EST QS1 v2.0 Technical Reference Manual PDF
EST QS1 v2.0 Technical Reference Manual PDF
Organization This manual provides information on how to properly install, wire, and
maintain the FACP and related components, and is organized as
follows:
Chapter 1 provides a detailed description of the fire alarm control panel
and its operation.
Chapter 2 provides instructions for installing the fire alarm control
panel.
Chapter 3 provides instructions for operating the control panel.
Chapter 4 provides instructions for programming the fire alarm system
from the front panel.
Chapter 5 provides simplified wiring schematics for standard
applications.
Chapter 6 provides instructions for maintaining the system.
Appendix A provides worksheets for calculating maximum wire lengths
for notification and Signature circuits, and for sizing standby batteries.
Appendix B provides a set of bar codes that you can use to enter text
for location messages.
Appendix C provides information on how to program the SIGA–REL
using the QS–CU (QuickStart Configuration Utility).
Safety information Important safety admonishments are used throughout this manual to
warn of possible hazards to persons or equipment.
Related documentation
Edwards Systems Technology 2–CTM City Tie Module Installation Sheet (P/N 270496)
6411 Parkland Drive
CDR–3 Bell Coder Installation Sheet (P/N 3100023)
Sarasota, FL 34243
DLD Dual Inline Dialer Installation Sheet (P/N 3100187)
PS6 Power Supply Card Installation Sheet (P/N 3100201)
QSA–1(X), QSA–2(X) Remote Annunciator Cabinet Installation
Sheet (P/N 3100295)
QS–CPU(X) CPU/Display Unit Installation Sheet (P/N 3100276)
SL30, SL30–1 LED/Switch Card Installation Sheet (P/N
3100193)
SLIC Signature Intelligent Controller Card Installation Sheet
(P/N 3100192)
RS485 (NT–A) Card and QS–232 UART Module Installation
Sheet (P/N 3100191)
ZR8 Relay Card Installation Sheet (P/N 3100190)
SIGA–APS Auxiliary Power Supply Installation Sheet (P/N
387342)
Signature Series Intelligent Smoke and Heat Detectors
Applications Bulletin (P/N 270145)
Signature Series Component Installation Manual (P/N 270497)
EST Strobe Applications Guide (P/N 85000-0049)
QuickStart Online Help Utility (P/N 7350047)
QuickStart ULI and ULC Compatibility Lists (P/N 3100335)
Network Hardware Technical Reference (P/N 250100)
Document history
Summary
This chapter provides a detailed description of the fire alarm control panel and its
operation.
Content
System overview • 1.2
Component descriptions • 1.3
Circuit descriptions • 1.4
Controls and indicators • 1.7
Controls and indicators behind the flip-down cover • 1.8
Controls and indicators on the zone annunciator card • 1.9
Interpretation of screen displays • 1.10
• 4.5 amps of 24 Vdc power for external notification • Executes the appropriate programmed output
appliances response for the input that signaled the event
• Battery charger capable of charging batteries rated • Sends a record of the event to the appropriate
up to 40 Ah. Maximum battery size for ULC display queue and out the serial port
applications is 30 Ah If there is no operator in attendance, the panel displays
• Up to eight, fully-supervised, mirrored or customized the content of the highest priority display queue
remote annunciators containing a record.
If there is an operator in attendance, the panel displays
Minimum system requirements the content of the current display queue regardless of
any new events introduced into the system.
A Local Protected Premises Fire Alarm System requires
only the FACP (CPU, PS6, and enclosure) with at least
one SLIC programmed with at least one audible output Failsafe operating mode description
circuit and one alarm input circuit. The panel operates in failsafe mode when the CPU
In addition to the hardware requirements of a Local loses the ability to communicate with the PS6 and JP1
system: on the PS6 is in the ON position. When this happens,
the power supply:
• Add a 2–CTM City Tie Module for an Auxiliary Fire
Alarm System • Closes the common trouble relay contacts
• Add a DLD Dual Line Dialer Card or RPM Reverse • Instructs the dialer to send the default trouble
Polarity Module for a Remote Supervising Station message
Fire Alarm System • Monitors the system for any alarm events
• Add a DLD Dual Line Dialer Card or RPM Reverse If an alarm event occurs, the power supply:
Polarity Module for a Central Station Fire Alarm
System • Changes the contact positions on the common alarm
relay
• Add a SIGA–REL and SIGA–APS for Releasing
Device Service • Turns on all conventional common alarm outputs.
Signature common alarm outputs are not affected.
Normal operating mode description • Instructs the dialer to send the default alarm
message
The panel operates in normal mode in the absence of
any alarm, supervisory, trouble, and monitor events. In
normal mode, the control panel monitors the system for
1 2 3 4 5 6 7
J6
J5
J7
J8 J3
JP1 CONFIGURATION
PIN 1 & 2 = MODEM PWR
PIN 2 & 3 = RTS
JP1
3 1 J2
9 8
1. SL30 LED/Switch Card: Provides thirty circuits for 6. SLIC Signature Loop Intelligent Controller Card:
point or zone annunciation. Each circuit has two LEDs Provides one Class A or Class B signaling line circuit
for annunciating alarm, supervisory, and trouble (loop) for connecting Signature series detectors and
signals, and a button numbered from 1 to 30. modules. The SLIC also provides two Class A or Class
B notification appliance circuits (NACs) for connecting
2. CPU/Display: Provides operator access to system
polarized 24 Vdc notification appliances (horns,
messages, status information, and programming strobes).
menus, and executes system responses based on the
panel programming. 7. DLD Dual Line Dialer Card: Provides two
telephone line connections for sending system
3. AC wiring block and fuse holder: Provides
messages to a compatible Digital Alarm Communicator
connections for mains ac (primary power) and 5A fuse.
Receiver.
4. Cabinet enclosure: Houses the panel electronics
8. Standby batteries: Provides dc power to the panel
and standby batteries.
electronics in the absence of ac power.
5. PS6 Power Supply Card: Provides primary dc
9. Transformer: Converts 120 Vac or 240 Vac supply
power for the panel electronics and auxiliary power for
into 24 Vdc for the panel electronics.
external circuits. The PS6 also provides common
alarm, supervisory and trouble relays.
