100% found this document useful (1 vote)
453 views

Type Test Verification - 24Kv Abb Power Distribution Safering (Rmu)

This document verifies type tests performed on an RMU (ring main unit) type called SafeRing. All tests were carried out according to relevant IEC standards and specifications. Key components like the switch and switch-fuse unit, vacuum circuit breaker, and earthing switches were tested for mechanical endurance, dielectric strength, short-circuit withstand, temperature rise, and making and breaking capacity. Test results are documented in various reports showing compliance with standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
453 views

Type Test Verification - 24Kv Abb Power Distribution Safering (Rmu)

This document verifies type tests performed on an RMU (ring main unit) type called SafeRing. All tests were carried out according to relevant IEC standards and specifications. Key components like the switch and switch-fuse unit, vacuum circuit breaker, and earthing switches were tested for mechanical endurance, dielectric strength, short-circuit withstand, temperature rise, and making and breaking capacity. Test results are documented in various reports showing compliance with standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Type test verification - 24kV ABB Power Distribution

SafeRing (RMU) October 4, 2001

Type Test Verification.

Product: Ring Main Unit type SafeRing


Manufacture: ABB Kraft, Skien, Norway
Ratings: 24kV, 630A, 16kA 3s

Doc. version: Last update 10 May 2000

This verification document is a statement of type tests which have been performed on RMU type SafeRing under
the surveillance of SATS/STL. All tests have been carried out according to relevant IEC Publications and other
significant specifications.
Switch and Switch-Fuse unit, C - module and F - module:
Type of test Specific. Test result Report
no.
1.0 Mech.Endurance IEC 60265
1.1 Switch manual 1000CO 99-B16
1.2 Earthing Switch 1000CO 99-B16
1.3 Switch Fuse manual 1000CO 99-B17
1.4 S.F. earthing switch 1000CO 99-B17

2.0 Dielectric tests IEC


60298/602
65
2.1 Lightning Impuls 125/145 kV 99-B19
2.2 Power frequncy 1 min. 50/60 kV 99-B19
2.3 P.D. measurement 26.4 kV/5 pC 99-B19

3.0 Short-Circuit tests IEC60298/6


0265
3.1 Main circuit/switch 40 kApeak 99-B14
16 kA 3 s
3.1 Earthing Switch 40 kA peak 99-B14
16 kA 3 s
3.2 S.F. downstream 12.5k Apeak 99-B15
Earthing Switch 5 kA 1 s

4.0 Make-Break tests


4.1 TD1 active load IEC 60265 100CO 630 A 99-B07
E3
4.2 TD2a closed loop IEC 60265 630 A 99-B07
E3
4.3 TD4a, 4c,4d capacitive IEC 60265 135 A 99-B07
E3
4.4 TD6a earth fault IEC 60265 150 A 99-B07
E3
4.5 TD6b e.f. cable charg. IEC 60265 87 A 99-B07
E3
4.6 TD2 max. I2t IEC 60420 CEF63 99-B09
4.7 TD3 long prearcing IEC 60420 CEF63 99-B09
4.8 TD4 transfer current IEC 60420 650 A 99-B09

5.0 Making tests


5.1 TD5 Switch IEC 60265 5C 99-A07
E3 40 kApeak
5.2 TD5 Earthing Switch IEC 60265 5C 99-A07
E3 40 kApeak
5.3 TD1 Switch Fuse IEC 60420 16 kA 99-A05
Combination prosp.current
CEF63
5.4 TD5 S.F downstream IEC 60265 5C 12.5 99-B15
Earthing Switch E3 kApeak
6.0 Temperature Rise
tests
6.1 Main circuit/Switch IEC 630 A 99-B01
60298/265
6.2 Switch Fuse Combin. IEC 60420 CEF63 99-B12
50 A

7.0 Mech. operating


tests

7.1 Gas leakage test IEC 60298 0,25%p.a 99-B16


7.2 Interlocks IEC 60298 50CO 99-B22
7.3 Submersion test UNESA 24 hrs. 24 kV 9905302
4A

8.0 Arc fault tests IEC 60298


8.1 without arc surpressor 16 kA 1 s NEFI
1401
8.2 with arc surpressor 20 kA 1 s NEFI
1364
8.3 Cable compartment 16 kA 1 s NEFI
1399
Vacuum Circuit -Breaker, V - module:
Type of test Specific. Test result Report
no.
1.0 Mech.Endurance
1.1 Vacuum CB manual IEC 60056 2000CO 000001
1.2 Earthing Switch IEC60129 1000CO 99-B16
1.3 Disconnector manual 1000CO 99-B16

2.0 Dielectric tests IEC


60298/600
56
2.1 Lightning Impulse 125/145 kV 980029
2.2 Power frequncy 1 min.
2.3 P.D. measurement

3.0 Short-Circuit tests IEC


60298/602
65
3.1 Main circuit and 52,5kApeak NEFI
vacuum CB 21kA 1sec. 1355
3.1 Earthing Switch 40kA peak 99-B14
16kA 3sec

4.0 Make-Break tests


4.1 TD1 10% Isc IEC 60056 1.7 kA KEMA
489- 99
4.2 TD2 30% Isc IEC 60056 4.5 kA KEMA
489- 99
4.3 TD3 60% Isc IEC 60056 9.8 kA KEMA
489- 99
4.4 TD4 100% Isc IEC 60056 16.1 kA KEMA
489- 99

5.0 Making tests


5.4 TD5 downstream IEC 60265 5C 99-A07
Earthing Switch E3 40 kApeak

6.0 Temperature Rise IEC 60056


tests
6.1 Vacuum CB 630 A 99-B21

You might also like