0% found this document useful (0 votes)
115 views

RM6

The document provides technical specifications for RM6 medium voltage switchgear for a project in Port Said Tunnel. Key details include: - RM6 is an SF6 insulated switchgear for MV networks and transformer substations. - Units comply with IEC standards and are rated for temperatures between -25°C to +40°C. - Voltage ratings are 12kV and 24kV, and current ratings are up to 630A. - Components include circuit breakers, switch-disconnectors, and metering devices. - Units undergo routine factory testing according to IEC standards.

Uploaded by

Mena Amir Khairy
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
115 views

RM6

The document provides technical specifications for RM6 medium voltage switchgear for a project in Port Said Tunnel. Key details include: - RM6 is an SF6 insulated switchgear for MV networks and transformer substations. - Units comply with IEC standards and are rated for temperatures between -25°C to +40°C. - Voltage ratings are 12kV and 24kV, and current ratings are up to 630A. - Components include circuit breakers, switch-disconnectors, and metering devices. - Units undergo routine factory testing according to IEC standards.

Uploaded by

Mena Amir Khairy
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Project: Port Said Tunnel

B
Client: JV Orascom & Arab contractor

TECHNICAL SPECIFICATIONS - RM6 RANGE-

1. SCOPE OF SUPPLY

RM6 is a "totally SF6" switchgear range with built-in functions and reduced dimensions.
This self-contained totally insulated unit constitutes the MV component of the MV/LV transformer
substation or the branching point of an MV network. The RM6 regroups, in a single metal
enclosure, all the medium voltage functions enabling MV cables and transformers to be connected,
supplied and protected.

2. CARACTERISTICS ACCORDING TO IEC STANDARDS

The equipment proposed in this offer has been designed, manufactured and tested in compliance with
IEC recommendations.
 Common clause for high voltage switchgear and low voltage switchgear IEC 60694
 Self-contained medium voltage apparatus IEC 60298
 High voltage circuit breakers IEC 62271-
100
 AC switches and earthing switches IEC 62271-
102
 Switches and disconnectors IEC 60265-1
 Combined switch/disconnectors IEC 62271-
105
 Current transformers IEC 60044-1
 Voltage transformers IEC 60044-2
 High voltage fuses IEC 60282-1
 Classification of degrees of protection for enclosures IEC 60529
 In accordance with IEC recommendations, these characteristics are valid for ambient
temperatures between -25°C and +40°C.
 All breaking units, including earthing switches, are contained in enclosure filled with SF6, sealed
for life according to the IEC standard EE Appendix Class III.

Schneider Electric Egypt & North East Africa


Project: Port Said Tunnel
B
Client: JV Orascom & Arab contractor

2.1 GENERAL CHARACTERISTICS

DESCRIPTION RM6
SELF-CONTAINED UNIT
Degree of protection
- RM6 tank IP 67
- Enclosure and operating mechanism IP 3X
Paint
- RM6 tank Unpainted
- Enclosure RAL 9002
- Front plate RAL 7016

Busbar
- Cross section Area 50 x 8 mm2

2.2 CLIMATIC CONDITIONS

Climatic Conditions

RM6 temperature (oC) 40 45 50 55

Maximum rated current (A) 400A version 400 400 400 355

630A version 630 575 515 460

Schneider Electric Egypt & North East Africa


Project: Port Said Tunnel
B
Client: JV Orascom & Arab contractor

2.3 ELECTRICAL CHARACTERISTICS

Description
Rated voltage kV rms 12 24
Operating voltage kV rms 11 22

Insualtion level:
Rated withstand voltage at power frequency: 50Hz/1 min kV rms 28 50
Rated impulse withstand voltage: 1.2/50µs kV peak 75 125

NETWORK AND BUSBARS


Rated current up to A 630 630
Rated short-time current kA rms/ 1s 25 20
Making capacity for switch-disconnectors and earthing switches KA peak 62.5 50

NETWORK SWITCH (I FUNCTION)


Rated current up to A 630 630

 SWITCH DISCONNECTOR
Breaking capacity of fuse-switch combination kA rms 25 20
Making capacity kA peak 62.5 50

LINE PROTECTION FEEDER (B FUNCTION)


Rated current A 630 630
 CIRCUIT BREAKER
Breaking capacity of fuse-switch combination kA rms 25 20
Making capacity kA peak 62.5 50
TRANSFORMER FEEDER (D FUNCTION)
Rated current A 200 200
 CIRCUIT BREAKER
Breaking capacity of fuse-switch combination kA rms 25 20
Making capacity kA peak 62.5 50
TRANSFORMER FEEDER WITH FUSE-SWITCH COMBINATION (Q FUNCTION)
Rated current A 200 200
 SWITCH-FUSE
Breaking capacity of fuse-switch combination kA rms 25 20
Making capacity kA peak 62.5 50

3. TECHNICAL DESCRIPTION

The technical description is presented in our leaflet : Ring main unit 3 to 24 KV “RM6 range” ref. ART.
93643
For detailed description see section 8 of this technical specification.

Schneider Electric Egypt & North East Africa


Project: Port Said Tunnel
B
Client: JV Orascom & Arab contractor

4. TESTS

Routine factory testing, in accordance with IEC standards, is provided for in this offer and includes the
following:
 Check of conformity with wiring diagrams and plans,
 Mechanical operation tests, and checking of interlocks,
 Testing of the interchangeability of moving parts,
 High voltage dielectric tests at the power frequency.
 Low voltage dielectric tests.
 Low voltage functional checking.

5.

