0% found this document useful (0 votes)
84 views

Terminal Blocks: Distribution Distribution

The document describes distribution terminal blocks for connecting and distributing electrical power. The terminal blocks come in various configurations, including unshrouded, partly shrouded, and fully shrouded terminals providing finger protection. They can be mounted on DIN rails or mounting plates and have options for incoming and outgoing connections from 1 to 33 wires with capacities ranging from 1.5 to 25 mm2. The terminal blocks conform to industry standards and provide insulation, surge protection, and flame retardancy.

Uploaded by

winkyawnaing
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
84 views

Terminal Blocks: Distribution Distribution

The document describes distribution terminal blocks for connecting and distributing electrical power. The terminal blocks come in various configurations, including unshrouded, partly shrouded, and fully shrouded terminals providing finger protection. They can be mounted on DIN rails or mounting plates and have options for incoming and outgoing connections from 1 to 33 wires with capacities ranging from 1.5 to 25 mm2. The terminal blocks conform to industry standards and provide insulation, surge protection, and flame retardancy.

Uploaded by

winkyawnaing
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

distribution terminal blocks distribution terminal blocks

■ Connection protection
Shroud available
IP 2x finger in 3 colours
protection
Captive screw with
0048 03
universal head (cross/
0048 22 flat blade screwdriver)
0048 32
0048 12

Conform to standard IEC 60998-2-1


Supplied ready for use (screws backed-off)

AA
100 A max. - 400 V with 25 mm2 incoming
80 A max. - 400 V with 16 mm2 incoming
Ipk (kA) 60 : Icw (kA) 3·5
Multiple fixing
Pack Cat. Nos. Unshrouded terminal blocks options – see details
Fix using M4 dia. screw from rear of Fixes into side
mounting plate Terminal supports to construct
Incoming capacity Outgoing capacity length (mm)
a distribution block
10 0048 01 1 x 6 to 25 mm2 4 x 1·5 to 16 mm2 45
10 0048 03 1 x 6 to 25 mm2 8 x 1·5 to 16 mm2 73
10 0048 05 1 x 6 to 25 mm2 14 x 1·5 to 16 mm2 122 ■ Use of terminal supports Cat. No. 0048 10
10 0048 06 1 x 6 to 25 mm2 19 x 1·5 to 16 mm2 157
10 0048 07 1 x 6 to 25 mm2 24 x 1·5 to 16 mm2 192 0048 10

Partly shrouded terminals on base


For fixing to 12 x 2 mm rail
Supplied with Duplix markers(1) Terminal
Incoming capacity Outgoing capacity length (mm)
(1) 2
10 0048 20 – 4 x 1·5 to 16 mm 47
10 0048 22(1)(2) – 8 x 1·5 to 16 mm2 75
10 0048 24(1)(2) 1 x 6 to 25 mm 12 x 1·5 to 16 mm2
2
113
10 0048 25(1) 1 x 6 to 25 mm2 16 x 1·5 to 16 mm2 141

Fully shrouded terminals providing Terminal supports Cat. No. 0048 10 fitted with fully shrouded terminals
providing custom made distribution
finger protection IP 2x
Phase Neutral For fixing to 12 x 2 mm rail Terminal
(black) (blue) Incoming capacity Outgoing capacity length (mm)
10 0048 50 0048 40 – 4 x 1·5 to 16 mm2 47 0048 50
10 0048 52(2) 0048 42(2) – 8 x 1·5 to 16 mm2 75 0048 11
10 0048 54(2) 0048 44(2) 1 x 6 to 25 mm2 12 x 1·5 to 16 mm2 113
10 0048 55 0048 45 1 x 6 to 25 mm2 16 x 1·5 to 16 mm2 141
10 0048 56 0048 46 1 x 6 to 25 mm2 21 x 1·5 to 16 mm2 176
10 0048 58 0048 48 2 x 6 to 25 mm2 33 x 1·5 to 16 mm2 276
Earth (green)
10 0048 30 – 4 x 1·5 to 16 mm2 47
10 0048 32(2) – 8 x 1·5 to 16 mm2 75
10 0048 34(2) 1 x 6 to 25 mm2 12 x 1·5 to 16 mm2 113
10 0048 35 1 x 6 to 25 mm2 16 x 1·5 to 16 mm2 141 0048 40
0048 22
10 0048 36 1 x 6 to 25 mm2 21 x 1·5 to 16 mm2 176 0048 34
10 0048 38 2 x 6 to 25 mm2 33 x 1·5 to 16 mm2 276
Fully shrouded terminals for looping
Supplied with Duplix markers(1) Terminal
Incoming capacity Outgoing capacity length (mm) Adaptor support Cat. No. 0048 11 showing method of fixing terminals
10 0048 12(1) 6 x 6 to 25 mm2 – 54
Fully shrouded terminal blocks
3 phase + neutral (3 black + 1 blue)
Terminal
Incoming capacity Outgoing capacity length (mm)
1 0048 14 Neutral x 1
1 x 4 to 25 mm2 12 x 1·5 to 16 mm2
Phase x 3 227
1x1·5 to16 mm2 3 x 1·5 to 16 mm2

