DIGITAL CONTROLLER REX series INSTRUCTION MANUAL 1. GENERAL INTRODUCTION ‘REX series PID Temperature Controller is the new product developed by our company. It adopts special microcomputer adjusting meter that ‘employs swiching power and surface mount technology (SM), theretor, the controler ie qute smart and reliable. Its special functons Ike auto diagnosing, auto sting and intligent control It can be used widely inthe splay and contol ofthe parameter of he temperature, pressure, flow, and qui evel 1. MAIN TECHNICAL INDEX 24° Inputs “Thermocouple(TC) Resistance Temperature Detect (RTO? ‘Standard Current and votage signals. 2.2 Display: Process Value (PV). Setting Vauo(SV}-1990-+1998 (uiput (QUT, OUT2) Alam CALM. ALM2) Auto seting(AT) Display: LED 23. Control way (1) PI Contokincuding ONIOFF, poston PID and continuous PIO) (2) Auto Setting Corto 2.4 Accuracy Measurement Accuracy 0.5%FS Compensation ertor of cold terminal:2C{amend within 0-50°C by sof) Resoluton:14be. Sampling peric:0 Sec. 25. Setting Range: Seftng Value(S¥): same range vith PY Proportional Band(P}0-fullrange(ONIOFF Control when seto 0), Integration Time():0-3800Sec(r0intogral action when set to 0) Derivative Tme(O}0-36008ec(n0 dervatve action when Set to 0) Proportional Perod1~ 100800 ‘Ont control output hysteretic loop with 1~100'C (or other PY units) 2.6 Control Output _ " (‘)Curency output: OC 0-T0Na¢-20mA(RL<5000) (2Noltage output: OC 0-5, 1-5V(RL>10K) (@)Relay output: Contact capacty:250V AC 3A(esistve load) (4Vottage Impulse output0-12V(apptcabe for so stat relay SSR) (©)Siicon Controled Rectfe(SCR) output zoro-cross.tiggering or ‘hase-shit tiggerngresistive load) (@ Alarming function output 2 groups output at most,12 modes ‘Output Contact Capaciy:250V AC 3A 4, PANEL NAME AND FUNCTION PV: Measured valve / mode dieplay value SV; Setting valualode dspay value [AT._PID auto calculation ndcator lamp OUT: ouput nscale OUT: output 2 inate ALM: Alam 1 inate lamp ‘ALM2:_ Alam 2iniator tap SET seting made key SRUS:svAkey V: Upkey A: Downey 5. MODEL DESCRIPTION AND MODEL SELECTION REX-cOoo - 0 OGO-00+00 ® @e ©® O® Eo REX-C100 - F K 02 -M ‘AN ‘@ Outline size(See Form 1) @ Control type P10 operation and ata calelton Reverse operation) PIO operaton and au eaiaton(Forerd operon) @ Input type: reterto ne input Range Table (See Form2) @ Range Code: referi the Input Range Table (See Form) © First Control Output( OUT! Heating side) McRelay conact output 8:Curont outwit 4-20mA) ¥: Votage impuse ouput (SSR) "Hydration ering output © Second Control Output(OUT2)(Cooiing side) Nl fitdoesn"tnave second output Relay Contact ouput 8 Curent outpt{ DC 4-20mA) ¥ Vote impuise output (SSR) T Hyation cing oxpat © First Alarm(ALM1) @ Second Alarm(ALM2) No alarm 2: Upp Lit bias lar -B:towertim bas aiarm ‘© Uppet.ower Lint is alarm D: Alarm in area E Standby uppers bias alam atachod F Standby lowernt bas sar alached 6: Stancby upperiower int bas alarm tached HE UpperLimt input valve alarm 4 Lower inpt va alarm 1: Standoyuppermitinut value alarm atacned Stan lowering value arm attached Forma: Input Range Table E dond maces SSS oS (oe eee ices leet lear eae « [kos [o-800r ‘Kos [0-10000 | K06|0-1200%. ees Kor[o-arze_—_[xr3]o-100e | Kialo-sooe town emma aceon girs _jusleeee sue Swmpeaasr(co me pelea ae other a 3. OUTLINE MOUNTING BORING Renta eee mae cease Cute & beng sue So [or ens fe ow aa pert eerie lore cutineico Pa ereercemeieteres ‘ ore eegeet eraeeee A | 72 Frosfossor +] [elte Dot 108s. 00.00 a [ans 200.7e| bos |AooneROT a Bolssteseed oo iareeniee(orace 8 ‘Caen: ¥ P7100) Do7[o.0-s00.0c [008 [00-200 0c | 009|0.0300 00 ria | [ewes Form 3 | —— [be oe pe neg a Lee ea uso font me Ps Honan rsa Par onee {ee oss [eee SSE Serle te tw [wl ef wlielae| [gtoarttismn caueaaaloegl islam] = oe Sayfa ae re foe fie foo afoot oe oe] (gama ree | ert [wf oo] ele gi #4, 03000: Accuracy snot guaranteed. #2, 190.9100 : Accuracy i not guaranteed 6. TERMINAL CONFIGURATION 7. OPERATION PROCEDURES 7.1 Procedures of Starting Power terminals ©100 Wiring diagram Se aoe ewe ee ‘eput Type Code = =p) Lip sy neoreee) OM (See Form3) perdaw | acee-essv 2 aa a tap Bean Dasara) — pv] Input Range Code qu ae Sasa) ae Coad mea ore (SW/PV oa esoma £4) Fors input Type Code eae Or Display] u) -]S[b[E [nl] PF [Cu foalawlaaley s | Tepe [_Thermocoupa(FC] —[ — RTO —_ Vollage/Ourent eer ype [K[4] [5] 2] [N] [Pri09|cuso] ou [mv|ma] v Enea Note: When the input sig 98 nai ren the