Toxic Detector
Toxic Detector
MANS4000TH
i
Model S4000TH
Table of Contents
MODEL S4000TH .......................................................................................................................... I
1.0 INTRODUCTION .................................................................................................................... 4
1.1 Protection for Life .......................................................................................................................4
1.2 Special Warnings .......................................................................................................................4
1.3 System Integrity Verification ......................................................................................................5
3.0 INSTALLATION ...................................................................................................................... 8
3.1 Receipt of Equipment .................................................................................................................8
3.2 Tools Required ...........................................................................................................................9
3.3 Choosing Product Locations ......................................................................................................9
3.3.1 Remote Mounting of the Sensor from the Electronics ................................................10
3.4 Mounting and Wiring ................................................................................................................11
3.5 Terminal Connections ..............................................................................................................13
3.5.1 Terminal Block TB1 – Sensor Connections ................................................................13
3.5.2 Terminal Block TB2 – Power and Signal Connections ...............................................13
3.5.3 DC Power and Ground Connections...........................................................................15
3.5.4 Analog Signal Connections .........................................................................................16
3.5.5 Terminal Block TB3 – Relay Connections ..................................................................16
3.5.6 European Union (EU) Approved Applications.............................................................17
3.5.7 Cable Termination in the Non-hazardous Area ..........................................................17
3.6 Maintaining the X/P Integrity ....................................................................................................18
iii
Model S4000TH
v
Model S4000TH
Table of Figures
Figure 1: S4000TH Outline and Mounting Dimensions, in inches.......................................................................... 1
Figure 2: S4000TH with RGC Outline and Mounting Dimensions, in inches ......................................................... 2
Figure 3: Spring Type Terminal Block Operation ................................................................................................... 2
Figure 4: Screw Type Terminal Block Operation .................................................................................................... 3
Figure 5: Model S4000TH Intelligent Sensor ......................................................................................................... 7
Figure 6: Model S4000TH Intelligent Sensor with RGC ......................................................................................... 8
Figure 7: S4000TH Outline and Mounting Dimensions, in inches........................................................................ 11
Figure 8: S4000TH with RGC Outline and Mounting Dimensions, in inches ....................................................... 12
Figure 9: S4000TH Terminal Block Locations ...................................................................................................... 13
Figure 10: Spring Type Terminal Block Operation ............................................................................................... 14
Figure 11: Screw Type Terminal Block Operation................................................................................................ 14
Figure 12: Wire Strip Length................................................................................................................................. 14
Figure 13: Relay Protection for DC and AC Loads............................................................................................... 17
Figure 14: Relay Reset ......................................................................................................................................... 20
Figure 15: User Menu Structure ........................................................................................................................... 21
Figure 16: Gas Check ........................................................................................................................................... 25
Figure 17: Automatic Calibration Mode ................................................................................................................ 26
Figure 18: Calibration in Progress Mode .............................................................................................................. 26
Figure 19: Calibration Complete Mode ................................................................................................................. 26
Figure 20: Ampoules with Breaker Bottles ........................................................................................................... 28
Figure 21: Portable Purge Calibrator .................................................................................................................... 28
Figure 22: Remote Gas Calibrator (RGC, P/N 80153-1) ...................................................................................... 29
vi
Model S4000TH
Table of Tables
Table 1: TB2 Power and Signal Connections ....................................................................................................... 14
Table 2: Ground or Common Connections ........................................................................................................... 15
Table 3: Power Connections ................................................................................................................................ 15
Table 4: Analog Signal Connections .................................................................................................................... 16
Table 5: Alarm Relay Connections ....................................................................................................................... 16
Table 6: Warn Relay Connections ........................................................................................................................ 16
Table 7: Fault Relay Connections ........................................................................................................................ 16
Table 8: GM Locations.......................................................................................................................................... 34
Table 9: Data Format ............................................................................................................................................ 35
Table 10: Exception Codes .................................................................................................................................. 37
Table 11: Command Register Locations .............................................................................................................. 40
Table 12: Com1 Baud Rate .................................................................................................................................. 45
Table 13: Com1 Data Format ............................................................................................................................... 45
Table 14: Com2 Baud Rate .................................................................................................................................. 45
Table 15: Com2 Data Format ............................................................................................................................... 46
Table 16: Sensor Scale ........................................................................................................................................ 46
Table 17: 24 VDC Cable Lengths ......................................................................................................................... 56
Table 18: Analog Output Cable Lengths .............................................................................................................. 56
Table 19: Sensor Cable Lengths .......................................................................................................................... 56
vii
Model S4000TH
Flat-head screwdriver maximum 3/16 in (5 mm) width for terminal block connections
(included with gas detector).
The outline and mounting dimensions for the Model S4000TH (Figure 1) should be used when
making installation determinations.
Information on Class I Division 1 and Zone 1 wiring methods can be found in the NEC and
CEC.
WARNING: Acetic acid will cause damage to metal components, metal hardware, ceramic
IC’s, etc. If damage results from the use of a sealant that outgases acetic acid
(RTV silicone), the warranty will be void.
1
Model S4000TH
Terminal Connections
The terminal blocks (TB) are located inside the housing and can be accessed by removing the
cover. A label inside of the housing cover provides a diagram of all the terminal connections.
It is recommended that a minimum three-wire shielded cable be used for making the power
and 0-20mA Output connection on TB2 of the S4000TH. It is also recommended that separate
two-wire shielded twisted pair cables be used for making the Modbus connections. The spring
type terminal block accepts 14 AWG to 20 AWG and the screw type terminal block accepts 12
AWG to 18 AWG stranded or solid wire. Each wire should be stripped before wiring the
S4000TH. To connect wiring to the spring type terminal block, insert a screwdriver into the
orange tab and press down (Figure 3), opening the terminal. Insert the wire into the terminal
and release the orange tab, clamping the wire in the terminal. Check the hold of the wire by
gently tugging it to ensure it is locked in.
2
Model S4000TH
To connect wiring to the screw type terminal block, loosen the top screw counter clock wise
(Figure 4). Insert the wire into the terminal and tighten the top screw clockwise.
NOTE: Power must remain disconnected until all other wiring connections have been made.
The maximum distance between the S4000TH and the power supply is 2,000 feet or 610
meters (each cable run should be as short as possible). See Section 9.3.3 for cable length
specifications.
Connect +24 VDC to TB2, position 9. Connect the ground or common wire to TB2, position 8.
For making power and ground connections to display devices, see Figures 2 and 3.
General Monitors recommends that the S4000TH Intelligent Sensor be calibrated 1 hour after
start-up and that the calibration be checked at least every 90 days to ensure system integrity.
The instrument is now ready to operate. Please consult the manual for more information on the
instrument’s many features.
NOTE: If in case of device failure during set-up or testing, please consult Troubleshooting
(Sec. 6.0) or call the factory.
3
Model S4000TH
1.0 Introduction
1.1 Protection for Life
General Monitors’ mission is to benefit society by providing solutions through industry leading
safety products, services, and systems that save lives and protect capital resources from the
dangers of hazardous flames, gases, and vapors.
This manual provides instruction for installing and operating General Monitors’ Model S4000TH
Intelligent Sensor for hydrogen sulfide gas detection. Although the S4000TH is easy to install
and operate, this manual should be read in full and the information contained herein
understood before attempting to place the system in service.
The safety products you have purchased should be handled carefully and installed, calibrated,
and maintained in accordance with the respective product instruction manual. Remember these
products are for your safety.
