
– Information on the weight of all the main components – Reduced need for additional generating capacity
of a transformer (including at least the conductor, the nature
of the conductor and the core material) Energy efficiency improvements can also provide additional
– For pole mounted transformers, a visible display plate operational benefits, such as improved productivity, improved
“For pole-mounted operation only” quality, and reduced maintenance burdens.
1LAB 000572
The information contained in this document is for general information purposes
Affolternstrasse, 44
only. While ABB strives to keep the information up to date and correct,
P.O. Box 8131 it makes no representations or warranties of any kind, express or implied,
8050 Zurich, Switzerland about the completeness, accuracy, reliability, suitability or availability with
respect to the information, products, services, or related graphics contained
www.abb.com/transformers in the document for any purpose. Any reliance placed on such information
is therefore strictly at your own risk. ABB reserves the right to discontinue
any product or service at any time.