Circuit descriptions
PS6 Power Supply Card
1. Relay 1 (Common Alarm)
Style: Form C
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF) 2 3 4 5 6
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
1 7
Nonsupervised and power-limited only when
connected to a power-limited source
2. Relay 2 (Common Supervisory)
Style: Normally-open
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when
connected to a power-limited source
3. Relay 3 (Common Trouble)
Style: Normally-open, held closed
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when
connected to a power-limited source
4. Relay 4 (Programmable)
Style: Normally-open
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when 9 8
connected to a power-limited source
5. Smoke/Accessory Power
Output: Continuous or interruptible via jumper
selection
Voltage: 24 Vdc, regulated
Current: 250 mA
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Supervised and power-limited
6. RS485 8. AUX Power #1, #2, and #3
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²) Voltage: 17.5 – 26.4 Vdc FWR (full wave rectified)
Wire type: Twisted pair, six twists per foot minimum Current: 1.5 A each
Circuit capacitance: 0.4 µF Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Circuit resistance: 100 Ω Power-limited and supervised for short circuit
Supervised and power-limited conditions only
7. RS232 9. Battery Circuit
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²) Charge current: 2 A
Nonsupervised and power-limited Charge capacity: 40 Ah (UL), 30 Ah (ULC)
Wire length: 20 ft maximimum Supervised and nonpower-limited
1. NAC #1
Configuration: Class B or Class A
Output voltage: 24 Vdc, nominal
Output current: 2.0 A @ 24 Vdc 1 2
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
End of line resistor: 10 kΩ, 1/2W
Supervised and power-limited
2. NAC #2
Configuration: Class B or Class A
Output voltage: 24 Vdc, nominal
Output current: 1.0 A @ 24 Vdc
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
End of line resistor: 10 kΩ, 1/2W
Supervised and power-limited
3. Signature Loop
Configuration: Class B (Style 4) or Class A (Style 6)
Capacity: 125 Signature detectors, 125 Signature single-address
modules
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
4 3
Circuit resistance: 65 Ω
Circuit capacitance: 0.3 µF
Supervised and power-limited
4. NAC Riser In/Out
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
1. Dry-contact relays R1 – R4
Outputs: Normally-open or normally-closed contacts via jumper 1
selection
Contact rating: 24 Vdc @ 1.0 A
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised, and power-limited only when connected to a
power-limited source
2. Dry-contact relays R5 – R8
Outputs: Normally-open or normally-closed contacts via jumper
selection
Contact rating: 24 Vdc @ 1.0 A
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised, and power-limited only when connected to a
power-limited source
1. Line #1
Supervised and nonpower-limited
2. Line #2
Supervised and nonpower-limited 1 2
1 2 3 4 5 6 7 8 9
12
11
10
1. Text display and controls: Displays system 5. Monitor LED: Indicates the panel posted a monitor
messages, status information, programming menus. event record into the corresponding display queue.
6. Trouble LED: Indicates the panel posted a trouble
Moves the cursor up one line at a time or to the event record into the corresponding display queue.
previous record in the display queue
7. Ground Fault LED: Indicates a ground fault in the
Moves the cursor down one line at a time or to system wiring. Ground faults also signal a system
the next record in the display queue trouble.
8. CPU Fail LED: Indicates an unexpected reboot or
Moves the cursor right one character at a time failure with the microprocessor. CPU failures also
or to the next display queue signal a system trouble.
Moves the cursor left one character at a time 9. Power LED: Indicates the panel has ac power.
or to the previous display queue 10. Panel Silence/Acknowledge button/LED: Turns
off the panel buzzer and acknowledges all events. The
Enters operator input and selects menu items Panel Silenced LED indicates that all off normal events
2. Alarm LED: Indicates the panel posted an alarm have been acknowledged and the internal buzzer is
event record into the corresponding display queue. off.
3. Supervisory LED: Indicates the panel posted a 11. Status button: Displays the Status menu from
supervisory event record into the corresponding which you can identify active or disabled points in the
display queue. system.
4. Disable/Test LED: Indicates part of the system is 12. Help button: Provides additional information for
disabled or is currently under test. Disabled the event record selected on the display.
components also signal a system trouble.
7 8 9 2
4 5 6
1 2 3 4 5 6 7 8 9 0
1. Enable Controls key switch: Gives priority access 6. Drill button: Turns notification appliances on
to control functions reserved for operators with Level 2 according to the panel programming but does not
access. place the panel in alarm. The LED indicates when the
panel is in Drill mode.
2. Barcode scanner jack: Input point for optional
barcode scanner. 7. Menu button: Displays the operator menus.
3. Numeric keypad: Numbered buttons for entering 8. Delete button: Returns to the previous menu or
data and selecting menu options. back spaces the cursor.
4. Reset button: Restores devices or zones in alarm 9. Enter button: Press the Enter button to accept
or trouble to their standby condition. The LED indicates information from the operator or continue to the next
when the panel is resetting. item.
5. Alarm Silence button: Turns active notification
appliances off according to the panel programming.
Pressing Alarm Silence a second time turns them back
on. The LED indicates when the panel is in alarm and
operating with notification appliances turned off.
1 2 3
1 6 11 16 21 26
2 7 12 17 22 27
3 8 13 18 23 28
4 9 14 19 24 29
5 10 15 20 25 30
1. Zone display button: Displays an event record for Note: ULC requires that every fire panel have the
each device in the corresponding zone that signaled capability to visually display system status by means of
an alarm. specific indicators for each zone. All status changes
must clearly indicate that the information is an Alarm
2. Zone active LED: Indicates a device in the
(ALM), Supervisory (SUP), Trouble (TBL), or Monitor
corresponding zone signaled an alarm condition. (MON).
3. Zone trouble LED: Indicates a device or wiring fault
in the corresponding Zone.
Project Name
Alarm History:
nnnn
HH:MM:SS This is what the panel display looks like when there are event records
Axxx Dxxx posted in a display queue.
HH:MM:SS is the current time in hours, minutes, and seconds
nnn event name
Axxx is the current number of active points
Custom message 1
Custom message 2 Dxxx is the current number of disabled points
Summary
This chapter provides instructions for installing the fire alarm control
panel.
Content
Installation do's and don'ts • 2.2
Installation checklist • 2.3
Two ways to install the cabinet: Surface or semi-flush mount • 2.4
How to assemble the panel • 2.5
Wiring mains ac and earth ground • 2.6
System jumper settings • 2.7
System addressing • 2.9
Terminal definitions • 2.12
Connecting a PT–1S printer • 2.18
Installing standby batteries • 2.19
Connecting a service computer • 2.20
When installing circuit boards... DO ground yourself with an approved static-protective wrist
strap when handling circuit boards.
DO keep circuit boards in their protective antistatic packaging.
Remove only for inspection or installation.
DO NOT touch component leads and connector pins when
handling circuit boards.
DO disconnect ac power and batteries before installing or
removing circuit boards. Installing or removing circuit boards
while the control panel is energized may damage the
equipment.
When installing circuit wiring... DO use appropriately sized wire for the application. Incorrectly-
sized wires degrade circuit performance.
DO make sure there are no wire-to-ground shorts or wire-to-
wire shorts before connecting field wires to the panel.
DO NOT over tighten screw terminals. Over tightening may
strip screw terminal threads and cause loose connections.
When installing Signature loops... DO NOT install more than fifteen SIGA–UMs or MABs
configured for two-wire smoke detectors on a loop.
DO NOT install more than seven SIGA–UMs or MABs
configured for two-wire smoke detectors on loops with isolator
devices.
DO NOT install more than ten SIGA–RELs on a loop. You must
use the QuickStart configuration utility to program a SIGA–REL.
Refer to the technical manual supplied with the SIGA–REL and
appendix C of this manual for programming information.
When installing standby batteries... DO NOT install standby batteries until after you completely
install and test the system.
Installation checklist
¨ Prepare the site Make sure the installation location is free from construction dust
and debris, and immune to extreme temperature ranges and
humidity.
Allow enough floor and wall space so the panel can be installed
and serviced without obstructions.
Pull and tag all field wiring. See Appendix A for wire length
calculations.
¨ Unpack the equipment Open the shipping container and carefully unpack the
equipment. Check for any visible signs of damage. If there is
any damage, return the equipment to the place of purchase.
Keep the shipping container and packing material until after
completely installing and testing the equipment. Use the
shipping container to return the equipment to the manufacturer.
Verify the shipping container contains the correct parts. If any
parts are missing or damaged, return the equipment to the
manufacturer.
¨ Install the cabinet
¨ Assemble the panel
¨ Wire mains ac and earth ground Bring the primary power conductors into the left side
(nonpower-limited area) of the cabinet and wire to the ac
terminal block.