WARNING: Hydrogen sulfide (H2S) is an extremely toxic gas, and exposure may result in a
loss of consciousness or death.
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSHPERE IS PRESENT.
READ AND UNDERSTAND INSTRUCTION MANUAL BEFORE
OPERATING OR SERVICING. OPEN CIRCUIT BEFORE REMOVING
COVER. POTENTIAL ELECTROSTATIC CHARGING HAZARD – USE
ONLY DAMP CLOTH FOR CLEANING.
NE PAS OUVRIR UN PRÉSENCE D’ATMOSPHÉRE EXPLOSIVE. LIRE
ET COMPRENDRE MANUEL D’INSTRUCTIONS AVANT D’UTILISER OU
SERVICE. OUVRIR LE CIRCUIT AVANT D'ENLEVER LE COUVERCLE.
DANGER POTENTIEL ÉLECTROSTATIQUE DE CHARGE –
UTILISATION UNIQUEMENT UN CHIFFON HUMIDE POUR LE
NETTOYAGE.
SPECIAL CONDITIONS OF SAFE USE PERTAINING TO ATEX/IECEx INSTALLATIONS:
The S4000TH shall not be used as a Safety Related Device as defined by ATEX Directive
94/9/EC,
When alternative detector elements are utilized, they shall only be mounted remotely in a
suitable certified enclosure in accordance with requirements of their respective certificates and
relevant local requirements. The associated cable shall be connected to the Intelligent Gas
Sensors using a suitably certified cable entry device with a ¾” thread form.
The Universal Gas Sensor (P/N 51457-XX) is suitable for use with the following enclosure
types and service temperature ranges that are dependent on the type of cement used in their
construction; therefore, they shall only be used with the enclosure type and where the surface
temperature, at the point of mounting, is as detailed below:
4
Model S4000TH
The Universal Gas Sensor (51457-XX), when tested in accordance with clause 15.4.2.1 of EN
60079-1, produced a maximum surface rise of 26.3 K. This value should be considered when
the component is incorporated into equipment.
The Universal Gas Sensor (51457-XX), utilizing Types 2850FT Cat 11 and 2762 Cat 17 cement
shall only be fitted to enclosures having a maximum reference pressure of 9.6 bar.
Before power-up, verify wiring, terminal connections and stability of mounting for all integral
safety equipment including the following items:
Power supplies
Control modules
Field detection devices
Signaling and output devices
Accessories connected to field and signaling devices
After the initial application of power (and any factory specified warm-up period) to the safety
system, verify that all signal outputs, to and from devices and modules, are within the
manufacturers’ specifications. Initial calibration, calibration checking, or testing should be
performed per the manufacturer’s recommendations and instructions.
Proper system operation should be verified by performing a full, functional test of all component
devices of the safety system, ensuring that the proper levels of alarming occur.
5
Model S4000TH
Verify wiring, terminal connections and stability of mounting for all integral safety equipment
including, the following items:
Power supplies
Control modules
Field detection devices
Signaling and output devices
Accessories connected to field and signaling devices
6
Model S4000TH
A digital display provides indications and display codes that can be viewed through a window in
the cover. A red LED above the digital display signifies an “alarm” condition, while a red LED
below the digital display signifies a “warning” condition. Analog signal (4-20 mA) and relays
provide remote and/or discrete indications of the sensor’s operation. Optional dual redundant
Modbus, HART, or HART and single Modbus provide digital communication.
The S4000TH Intelligent Sensor is rated explosion-proof for use in the following hazardous
areas:
NOTE: The image in Figure 5 is for reference only. See section 9.3 for actual product
specifications.
7
Model S4000TH
NOTE: The image in Figure 6 is for reference only. See section 9.3 for actual product
specifications.
3.0 Installation
3.1 Receipt of Equipment
All equipment shipped by General Monitors is pre-packed in shock absorbing containers, which
provide protection against physical damage (original containers should be kept for future
shipping or storage needs).
Shipping container contents should be carefully removed and checked against the packing list.
If any damage has occurred or there is any discrepancy in the order, please notify General
Monitors as soon as possible.
8
Model S4000TH
All correspondence with General Monitors must specify the equipment part number and serial
number.
Although the factory tests each unit, a complete system checkout is suggested upon initial
installation to ensure system integrity.
WARNING: Only suitably skilled and competent personnel should carry out installation and
maintenance.
WARNING: The S4000TH Intelligent Sensor contains components, which can be damaged by
static electricity. Special care must be taken when wiring the system to ensure that only the
connection points are touched.
Flat-head screwdriver maximum 3/16 in (5 mm) width for terminal block connections
(included with gas detector).
Mount sensor pointing down to prevent water build-up on the sensor head.
Do not place sensor where contaminating substances may coat it.
Although the S4000TH is RFI resistant, do not install sensor in close proximity to radio
transmitters or similar equipment.
Locate the S4000TH where prevailing air currents contain the maximum concentration
of gas.
Locate the S4000TH near possible sources of gas leaks.
Observe the S4000TH’s temperature specification and locate the unit away from
concentrated sources of heat.
Install sensor in an area that is as free from wind, dust, water, shock, and vibration as
possible. See Section 9.3.4 for the environmental specifications of the unit. If dust and
rain cannot be avoided, we recommend the use of our splash guard (GM P/N 10395-1).
9
Model S4000TH
The presence of contaminants in an area does not necessarily preclude the use of a S4000TH
Intelligent Sensor. The feasibility of using a sensor in such areas must be determined by an
analysis of the specific factors in each application, and General Monitors should be consulted
before attempting any such installation.
Sensors used in these areas usually require more frequent calibration checks than normal, and
typically have a shorter life. In many such applications the standard 2-year warranty would not
apply.
IMPORTANT: Each H2S sensor is shipped with a red plastic cap fitted over the sensor head.
Inside the cap is a desiccant. Do not remove this cap until the system is ready
to be powered. Save the cap and re-cap the sensor anytime the system power
is off for more than 1 hour.
WARNING: General Monitors discourages the painting of sensor assemblies. If the sensor
head is painted over, the gas will not be able to diffuse into the sensor. If the
assembly cover is painted over, the digital display cannot be read.
For remote mounting in Canada where the location is classified using the Zone classification
system, the sensors must be mounted in sensor housing B14-020. Only sensors 51457 can
be used in this configuration.
10
Model S4000TH
The outline and mounting dimensions for the S4000TH (Figure 5) should be used when making
installation determinations. A complete list of the mechanical specifications can be found in
Section 9.3.2.
NOTE: For ATEX and IECEx applications, conduit connections must only be made via suitably
certified ATEX (or IECEx as appropriate) conduit stopping boxes.
Information on Class I Division 1 and Zone 1 wiring methods can be found in the NEC or CEC.
11
Model S4000TH
WARNING: Acetic acid will cause damage to metal components, metal hardware, ceramic
IC’s and other parts. If damage results from the use of a sealant that outgases
acetic acid (RTV silicone), the warranty will be void.
Once correctly installed, the S4000TH requires little or no maintenance, other than periodic
calibration checks to ensure system integrity. General Monitors recommends that a schedule
be established and followed.
NOTE: The S4000TH full 2-year warranty will be voided if customer personnel or third parties
damage the S4000TH during repair attempts.
Sensor heads exposed to the elements may require the accessory mounting threads to be
lubricated. Grease must not be used. As an alternate, PTFE (Teflon) tape may be used on
sensor accessory threads.
