Specifications:: Vicinity Map Vicinity Map

This document provides a schedule of load and computations for an electrical circuit. It lists 8 circuits, showing the load, voltage, volt-amperes, amps, circuit breaker size, wire size, and conduit size for each. It specifies that all work must comply with electrical codes and utility requirements, the nature of single phase 230V 60Hz AC service, and requirements for materials, wiring methods, mounting heights, and other installation details. It calculates the total load as 9520VA, total current as 41.36A, and specifies the feeder and service wire sizes.

Uploaded by

Fahmie Pagayawan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views1 page

Specifications:: Vicinity Map Vicinity Map

This document provides a schedule of load and computations for an electrical circuit. It lists 8 circuits, showing the load, voltage, volt-amperes, amps, circuit breaker size, wire size, and conduit size for each. It specifies that all work must comply with electrical codes and utility requirements, the nature of single phase 230V 60Hz AC service, and requirements for materials, wiring methods, mounting heights, and other installation details. It calculates the total load as 9520VA, total current as 41.36A, and specifies the feeder and service wire sizes.

Uploaded by

Fahmie Pagayawan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SCHEDULE OF LOAD AND COMPUTATIONS

LOAD
CKT. V VA AMPS CB SIZE OF WIRE CONDUIT
L.O. C.O. S.O.
1 3 230 300 1.30 15 AT,2P 2- 2.00 SQ.MM TW WIRE 20 MM Ø SPECIFICATIONS:
ALL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE
2 9 230 900 3.91 15 AT,2P 2- 2.00 SQ.MM TW WIRE 20 MM Ø ELECTRICAL CODE, LOCAL ORDINANCES, AND REQUIREMENTS OF THE LOCAL ELECTRIC UTILITY COMPANY.

3 12 230 1200 5.21 20 AT,2P 2- 3.50 SQ.MM TW WIRE 20 MM Ø NATURE OF SERVICE SHALL BE SINGLE PHASE, TWO WIRE, 230 VOLTS, 60 HZ. A.C.

4 2 230 360 1.56 20 AT,2P 2- 3.50 SQ.MM TW WIRE 20 MM Ø ALL MATERIALS TO BE USED SHALL BE BRAND NEW, WITH TRADE NAME, AND OF THE APPROVED TYPE FOR THE
PURPOSE AND LOCATION INTENDED.

5 7 230 1260 5.47 20 AT,2P 2- 3.50 SQ.MM TW WIRE 20 MM Ø


WIRING METHOD TO BE USED SHALL BE: USE TYPE TW WIRES, UNLESS OTHERWISE SPECIFIED, AND RIGID
NON-METALLIC CONDUITS TO BE CONCEALED IN CEILINGS AND DOUBLE WALLS, AND EMBEDDED IN CONCRETE
6 5 230 900 3.91 20 AT,2P 2- 3.50 SQ.MM TW WIRE 20 MM Ø AND FLOOR SLABS.

7 SPARE 230 2300 10.00 20 AT,2P 2- 3.50 SQ.MM TW WIRE 20 MM Ø MOUNTING HEIGHTS SHALL BE:
SWITCHES- 1.40 M ABOVE FINISHED FLOOR LINE
CONVENIENCE OUTLETS- 0.30M ABOVE FIN. FLR. LINE/ FINISHED COUNTERS
8 SPARE 230 2300 10.00 20 AT,2P 2- 3.50 SQ.MM TW WIRE 20 MM Ø
TV & TELEPHONES OUTLETS- 0.30M ABOVE FIN. FLR. LINE
ACU OUTLETS- 1.80M MAXIMUM FROM FIN. FLR. LINE
A A1 A2 A3 9520 41.36 60 AT,2P WALL LAMPS- 2.00M ABOVE FIN. FLR. LINE
PANELBOARD- 1.75M FROM FIN. FLR. LINE TO TOP OF PANEL
EMERGENCY LIGHTS- 2.0M ABOVE FIN. FLR. LINE

SIZE OF MAIN SERVICE WIRE: PULL OR JUNCTION BOXES SHALL BE INSTALLED WHERE NECESSARY EVEN IF NOT INDICATED IN THE PLAN.
TOTAL POWER : 9520 VA USE 2- 14.00 SQ. MM THW WIRE IN
TOTAL CURRENT=9520/230=41.39 A A 32 MMØ PVC CONDUIT S-40 ALL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER.
AMPACITY OF FEEDER= 1.25 X 41.39 = 51.73 A & 60 AT,2P, 250V, ACB
11.00

4.00 4.00 3.00 1.35 FED FROM : AKELCO TOTAL LOAD :9520 VA LEGEND :
40W FLUORESCENT LAMP ACU OUTLET

4 9W COMPACT FLUORESCENT LAMP t TELEPHONE OUTLET

J JUNCTION BOX TV CABLE TV OUTLET


4.50

4.50
DN
CEILING MOUNTED EXHAUST FAN POWER SERVICE ENTRANCE

Sa ONE GANG SWITCH EMERGENCY LIGHT

3 ROOF DECK Sbc TWO GANG SWITCH PANELBOARD


10.50

Sdef THREE GANG SWITCH CIRCUIT BREAKER


13.50

4.50

4.50

CIRCUIT HOMERUN CONVENIENCE OUTLET

SERVICE ENTRANCE
TO KHM
2 1Ø, 2 WIRE, 230V, 60 HZ
1.50

1.50

PANEL
1
BOARD (PB)
3.00

3.00

M SERVICE METER
4.00 4.00 3.00 1.35
60 A, 2P, 230V
12.35

15 AT 15 AT
CKT 1 CKT 2
20 AT 20 AT
USE 2- 14.00 SQ. MM THW WIRE IN
CKT 3 CKT 4
20 AT 20 AT A 32 MMØ PVC CONDUIT S-40

CKT 5 CKT 6
20 AT 20 AT
CKT 7 CKT 8
4 ROOF DECK Plan
ID- SCALE : 1:100
PANEL BOARD 1
SINGLE LINE DIAGRAM
VICINITY MAP
SCALE NTS.

Comtractor: IJC Buildworks Solution


Build Now Pay Later

APPROVED BY: PRC NO. PROJECT TITLE AND LOCATION: OWNER:/ ADDRESS: DRAWN BY: SHEET NO.

PTR. NO. STEPHEN B. IGNACIO

ISSUED AT: PROPOSED THREE STOREY BUILDING ADDRESS: NEW BUSWANG, KALIBO, AKLAN E
WITH ROOF DECK ASNALI S. SARIP
ISSUED ON: 1200 PEDRO GIL ST. PACO MANILA
CP #: 09994292982 2/2
P.E. ENGINEER
1200 PEDRO GIL ST. PACO MANILA
TIN: EMAIL: [email protected]

You might also like