Supports for terminal blocks


1 0048 10 Consists of two side supports enabling the
positioning of up to 4 x IP 2x terminal
blocks with the same dimensions to create
a 2, 3 or 4 pole distribution block
5 0048 11 Adaptor support for 4 1
or rail. Provides
a firm fixing allowing IP 2x terminal blocks IP 2x terminals are the ideal
to be side or top mounted on to adaptor companion for Plexo boxes,
10 0048 19 1 metre length of 12 x 2 mm terminal mounting see p. 258
rail - accepts partly and fully shrouded
terminals

(1) Each terminal supplied with :


T
- 2 green Duplix markers ( ) - 2 blue Duplix markers (N) - 2 red Duplix markers (L)
(2) Can be fixed directly to DIN rail without accessory

294
distribution blocks 40 to 160 A distribution blocks 40 to 160 A
modular style - rail or screw fixing modular style - rail or screw fixing

Conform to standard EN 60947-1


Insulation voltage according to EN 60947-1/IEC 60664-1 : 500 V
Impulse (surge) voltage (Uimp) : 8 kV
Degree of pollution : 3 (conductive dust)
Self-extinguishing 960 °C for supports and active parts

■ Dimensions
Double pole 40 - 100 - 125 A
Cat. Nos. Length

23
0048 80 70
0048 81 105

39

49
0048 88 + 0048 45 0048 82 140
0048 84 70
44
0048 85 105
L 50
0048 86 105
0048 88 140
Four pole 40 - 100 - 125 A 0048 79 179

23

88.5
0048 79 86

Connection with or without Starfix ferrules (p. 301) 44


L 50
Pack Cat. Nos. Modular style blocks
Fixing on rail 4or on plate using 2 screws Four pole 160 A
Supplied complete with rear insulated plate and
transparent cover
23

Bar identification possible using CAB 3 markers


When installing under a front plate a blank can also
be clipped on to the front plate
91.5

96.8
Additional IP 2x terminals can be fitted
(see table opposite)
Double pole
Ipk peak Number
Ways Capacity withstand Icw of
per bar rigid flexible current modules 44
(mm2) (mm2) (kA) (kA) L 50
5 0048 81 40 A 11 1·5 to 4 0·75 to 4 20 3 6
2 6 to 16 4 to 10
10 0048 80 100 A 5 2·5 to 10 1·5 to 10 20 4·5 4
2 10 to 25 6 to 16
5 0048 82 125 A 11 2·5 to 10 1·5 to 10 18 4·5 8
2 10 to 25 6 to 16
2 10 to 35 10 to 25
Four pole
Ipk peak Number
Ways Capacity withstand Icw of
per bar rigid flexible current modules
(mm2) (mm2) (kA) (kA)
5 0048 85 40 A 11 1·5 to 4 0·75 to 4 20 3 6
2 6 to 16 4 to 10
10 0048 84 100 A 5 2·5 to 10 1·5 to 10 20 4·5 4
2 10 to 25 6 to 16
5 0048 86 125 A 7 2·5 to 10 1·5 to 10 20 4·5 6
2 10 to 25 6 to 16
2 10 to 35 10 to 25
5 0048 88 125 A 11 2·5 to 10 1·5 to 10 14·5 4·2 8
4 10 to 35 6 to 25(1) 0048 88 + 0048 45

1 0048 79 160 A 1 35 to 70 35 to 70 27 8·4 10


8 2·5 to 10 1·5 to 10 Extend your wiring capability using IP 2x fully shrouded terminals
4 10 to 25 6 to 16 on the following :
2 10 to 35 10 to 25(1) (see p. 294)
Distribution IP 2x Characteristics
block Cat. Nos. Terminal Voltage Rating
(1)
0048 80 0048 32 400 V 80 A
0048 81 0048 34(1) 400 V 40 A
0048 82 0048 35(1) 400 V 100 A
0048 84 0048 42(2) 400 V 80 A
0048 85 0048 44(2) 400 V 40 A
0048 86 0048 44(2) 400 V 100 A
0048 88 0048 45(2) 400 V 100 A
0048 80 + 0048 32
0048 79 0048 45(2) 400 V 100 A