Schneider Electric Egypt & North East Africa


Project: Port Said Tunnel
B
Client: JV Orascom & Arab contractor

Un: 24kV -
630A(Busbar) -
Characteristics 20 kA/1sec
Us: 22 kV
Metering
DE-BB+DE-Mt+DE- INCOMING OUTGOING
Cubicle label D CUBICLE CUBICLE
Cell

Product RM6

Cubicle Type CB type (B) CB type (D) DE-Mt


Quantity 2 1 1
20kA/1
Ith 20kA/1 sec 20kA/1 sec
sec
Frequency 50 Hz 50 Hz 50 Hz
Temperature 40 degree 40 degree 40 degree
Depth / mm 710 710 710
Height / mm 1142 1142 1142
Width / mm 1186
Colour RAL9002

Internal Arc
Safety Protection - Tank
No No No
Internal Arc
--- --- ---
Protection Level
IP protection degree
IP67 IP67 IP67
- Tank
IP protection degree
- Enclosure & IP3X IP3X IP3X
Mechanism

Busbar Busbar Current / A 630A 630A


SF6
Manometer/Pressure Standred Standred
switch

Switching Withdrawable or N/A


Fixed CB Fixed CB
Compartment Fixed
Type of N/A
SF6 SF6
Breaker/switch
Rated current (40C N/A
630 A 200 A
degree)

Schneider Electric Egypt & North East Africa


Project: Port Said Tunnel
B
Client: JV Orascom & Arab contractor

Short time withstand 20kA/1 sec 20kA/1 sec N/A


Close/Open aux. No
No No
contact

Circuit Breaker Charging Motor Yes (110V Yes (110V N/A


(D/B) (qty:1) DC) DC)
Shunt Trip Coil ( Yes (110V Yes (110V N/A
qty:1) DC) DC)
No N/A
Undervoltage Coil No (optional)
(optional)
Yes ( Yes ( N/A
Tripping Indication Protection Protection
Relay) Relay)

Load Break Charging Motor N/A


NA NA
Switch (I) (qty:1)
Opening Coil ( qty:1) NA NA N/A

Fuse Load N/A


Charging Motor
Break Switch (qty:1)
NA NA
(Q)
Opening Coil ( qty:1) NA NA N/A
Fuse Flown Auxilary NA NA N/A

Earth Switch Switch YES YES N/A


No N/A
Signalling Contact No (optional)
(optional)

Voltage Type (Withdrawable Fixed


NA NA
Transformer - Fixed)
Connection --- --- Wires
3 Phase to
Q'ty / Manufacturer --- ---
Earth VT's
Primary/Secondary 22000:r.3 /
--- ---
Voltage 110:r.3
1. Secondary --- --- - 20VA cl 0,5
2. Secondary --- ---
MV Fuse --- --- OK

Current 3
Q'ty / Manufacturer --- ---
Transfomer
One Set Type --- ---
Primary Current (A) --- --- 200A
1. Secondary --- --- 5A
2. Secondary --- --- N/A
3. Secondary --- --- N/A

Schneider Electric Egypt & North East Africa


Project: Port Said Tunnel
B
Client: JV Orascom & Arab contractor

Ith --- ---

Core Balance N/A


TYPE CSH120/200 ARC2 ARC2
CT

Cable Connection Bottom Bottom N/A


Cable connection N/A
703 703
height (mm)
C=Bolted- C=Bolted- N/A
Bushing Type M16 up to M16 up to
630A 630A
Cable Type N/A
Three core Three core
Single/Three core
MV Cable Box NO NO N/A
No N/A
Surge Arrester No (optional)
(optional)

Mechanical Key Lock On Switch No N/A


No (optional)
Interlocks / Circuit Breaker (optional)
Key lock On No N/A
No (optional)
Earthing Switch (optional)
Key Lock Type N/A
--- ---
Ronis/Praufix
Key lock Diagram N/A
--- ---
Type

Cable N/A
compartment Bolted Yes Yes
Interlock
Removable with N/A
NO NO
ESW interlocking
Removable with N/A
No
ESW interlocking No (optional)
(optional)
and CB interlocking

CB/LBS Position N/A


LV Equipment Indicator
NA NA

ES Position Indicator NA NA N/A


Voltage pressence N/A
NA NA
indicator (VPIS)
Fault Passage N/A
NA NA
Indicator : QTY(1)
Ammeter Facility NA NA N/A

Voltmeter Facility NA NA N/A

Power meter NA NA N/A

Energy Displaying NA NA N/A


Power Factor N/A
NA NA
Displaying

Schneider Electric Egypt & North East Africa


Project: Port Said Tunnel
B
Client: JV Orascom & Arab contractor

Frequency N/A
NA NA
Displaying

ATS System Type --- ---


Function --- ---
Communication
--- ---
modem type
Protocol type --- ---
Information
--- ---
Acquisition

Mimic Diagram Type Yes Yes

Circuit Breaker N/A


Protection Raly VAMP259 VAMP52
Protection
I/O Board for Sepam N/A
No No
1000+ Relay
Communication N/A
(Modbus/IEC 60870- yes yes
5-103)
Over Over N/A
Sepam/VIP current/ current/
Protection index Earth fault/ Earth fault/

Sepam Auxilary N/A


NA NA
voltage
Telecontrol (Easergy No N/A
No (optional)
T200I) ATS (optional)
VIP (40 / 45 / 400) No No N/A

Standard/Superlong N/A
Handles : / Qty
Standard (1)

Schneider Electric Egypt & North East Africa

You might also like