0% found this document useful (0 votes)
230 views

Buried Pipe Design HDPE

This document provides design details for a buried firewater pipe at the Deep Rock Petroleum Product Terminal project for Deep Rock Tanks, LLC. It includes calculations of soil pressure, surface loads, impact factors and live and dead pressures on the pipe. Ring deflection, compressive strength and critical buckling pressure were calculated and found to meet allowable limits for the 20-inch diameter polyethylene pipe buried at 3.5 feet.

Uploaded by

Michael J. Bane
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
230 views

Buried Pipe Design HDPE

This document provides design details for a buried firewater pipe at the Deep Rock Petroleum Product Terminal project for Deep Rock Tanks, LLC. It includes calculations of soil pressure, surface loads, impact factors and live and dead pressures on the pipe. Ring deflection, compressive strength and critical buckling pressure were calculated and found to meet allowable limits for the 20-inch diameter polyethylene pipe buried at 3.5 feet.

Uploaded by

Michael J. Bane
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 12

PROJECT: DEEP ROCK PETROLEUM PRODUCT TERMINAL

CUSTOMER: DEEP ROCK TANKS, LLC


JOB: 2211-3704 BY: JPH
DATE: 7/13/2010 CHK. BY:
SECTION: BURIED PIPE DESIGN-FIREWATER REVISION: 0
SHT: 1

BURIED PIPE DESIGN-FIREWATER


DEEP ROCK PETROLEUM PRODUCT TERMINAL
DEEP ROCK TANKS, LLC
2211-3704
PROJECT: DEEP ROCK PETROLEUM PRODUCT TERMINAL
CUSTOMER: DEEP ROCK TANKS, LLC
JOB: 2211-3704 BY: JPH
DATE: 7/13/2010 CHK. BY: 0
SECTION: BURIED PIPE DESIGN-FIREWATER REVISION: 0
SHT: 2
INDEX

PAGE NUMBER REVISION PAGE NUMBER REVISION


1 of 6 0
2 of 6 0
3 of 6 0
4 of 6 0
5 of 6 0
6 of 6 0
PROJECT: DEEP ROCK PETROLEUM PRODUCT TERMINAL
CUSTOMER: DEEP ROCK TANKS, LLC
JOB: 2211-3704 BY: JPH
DATE: 7/13/2010 CHK. BY: 0
SECTION: BURIED PIPE DESIGN-FIREWATER REVISION: 0
SHT: 3
BURIED PIPE DESIGN-FIREWATER
REF: DESIGN OF PE PIPING SYSTEMS - PPI (INSTALLATION CATEGORY 1, SOLID WALL)
GUIDELINES FOR THE DESIGN OF BURIED STEEL PIPE - ASCE JULY 2001
WEIGHT OF SOIL, γS = 110 PCF
BURIED PIPE DEPTH, C = 3.500 FT = 42.000 IN
SOIL PRESSURE TRANSMITTED TO PIPE, PV = 2.67 PSI (DEAD LOAD)

DESIGN SURFACE LOAD, PS (SLAB + SUPPORTED LOAD)


CONCRETE WEIGHT, WC = PCF
SLAB SIZE = FT (length) FT (width)
SLAB WEIGHT, SWT = 0 LBS = 0 CF
SUPPORTED LOAD, SL = LBS
MAXIMUM DESIGN SURFACE LOAD = 0 LBS = 0 PSF
PRESSURE TRANSMITTED TO PIPE, Ps = 0.00 PSI (DEAD LOA

INCLUDE TRUCK/RAILWAY LOADS : 1 (YES=1, NO=0)


LIVE LOAD TRANSFERRED TO PIPE : 1 (TRUCK LOAD=1, RAILWAY=2)
PRESSURE TRANSMITTED TO PIPE, PP1 = 3.48 PSI

MAXIMUM DESIGN SURFACE LOAD, PS1 = 0 LBS


dOFF = 0.000 FT = 0.000 IN
PRESSURE TRANSMITTED TO PIPE, PP21 = 0.00 PSI = 3*PS/(2*π*C2*[1+(dOFF/C)2]2.5)

IMPACT FACTOR, IF = 1.00 2.0 for unimproved road


TOTAL LIVE PRESSURE = PL = IF*(PP21 + PP22) = 3.48 PSI
TOTAL DEAD PRESSURE, PD = Pv + Ps = 2.67 PSI

DIAMETER RATIO, DR = 9.00


PIPE DIAMETER, DP = 20.000 IN Ф = 1.667 FT Ф (no impact on calc)
PIPE THICKNESS, TP = 2.222 IN
PIPE MODULUS, E = 27,000 PSI PE 3408, 100 Years

RING DEFLECTION, ΔX/DM = K*(DL*PD+PL) / { 2/3*E*[(1/(DR - 1)]^3 + 0.061*FS*E' }


DEFLECTION LAG FACTOR, DL= 1.50 (≈ 1.00 TO 1.50, 1.50 Conservative))
BEDDING CONSTANT, K = 0.10 (≈ 0.10)
MODULUS OF SOIL REACTION, E' = 500 PSI (MEDIUM CLAYS)
SOIL SUPPORT FACTOR, FS = 0.15 0.15 min (conservative)
ΔX/DM = 1.88% 7.5% Max Allowable, Non-Pressurized Pipe

COMPRESSIVE RING THRUST, S = (PD + PL)*DR / 2


σBW = 28 PSI 1000 PSI Allowable for PE 3408

CRITICAL RING BUCKLING PRESSURE, PWC = 5.65 / N * SQRT[32 * R * B' * E' * E / 12 / (DR - 1)^3]
N= 2.00 2.0 TYP for thermoplastic pipe
BUOANCY REDUCTION FACTOR, R = 1.00 - 0.33*(hGW/C) HGW = 3.500 FT
R= 0.67
EMPIRICAL COEFFICIENT OF ELASTIC SUPPORT, B' = 1/(1 + 4 e^(-0.065*C))
B' = 0.793
CRITICAL RING BUCKLING PRESSURE, PWC = 96.53 PSI Acceptable
OF 6
0
OF 6
0
OF 6

FT (height)

(DEAD LOAD)

(LIVE LOAD)

(LIVE LOAD)

(no impact on calc)

7.5% Max Allowable, Non-Pressurized Pipe


PROJECT: DEEP ROCK PETROLEUM PRODUCT TERMINAL
CUSTOMER: DEEP ROCK TANKS, LLC
JOB: 2211-3704 BY: JPH
DATE: 7/13/2010 CHK. BY: 0
SECTION: BURIED PIPE DESIGN-FIREWATER REVISION: 0
SHT: 4
BURIED PIPE DESIGN-FIREWATER
PROJECT: DEEP ROCK PETROLEUM PRODUCT TERMINAL
CUSTOMER: DEEP ROCK TANKS, LLC
JOB: 2211-3704 BY: JPH
DATE: 7/13/2010 CHK. BY: 0
SECTION: BURIED PIPE DESIGN-FIREWATER REVISION: 0
SHT: 5
BURIED PIPE DESIGN-FIREWATER REF: API 1102
PROJECT: DEEP ROCK PETROLEUM PRODUCT TERMINAL
CUSTOMER: DEEP ROCK TANKS, LLC
JOB: 2211-3704 BY: #REF!
DATE: 7/13/2010 CHK. BY: #REF!
SECTION: BURIED PIPE DESIGN-FIREWATER REVISION: 0
SHT: 6
BURIED PIPE DESIGN-FIREWATER REF: API 1102
0
OF 6
0
OF 6
0
OF 6