input signal is curent or vokage, you must use our appropriatve curren 8 Voltage input adapter el 7.2 8V Setting Mode “an Under SVIPV normal display stato, est, press SET hoy to make the 'V Geply nth ating tat, second, pres the < hey ode lace ‘umber of requted seting temperature, ti, press UP or DOWN key 10 sel to requred temperature, ater ending the seting, poss SET hey again ot the moter como back o SVPV normal dspay state 7.3 Parameter Setting Mode €700 Wiring diagram ‘his parameters used tooo he alarming parameter, IO constant cleuncer the noma dspiayng state, press. the” SET Key for tee Seconds, te PV dapay will show the parameter sting stat, and 3 311 '8V daplay wil show the coresponcing value, then press ‘SET hay n (Gasuay Jp to dspay he parameter symbol spectied inte folowing table ee. acces Bor aed fs a3], Fedor Paes Setting range an Futrange Att | Aarmi_seting | Fa ange ‘deso FL e_| Armd seting | Fullrenge 50 50 APE | Sereatne | SAtseina rcsha | 9 {1 Auto-seting for opening rational band | ONOFF contol when | 30 or P| Propominal band | ccting 00 Ed 3e00see [No deevatve acton when 240 soting 120. gration timete) 73600806 | Dereative time(s) | No derivative acton when 60 soting 100. (0400 /¢410/ C900 ‘Wiring diagram ——) ® tol i 2 a “4 15 18 Timi —tagraton Ae | operation work | Proportional band 1-100% | 25 = fo eed on Unit same as PV 4 SC_| amendment Unit same as PV — LOY | Date tock (refer to°2) 0000 __Input terminals —! o Note: some parameter signals maybe not showed +1. Relay contact output20s, votage impulse output or ving of gas control tube is made by tigger ouput © gas contol tube output for 2s +2. Data lock grade selects + Monitored ony aftr data locked + Each alarm data(HBA.LBA.LBD) can be lock under the folowing grades 0001.0011.0111 41, When LOK=0000 al data may be amended 2. When LCK=0001, ll data may not be amended except Sv, ALIALZ 3, When LOK=0011, alldta may not be amended except SV, 44, When LCK=0111, all data may not be amended 7.4 Function Setting \Wmen the meter is eneraized normally, find the data lock parameter LLckaccording tothe parameter setting mode, SET the code to 1000, Form? Disa Factory Simba Description een SUH | Unrerintcraeing we nesmrenectarge |e ‘lS le ol eh rt Ce ra ha sc ON 68 EY pre ches Ea | erent tora a preying |e ce incre apay (Se Form) fa 6 rete opener [aera far seme eatin te rons lation acest | Display! Setting Description transformer ) pre ee ote ieee Toe i tHolalotol SIF a |Timetactorof stablemeasuring value: range0-200s| 100 fetal SFE [Caaiars wee cloesoton ond meebo OT fe EF longi marsragcoreeeate 1 ololits Thermocouple(TC) setts > eon he oltlolate 8 Instrument Data viewing eset e te ‘When Cod = 0002, ali data is the recorder of meter operation, can ofite ct aay soon otic ananiedlesd rains tfetofoL ea steed OO TD out tTetstetoaoen ca oe HeLite fossoat foe Loan oe Tis apn op aT ee SEH |e oi ose a Oa aS ar it immu estan cece aarti 1 oe a | Arestngrs) —— | srieion caine 7-7 Fallure Message indicate +1 Tiner ssn) —| na Foil tft esaere Yonartag a a tol ott [tat tu miter Gagrosed subrramaly to dopay bo meceage [St 3lelolo|o{ome promot (eter) SCG [0] 0] 0 No setalam Marcio | me {of er nti ar | Teli lolieesdmectnitissom —| conan | Caray Description Ta i Ne ee seria Bari at shea a — ‘The wire is disconnected at inputting, the polarity Go Tir} 2900 | is connected inversely or above input range it eine ver see Race y qeovecsiataey te acy a qv udbiaetrmnayer oh vette [sus Seapine teas — [ois BEB LT to eee cat coma aromas 1 [Rsvens-opeion conoiiesia] operaion selection |, OPERATION PROCEDURES (see Fig2inPage4) SL-1 pansmec ene acet [ook a mah Tans Saat cata SC TLL [0 [eetatn slerring ——Exciatonslorning hone ‘feraeasstns focumnsamegiortan| 9 AFTER SERVICE Se ‘We lnemunent ls guranteed of 18-nenth tee msnenace | fRorssetaior arr esun samrg s aAARbaanahs ten neeiacneblerterer re SiG lolo/ololomi product damaged by mistake operating or product with expired fi sont 1 Meet epoca perrensiee Si ig] 0) Non Run/Stop function Besides,we can give the lifelong maintenance for our products. 1 ana ion | son’ fon ‘Selection of 1. Before use the product, please read Seccorscion tion —| Soon con ipeeh arse. pe ns afolaloloma A cre ebeclinoeerae sae “1. Excitation alarming means alarm relay contact changes from NO to NC. Non-excitaton alarming means alarm relay contact changes from NC to NO "2. RunvStop setting is effective, press "

You might also like