NOTE: Do not use any material or substance on threads that contact the sensor housing.
The removal of particulate matter from sensor accessories may be done through the use of an
appropriate halogen-free solvent. Water or ethanol are examples of suitable solvents. The
accessories should be thoroughly dried, with compressed air if necessary, before refitting to the
sensor body.
12
Model S4000TH
WARNING: Do not connect +24 VDC to TB1. Damage to the electronics or sensor may
result.
13
Model S4000TH
4 CH2 Modbus -
5 CH2 Modbus +
6 Remote Calibration
7 Relay Reset
8 Ground
9 +24 VDC Power
Table 1: TB2 Power and Signal Connections
It is recommended that a minimum three-wire shielded cable be used for making the power and
0-20mA Output connection on the S4000TH. It is also recommended that separate two-wire
shielded twisted pair cables be used for making the Modbus connections. The spring type
terminal block accepts 14 AWG to 20 AWG and the screw type terminal block accepts 12 AWG
to 18 AWG stranded or solid wire. Each wire should be stripped before wiring the S4000TH. To
connect wiring to the spring type terminal block, insert a screwdriver into the orange tab and
press down (Figure 10). Insert the wire into the terminal and release the orange tab, clamping
the wire in the terminal. Check the hold of the wire by gently tugging it to ensure it is locked in.
To connect wiring to the screw type terminal block, loosen the top screw counterclockwise
(Figure 11). Insert the wire into the terminal and tighten the top screw clockwise. Check the
hold of the wire by gently tugging it to ensure it is locked in.
14
Model S4000TH
NOTE: Up to 12 AWG wire can be used if it is carefully striped. This applies only to a screw
type terminal connection (Figure 8).
TA202A Trip Amplifier Module with a PS002 Power Supply and Relay Module
The following General Monitors’ Modules provide power connections for the S4000TH, but
need a customer supplied DC source:
Since the S4000TH is designed to operate continuously, a power switch is not included, in
order to prevent accidental system shutdown.
NOTE: Power must remain disconnected until all other wiring connections have been made.
For making power and ground connections to display devices see Table 2 and Table 3.
FROM TO
FROM TO
Rear
TB2-9 Rear
CH 1 - 8
“+24 VDC” Pin 28d or 28z
24V
15
Model S4000TH
The 4 to 20 mA signal provides for control room or other locations remote to the S4000TH to
display indications of operation and alarm conditions.
To connect the 4 to 20 mA output signal with another unit, connect the wire into TB2, position 1,
labeled 4-20 mA OUT. For making output signal connections to display devices, refer to the
specific manual for that device (Table 4).
FROM TO
If a device other than a General Monitors readout and relay display module is being used, the
DC ground, COM, of both systems must be connected together.
16
Model S4000TH
NOTE: Fault relay is normally energized. Relay will change state after power up.
WARNING: Contact with PCB components should be avoided to prevent damage by static
electricity. All wire connections are made to the Terminal Blocks.
WARNING: Relay contacts must be protected against transient and over voltage conditions
(Figure 13).
North American Approved Applications - The alarm relay contact ratings are 8 A @ 250 VAC
and 8 A @ 30 VDC resistive max.
European Union (EU) Approved Applications - The alarm relay contact ratings are 8 A, 30 V
RMS/42.4 V peak or 8 A @ 30 VDC resistive max.
17
Model S4000TH
The acceptable limits for explosion-proof housings that are used in Class I hazardous locations
are defined in CSA Standard C22.2 No.30, FM 3615, and EN/IEC 60079-1
Anytime the cover of the S4000TH housing is removed or the cover bolts are loosened, the
flame path between the lid and the housing is affected. If power is to be left on while removing
the cover or loosening the cover bolts on the Model S4000TH, the area must be declassified.
When replacing the cover, the gap between the lid and the housing should be less than 0.0015
inch (0.038 mm). Make sure that the flame path is clear of dirt and debris before replacing the
cover. This can be verified by tightening the cover bolts to a torque setting of 50 inch-pounds or
by using a feeler gauge to ensure the gap between the cover and the housing is less than
0.0015 inch (0.038 mm).
There are four entry holes, one each on the left and right sides, and two on the bottom of the
S4000TH housing. These holes are dedicated for the sensor,and conduit/cable. Each hole is
tapped for ¾” NPT threads. If a particular entry hole is not used, it must be plugged during
operation in the field. The factory installs plugs in the unused entry holes, except one. A red
plastic cap is placed into this remaining hole and must be removed before conduit/cable can be
attached to the housing.
The S4000TH will have the following items placed in the four entry holes, at the factory:
The sensor and aluminum stopping plugs have seven threads. Each of these components is
screwed into the housing using five to seven turns. If any of these components must be
replaced, apply five to seven turns upon replacing the component to ensure the explosion proof
integrity of the device is maintained.
18
Model S4000TH
4.0 Operation
4.1 Start-Up Checklist
Prior to starting the system, verify the following:
Inhibit any external devices, such as trip amplifiers, PLC, or DCS systems.
Verify that the optional settings are set for the desired configuration.
Verify that the unit is properly mounted. Ensure the conduit/cable gland entries are
pointed downward.
Verify that the power supply is connected properly. The S4000TH is powered by +24
VDC (20 to 36 VDC voltage range). The detector will output a low voltage fault (F6) at
18.5 VDC or below.
Make sure the lid is securely installed or the area has been declassified.
4.2 Start-Up
Before applying power to the system for the first time, all wiring connections should be checked
for correctness and the housing cover replaced. Upon first power-up, the sensor may take up to
fifteen minutes to stabilize.
At the initial application of power, the unit tests all LED segments by displaying “88.8”. The
software revision letter is then displayed for a few seconds. When the software revision level
appears, the unit enters Operational Mode and the current gas concentration at the sensor will
be displayed. For details on Calibrating and Gas Checking the unit, see Sections 4.56 and 4.7.
The relays can be reset by using a magnet. To do this, place the magnet over the GM
logo on the cover of the unit. After 3 seconds, the display shows “rSt”. After the LED
displayed this code, remove the magnet. The relays are now reset (Figure 14).
19
Model S4000TH
The relays can be reset via the remote reset input terminals on TB2. Connect a
normally open switch between terminal TB2-7 and TB2-8. Closing the switch
momentarily will reset the relays. General Monitors’ explosion-proof switch, P/N 30051-
1 can be used for this purpose. See Section 9.5 for ordering instructions.
The relays can be reset via the Modbus Interface (Section 8.8.22).
NOTE: Red LED’s above and below the digital display indicate that the alarm and warn relays
are active. Latching relays can only be reset if the gas concentration has fallen below
the respective relay set point.
A flow diagram is included to help the user in understanding the process of reviewing and
changing the available options (Figure 15).
NOTE: If the unit was ordered without relays, HART, or Modbus communications, changing the
relay, HART, or Modbus settings will have no effect on the operation of the unit.
Modbus
Dual Redundant Modbus
Single Modbus and HART
HART
HART is a Master to Slave -One to One communication channel.
RGC
The Remote Gas Calibrator (RGC) is an accessory that allows remote calibration.
With this device, the user turns on and off the calibration gas manually.