¨ Connect the field wiring Bring the field wiring into the power-limited area of the cabinet.
Verify there are no open or shorts then connect the wires to
their respective terminals.
¨ Use the AutoLearn and AutoLoop Refer to chapter 4.
utilities to configure the system
¨ Customize the system Refer to chapter 4.
configuration
¨ Install the standby batteries Do not connect standby batteries to the panel until after
completely testing the panel.
¨ Perform system acceptance tests
18-3/16 in
(46.2 cm)
H G
(L1) (E)
N
(L2)
System addressing
Card addresses ON ON
= 01 = 08
Each option card installed in the panel is 1 2 3 4 1 2 3 4
= 04 = 11
14: Reserved for the DLD 1 2 3 4 1 2 3 4
= 05 = 12
1 2 3 4 1 2 3 4
ON ON
= 06 = 13
1 2 3 4 1 2 3 4
ON
= 07
1 2 3 4
01
PPCC006 PPCC007
PPCC005 PPCC008
GG02 2 7 12 17 22 27
GG03 3 8 13 18 23 28
GG04 4 9 14 19 24 29
GG05 5 10 15 20 25 30
Terminal definitions
SMOKE
RELAY 1 RELAY 2 RELAY 3 RELAY 4 ACC PWR RS485 RS232
NO C NC C NO C NO C NO N.C. + – + – RTS TX RX COM
TB1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
BATT PWR
+ – NC
TB2
1 2 3
AUX POWER
AUX1 AUX2 COM AUX3 COM
TB3
1 2 3 4 5
NAC 1 NAC 2
B+ B– A+ A– B+ B– A+ A–
TB1
1 2 3 4 5 6 7 8
OUT IN LOOP
+ – + – A+ A– B+ B–
TB2
1 2 3 4 5 6 7 8
+ R1 – + R2 – + R3 – + R4 –
TB1
1 2 3 4 5 6 7 8
+ R5 – + R6 – + R7 – + R8 –
TB2
1 2 3 4 5 6 7 8
RS485
+ CH2 – + CH1 –
TB1
1 2 3 4
LINE 1 LINE 2
IN OUT IN OUT
TIP RING TIP RING TIP RING TIP RING
TB1
1 2 3 4 5 6 7 8
JB1
connections on the IOP3A then plug the cable
UP
1
2
3
into the printer.
SW1
PS6 TB1–17
4. Configure the IOP3A as follows:
JP1 = 2–3
JB4
JP2 = ON
JP3 = ON
JP4 = ON IOP3A
TO
SW1 = UP PT–1S
7 32
5. Set the printer switches for 9600 bps, 8 bits,
TB3 TB2
no parity. Refer to the documentation included
JB3
JB2
+ + – –
BC-1
Summary
This chapter provides instructions for operating the control panel.
Content
Instructions for the Level 1 operator (public mode access) • 3.2
Instructions for the Level 2 operator (emergency mode access) • 3.5
Instructions for the Level 3 operator (maintenance mode access) • 3.7
Instructions for the Level 4 operator (service mode access) • 3.10
QuickReference list • 3.11
Log onto the panel as a Level 2 Turn the Enable Controls key 1/4 of a turn clockwise.
operator
— or —
1. Press Menu.
2. Choose Login then enter the password required for Level 2
access.
Change the password required for 1. From the Main Menu, select Program.
Level 2 access
2. Select Edit Password.
3. Select Level 2 then enter the new password.
Reset the alarm history counter 1. From the Main Menu, select Program.
2. Select Reset.
3. Enter the panel's address.
QuickReference list
Required access level
What is it you want to do L1 L2 L3 L4
Change smoke detector sensitivity settings to their alternate values ü ü ü
Change smoke detector sensitivity settings to their primary values ü ü ü
Change the current state of an LED (manual override) ü ü
Change the current state of an output circuit (manual override) ü ü
Change the password required for Level 1 access ü ü ü
Change the password required for Level 2 access ü ü
Change the password required for Level 3 access ü
Change the password required for Level 4 access ü
Disable or enable a device ü ü ü
Disable or enable a switch on a zone display ü ü
Disable or enable a zone ü ü ü
Disable or enable all the devices on a single card ü
Disable or enable an And Group, Matrix Group, or Time Control ü ü
Disable or enable the mapping function on an SLIC ü ü
Get a list of all the active points on a panel ü ü ü ü
Get a list of all the hardware and software components installed on a ü ü
panel and their revision levels
Get a list of smoke detectors that may require servicing (DIRTY attribute ü ü ü ü
greater than 20%)
Get a list of smoke detectors that require servicing (DIRTY attribute ü ü ü ü
greater than 80%)
Get the attributes for a single smoke detector ü ü ü ü
Get the attributes for all the smoke detectors on a single SLIC ü ü ü ü
Identify output devices that are turned on ü ü ü ü
Identify active points in a Service Group that is being tested ü ü ü ü
Identify points that are disabled ü ü ü ü
Identify points that are in their active state ü ü ü ü
Identify points that are in trouble ü ü ü ü
Log onto the panel as a Level 2 operator ü ü ü
Log onto the panel as a Level 3 operator ü ü
Log onto the panel as a Level 4 operator ü
Perform a lamp test ü ü ü ü
Summary
This chapter provides instructions for programming the fire alarm system
from the front panel. Worksheets are provided at the end of the chapter
to use as programming aids and to document the system programming.
Content
Overview • 4.2
QuickStart setup instructions • 4.4
Customizing the system configuration • 4.12
Setting up an Output Group • 4.19
Setting up a Zone • 4.22
Overview
ZONE 1
FACP
ZONE 2 ZONE 3
J
What is an Output Group? An Output Group is a function in the system software that
establishes the correlation between input circuits and
responses. When an input changes states, the condition of the
input determines which response the panel runs. For example,
a smoke detector initiates the Active response when it signals
an alarm condition but initiates the Trouble response when
removed from its base.
Output 1
ZONE 1
Active
Trouble
Output 2
Active
Trouble
Step 2: 1. Verify that each circuit card installed in the control panel
Apply power to the system has a unique card address.
2. Apply power to the control panel and to all the remote
annunciators.
After applying power, the panel CPU performs a diagnostic
check in the background. You can not begin programming
until this finishes and the AutoLearn option becomes
available.
Step 10: Run the AutoLoop utility on each loop controller installed in
AutoLoop the loop controller the control panel.
cards
Caution: When the system reboots, the loop controller
reinitializes the loop. If you attempt to run the AutoLoop utility
during this time, you could corrupt the project database.
Step 11: At this point, you have configured the project database for a
Saving the project database general alarm system. Refer to Table 4-2, Table 4-3, and
Table 4-4 for initial system settings.
Tip: Only Save and Sync after you
have finished programming the control If you want to accept the general alarm system configuration,
panel and you want to update the choose Save and Sync.
project databases in the remote If you want to make changes to the system configuration,
annunciators. choose Save, and then make your changes. See Customizing
the system configuration. After making all of your changes:
1. Press Menu.
2. Choose Login then enter the password required for Level 4
access.
3. Choose Program > Configure > Exit.
4. Choose Save and Sync.
Note: If the local AHJ requires a hard copy of your site
programming, use the QuickStart Configuration Utility to
retrieve the database from the panel and print the required
information.
Alarm Silence Audible only Turns off Audible and Common Alarm Output circuits CU
when someone presses Alarm Silence.