T
(1) (green cover)
(2) Neutral (blue cover)
(1) Supplied with short ferrule

295
distribution blocks 125 to 400 A distribution blocks 125 to 400 A
four pole four pole

■ Extra-flat distribution blocks for lugs


125 A Cat. No. 0374 47 - Ipk peak withstand current 25 kA
Insulation voltage according to EN 60947-1/IEC 60664-1 : 500 V
Self-extinguishing : 960 °C
58 265

61.5
44

59
135
N N
60 289

250 A Cat. No. 0374 00 - Ipk peak withstand current 60 kA


0374 00 0373 08 Insulation voltage according to EN 60947-1/IEC 60664-1 : 1 000 V
Self-extinguishing
0 : 960 °C
5
Pack Cat. Nos. Extra-flat distribution blocks for lugs
125 A screw type (60 mm depth)
1 0374 47 Fix to 2(15 mm high) or by M6 screws
M8
Plate width : 35 mm
Four bars each equipped with :

228
No. of

220

200
140
17·5 mm
Incoming Phase outgoing Neutral outgoing modules
1 x 35 mm2 10 x 16 mm2 17 x 16 mm2 16
M5 M5
Connection possible using connector
Cat. No. 0373 65 (p. 297) 125
75.5 150
250 A (75·5 mm depth)
165
1 0374 00 Fix to mounting plate by M6 screws
Four bars each equipped with : ■ Stepped distribution blocks for lugs
Incoming Outgoing 125 A Cat. No. 0373 95 - Ipk peak withstand current 20 kA
150 mm2 either 1 x 70 mm2 or Insulation voltage according to EN 60947-1/IEC 60664-1 : 600 V
Self-extinguishing : 850 °C
1 x 50 mm2 plus 1 x 35 mm2 or
77
2 x 35 mm2 71 108

or 1 connector Cat. No. 0374 03


6.5
44
83.5

0374 03 Connector for Cat. No. 0374 00 converts


98

1
outgoing terminal to :
• 1 x 1·5 to 6 mm2 Ø 5·3 mm
• 2 x 6 to 16 mm2 Ø 7·5 mm 14.5
122.5
Dimensions : 29 x 29 x 16·8 mm
125/160/250 A Cat. Nos. 0374 30/31/35 - Ipk peak withstand current 35 kA
0
Stepped distribution blocks for lugs Insulation voltage according to EN 60947-1/IEC 60664-1 : 1 000 V
Impulse (surge) voltage (Uimp) : 12 kV
125 A (77 mm depth) Degree of pollution : 3 (conductive dust)
1 0373 95 Fix to 2 (15 mm high) or by M4 screws
Self-extinguishing : 850 °C
A
I
Four 12 x 4 mm bars each equipped with : J
• Five 2 x 10 mm2 claw connectors per bar
(not mounted)
125 A (125 mm depth)
B

1 0374 30 Fix to mounting plate by M6 screws


Four 15 x 4 mm bars each equipped with : C
Incoming Outgoing G
D
1 x 35 mm2 - M8 screw 5 x 25 mm2 - M6 screw E
F
160 A (125 mm depth)
1 0374 31 Fix to mounting plate by M6 screws Dimensions (mm)
Four 18 x 4 mm bars each equipped with : Rating A B C D E F G H I J
Incoming Outgoing
125 A 225 125 110 125 165 189 6·5 117·5 165 108
1 x 70 mm2 - M8 screw 5 x 35 mm2 - M6 screw
160 A 240 125 110 125 165 189 6·5 117·5 180 120
250 A (155 mm depth)
250 A 260 155 110 125 185 209 6·5 147·5 195 120
1 0374 35 Fix to mounting plate by M6 screws
Four 25 x 4 mm bars each equipped with : 400 A(1) Cat. No. 0373 08 - Ipk peak withstand current 42 kA
Incoming Outgoing Insulation voltage according to EN 60947-1/IEC 60664-1 : 1 000 V
1 x 120 mm2 - M10 screw 5 x 50 mm2 - M8 screw Impulse (surge) voltage (Uimp) : 12 kV
Degree of pollution : 3 (conductive dust)
400 A (107 mm depth) Self-extinguishing : 960 °C 4
460
395
1 0373 08 With front insulation sheet 260
300
Four 32 x 5 mm bars equipped with :
Incoming Outgoing
2 x Ø 8·5 mm holes for 21 x M6 holes
107