20
Model S4000TH
Rm
Hm Hm Hm Hm Hm
“rSt” “- -” “AC” “SE” “SE” Time Out Y Fault
Rm Rm Rm Rm N
Am Set Sensor Range
Reset Enter Calibration “Sr” “Fi”
Enter Gas Check Mode 20,50,100 ppm
Relays Mode
N If Hart Enabled
Gas
Detected? Reset Sensor N
Life? N
Am
“Co” Enable Disable “Fi”
Y Am
Y
Reset Sensor Life If Hart installed
Gas to 100%
Removed?
Y
Am
“Lo” Energized or Latching or “Fi”
Warm Relay Setpoint
De-Energized Non-Latching
Am – Apply magnet
Am
“CH1”
Rm – Remove magnet Modbus Ch. 1 Baud Data “Fi”
Address
Rate Format
N – No
Am
“Fi”
Finished
NOTE: “Co” stands for Calibration Output. When “Co” is enabled and calibration is
successful, the analog output goes from 1.5 mA to 3.2 mA for five seconds, settling
at the desired value of 4 mA. This option is commonly used with the General
Monitors’ HazardWatch system.
21
Model S4000TH
magnet, to return to the next level of the setup menu. When “Fi” is displayed again, apply and
remove the magnet, the unit will go to calibration mode. The display will flash the remaining
sensor life for a few seconds. Ensure that the sensor is seeing clean air during this time. Apply
the calibration gas concentration to the sensor (50% FS of the desired range of H2S. *See
notes section below.). The display will change from “AC” (Automatic Calibration) to “CP”
(Calibration in Progress) indicating that the sensor is responding to the calibration gas. After 3
to 5 minutes, the display will change from “CP” to “CC”, indicating that the calibration is
complete. Remove the gas and wait for the unit to return to normal operation. The unit is now
calibrated and the new span value has been stored in the non-volatile memory (EEPROM). If a
fault occurs during this process, please refer to the notes section below.
NOTE: When the sensor range is changed, the warning and alarm set points are automatically
scaled to the new range. The unit must now be calibrated to the new range (Section
4.7.1). The Sensor Range and the Alarm/Warning set points will remain at the previous
setting if the calibration is aborted, faulted, or the power is cycled before the calibration
is completed.
It is recommended to go back through the SE mode to confirm range and sensor set-
points have been changed correctly. Changing the sensor range will require that the
operator change the concentration H2S previously used for calibrating the unit. It is
necessary to use 50% of the "new" full scale reading when changing the scale, as well
as after the scale is changed during normal calibration maintenance periods (i.e.
10ppm for a 0-20ppm, 25ppm for a 0-50ppm and 50ppm for a 0-100ppm). It is
important to note that changing a units range may require changing the sensor
to match the new sensor range. (-1 sensor for 0-100ppm, -5 sensor for 0-50ppm,
and -9 for 0-20ppm).
Once the operator reaches the calibration mode, the operator will have 12 minutes to complete
a calibration. If the 12 minute timeframe elapses and the calibration is not complete (unit must
return to "0" reading for calibration to be considered complete), the unit's display will show an
"F2" fault. If this occurs while changing the Sensor Range, the operator must start the Sensor
Range process over until the process is completed properly without any faults being shown
throughout the process. If faults continue during this process, please consult the factory
directly.
22
Model S4000TH
First, the energized/de-energized state of the relay is shown by either “En” or “dE” being
displayed, respectively. Apply and remove the magnet until the desired state is displayed.
After a few seconds the latching/non-latching state of the relay is shown by either “La” or “nL”.
Apply and remove the magnet, until the desired state is displayed.
After a few seconds, the current warning relay set point is displayed. Apply and remove the
magnet, until the desired set point is displayed. Once the desired set point value is displayed,
wait 3 seconds and “Fi” will be displayed. Apply and remove the magnet to return to the next
level of the Setup menu. When “Fi” is displayed again, apply and remove the magnet to return
to normal operation.
The default warning relay settings are non-latching, de-energized, 30% FS set point. The
maximum allowable set point is 50 ppm.
NOTE: The warn relay set point cannot be set higher than the alarm relay set point.
First, the energized/de-energized state of the relay is displayed by either “En” or “dE” being
displayed respectively. Apply and remove the magnet, until the desired state is displayed.
After a few seconds the latching/non-latching state of the relay is displayed by either “La” or
“nL”. Apply and remove the magnet until the desired state is displayed.
After a few seconds the current Alarm relay set point is displayed. Apply and remove the
magnet until the desired set point is displayed. Once the desired set point value is shown, wait
3 seconds and “Fi” will be displayed. Apply and remove the magnet to return to the next level of
the setup menu. When “Fi” is displayed again, apply and remove the magnet, to return to
normal operation.
The default Alarm relay settings are: latching, de-energized, 60% FS set point.
NOTE: The alarm relay set point cannot be set lower than the Warning relay set point.
First, the current Baud Rate Modbus Channel 1 is displayed. If another baud rate is to be
selected, apply and remove the magnet until the desired baud rate is displayed. The choices
are 19.2k baud “19.2”, 9600 baud “96”, 4800 baud “48”, or 2400 baud “24”.
23
Model S4000TH
After a few seconds, the current Data Format for Modbus Channel 1 is displayed. If another
data format is to be selected, apply and remove the magnet until the desired data format is
displayed. The choices are: 8-N-1 “8n1”, 8-N-2 “8n2”, 8-E-1 “8E1”, or 8-O-1 “8O1”.
After a few seconds, the current address for Modbus Channel 1 is displayed. Apply and
remove the magnet until the desired address is displayed. Once the desired address is
displayed, wait for 3 seconds and “Fi” will be displayed. Apply and remove the magnet to
return to the next level of the Setup menu. When “Fi” is displayed again, apply and remove the
magnet to return to normal operation.
NOTE: The address can be adjusted from 1 to 247. Channel 1 and Channel 2 addresses may
be the same.
To change the Modbus channel 2 settings, apply the magnet to the GM logo and set the unit in
set up mode. Once “CH2” is displayed, follow the same steps as in section 4.4.5 above.
NOTE: The address can be adjusted from 1 to 247. Channel 1 and Channel 2 addresses may
be the same.
4.5 HART
This option is not shown if HART was not purchased for the S4000TH. When HART is selected
via setup, the Channel 2 setup is not displayed or available. When Channel 2 is changed from
HART to Modbus, the previous settings are used.
To change the HART setting of the S4000TH, apply the magnet to the GM logo on the cover of
the unit until “SE” is displayed, then remove the magnet. This puts the unit into setup mode.
After a few seconds “Hrt” will be displayed. Apply and remove the magnet to enter the HART
setting. The current setting (Enable or Disable) will then be displayed. To change this setting,
apply and remove the magnet repeatedly until the desired setting is displayed. Once it is
displayed, wait three seconds and “Fi” will be displayed. Apply and remove the magnet to
return to the next level of the setup menu. When “Fi” is displayed again, apply and remove the
magnet to return to normal operation.
The S4000TH has a HART option. The HART option allows the user to get management
information and to remotely calibrate the unit. Because HART preserves the 4-20 mA signal, it
enables two-way digital communication to occur without disturbing the integrity of the analog
connection. The DDL is available at the HART foundation’s website
(http://www.hartcomm2.org/index.html). If the S4000TH is ordered with the HART option it is
in the enabled state. The HART function can also be disabled and then Channel 2 can be used
for Modbus.