Drill Audible only Turns off Audible and Common Alarm Output circuits CU
when someone presses Drill.
Drill Activation Type Steady The Drill signal is a constant signal. CU
Alarm Signal None Alarm Silence or Reset functions are not inhibited. You FPP/CU
Silence/Reset Inhibit can turn off (silence) notification circuits or reset the
panel any time after notification circuits are activated.
Buzzer Reminder Time Indefinitely The panel trouble buzzer remains silenced until the No
control panel processes a new off-normal signal.
AC Power Trouble 6h The panel will operate on battery power for 6 hours FPP/CU
Delay before signaling a trouble condition.
Two-stage Timer 0 s (UL) The panel will turn on notification circuits immediately CU
300 s (ULC) after processing an alarm signal (UL) or after 5 minutes
(ULC).
Zone Resound Inhibit No Turn silenced NAC circuits back on if an active alarm No
input circuit remains in the active condition after
resetting the panel.
Primary Routing All Cabinets Distribute event records to all panels in the system CU
when primary routing is activated.
Alternate Routing All Cabinets Distribute event records to all panels in the system CU
when alternate routing is activated.
Language English (U.S.) U.S. English displayed on CPU/Display. No
Relay 1 Type Alarm Alarm events cause the contact positions of Relay 1 on No
the PS6 to change positions.
Relay 2 Type Supervisory Supervisory events cause the contact positions of Relay No
2 on the PS6 to change positions.
Relay 3 Type Trouble Trouble events cause the contact positions of Relay 3 No
on the PS6 to change positions.
Relay 4 Type Monitor Monitor events cause the contact positions of Relay 4 CU
on the PS6 to change positions.
Note: If you use Signature devices from another system, the AutoLoop utility uses the attributes programmed from
the previous system as the initial settings for a general alarm system.
Make information about the installer available 1. On the Configure menu, choose System > User
on the CPU/Display Labels.
AutoLearn default: No text 2. Choose Facility Name, scan in the name of the
project, and then press Enter.
3. Choose Inst Company, scan in the name of the
installing company, and then press Enter.
4. Choose Phone Number, scan in the telephone
number to call for service-related issues, and
then press Enter.
5. Choose Programmer, scan in the name of the
person that programmed the system, and then
press Enter.
6. Choose Exit.
Set how long notification circuits must stay on 1. On the Configure menu, choose System >
before pressing Alarm Silence can turn them ALM/RST Inhib.
off or pressing Reset can reset the panel
2. Select a time delay from the pick list then press
AutoLearn default: None (no delay) Enter.
Set how long the panel must wait before 1. On the Configure menu, choose System > AC
signaling an ac power failure Power Dly.
AutoLearn default: 0 (no delay) 2. Select a time delay from the pick list then press
Enter.
Change the performance class of the Signature 1. On the Configure menu, choose Cards > Edit
loop wiring then enter the card address number.
AutoLearn default: Wiring is Class B. 2. Choose Config Card.
3. Choose Wiring Class then choose how the loop
is wired to the SLIC.
4. Choose Exit > Save Edits, then wait while the
database is updated.
Enter location message text for an automatic 1. On the Configure menu, choose Cards > Edit
detector and then enter the card address number of the
loop controller.
2. Choose Config Detect > Edit > Enter Serial #
and then scan or enter the detector's serial
number.
3. Choose Message then scan in the text that you
want sent when the detector signals an event.
4. Choose Exit > Save Edits.
Change the Alarm Verification setting of a 1. On the Configure menu, choose Cards > Edit
smoke detector and then enter the card address number of the
loop controller.
2. Choose Config Detect > Edit > Enter Serial #
and then scan or enter the detector's serial
number.
3. Choose Verification then choose the length of
the alarm verification period.
4. Choose Exit > Save Edits.
Enter location message text for a circuit on a 1. On the Configure menu, choose Cards > Edit
SIGA module and then enter the card address number of the
loop controller.
2. Choose Config Module > Edit > Enter Serial #
and then scan or enter the serial number of the
module.
3. For a single-address module or the first
address of a dual-address module, choose
Device 1.
— or —
For the second address of a dual-address
module, choose Device 2.
4. Choose Message, scan in the text, and then
press Enter.
5. Choose Exit.
Change the device type for a circuit on a SIGA 1. On the Configure menu, choose Cards > Edit
module and then enter the card address number of the
loop controller.
Note: The device types shown in the pick lists vary
depending on the SIGA module. The device types 2. Choose Config Module > Edit > Enter Serial #
shown in the pick lists for the second address of a and then scan or enter the serial number of the
dual-address module also vary depending on the module.
device type chosen for the first address.
3. For a single-address module or the first
address of a dual-address module, choose
Device 1.
— or —
For the second address of a dual-address
module, choose Device 2.
4. Choose Type, select a device type from the
pick list, and then press Enter.
5. Choose Exit.
Change the personality code for a circuit on a 1. On the Configure menu, choose Cards > Edit
SIGA module and then enter the card address number of the
loop controller.
Note: The personality codes shown in the pick lists
vary depending on the SIGA module and the 2. Choose Config Module > Edit > Enter Serial #
chosen device type. and then scan or enter the serial number of the
module.
3. For a single-address module or the first
address of a dual-address module, choose
Device 1.
— or —
For the second address of a dual-address
module, choose Device 2.
4. Choose Personality, select a personality code
from the pick list, and then press Enter.
5. Choose Exit.
Alarm Device type assigned to IDC circuits that connect to automatic or a combination of automatic
and manual alarm-signal initiating devices. Alarm circuits signal Alarm Active events.
Alarm Output Device type assigned to IDC/NAC circuits that connect to notification appliances that you want
turned on automatically when the panel processes an alarm signal. Alarm Output circuits turn
off when you press Alarm Silence and turn on when you press Drill.
Audible Device type assigned to IDC/NAC circuits that connect to audible notification appliances
(horns). Audible circuits turn off when you press Alarm Silence and turn on when you press
Drill.
Heat Device type assigned to IDC circuits that connect to automatic alarm-signal initiating devices
that detect a rise in the surrounding temperature. Heat circuits signal Heat Alarm events.
Monitor Device type assigned to IDC circuits that connect to monitor-signal initiating devices that
monitor the operation of ancillary system functions. Monitor circuits signal Monitor events.
Output Device type assigned to IDC/NAC circuits that supervise their output wiring for opens and
shorts. Output circuits do not turn off when you press Alarm Silence or turn on when you press
Drill.
Pull Device type assigned to IDC circuits that connect to manually operated alarm-signal initiating
devices. Pull circuits signal Pull Station events.
Supervisory Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that
detect abnormal conditions that could make the sprinkler system inoperative or ineffective.
Supervisory circuits signal Supervisory events.
Tamper Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that
detect when someone tampers with a component of the sprinkler system. Tamper circuits signal
Tamper events.
Verified Smoke Device type assigned to IDC circuits that connect to automatic alarm-signal initiating devices
that use alarm verification. Verified Smoke circuits signal Alarm Verify events when the fire
condition is first detected then Alarm Active events after verifying the fire condition exists.
Visible Device type assigned to IDC/NAC circuits that connect to visual notification appliances
(strobes). Visible circuits do not turn off when you press Alarm Silence or turn on when you
press Drill unless programmed to do so.
Water Flow Device type assigned to IDC circuits that connect to alarm-signal initiating devices that detect
water flowing through the sprinkler system. Water Flow circuits signal Waterflow events.
