RM6
RM6
B
Client: JV Orascom & Arab contractor
1. SCOPE OF SUPPLY
RM6 is a "totally SF6" switchgear range with built-in functions and reduced dimensions.
This self-contained totally insulated unit constitutes the MV component of the MV/LV transformer
substation or the branching point of an MV network. The RM6 regroups, in a single metal
enclosure, all the medium voltage functions enabling MV cables and transformers to be connected,
supplied and protected.
The equipment proposed in this offer has been designed, manufactured and tested in compliance with
IEC recommendations.
Common clause for high voltage switchgear and low voltage switchgear IEC 60694
Self-contained medium voltage apparatus IEC 60298
High voltage circuit breakers IEC 62271-
100
AC switches and earthing switches IEC 62271-
102
Switches and disconnectors IEC 60265-1
Combined switch/disconnectors IEC 62271-
105
Current transformers IEC 60044-1
Voltage transformers IEC 60044-2
High voltage fuses IEC 60282-1
Classification of degrees of protection for enclosures IEC 60529
In accordance with IEC recommendations, these characteristics are valid for ambient
temperatures between -25°C and +40°C.
All breaking units, including earthing switches, are contained in enclosure filled with SF6, sealed
for life according to the IEC standard EE Appendix Class III.
DESCRIPTION RM6
SELF-CONTAINED UNIT
Degree of protection
- RM6 tank IP 67
- Enclosure and operating mechanism IP 3X
Paint
- RM6 tank Unpainted
- Enclosure RAL 9002
- Front plate RAL 7016
Busbar
- Cross section Area 50 x 8 mm2
Climatic Conditions
Maximum rated current (A) 400A version 400 400 400 355
Description
Rated voltage kV rms 12 24
Operating voltage kV rms 11 22
Insualtion level:
Rated withstand voltage at power frequency: 50Hz/1 min kV rms 28 50
Rated impulse withstand voltage: 1.2/50µs kV peak 75 125
SWITCH DISCONNECTOR
Breaking capacity of fuse-switch combination kA rms 25 20
Making capacity kA peak 62.5 50
3. TECHNICAL DESCRIPTION
The technical description is presented in our leaflet : Ring main unit 3 to 24 KV “RM6 range” ref. ART.
93643
For detailed description see section 8 of this technical specification.
4. TESTS
Routine factory testing, in accordance with IEC standards, is provided for in this offer and includes the
following:
Check of conformity with wiring diagrams and plans,
Mechanical operation tests, and checking of interlocks,
Testing of the interchangeability of moving parts,
High voltage dielectric tests at the power frequency.
Low voltage dielectric tests.
Low voltage functional checking.
5.
Un: 24kV -
630A(Busbar) -
Characteristics 20 kA/1sec
Us: 22 kV
Metering
DE-BB+DE-Mt+DE- INCOMING OUTGOING
Cubicle label D CUBICLE CUBICLE
Cell
Product RM6
Internal Arc
Safety Protection - Tank
No No No
Internal Arc
--- --- ---
Protection Level
IP protection degree
IP67 IP67 IP67
- Tank
IP protection degree
- Enclosure & IP3X IP3X IP3X
Mechanism
Current 3
Q'ty / Manufacturer --- ---
Transfomer
One Set Type --- ---
Primary Current (A) --- --- 200A
1. Secondary --- --- 5A
2. Secondary --- --- N/A
3. Secondary --- --- N/A
Cable N/A
compartment Bolted Yes Yes
Interlock
Removable with N/A
NO NO
ESW interlocking
Removable with N/A
No
ESW interlocking No (optional)
(optional)
and CB interlocking
Frequency N/A
NA NA
Displaying
Standard/Superlong N/A
Handles : / Qty
Standard (1)