Chapter Three
Chapter Three
CHAPTER THREE
INDUCTION MACHINES
3.1. ELECTROMECHANICAL CONVERSION
Three electrical Machines (dc, induction & synchronous) are used extensively for
electromechanical energy conversion. In these machines, conversion of energy
results from the following two electromagnetic phenomena.
1. When a conductor moves in a magnetic field voltage is induced in the
conductor: (generator action)
2. When a current –carrying conductor is placed in a magnetic field, the
conductor experiences a mechanical force (Motor action)
1
Introduction to Electrical Machines
2
Introduction to Electrical Machines
(a) (b)
Figure 3.2 induction machine laminations (a)Stator and (b)rotor
b) Rotor
The rotor also consists of laminated ferromagnetic material, with slots punched out
on the outer surface (Figure 3.2 (b). The frequency of the rotor flux is very low; as a
result thicker laminations can be used without excessive iron losses. Two types of
rotor construction is normally used for three phase induction motor.
Bearings, mounted on the shaft, support the rotor and allow it to turn. Some
motors, like the one shown in the following illustration, use a fan, also mounted on
the rotor shaft, to cool the motor when the shaft is rotating.
(i) Squirrel-cage rotor: Motors employing this type of rotor are known as
squirrel-cage induction motors.
(ii) Phase-wound or wound rotor: Motors employing this type of rotor are
variously known as phase-wound motors or wound motors or slip-ring motors.
Squirrel –Cage Rotor
Almost 90 per cent of induction motors are squirrel-cage type, because this type
‘rotor' has the simplest and most rugged construction imaginable and is almost
indestructible. The squirrel cage rotor is so called because its construction is
reminiscent of the rotating exercise wheels found in some pet cages. The rotor
consists of a cylindrical laminated core with parallel slots for carrying the rotor
conductors which, it should be noted clearly, are not wires but consist of heavy bars
of copper, aluminum or alloys. One bar is placed in each slot; rather the bars are
inserted from the end when semi-closed slots are used. The rotor bars are brazed or
electrically welded or bolted to two heavy and stout short circuiting end-rings.
It should be noted that the rotor bars are permanently short-circuited on
themselves, hence it is not possible to add any external resistance in series with the
rotor circuit for starting purposes.
Introduction to Electrical Machines
b)
a)
Figure 3.4 a) Real squirrel cage rotor and b) Schematic diagram of cage
rotor
The rotor slots are usually not quit parallel to the shaft but are purposely give a
slight skew. This is useful in two ways:
i.) it helps to make the motor run quietly by reducing the magnetic hum and
ii.) it helps in reducing the locking tendency of the rotor i.e. the tendency of the
rotor teeth to remain under the stator teeth due to direct magnetic attraction
between the two.
In small motors, another method of construction is used. It consists of placing the
entire rotor core in a mould and casting all the bars and end-rings in one piece. The
metal commonly used is an aluminum alloy.
Phase –Wound Rotor
This type of rotor is provided with 3-phase, double-layer, distributed winding
consisting of coils as used in alternators. The rotor is wound for as many poles as
the number of stator poles and is always wound 3-phase even when the stator is
wound two-phase.
Introduction to Electrical Machines
a)
b)
3-phase
supply
stator
Slip-rings
rotor
Starting
Rheostat
Figure 3.7 Three-phase wound –rotor induction motor with external starting
rheostat.
c) Enclosure
The enclosure consists of a frame (or yoke) and two end brackets (or bearing
housings). The stator is mounted inside the frame. The rotor fits inside the stator
with a slight air-gap separating it from the stator. There is no direct physical
connection between the rotor and the stator. The enclosure protects the internal
parts of the motor from water and other environmental elements. The degree of
protection depends upon the type of enclosure (See Appendix D).
Comparison of squirrel cage and wound rotors.
The squirrel cage motor has the following advantages as compared with the wound
rotor machine.
i. No slip rings, brush gear, short circuiting devices, rotor terminals for starting
rheostats are required. The star delta starter is sufficient for staring.
ii. It has slightly higher efficiency.
iii. It is cheaper and rugged in construction
iv. It has better space factor for rotor slots, a shorter overhang and consequently
a smaller copper loss.
v. It has bare end rings, a larger space for fans and thus the cooling conditions
are better
vi. It has smaller rotor overhang leakage which gives a better power factor and
greater pull out torque and overload capacity.
