What Is A Pressure Transmitter ?: Differential Pressure Pressure Measuring Instrument
What Is A Pressure Transmitter ?: Differential Pressure Pressure Measuring Instrument
The DP flow transmitter output signal may also include square root
extraction for flow calculation,although it is common for this
function to be handled in control system.
For the purposes for this guidance note it is assumed that both the
transmitter and the remote control panel require a 24Vdc supply.
Disadvantages:
The transmitter and control panel can use the same 0V and 24V dc
supply lines. The 4-20mA signal flows through the 0V dc line and
the signal line to the controller.
Advantages:
Disadvantages:
Disadvantages:
Disadvantages:
In a bench test situation, power is applied to the transmitter, so it fires up and runs fine. But there’s
no analog input in the loop as there is when the transmitter is wired in the field. What’s missing is the
dropping resistor on the analog input that supplies the loop resistance needed for the HART signal to
develop.
4-20mA loops transmit the signal as electrical current (milliamps), but the receiver device with the analog
input ‘reads’ the signal as a voltage, whether the signal to be read is analog or HART. The current signal
becomes a voltage drop when the current passes through a resistor (Ohms Law).
The HART signal is a 1200 baud signal superimposed on the loop’s 4-20mA DC signal. 1200 baud is a
relatively high frequency signal compared to the 4-20mA DC current signal.
Some minimum loop impedance is needed so that the HART signal can be ‘seen’ or ‘read’ by a HART
master, like a HART communicator or HART modem. The analog inputs on the receiver device (DCS,
PLC, RTU, PAC, controller, recorder, or indicator) have a precision shunt resistor installed at each analog
input. It is usually 250 ohms, but not always.
The voltage (IR) drop needed for HART communications is produced by the resistance at the loop
receiver’s analog input. The loop’s wire resistance contributes very little resistance. When a transmitter
is powered up with just a DC power supply there isn’t enough voltage from the 1200 baud HART signal
for the for the HART master (handheld communicator or a HART modem) to ‘see’ the signal. The
internal resistance of a DC power supply is insufficient to develop a HART voltage drop, and its filter
capacitors act as a low pass filter to squelch the relatively high frequency 1200 baud HART signal.
In the absence of a receiver device with its analog input resistance being part of the loop, there is
insufficient loop resistance for a HART master device to ‘see’ the FSK HART signal and HART
communications fails.
The good news is that a resistor can be inserted into the loop and the HART signal will develop a voltage
drop and the HART master can ‘see’ the HART signal.
The HART Foundation’s website has a technical specification that states that the minimum loop
resistance needed is 230 ohms. A 250 ohm resistor is commonly used because 250 ohm resistors work
for that purpose and are typically available in the instrument shops where these types of bench tests are
done. The resistor need not be a precision resistor.
Connect a 250 ohm resistor with alligator clips, like this one, to a wiring terminal and a loose wire in a
loop circuit to test HART communications at the benchtop.
HART handheld communicators (275/375/475, Meriam 5150) usually have a pair of banana jacks on the
handheld for the purpose of connecting a plug adapter with a 249 or 250 ohm resistor to provide the
needed loop resistance. If a HART communicator or HART modem fails to establish communications, it is
advisable to insert a 250 ohm resistor in series in the loop (or use the banana plug adapter with a
communicator).