Before you begin Before you begin, you should complete an Output Group
Programming Worksheet (Figure 4-6) for each Output group.
Keep a copy for your records.
Response Description
PppCccDddd 1234 This is what the panel display looks like when you review a response for an output
circuit.
P:pp C:cc D:ddd is the address of the of the output circuit (P = panel number, C =
card number, D = device number)
1 is the command direction (B = Both activation and restoration, A = Activation only,
R = Restoration only)
2 is the command (N = no operation, A = Activate, E = Enable, R = Restore, I =
Disable, D = Delay)
3 is the priority attribute (S = Set, A = Latch, L = Low, M = Medium, H = High)
4 is the command attribute (S = Set, R = Reset, W = 20 bpm, F = 120 bpm, T =
Temporal)
PppCccDddd 1234 This is what the panel display looks like when you review a response for an LED.
P:pp C:cc D:ddd is the address of the of the output circuit (P = panel number, C =
card number, D = device number)
1 is the command direction (B = Both activation and restoration, A = Activation only,
R = Restoration only)
2 is the command (N = no operation, A = Activate, E = Enable, R = Restore, I =
Disable, D = Delay)
3 is the priority attribute (S = Set, A = Latch, L = Low, M = Medium, H = High)
4 is the command attribute (S = Steady, R = Restore, W = Slow Blink, F = Fast
Blink)
Delay: ssss 1 This is what the panel display looks like when you review a response for delay.
ssss is the amount of delay in seconds
1 is the command direction (B = Both activation and restoration, A = Activation only,
R = Restoration only)
ACCT12QEEEGGPPP This is what the panel display looks like when you review a response for dialer
string.
— or —
ACCT is the 4-digit subscriber account number (0000–9999)
ACCT12PP
1 is the priority attribute (L = Life Safety, P = Property, S = System Integrity)
2 s the command direction (B = Both activation and restoration, A = Activation only,
R = Restoration only)
For Contact ID dialer strings:
Q is the event qualifier (1 = activation event, 3 = restoration event)
EEE is the event code. See Table 4-9.
GGPPP is the point being reported
For 4/2 dialer strings:
PP is the point being reported (00–99)
Setting up a Zone
Before you begin Before you begin, you should complete a Zone Programming
Worksheet (Figure 4-7) for each Zone. Keep a copy for your
records. You will also need to refer to the Output Group
programming worksheets.
To set up a Zone:
1. On the control panel, press Menu.
2. Choose Login then enter the password required for Level 4
access.
3. Choose Program > Configure > Zone.
4. To program a new Zone, choose Add, and then choose a
zone type (Alarm, Supervisory, or Monitor).
— or —
Choose Edit, select an existing zone from the pick list, and
then press Enter.
Configure the Zone 1. Choose Message, scan in the message text, and then
press Enter.
2. Choose Members, then for each device that comprises the
Zone:
Choose Device Address, then enter the member's device
number from the worksheet
— or —
Choose Enter Serial#, scan in or enter the member's serial
number.
3. Choose Review to verify which devices you added to the
Zone. If you added any devices in error, delete them.
4. Choose Output Group > Add, then select the Output group
from the pick list that contains the responses you want
activated, and then press Enter.
Repeat for each Output group you want to add.
5. Choose Review to verify which Output groups you added to
the Zone. If you added any Output groups in error, remove
them.
6 For coded systems, choose Coding, and then enter the
Zone Code.
# of CMS receivers: ¨1 ¨2
Retry Count: ¨ 5 ¨ 6 ¨ 7 ¨ 8 ¨ 9 ¨ 10
004
001 ¨ NC (normally-closed) 004+ 004–
003
¨ NO (normally-open) 002
Device type: 001 JP4
002 ¨ NC (normally-closed)
¨ NO (normally-open) NC
Device type:
NO
003 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
NC
004 ¨ NC (normally-closed)
NO
¨ NO (normally-open)
Device type:
006 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
007 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
008 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
Card:
NAC 1 device type: ¨ Audible ¨ Visible NAC 2 device type: ¨ Audible ¨ Visible
Wiring class: ¨ Class A ¨ Class B
Number of detector addresses used on loop:
Number of module addresses used on loop:
Card:
NAC 1 device type: ¨ Audible ¨ Visible NAC 2 device type: ¨ Audible ¨ Visible
Wiring class: ¨ Class A ¨ Class B
Number of detector addresses used on loop:
Number of module addresses used on loop:
Card:
NAC 1 device type: ¨ Audible ¨ Visible NAC 2 device type: ¨ Audible ¨ Visible
Wiring class: ¨ Class A ¨ Class B
Number of detector addresses used on loop:
Number of module addresses used on loop:
Card:
NAC 1 device type: ¨ Audible ¨ Visible NAC 2 device type: ¨ Audible ¨ Visible
Wiring class: ¨ Class A ¨ Class B
Number of detector addresses used on loop:
Number of module addresses used on loop:
Verification: ¨ None ¨ 12 s ¨ 24 s ¨ 36 s ¨ 60 s
Message: 1) 2)
Verification: ¨ None ¨ 12 s ¨ 24 s ¨ 36 s ¨ 60 s
Message: 1) 2)
Verification: ¨ None ¨ 12 s ¨ 24 s ¨ 36 s ¨ 60 s
Message: 1) 2)
Verification: ¨ None ¨ 12 s ¨ 24 s ¨ 36 s ¨ 60 s
Message: 1) 2)
Device #1 Device #2
Personality: Personality:
Message: 1) Message: 1)
2) 2)
Device #1 Device #2
Personality: Personality:
Message: 1) Message: 1)
2) 2)
Device #1 Device #2
Personality: Personality:
Message: 1) Message: 1)
2) 2)
Device #1 Device #2
Personality: Personality:
Message: 1) Message: 1)
2) 2)
Zone Code:
Message: 1)
2)
Summary
This chapter provides simplified wiring schematics for standard
applications.
Content
Notification appliance circuits • 5.2
Initiating device circuits • 5.4
Coded alarm signaling • 5.6
Remote station protective signaling system • 5.8
Auxiliary protective signaling • 5.10
SLIC
Note: The plus and
minus symbols
NAC1 B+ indicate signal
polarity when the
NAC1 B– NAC circuit is turned
on.
NAC1 A+
NAC1 A–
UL/ULC LISTED
10 KΩ EOLR
NAC2 B+
NAC2 B–
NAC2 A+
NAC2 A–
UL/ULC LISTED
10 KΩ EOLR
SLIC
Note: The plus and
minus symbols
NAC1 B+ indicate signal
polarity when the
NAC1 B– NAC circuit is turned
on.
NAC1 A+
NOT USED UL/ULC LISTED
NAC1 A– 10 KΩ EOLR
NAC2 B+
NAC2 B–
NAC2 A+
NOT USED UL/ULC LISTED
NAC2 A– 10 KΩ EOLR
UL/ULC LISTED
47 KΩ EOLR
10 9
SIGA–CC1 SIGA–RM1
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
PS6
AUX(n)
COM
SLIC
TO DATA IN TERMINALS
LOOP B+ ON NEXT DEVICE
LOOP B–
Note: The plus and minus symbols indicate signal polarity when the NAC circuit is turned on.