24
Model S4000TH
The S4000TH HART configuration is compatible with the Emerson 375 Field Communicator
and AMS Aware. http://www.emersonprocess.com/ http://www.emersonprocess.com/ams/
NOTE: If HART is enabled, the current may be different. See HART analog output selection
chart.
When the reading has stabilized and the test is complete, remove the gas and the unit will
return to normal operation, when the concentration drops below 5% full-scale.
If, after the reading has stabilized, the sensor is to be calibrated, simply apply the magnet to the
GM logo on the housing cover and the unit will enter Calibration Mode.
Gas Check Mode can be aborted if gas has not been applied to the sensor. Simply reapply the
magnet to the GM logo on the cover and the unit will return to normal operation.
NOTE: The test gas concentration must be at least 10% full-scale before the unit will complete
the gas check sequence. If the S4000TH is placed in the gas check mode and no gas
is applied for twelve minutes, the unit will revert to a Fault condition. Re-applying the
magnet over the GM logo will return the unit to normal operation.
4.7 Calibration
General Monitors recommends that the S4000TH Intelligent Sensor be calibrated 1 hour after
start-up, and again 24 hours after initial start-up, and that the calibration be checked at least
every 90 days to ensure system integrity of this life protecting equipment.
The above statement is not intended to discourage the customer from checking calibration
more frequently. Frequent calibration checks are recommended for environments that have
25
Model S4000TH
problems, such as mud collecting on the sensor head, sensors accidentally being painted over,
etc.
Entering Calibration Mode automatically disables the alarm circuits by sending a 1.5 mA output
signal and disabling the warn and alarm relays, if present. This will also prevent activation of
the remote relay contacts when using a General Monitors readout/relay display module with the
Model S4000TH. Please see section 9.3.3 for more information on the analog output values.
To enter Calibration Mode, place the magnet over the GM logo on the cover of the unit (Figure
5) and hold it there until “AC” (Figure 17) appears on the display (about 10 seconds). The
display will flash the remaining sensor life (Section 4.7.3) for a few seconds. Ensure that the
sensor is seeing clean air during this time.
Apply the calibration gas concentration to the sensor (50% FS of the desired range of H2S).
The display will change from “AC” (Automatic Calibration) to “CP” (Calibration in Progress)
indicating that the sensor is responding to the calibration gas (Figure 18).
After 3 to 5 minutes, the display will change from “CP” to “CC” indicating that the calibration is
complete. (Figure 19).
Remove the gas and wait for the unit to return to normal operation. Once the gas concentration
decreases, the display will read a few percent parts per million and then will reach “0.”
26
Model S4000TH
The unit is now calibrated and the new span value has been stored in the non-volatile memory
(EEPROM).
NOTE: The sensor life figure displayed is that calculated on completion of the last calibration.
To determine the current sensor life, calibrate unit and then repeat steps 1 and 2.
NOTE: Once gas has been applied, it is not possible to abort a calibration.
If the S4000TH is placed in the Calibration Mode and no gas is applied for 12 minutes, the unit
reverts to a Fault (F2) condition. Re-applying the magnet over the GM logo returns the unit to
operational mode with the previous calibration values unchanged.
NOTE: Remaining sensor life is an estimate of sensor degradation derived from sensor
sensitivity. Because sensor sensitivity is affected by factors other than the natural
sensor degradation, users must establish their own reference by resetting sensor life
whenever these factors are at play. Some examples of these factors are new sensor
installations, sensor replacement, change of the target gas, and changes in the access
of gas to the sensor (produced by the TGA, RGC, or splash guard). If sensor life is not
reset, the remaining sensor life indicator will no longer reflect the true state of the
sensor.
27
Model S4000TH
50% FS of H2S of the sensor range. Follow the calibration procedure in Section 4.7. When the
display indicates “AC”, break the ampoule by turning the thumbscrew on the side of the breaker
bottle clockwise. The display will change to “CP” indicating that the sensor is seeing the gas.
When the display reads “CC”, the calibration is complete. Remove the breaker bottle and allow
the sensor to see clean air. It will return to normal operation once the gas at the sensor is below
5% of full-scale. See Section 9.5 for available equipment.
NOTE: Do not store the cylinder with the regulator fully engaged in the cylinder valve.
To calibrate, make sure the portable purge calibrator contains a gas concentration equivalent to
50% of full-scale for the unit that is going to be calibrated. Ensure that the sensor is seeing
clean air. If it is suspected that hydrogen sulfide gas is present, it will be necessary to purge the
sensor environment with clean air.
28
Model S4000TH
Place the gas cup over the sensor and initiate the calibration sequence, by placing the magnet
over the GM logo on the cover of the unit. When the letters “AC” appear in the display window,
remove the magnet and apply the calibration gas (50% of full-scale) by opening the valve on
the cylinder. When the sensor begins to see the gas, the display will change from “AC” to “CP”
to indicate “Calibration in Progress”. When the calibration sequence is complete, the display will
change from “CP” to “CC” to indicate “Calibration Complete”.
Remove the gas by closing the valve on the cylinder, and remove the cup allowing the sensor
to see clean air. The display will change from “CC” to indicate a few parts per million (ppm) and
then drop to “0”. The unit is now calibrated and the new values have been stored in the
EEPROM (non-volatile memory). See Section 9.5 for available equipment.
29
Model S4000TH
5.0 Maintenance
5.1 General Maintenance
WARNING: Disconnect or inhibit external devices such as trip amplifiers, PLC’s, or DCS
systems before performing any maintenance.
European Union (EU) Approved Applications: The following grease compound is recommended
for use: PBC Polybutylcuprysil, (or equivalent), which has BASEEFA Health & Safety Executive
Component Approval No. 1051U for use as a jointing compound on flameproof electrical
enclosures. This is available from General Monitors.
The neoprene rubber gasket should also be lubricated with Type P80 lubricant, available from
General Monitors (P/N 610-010).
5.2 Storage
The S4000TH Intelligent Sensor should be stored in a clean, dry area and within the
temperature and humidity ranges quoted in the Appendix under Environmental Specifications.
Insert red dust caps into any vacant cable entry holes. See section 9.3.4.
30
Model S4000TH
6.0 Troubleshooting
CAUTION: Component level repair must be undertaken either by General Monitors’ personnel,
or by competent authorized service engineers. SMT PCB repair shall only be
performed at a General Monitors’ facility. Failure to comply with this requirement
will invalidate the warranty.
Be sure to inhibit or disconnect external alarm wiring before making any check, which might
send the unit into alarm.
There are nine fault conditions that are monitored by the microprocessor as follows:
ACTION - Remove gas, if present. Apply magnet to GM logo on the cover to clear fault. Re-
calibrate, if necessary.
ACTION - The unit must be returned to the factory or authorized service center for repair.
ACTION - Check the integrity of all sensor connections, and ensure that the cable from the
S4000TH to the remote sensor is not damaged. If all sensor leads are connected
properly, attempt to re-calibrate the unit. If calibration fails, replace the sensor and
re-calibrate.
NOTE: Anytime a sensor is replaced, the unit should be disconnected from all alarms as the
unit may go upscale upon power-up.
31
Model S4000TH
If this does not solve the problem the internal sensor amplifier has a defective part. The unit
must be returned for service.
ACTION - Check the integrity of all sensor connections and ensure that the cable from the
S4000TH to the remote sensor is not damaged. If this does not correct the problem,
replace the sensor and recalibrate.
NOTE: When the black lead is accidentally shorted to +24 Volts, the S4000TH delays coming
out of fault to allow parts to cool down.