The greatest disadvantage of squirrel cage rotor is that it is not possible to insert
resistance in the rotor circuit for the purpose of increasing the starting torque,
reducing the starting current and varying the speed as compared with wound rotor
motor.
3.4. ROTATING MAGNETIC FIELD
It will now be shown that when three-phase windings displaced in space by 1200 are
fed by three-phase current displaced in time by 1200 they produce a resultant
magnetic flux which rotated in space as if actual magnetic poles were being rotated
mechanically.
6
Introduction to Electrical Machines
Let a 3-phase , two-pole stator having three identical winding placed 120 space
degrees apart and the flux ( assumed sinusoidal) due to three-phase windings as
shown in Figure 3.8(a). The assumed positive directions of the fluxes are shown
Figure 3.8(b).
B
m
120
A 120
120
θ
C
(a) (b)
Figure 3.8 (a) flux waveforms due to three-phase windings and (b) positive
directions of the fluxes
Let the maximum value of flux due to any one of the three phases to m. The
resultant flux r, at any instant, is given by the vector sum of the individual fluxes
A, B and C due to three phases. We will consider values of r at four instants 1/6
time-period apart corresponding to points marked 0,1,2 and 3 in Figure 3.7(a).
i) When = 00 i.e. corresponding to point 0 in Figure 3.8 (a).
Here
3 3
A 0, B m , C m ,
2 2
The vector for O B in Figure 3.9(i) is drawn in a direction opposite to the direction
assumed positive in Figure 3.8(b).
3 600 3 3
r 2 mCos 3 m m
2 2 2 2
(ii) When = 600 i.e. corresponding to point 1 in Figure 3.8(a).
Here
3
A m
2
………drawn in parallel to OA of Figure 3.8 (b) as shown in Figure 3.9 (ii)
3
B m
2
………drawn in opposition to O B of Figure 3.8(b) as shown in Figure 3.9(ii)
C = 0
3 3 3
r 2 m Cos30 3 m m
2 2 2
7
Introduction to Electrical Machines
3
It is found that the resultant flux is again m but has rotated clockwise through an
2
angle of 600.
(iii) When = 1200 i.e. corresponding to point 2 in Figure 3.8(a).
Here
3 3
A m , B 0, c m
2 2
3
It can be again proved that r m .So, the resultant flux is again of the same
2
value but has further rotated clockwise through an angle of 600 [Figure 3.9 (iii)].
(iv) When = 1800 i.e. corresponding to point 3 in Figure 3.7a.
3 3
A 0, B m , C m
2 2
3
The resultant is m and has rotated clockwise through an additional angle of 600 or
2
through an angle of 1800 from the start.
A
B C
B
Φ r 1.5Φm Φr 1.5Φ m
i) θ 0 ii) θ 60
Φr 1.5Φm
C
C B
A
Φr 1.5Φ m
8
Introduction to Electrical Machines
Figure 3.10 shows the graph of the rotating flux in simple way. As before the
positive directions of the flux phasors have been shown separately in Figure 3.10.
Arrows on these flux phasors are reversed when each phase passes through zero
and becomes negative.
A B C
m
9
Introduction to Electrical Machines
stator
Stator
rotating fields
rotor
(a)
10
Introduction to Electrical Machines
Let at any slip speed, the frequency of the rotor current be fr . Then,
120 f r
Ns N .
p
120 f
Also N s
p
fr Ns N
S;
Dividing one by the other, we get, f Ns
f r sf
As seen, rotor currents have a frequency of fr = sf and when flowing through the
individual phases of rotor winding give rise to rotor magnetic fields. These individual
rotor magnetic fields produce a combined rotating magnetic field whose speed
relative to rotor is
120 f r 120 sf
sN s
P P
However, the rotor itself is running at speed N with respect to space.
Hence,
speed of rotor field in space speed of field to rotor speed of rotor relative to space
SN s N N s (1 S) N s
It means that no matter what the value of slip, rotor currents and stator currents
each produce a sinusoidally distributed magnetic field of constant magnitude and
constant space speed of Ns. In other words, both the rotor and stator field rotate
synchronously which means that they are stationary with respect to each other.
These two synchronously rotating magnetic fields in fact, superimpose on each other
and given rise to the actually existing rotating field which corresponds to the
magnetizing current of the stator winding.
Example 3.1 A 3-phase, 50 Hz induction motor has a full-load speed of 1440 r.p. m.