Typical NAC riser wiring
PS6
24VDC+
24VDC–
JP2
ACC PWR
UL/ULC LISTED
SMK PWR 8 7 47 KΩ EOLR
SIGA–CT1
4 3 2 1
SLIC
LOOP B+ TO DATA IN TERMINALS
LOOP B– ON NEXT DEVICE
PS6
UL/ULC LISTED
24VDC+ 22 KΩ EOLR UL/ULC LISTED
24VDC– 15 KΩ EOLR
JP2
ACC PWR
14 13 3-2-1 12 11 10 9
SMK PWR
2–SMK SIGA–UM
8 7 6 5 4 3 2 1
SLIC
LOOP B+ TO
DATA IN TERMINALS
LOOP B– ON NEXT DEVICE
PS6
UL/ULC LISTED
24VDC+ 22 KΩ EOLR
24VDC–
JP2
ACC PWR
14 13 3-2-1 12 11 10 9
SMK PWR
2–SMK SIGA–UM
8 7 6 5 4 3 2 1
SLIC
LOOP B+ TO
DATA IN TERMINALS
LOOP B– ON NEXT DEVICE
1 2 3
PS6TB1–16
PS6TB1–18
PS6TB1–12
PS6TB1–11
TB1
TB2
JP1 JP2
CDR–3
Figure 5-2: Coded alarm signaling wiring (coded alarm signal only)
PS6TB1–16
PS6TB1–18
PS6TB1–12
PS6TB1–11
TB1
TB2
JP1 JP2
CDR–3
Figure 5-3: Coded alarm signaling wiring (coded signal followed by evacuation signal)
1 2 3
Figure 5-4: Typical equipment layout, Remote station protective signaling application
PS6 RPM
Note: Plus and minus symbols indicate signal polarity when the circuit is active.
Wire as shown in Figure 5-6. Program the SIGA–CC1 as a common alarm output device. Plus and
minus symbols indicate signal polarity with the circuit turned on.
10 9 1 2
SIGA–CC1 2–CTM
8 7 6 5 4 3 2 1 2 1
LISTED 24VDC
SUPPLY Master box
24VDC+
24VDC–
TO NEXT DEVICE
SLIC
LOOP B+ TO DATA IN TERMINALS
LOOP B– ON NEXT DEVICE
Summary
This chapter provides instructions for maintaining the system.
Content
Pseudo point definitions • 6.2
Table 6-1: Main Panel pseudo points • 6.2
Table 6-2: Remote Annunciator pseudo points • 6.2
Table 6-3: Power Supply pseudo points • 6.3
Table 6-4: SLIC card pseudo points • 6.3
Table 6-5: Dialer pseudo points • 6.4
Table 6-6: General CPU pseudo points • 6.5
Maintenance tasks • 6.6
Panel xx Card Communications Trouble CPU has failed to communicate with the option
card at address xx.
Panel 01 Reset Extension Monitor/Trouble Signature loop is still resetting.
Panel 01 Service Active Trouble Trouble Service group was restored with a device still in
the active condition.
Pnl 0x Database Incompatible Trouble Changes made to the system programming on the
control panel were not updated in this unit.
Panel 01 Reboot Fault Control panel CPU restarted unexpectedly.
Panel 0x, CH1 Communications Trouble Annunciator is not communicating on RS485
channel 1.
Panel 01 Task Failure Trouble Internal processing fault.
Card xx Setup Mismatch Trouble CPU encountered problem configuring the option
card at address xx.
Dailer Setup Mismatch Trouble A problem has occurred with the CPU configuring
the dialer card.
Power Supply Setup Mismatch Trouble A problem has occurred with the CPU configuring
the POWER supply card.
Panel 01 LED/Switch display Trouble LED/Switch card is not connected.
Panel 0x, CH2 Communications Trouble Annunciator is not communicating on RS485
channel 2.
Pnl 01 Database Supervision Trouble Internal CPU memory failure
Panel 01 Code Supervision Trouble Internal CPU memory failure
Panel 01, Call For Service Trouble Internal CPU processing error
Panel 01, ROM Supervision Trouble Internal CPU memory failure
Panel 01 RS232 Port Fault Trouble
Panel 01 Unexpected Card Trouble CPU detected an option card not defined in the
database.
Panel 01 Switch Latched Trouble Button either on the main display or on an
LED/Switch card has been pressed too long.
Panel 01 Loop Database Fault Trouble Internal CPU memory failure with Signature data.
Ann 0x Service Active Trouble Trouble Indicates that a device was left in an active
condition after service group has restored.
Ann 0x Database Incompatible Trouble Indicates that the data
Annunciator 0x Reboot Fault Trouble Indicates CPU has restarted due to internal
processing failure.
Ann 0x, CH1 Communications Trouble Indicates failure to communicate with the main
panel on RS485 channel 1.
Annunciator 0x Task Failure Trouble Internal software failure
Ann 0x, LED/ Switch Display Trouble Indicates that a SL30-x has been disconnected or
is connected but not defined.
Ann 0x, CH2 Communications Trouble Indicates failure to communicate with the main
panel on RS485 channel 2.
Ann 0x Database Supervision Trouble Internal memory failure
Ann 0x Code Supervision Trouble Internal memory failure
Ann 0x, Call For Service Trouble Internal software failure
Ann 0x ROM Supervision Trouble Internal memory failure
Ann 0x RS232 Port Fault Trouble
Ann 0x Program Mode Trouble Panel has entered program mode.
Ann 0x Switch Latched Trouble Indicates that a button either on the main display
or on an SL30-x has been pressed to long.
Annunciator 0x Power Fault Trouble Indicates a loss of power on either of the 24vdc
inputs to the RAI card.
Battery Charger Fault Trouble This fault will occur when the battery charger
charging voltage falls below 20.4vdc.
Battery Wiring or Battery Fault Trouble Caused by an open in the battery wiring or if the
batteries are below 20.4vdc.
Aux Power 1/2 Shorted Trouble This point occurs when Aux 1 or Aux 2 power is
shorted on the PS6
Aux Power 3 Shorted Trouble This point occurs when Aux 3
Smoke Power Shorted Trouble This point occurs when smoke power is shorted
Primary AC Power Failure Trouble Caused by loss of AC or very low AC.
Excessive Battery Current Trouble Will go active when PS6 detects over current
condition
Check System Wiring Trouble Indicates a ground fault exists on field wiring.
Power Supply Card RAM Fault Trouble Internal memory fault
Power Supply Card ROM Fault Trouble Internal memory fault
Power Supply EEPROM Fault Trouble Internal memory fault
Card 0x, Loop Wiring Problem Trouble Indicates a break on a Class A signature loop
Card 0x Map Fault Trouble Signature map is different than the one written in
memory
Card 0x, Mapping In Progress Monitor Indicates Signature devices are in the process of
being mapped.
Card 0x Unconfig. Device Trouble Indicates that a new signature device has been
detected on a loop.
Card 0x, Line Initialization Monitor Occurs after power up or a restart. Indicates
signature devices are being initialized.
Card 0x, Loop Ground Fault Trouble Indicates a ground fault on a signature module.
Card 0x, LIM Driver Fault Trouble Internal hardware failure.
Card 0x, RAM Supervision Trouble Internal memory fault
Card 0x, ROM Supervision Trouble Internal memory fault
Card 0x, EEPROM Supervision Trouble Internal memory fault
Primary Phone Line:check Telco Trouble Telephone line has low or no voltage
Secondary Phone Line:check Telco Trouble Telephone line has low or no voltage
Pri. Receiver Failed to answer Trouble Dialer attempted to dial event to CMS but did not
get an answer.
Sec. Receiver Failed to answer Trouble Dialer attempted to dial event to CMS but did not
get an answer.