ACTION - Ensure that the supply voltage is at least +20 VDC at the S4000TH.
NOTE: With long supply leads, a considerable voltage drop may occur due to the electrical
resistance of the leads. The maximum cable resistance, which the S4000TH can
tolerate, is dependent on the supply voltage.
ACTION - The unit must be returned to the factory or authorized service center for repair.
32
Model S4000TH
ACTION - Exit setup mode. Enter setup mode again to change any user selectable options, if
necessary.
ACTION - Place the magnet over the GM logo on the cover to return the unit to normal
operation.
NOTE: Anytime a sensor is replaced, the unit should be disconnected from all alarms, as the
unit may go upscale upon power-up.
ACTION – Check the wiring on the remote reset and remote calibrate switches. Once the short
circuit is cleared, the unit will return to normal operation. If the magnetic switch is shorted, the
unit must be returned to the factory or to an authorized service center for service.
ACTION - The unit must be returned to the factory for service. A possible error is that internal
voltages are not at their proper values. Different options will have different internal
errors.
33
Model S4000TH
IRELAND
Ballybrit Business Park
Galway
Republic of Ireland, H91 H6P2 Phone: +353-91-751175
SINGAPORE
No. 2 Kallang Pudding Rd.
#09-16 Mactech Building
Singapore 349307 Phone: +65-6-748-3488
MIDDLE EAST
PO Box 54910
Dubai Airport Free Zone
United Arab Emirates Phone: +971-4294 3640
Table 8: GM Locations
34
Model S4000TH
*NOTE: Address 0 is reserved for broadcast mode and will not be supported at this time.
35
Model S4000TH
*NOTE: Address 0 is reserved for broadcast mode and will not be supported at this time.
Function Code 06 (Preset Single Register) is used to write a command to the slave unit.
If the S4000TH does not receive the query due to a communications error, then no
response is returned from the S4000TH and the master device eventually processes a
timeout condition for the query.
If the S4000TH receives the query, but detects a communication error (CRC, etc.), then
no response is returned from the S4000TH and the master device eventually
processes a timeout condition for the query.
36
Model S4000TH
If the S4000TH receives the query without a communications error, but cannot process
the response to the master within the master’s timeout setting, then no response is
returned from the S4000TH. The master device eventually processes a timeout
condition for the query. In order to prevent this condition from occurring, the maximum
response time for the S4000TH is 200 milliseconds. Therefore, the master’s timeout
setting should be set to 200 milliseconds or greater.
If the S4000TH receives the query without a communications error, but cannot process
it due to reading or writing to a non-existent S4000TH command register, then the
S4000TH returns an exception response message informing the master of the error.
The exception response message (ref. No. 4 above) has two fields that differentiate it from a
normal response:
Byte Modbus Range Referenced to S4000TH
1st Slave Address 1-247* (Decimal) S4000TH ID (Address)
2nd Function Code 83 or 86 (Hex) MSB is set with Function Code
3rd Exception Code 01 - 06 (Hex) Appropriate Exception Code (See Below)
4th CRC Lo 00-FF (Hex) CRC Lo Byte
5th CRC Hi 00-FF (Hex) CRC Hi Byte
8.6.2 Exception Code
Exception Code Field: In a normal response, the S4000TH returns data and status in the data
field, which was requested in the query from the master. In an exception response, the
S4000TH returns an exception code in the data field, which describes the S4000TH condition
that caused the exception. Below is a list of exception codes that are supported by the
S4000TH:
Code Name Description
The function code received in the query is not an
01 Illegal Function
allowable action for the S4000TH
The data address received in the query is not an
02 Illegal Data Address
allowable address for the S4000TH.
A value contained in the query data field is not an
03 Illegal Data Value
allowable value for the S4000TH.
An unrecoverable error occurred while the S4000TH
04 Slave Device Failure
was attempting to perform the requested action.
The S4000TH has accepted the request and is
processing it, but a long duration of time will be
05 Acknowledge
required to do so. This response is returned to prevent
a timeout error from occurring in the master.
The S4000TH is engaged in processing a long-
06 Device Busy duration program command. The master should
retransmit the message later when the slave is free.
Table 10: Exception Codes
37
Model S4000TH
38
Model S4000TH
39
Model S4000TH
Address Address
Ch2 Bus Activity Bus Activity Rate in % of This Decimal R 0071 40114
Rate % Addressed Node vs. Other
Addressed Nodes
Ch2 Function Total # of Function Code Value 16-Bit R 0072 40115
Code Errors Errors
Ch2 Starting Total # of Starting Address Value 16-Bit R 0073 40116
Addr Errors Errors
Ch2 No of Total # of Register Errors Value 16-Bit R 0074 40117
Register Errors
Ch2 CRC errors Value 16-Bit R 0075 40118
Ch2 CRC errors Value 16-Bit R 0076 40119
Ch2 Parity Total parity errors Value 16-Bit R 0077 40120
Errors
Ch2 Overrun Total overrun errors Value 16-Bit R 0078 40121
errors
Ch2 Framing Total Framing errors Value 16-Bit R 0079 40122
errors
Ch2 Software Total Ch 2 Software request Value 16-Bit R 007A 40123
Errors errors
Not used Not used 007B 40124
Ch2 Clear errors Ch2 Clear Hardware errors Bit 0 R/W 007C 40125
Ch2 Clear errors Ch2 Clear Software errors Bit 0 R/W 007D 40126
Not used Not used 007E 40127
Table 11: Command Register Locations
A write command changes the mode to the requested mode. A data value of 08 starts
calibration mode if the unit is in the run mode. It also goes from cal check to cal mode.
A calibrate command returns an exception code 01 (Acknowledge 05). The operation will take
a long time to complete.
40
Model S4000TH
41
Model S4000TH
42
Model S4000TH
digit (MID) and the least significant digit (LSD) in ASCII. The upper word represents the MID
and the lower word represents the LSD.
DP_LSD 0x01
DP_MID 0x02
DP_MSD 0x04
WRN_LED 0x08
ALM_LED 0x10
8.8.12 Serial Number (0BH/0CH)
The serial number is a 32-bit word but the value is only 23 bits long. The upper bits are
always zero. This is done to keep the same serial number as the HART serial number.
Address 0x0C contains the lower part of the number and address 0X0B contains the upper
part.
NOTE: The maximum alarm setting for the S4000TH is 60% FS..
A “1” in the 9th bit position means the output is latching, a “0” means it is non-latching. A “1” in
the 8th bit position means the output is normally energized a “0” means it is normally de-
energized. The alarm set point cannot be set below the warn set point.
43
Model S4000TH
NOTE: The maximum alarm setting for the S4000TH is 60% FS.
A “1” in the 9th bit position means the output is latching, a “0” means it is non-latching. A “1” in
the 8th bit position means the output is normally energized a “0” means it is normally de-
energized. The warn set point cannot be set above the alarm set point.
Factory default is 30% FS, non-latching, de-energized. The maximum allowable set
point is 50 ppm.
44
Model S4000TH
Exception: If the baud rate is not in range, an illegal data value (03) is returned.
Exception: If the data format is not in range, an illegal data value (03) is returned.
Exception: If the address is not in range an illegal data value (03) is returned.
Exception: If the baud rate is not in range an illegal data value (03) is returned.
45
Model S4000TH
Exception: If the data format is not in range an illegal data value (03) is returned.
0x01 enables this option, 0x00 disables this option, similar to the write.