101

bar/flexible bar for 70 mm2 max cable lugs

2 250 440

(1) It is recommended that the unit is fitted horizontally with a minimum face plate height of 300 mm

296
distribution blocks distribution blocks
for assembly for assembly

c
■ Copper connector bars with threaded holes
Cat. Nos. 0373 88/89 Cat. No. 0374 33/34
990 990

15/18
12
c M6
M5
9 18 18 18 18
9 18 18 18 18

0373 96 0373 98 0374 37 Cat. No. 0374 38 Cat. No. 0374 19


990 1 750

25

32
M6
M6
9 18 18 18 18
0374 33 9 50 50 50 50

Cat. Nos. Size Ithe (A) Ic (A)


Pack Cat. Nos. Insulated supports Current ratings according to
0373 88 12 x 2 110 80 EN 60947-1 :
For making up distribution blocks of varying 0373 89 12 x 4 160 125 • Ith : bars in free air
lengths using bars and connectors below 0374 33 15 x 4 200 160 • Ithe : bars enclosed with
Supplied with insulated screws for mounting 0374 34 18 x 4 245 200 ventilation
optional protective cover (except 0373 98) 0374 38 25 x 4 280 250 • Ic : bars totally enclosed in
Set of 2 insulated 4 pole supports Mounting
0374 19 32 x 5 450 400 a weatherproof enclosure
5 0373 96 For bars 12 x 2 or 12 x 4 mm by claws 0044 16
■ Insulated supports four pole :
supplied or M4
screws not supplied Insulation voltage according to EN 60947-1/IEC 60664-1 :
Single pole supports Cat. No. 0373 96 : 690 V - Impulse voltage (surge) (Uimp) : 8 kV
10 0373 98 For bars 12 x 2 or 12 x 4 mm by M4 screws
Degree of pollution (conductive dust) : 3
10 0374 37 For bars 15 x 4, 18 x 4 or 25 x 4 mm supplied Distance between supports (mm)
Cat. Nos. 0373 96
Bar size 12 x 4 (12 x 2) Cat. No. 0373 96
Copper connector bars In (A) 125 (80)
With threaded holes Peak withstand
current (kA)

14
Threaded Max. 10 400 (200) 83
Size holes thermal Length 15 300 (150)
(mm) Ø mm Pitch rating (A) (mm)
20 200 (125)

70
10 0373 88 12 x 2 M5 18 110 990 25 150 (100)
10 0373 89 12 x 4 M5 18 160 990 30 –
10 0374 33 15 x 4 M6 18 200 990 35 –
10 0374 34 18 x 4 M6 18 245 990
40 –
10 0374 38 25 x 4 M6 18 280 990
4 0374 19 32 x 5 M6 25 450 1 750
■ Insulated supports single pole
Insulation voltage according to EN 60947-1/IEC 60664-1 : 500 V
Connectors Impulse voltage (surge) (Uimp) : 8 kV
Degree of pollution (conductive dust) : 3
Clamp type – For bars with
threaded holes Cat. No. 0373 98 Cat. No. 0374 37
12 x 4 (mm) 6.2
Front view for View from 53
For one or two conductors 12 x 2 mm bar above
100 0373 65 1·5 to 10 mm2 (supplied with
Ø 5 mm screw) 9
2

12.4 4.5
25.5

Cage type – For bare 12 x 4 mm bars


75
Capacity
8.7

100 0373 60 1·5 to 4 mm2 8.7


10 0373 61 6 to 16 mm2 Front view for 25.5
35

10 0373 62 10 to 35 mm2 (supplied with 12 x 4 mm bar


hexagonal 5 mm M6 screw)
6.2 25
4

= =
Clips 17.5 42
12.4
25.5

4
= =
For mounting on rail EN 60715
and 3
15 mm depth
Max. space between 2 supports :
10 0044 16 10 mm width bar size 12 x 2 : 20 cm, 12 x 4 : 25 cm
With threaded Ø 4 mm hole
The distance between supports can be determined using the chart
Select the peak withstand current (kA rating) and the distance
between bars - dimension E (mm) after choosing your bar and support
Distance between supports (mm)
Cat. Nos. 0373 98 0374 37
Bar size 12 x 2/12 x 4 15 x 4/18 x 4/25 x 4
In (A) 80/125 160/200/245
E (mm) 50 75 100 125 50 75 100 125
Peak withstand
current (kA)
10 400 600 800 – 350 600 750 –
15 300 450 600 800 250 400 500 700
20 250 350 450 600 150 225 300 375
25 200 250 300 400 125 150 200 250
30 – – – – 100 125 150 175
35 – – – – – 100 125 150
40 – – – – – – – –

297