Dialer Account 1 Fault Trouble Indicates dialer did not get proper handshake for
event sent to the CMS for Account 1.
Dialer Account 2 Fault Trouble Indicates dialer did not get proper handshake for
event sent to the CMS for Account 2.
Dialer Account 3 Fault Trouble Indicates dialer did not get proper handshake for
event sent to the CMS for Account 3.
Dialer Account 4 Fault Trouble Indicates dialer did not get proper handshake for
event sent to the CMS for Account 4.
Dialer Account 5 Fault Trouble Indicates dialer did not get proper handshake for
event sent to the CMS for Account 5.
Dialer Account 6 Fault Trouble Indicates dialer did not get proper handshake for
event sent to the CMS for Account 6.
Dialer Account 7 Fault Trouble Indicates dialer did not get proper handshake for
event sent to the CMS for Account 7.
Dialer Account 8 Fault Trouble Indicates dialer did not get proper handshake for
event sent to the CMS for Account 8.
Dialer ROM Fault Trouble Internal memory fault
Dialer Queue Overflow Trouble Indicates that too many dialer messages are trying
to be sent.
Dialer Card, RAM Supervision Trouble Internal memory fault
Startup Response Monitor Monitor point that goes active on system startup or
after restart.
First Alarm Alarm Occurs anytime that the system goes into alarm
for the first time.
First Supervisory Supervisory Occurs anytime that the system goes into
supervisory for the first time.
First Trouble Trouble Occurs anytime that the system goes into a
trouble for the first time.
First Monitor Monitor Occurs anytime that the system goes into a
monitor condition for the first time.
Evacuation
Drill Monitor This point will go active anytime drill is pressed.
Alarm Silence Monitor This point will go active anytime alarm silence is
pressed.
Two Stage Expiration
Reset Monitor This point goes active anytime reset is pressed.
Reset Phase 1 Monitor Active during the power down phase of reset.
Reset Phase 2 Monitor Active during the retard phase of reset.
Reset Phase 3 Monitor Active during the restoration phase of reset.
First Disable Trouble Activated the first time an item is disabled from the
front menu.
First Test Trouble Activated the first time a service group is started
from the front menus.
Two Stage Timer Started
User Trouble Trouble Triggered by custom programming.
Maintenance tasks
Replacing a SIGA device when WARNING: Replacing a device when mapping is disabled
mapping is disabled) leaves the area unprotected. The control panel does not
automatically reassign responses to replaced devices when
mapping is disabled.
Summary
This appendix provides worksheets for calculating maximum wire lengths
for notification and Signature circuits, and for sizing standby batteries.
Content
Notification appliance circuit maximum wire length calculation • A.2
Signature loop maximum wire length calculations • A.3
Battery calculation • A.8
Use this worksheet to determine the maximum wire length of a notification appliance circuit. Fill in one
worksheet for each NAC circuit connected to the panel.
1
Maximum signal loss allowed 1.5 V
× 1000
1500
2
Wire resistance per 1000 ft/pair ÷ Ω
3
Total operating current required ÷ A
Notes
1. For worst case estimates, allow a 1.5-volt signal loss due to line impedance and that all appliances are clustered
at the end of the circuit.
2 2 2
2. Use 3.5 for 12 AWG and 2.5 mm wire, 5.2 for 14 AWG and 1.5 mm wire, 8.0 for 16 AWG and 1.0 mm wire, and
2
13.0 for 18 AWG and 0.75 mm wire.
3. Use the filtered 20 Vdc Average Operating Current ratings found on the installation or catalog sheet of each
device.
500000
Total wire ft
Table A-1: Maximum amount of wire you can use to construct a Signature loop
2
Wire type 14 AWG / 1.5 mm² 16 AWG / 1.0 mm² 18 AWG / 0.75 mm
Twisted pair, nonshielded 13157 ft 13888 ft 20000 ft
25 pF/36 pF/38 pF (4010 m) (4233 m) (6096 m)
Twisted pair, shielded 5952 ft 6098 ft 8621 ft
58 pF/82 pF/84 pF (1814 m) (1859 m) (2628 m)
Nontwisted pair, nonshielded 20000 ft 20000 ft 20000 ft
20 pF/20 pF/20 pF (6096 m) (6096 m) (6096 m)
Step 2: Use Table A-2, Table A-3, Table A-4, and Table A-5 to determine the longest allowable circuit
path based on wire size and type, and the number of detector, module, SIGA–UMs or –MABs installed on
the loop.
In the illustration below, the longest circuit path (shown in bold lines) is 1240 ft (377.95 m). The total
amount of wire comprising the loop is 1740 ft (530.35 m)
10 ft 200 ft
(3.05 m) (60.96 m)
FACP J
30 ft
(9.14 m)
200 ft 200 ft
(60.96 m) (60.96 m)
J J
100 ft 1000 ft
(30.48 m) (304.8 m)
Table A-2: Longest allowable circuit path with 0 SIGA-UMs or SIGA-MABs configured for 2-wire
smokes
Maximum allowable wire distance using nontwisted, nonshielded wire pairs
Signature Signature
detector module 18 AWG 16 AWG 14 AWG
addresses addresses
ft m ft m ft m
Table A-3: Longest allowable circuit path with 1–5 SIGA-UMs or SIGA-MABs configured for 2-wire
smokes
Maximum wire distance using nontwisted, nonshielded wire pairs
Signature Signature
detector module 18 AWG 16 AWG 14 AWG
addresses addresses
ft m ft m ft m
0 101–125
1–25 101–125
26–50 101–125
51–75 101–125
76–100 101–125
101–125 101–125
Table A-4: Longest allowable circuit path with 6–10 SIGA-UMs or SIGA-MABs configured for 2-wire
smokes
Maximum wire distance using nontwisted, nonshielded wire pairs
Signature Signature
detector module 18 AWG 16 AWG 14 AWG
addresses addresses
ft m ft m ft m
0 101–125
1–25 101–125
26–50 101–125
51–75 101–125
76–100 101–125
101–125 101–125
Table A-5: Longest allowable circuit path with 11–15 SIGA-UMs or SIGA-MABs configured for 2-
wire smokes
Maximum wire distance using nontwisted, nonshielded wire pairs
Signature Signature
detector module 18 AWG 16 AWG 14 AWG
addresses addresses
ft m ft m ft m
0 101–125
1–25 101–125
26–50 101–125
51–75 101–125
76–100 101–125
101–125 101–125
[1][5]
Base panel 249 324
[4]
Extra card
SL30
[2]
Total Current Required
× hr × min
÷ 60
+ = mAh
× 1.2
mAh
÷ 1000
[3]
Battery size = Ah
Notes
[1] Base panel current includes the PS6, the CPU/Display, and a fully-loaded SLIC.
[2] If the Total Current Required value exceeds 6 A, switch part of the load to an auxiliary power source. The auxiliary power
source must be UL/ULC listed for Fire Protective Signaling Systems.
[3] If the calculated battery size exceeds 40 Ah, switch part of the load to an auxiliary power source.
[4] If a DLD is installed, enter 13 mA for Standby Current and 20 mA for Alarm Current.
If a ZR8 is installed, enter 11 mA for Standby Current and 18 mA for Alarm Current plus 18 mA for each energized relay.
If a RS485 card is installed, enter 60 mA for Standby Current and 60 mA for Alarm Current.
[5] If an SL30 is installed, enter 1 mA for Standby Current and 20 mA for Alarm Current and 0.75 mA for each energized LED.