46
Model S4000TH
Code Results
0 Normal
1 Constant ones
2 Constant zeros
8.9.2 Abort Calibration (1Fh)
Sending a “1” causes a calibration or calibration abort.
A read indicates the number of starting address errors that occurred in the slave device. When
the counter for these errors reaches 255, it rolls over to zero and begins counting again.
47
Model S4000TH
Run 4 to 20 mA 4 to 20 mA
Faults
Whenever the fault word changes, the time is recorded.
Time of fault is saved.
The quantity of faults is saved in a counter.
When the fault is removed, it is not saved and the counter is not incremented.
A fault event is logged for every 30 seconds recorded.
There are a total of ten event time stamps stored.
Warning
48
Model S4000TH
The time the gas level reaches the warning level is recorded. Each time this happens a counter
is incremented. The end of the event is when the gas goes below 5%.The counter is also
saved. There are a total of ten event time stamps stored.
Alarm
The time where the gas level reaches the alarm level is recorded. Each time this happens a
counter is incremented. The end of the event is when the gas goes below 5%.The counter is
also saved. There are a total of ten event time stamps stored.
Calibration
The time a successful zero and calibration occurs is saved in the event log. A counter is
increment for each successful calibration. If the unit fails to zero or calibrate, the event is not
recorded. If the calibration is aborted the event is also not recorded. Note the zero and
calibration are one operation in the S4000TH. There are a total of ten event time stamps
stored.
Maintenance
The time a Check Calibration occurs is saved in the maintenance event log. Each successful
calibration increments the maintenance counter. There are a total of 10 event time stamps
stored.
Setting structure clock
See table below.
Event Logging Registry Table
Address
Parameter Function Data Type Data range Access
(hex)
30 Seconds Time Hi Seconds Time Hi Numeric value 0 – 65535 Timer Sec
31 Seconds Time Seconds Time Numeric value 0 – 65535 Timer Sec
Low
32 Real Time Clock Read/Set year and 2 Numeric Values 0-99 year, Timer Struct
Year, Month month of RTC 1 – 12 month
33 Real Time Clock Read/Set day and hour 2 Numeric Values 1 – 31 day,
Day, Hour of RTC 0 – 23 hour
34 Real Time Clock Read/Set minutes and 2 Numeric Values 0 – 59 minute, Timer Struct
Minute, Second seconds of RTC 0 – 59 second
35 Power Cycle Flag Read Power Cycle Numeric Value 1 – Time Not Flag
Flag. Reset;
0 – Time Was
Reset
36 Event Index Event index of Logged Numeric value 0-9 Index
Event
37 Warn Seconds Time Hi for Numeric value 0 – 65535 Warn
Seconds Time Hi warning event log
entries
38 Seconds Time Seconds Time Low for Numeric value 0 – 65535 Warn
Low warning event log
entries
39 Structure time Hi Hi byte – year, low byte Numeric value 0 – 65535 Warn
– month for warning
Address
Parameter Function Data Type Data range Access
(hex)
49
Model S4000TH
3A Structure time Hi byte – day, low byte Numeric value 0 – 65535 Warn
Mid – hour warning event
log entries
3B Structure time Hi byte – min, low byte Numeric value 0 – 65535 Warn
Low – sec for warning event
log entries
3C Reserved Reserved Numeric value 0
3D Reserved Reserved Numeric value 0
3E Warn Warning Event Count Numeric value 0 – 65535 Warn
Event Count
3F Alarm Seconds Time Hi for Numeric value 0 – 65535 Alarm
Seconds Time Hi alarm event log entries
40 Seconds Time Seconds Time Low for Numeric value 0 – 65535 Alarm
Low alarm event log entries
41 Structure time Hi Hi byte – year, low byte Numeric value 0 – 65535 Alarm
– month for alarm event
log entries
42 Structure time Hi byte – day, low byte Numeric value 0 – 65535 Alarm
Mid – hour alarm event log
entries
43 Structure time Hi byte – min, low byte Numeric value 0 – 65535 Alarm
44Low – sec for alarm event
log entries
44 Reserved Reserved Numeric value 0
45 Reserved Reserved Numeric value 0
46 Alarm Alarm Event Count Numeric value 0 – 65535 Alarm
Event Count
47 Fault Seconds Time Hi for Numeric value 0 – 65535 Fault
Seconds Time Hi fault event log entries
48 Seconds Time Seconds Time Low for Numeric value 0 – 65535 Fault
Low fault event log entries
49 Structure time Hi Hi byte – year, low byte Numeric value 0 – 65535 Fault
– month for fault event
log entries
4A Structure time Hi byte – day, low byte Numeric value 0 – 65535 Fault
Mid – hour alarm event log
entries
4B Structure time Hi byte – min, low byte Numeric value 0 – 65535 Fault
Low – sec for fault event log
entries
4C Fault code Fault code. Same code Numeric value 0 – 65535 Fault
as register 2
4D Reserved Reserved Numeric value 0
4E Fault Fault Event Count Numeric value 0 – 65535 Fault
Event Count
4F Maintenance Seconds Time Hi for Numeric value 0 – 65535 Maintenance
Seconds Time Hi lamp test event log
entries
Address
Parameter Function Data Type Data range Access
(hex)
Seconds Time Low for
50
Model S4000TH
50 Seconds Time lamp test event log Numeric value 0 – 65535 Maintenance
Low entries
51 Structure time Hi Hi byte – year, low byte Numeric value 0 – 65535 Maintenance
– month for lamp test
event log entries
52 Structure time Hi byte – day, low byte Numeric value 0 – 65535 Maintenance
Mid – hour lamp test event
log entries
53 Structure time Hi byte – min, low byte Numeric value 0 – 65535 Maintenance
Low – sec for lamp test
event log entries
54 Maintenance Cal check Numeric value 0 Maintenance
code
55 Reserved Reserved Numeric value 0
56 Maintenance Maintenance Count Numeric value 0 – 65535 Maintenance
Count
57 Calibrate Seconds Time Hi for Numeric value 0 – 65535 Calibrate
Seconds Time Hi lamp test event log
entries
58 Seconds Time Seconds Time Low for Numeric value 0 – 65535 Calibrate
Low lamp test event log
entries
59 Structure time Hi Hi byte – year, low byte Numeric value 0 – 65535 Calibrate
– month for lamp test
event log entries
5A Structure time Hi byte – day, low byte Numeric value 0 – 65535 Calibrate
Mid – hour lamp test event
log entries
5B Structure time Hi byte – min, low byte Numeric value 0 – 65535 Calibrate
Low – sec for lamp test
event log entries
5C Calibrate code Cal Numeric value 0 Calibrate
5D Reserved Reserved Numeric value 0
5E Calibrate Calibrate Numeric value 0 – 65535 Calibrate
Count Count
5F Reset Event Reset Event Counters Numeric value 1 Reset
Counters
51
Model S4000TH
52
Model S4000TH
53
Model S4000TH
9.0 Appendix
9.1 Warranty
General Monitors warrants the S4000TH to be free from defects in workmanship or material
under normal use and service within two years from the date of shipment.
General Monitors will repair or replace without charge any such equipment found to be
defective during the warranty period. Full determination of the nature of, and responsibility for,
defective or damaged equipment will be made by General Monitors’ personnel.
All warranties are contingent upon proper use in the application for which the product was
intended and does not cover products which have been modified or repaired without General
Monitors’ approval, or which have been subjected to neglect, accident, improper installation or
application, or on which the original identification marks have been removed or altered.
Except for the express warranty stated above, General Monitors disclaims all warranties with
regard to the products sold, including all implied warranties of merchantability and fitness and
the express warranties stated herein are in lieu of all obligations or liabilities on the part of
General Monitors for damages including, but not limited to, consequential damages arising out
of, or in connection with, the performance of the product.
The change in resistance is converted to a change in voltage, and amplified by the input circuit.
This amplified signal is fed to an Analog to Digital (A/D) Converter, converted to a digital signal
and sent to the microprocessor to be processed. The process of H2S adsorbing onto the MOS
film is most effective at an elevated temperature. On the outer edge of the substrate is a heater
ring. The temperature of this heater ring is measured with a thermistor, and kept constant by a
circuit located inside the body of the sensor.
As H2S adsorbs onto the film, electrons move more freely from one electrode to the other. This
is represented as a decrease in resistance. The process of H2S adsorbing onto the MOS film is
completely reversible. As the concentration of H2S decreases (H2S desorbs), the resistance
between the electrodes will increase.
54
Model S4000TH
9.3 Specifications
9.3.1 System Specifications
Sensor Type: Continuous diffusion, adsorption type metal oxide semiconductor
(MOS)
Sensor Life: 3 to 5 years typical
Repeatability: +2 ppm or 10% of the applied gas, whichever is greater
Long Term Drift: ±2 ppm or 10% of reading, whichever value provides the wider
tolerance (as defined per ISA-92.0.01)
Response Time T50 < 14 seconds (screen); T50 < 30 seconds (sintered)
(Typical): with full scale gas applied according to ISA 92.0.01
Measuring Ranges: 0-20 ppm, 0-50 ppm, 0-100 ppm
Modes: Calibration, gas check, setup
Approvals: CSA/FM: Class I, Division 1, Groups B, C, D T6; Tamb = -40°C to
+60°C (FM); -40°C to +75°C (CSA)
CSA: Ex db IIB + H2 T4 Gb (Tamb = -40°C to +70°C)
Ex tb IIIC T135°C Db
ATEX/IECEx: II 2 GD Ex db IIB+H2 T4 Gb, Ex tb IIIC T135°C Db
(Tamb=-40°C to +70°C)
Warranty: Two years
9.3.2 Mechanical Specifications
Length: 6.4 inches (161 mm)
Height: 3.4 inches (86 mm)
Width: 4.1 inches (104 mm)
Weight: 5.5 lbs. (2.5 kg) – AL, 14.0 lbs (6.4 kg) – SS
Mounting Holes: 5.0 inches (127mm) center to center
Housing: Aluminum alloy (6061-T6 cover, A356-T6 base) or 316 stainless
steel
9.3.3 Electrical Specifications
Input Power: 24 VDC nominal, 20 to 36 VDC, 350 mA max.
Power Consumption Start-up 270 mA, Normal Operation 120 mA
Relay Ratings: 8 A @ 250 VAC / 8 A @ 30 VDC resistive max.
(3x) SPDT - Warning, Alarm & Fault
Analog Signal:
HART not HART
Mode HART
enabled modified AO
Malfunction 0 mA 3.5 mA 1.25 mA
Calibration 1.5 mA 3.5 mA 1.5 mA
Gas Check 1.5 mA 3.5 mA 1.5 mA
Setup mode 1.5 mA 3.5 mA 1.5 mA
Startup 4.05 mA 4.05 mA 4.05 mA
Zero reading 4.05 mA 4.05 mA 4.05 mA
0-100% FS 4-20 mA 4 – 20 mA 4.0 – 20 mA
Over-range 20-22 mA 20 – 21.7 mA 20 – 21.7 mA
Status Indicators: Three-digit digital display with gas concentration, warn and alarm
LED’s, calibration prompts, fault codes, and setup options
RS-485 Output: Dual Redundant Modbus RTU, suitable for linking up to 128 units
or up to 247 units with repeaters
Baud Rate: 2400, 4800, 9600, or 19200 BPS
55
Model S4000TH
Faults Monitored: Calibration error, sensor heater error, low DC supply, EEPROM,
EPROM, setup error, gas check time exceeded, switch error,
magnet error.
EMC Protection: Complies with EN 50270, EN 61000-6-4
HART: RX 100K CX 5nF
Cable Requirements: 3-wire shielded cable. Maximum distance between S4000TH and power
source @ 24 VDC nominal with warn & alarm relay energized. If no relays are used the
distance can be increased by 10%.
AWG FEET METERS
14 2240 824
16 1408 518
18 886 326
20 557 205
Table 17: 24 VDC Cable Lengths
Based on 20 Ohm cable resistance the recommended analog output cable length is shown in
Table 18. The total resistance should not exceed 600 Ohms @ 24 Volts.
AWG FEET METERS
14 8000 2400
16 5000 1500
18 3100 950
20 2000 600
Table 18: Analog Output Cable Lengths
Maximum distance between the transmitter and sensor with one way resistance of 10 Ohms
(20-Ohm loop):
AWG FEET METERS
14 4000 1200
16 2500 750
18 1500 460
20 1000 300
Table 19: Sensor Cable Lengths
56
Model S4000TH
9.4 Approvals
CE Marking; CSA, FM, ATEX, IECEx and EAC approved. Complies with ANSI/ISA-
92.0.01:1998, performance requirements. SIL 2/3 suitable (use in typical environments has
a lower safety rating than in clean environments). HART Registered.
HART:
Approved by the HART Communication Foundation.
Compatible with Emersion 375 Field Communicator.
Listed in Emerson Process Management’s Aware device list.
9.5.1 Sensors
50445-1 0 to 100 ppm, Aluminum Body, Wire Screen Arrestor
57
Model S4000TH
58
Model S4000TH
Replacement Hose
59
Model S4000TH
9.6 FM Approval
Factory Mutual Research Corporation
1151 Boston-Providence Turnpike
Norwood, Massachusetts 02062
Approval of the transmitter does not include or imply approval of apparatus, to which the
transmitter may be connected and which processes the electronic signal for the eventual end
use. In order to maintain FMRC approved system, the control instrument, to which the subject
instrument is connected, must also be FMRC approved.
The following sensors have been FMRC approved for use with the Model S4000TH:
50445-1 Aluminum Body H2S Gas Specific MOS Sensor, 0 to 100 ppm
50445-5 Aluminum Body H2S Gas Specific MOS Sensor, 0 to 50 ppm
50445-9 Aluminum Body H2S Gas Specific MOS Sensor, 0 to 20 ppm
50448-1 Stainless Steel Body H2S Gas Specific MOS Sensor, 0 to 100 ppm
50448-5 Stainless Steel Body H2S Gas Specific MOS Sensor, 0 to 50 ppm
50448-9 Stainless Steel Body H2S Gas Specific MOS Sensor, 0 to 20 ppm
The following apparatus have been FMRC approved (although they have not been verified as
part of a Model S4000TH system):
Model DT210 Eight-Channel Readout/Relay Display Module with Power Supply and
Relay Module
60
Model S4000TH
ADDENDUM
Product Disposal Considerations
EU Member states shall dispose according to WEEE regulations. For further General Monitors’ product
WEEE disposal information please visit: www.MSAsafety.com
All other countries or states: please dispose of in accordance with existing federal, state and local
environmental control regulations.
61