(A) Smoke/Accessory (SMK/ACC) Power current load calculation (max 250 mA)
Standby Qty × Standby Alarm Qty × Alarm
Card Qty Current (mA) Current (mA) Current (mA) Current (mA)
CDR–3 60 100
IOP3A 60 60
[1]
RPM 20 20
[3]
SIGA-UM, -MAB 2 17 17
Totals
Notes
[1] Add 0.7 mA for each output used.
[2] This represents the smoke power requirements. Only the
SIGA–UM or SIGA–MAB that signaled the alarm draws alarm
current. The remaining SIGA–UMs or SIGA–MABs do not.
Summary
This appendix contains a set of barcodes that you can use to add
location messages.
Content
Uppercase letters • B.2
Numbers and ordinals • B.2
Common words • B.3
Uppercase letters
A B C D Backspace
E F G H Delete
I J K L Enter
M N O P
Q R S T
U V W X
Y Z Space
1 2 3 4 Backspace
5 6 7 8 Delete
9 0 Enter
9TH 0TH
Common words
ABORT
ABOVE
ALARM
APARTMENT
APT
AREA
ATRIUM
AUDITORIUM
BASEMENT
BELOW
CAFETERIA
CEILING
CLASSROOM
CLOSET
COMPUTER
CONFERENCE
CORRIDOR
DAMPER
DETECTOR
DOOR
DUCT
EAST
ELECTRICAL
ENTRANCE
EXIT
FAN
FAULT
FIRE
FIRE PUMP
FLAME
FLOOR
FOYER
GARAGE
GENERATOR
GYM
HALL
HEAT
HORN
JANITOR
KITCHEN
LAB
LEFT
LEVEL
LIBRARY
LOBBY
LOWER
MACHINE
MECHANICAL
MENS
MEZZANINE
MONITOR
NORTH
OFFICE
PARKING
PENTHOUSE
PULL
RELAY
RESTROOM
RIGHT
ROOM
SECURITY
SHAFT
SMOKE
SOUTH
STAGE
STAIRWELL
STOCKROOM
STORAGE
STROBE
SUITE
SUPERVISORY
TROUBLE
UNDER
UPPER
UTILITY
WAREHOUSE
WATERFLOW
WEST
WOMENS
ZONE
Summary
This appendix provides information on how to program the SIGA–REL
using the QuickStart Configuration Utility
Content
Application block diagram • C.2
Programming instructions • C.3
24VDC
SLIC LOOP DATA SIGA–APS LOOP DATA SIGA–REL
Related documentation
Refer to the SIGA–REL Technical Reference
Manual (P/N 387348) and the latest technical
bulletins for installation and connection information.
Refer to the SIGA–APS installation sheet for
installation and connection information.
Refer to the RACCR installation sheet for
installation information.
Programming instructions
¨ Read me first WARNING: Attempting to program this application without a
complete understanding of the operation of the SIGA–REL, the
latest technical information, and the consequences of exposing
someone to fire suppression agents may cause personal injury,
event death.
WARNING: Improper application of fire suppression agents can
lead to property damage, serious injury, or loss of life. Consult
the applicable NFPA documents and the local authority having
jurisdiction (AHJ) for more information.
WARNING: Disabled and Service Group points will not prevent
activation of the release circuits.
¨ Add the Abort and Manual 1. Click Configure, then click Cabinets.
Release Switch circuits
2. Select the SLIC connected to the SIGA–REL then click
Note: Enter the information exactly as Configure.
shown to ensure that you program the
3. Click the Modules tab, then set the Quantity box to 1.
application according to manufacturer's
specifications. 4. Enter the following information:
Device Type: Monitor
Model: REL
Personality: (3) Active B
Message Specification: SIGA–REL1 A001 and ABORT SW
2nd Device Type: Pull
2nd Personality: (1) Alarm B
2nd Message Specification: SIGA–REL1 A002 and MAN
RELEASE SW
5. Click Add.
This is how your entries in the Modules table should look. Your addresses may be different.
¨ Create a response that activates 1. Click the And Groups tab, then click Add AND Group.
the release circuits when two or
2. Set the Activation Count box for 2.
more detectors in the protected
area signal an alarm 3. Click the Members tab, then click Add Device.
Note: To comply with NFPA 72, you 4. Select only the detectors required to activate the SIGA–
must program an And Group with at REL release circuits then click OK.
least two smoke detectors and a
minimum activation count of 2. The 5. Click the Responses tab, click the Response Type arrow,
and then select Active.
smoke detectors must have their
Primary and Alternate Verification 6. Click Delays
properties set to None (verified smoke
detectors not allowed). 7. In the Delay On list, click Activation and Restoration.
8. Set the Seconds box to 10.
9. Click Outputs, select the device labeled SIGA REL1 A003
RELEASE 1&2, and then click OK.
¨ Create a response that activates 1. Click the Devices tab, then select the circuit labeled
the release circuits when someone SIGA–REL A002 MAN RELEASE SW.
presses the manual release switch
2. Click the Responses tab, click the Response Type arrow,
and then select Active.
3. Click Outputs, then:
Hold the Ctrl key down
Select the device labeled SIGA REL1 A005 Prerelease
1&2
Select the device labeled SIGA REL1 A003 Release 1&2
Release the Ctrl key then click OK.
Note: The prerelease circuit must appear before the releasing
circuit in the response list.
¨ Create a response that activates 1. Click the Devices tab then select the Show Pseudo Points
the prerelease circuits when check box.
someone presses the Drill switch
2. Select the circuit labeled Drill (address 007).
Note: Create this response only if
3. Click the Responses tab, click the Response Type arrow,
required. Pressing Drill will activate the
and then select Active.
prerelease circuits but pressing Drill a
second time will not restore the 4. Click Outputs, select the device labeled SIGA REL1 A005
prerelease circuits. You must press PRERELEASE 1&2, and then click OK.
Reset to silence the prerelease circuits.
¨ Retrieve the loop data from the 1. Click Configure, then click Cabinets.
SLIC
2. Select the SLIC connected to the SIGA–REL then click
Configure.
3. Set the Communications Port setting for the COM port used
to connect the service computer to the control panel.
4. Click Retrieve Signature Data
5. After the upload has finished, click OK.
¨ Reconcile the actual and 1. Click the Mapping tab, then click Model.
expected data
2. Look for a string of at least six RELs marked with red
Caution: Clicking Accept Actual will backgrounds and double-click the first REL in the string.
enter the selected device into the
3. If the serial number displayed in the Module Properties
database with its current programmed
dialog is not the same as the serial number shown on the
parameters. This will corrupt the
bar code attached to the SIGA–REL, click Close, and then
database if you have already entered
double-click the next REL in the string.
the device.
4. If the serial numbers are the same:
Click Select Expected.
In the Module Selection dialog, select the row that has the
REL with the Monitor device type and marked SIGA–REL1
A001 Abort SW, then click OK.
Click Close.
5. Select the next REL then click Select Expected.
In the Module Selection dialog, select the row that has the
REL with the Output device type and marked SIGA–REL1
A003 Release 1&2, then click OK.
Click Close.
6. Select the next REL then click Select Expected.
In the Module Selection dialog, select the row that has the
REL with the Output device type and marked SIGA–REL1
A005 Prerelease 1&2, then click OK.
Click Close.
¨ Send the reconciled data to the Click the Controller tab, then click Send Signature Data.
loop controller