For this motor, calculate the following:
(a) number of poles ; (b) full-load slip and rotor frequency ;(c) speed of stator
field with respect to (i) stator structure and (ii) rotor structure and (d) speed of
rotor field with respect to (i) rotor structure (ii) stator structure and (iii) stator field.
For parts (c) and (d), answer should be given in rpm and rad /sec.
Solution. (a) The use of full-load speed of 1440 rpm as synchronous speed gives
120 f 1
NS
P
120 50
Or 1440
P
120 50 1
or P 4 poles
1440 6
Since the number of poles must be even and a whole number, the induction motor
must have 4 poles. Note that an induction motor runs at a speed, a little less than
synchronous speed.
(b) Synchronous speed,
11
Introduction to Electrical Machines
120 f1 120 50
NS 1500 r.p.m.
P 4
N s N 1500 1440
Slip, S 0.04
Ns 1500
Rotor frequency, f 2 Sf1 0.04 50 2 Hz
(c) (i) Speed of stator field with respect to stator structure
N S 1500rpm
2 N S 2 1500
S 150.08 rad / s
60 60
(ii) Speed of stator field w.r.t. revolving rotor structure
= 1500 1440 = 60 rpm
2 60
6.283 rad / s
60
(d) (i) Speed of rotor field w.r.t. rotor structure
120 ( rotor frequency)
poles
120 2
60 r.p.m. 6.283 rad / s
4
(ii) Speed of rotor field w.r.t. stator structure
=(Mechanical speed of rotor) + (Speed of rotor field w.r.t rotor structure)
= 1440 + 60 =1500 rpm = 150.08 rad/s.
(iii) Since both the stator and rotor fields are rotating at synchronous speed of 1500
rpm with respect to stator structure, speed of rotor field with respect to stator field
is zero. Thus the stator and rotor fields are stationary with respect to each other.
Example 3.2 A properly shunted centre-zero galvanometer is connected in the
rotor circuit of a 6-pole, 50 Hz wound-rotor induction motor. If the galvanometer
makes 90 complete oscillations in one minute, calculate the rotor speed.
Solution. One complete oscillation of galvanometer corresponds to one cycle of
rotor frequency.
90
Rotor frequency, f 2 Sf1 1.5 Hz
60
f 2 1.5
or Slip, S 0.03 s = fz fl =501.5 = 0.03
f1 50
120 50
Rotor speed, N N S (1 S) (1 0.03) 970 r.p.m.
6
12
Introduction to Electrical Machines
R1 X1
V1 Rc Xm E1
(a)
Where V1 = per-phase terminal voltage
R1 = per-phase stator winding resistance
X1 = per-phase stator leakage reactance
E1 = per-phase induced voltage in the stator winding
Xm = per-phase stator magnetizing reactance
Rc = per-phase stator core loss resistance
Note that there is no difference in form between this equivalent circuit and that of
the transformer primary winding. The difference lies only in the magnitude of the
parameters. For example, the excitation current Io is considerably large in the
induction machine because of the air gap. In induction machines it is as high as 30
to 50 percent of the rated current, depending on the motor size where as it is only 1
13
Introduction to Electrical Machines
R2
S
(b) (c)
Where, E2 = per-phase induced voltage in rotor at standstill (i.e. at stator
frequency f1)
R2 = per –phase rotor circuit resistance
X2 = per –phase rotor leakage reactance
Note that this circuit is at frequency f2. The rotor current I2 is
sE 2
I2 3.1
R2 jsX 2
The power involved in the circuit is
2
P2 I 2 R2 3.2
2 R2 P2
P I2 3.4
S S
Because induction machines are operated at low slips (typical values of slip s are
0.01 to 0.05) the power associated with Figure 3.13(c) is considerably larger. Note
that the equivalent circuit of Figure 3.13(c) is at the stator frequency, and therefore
this is the rotor equivalent circuit as seen from the stator. The power in Eq.(3.4)
therefore represents the power that crosses the air gap and thus includes the rotor
copper loss as well as the mechanical power developed, Equation (3.4) can be
rewritten as .
14
Introduction to Electrical Machines
R
P Pag I 2 2 R2 2 ( 1 s
S 3.5
R
I 22 2
S
The corresponding equivalent circuit is shown in Figure 3.13(d).
R2
1 S
S
(d)
The speed dependent resistance R2 (1-s)/s represents the mechanical power
developed by the induction machine.
R 2
P mech I22 ( 1 S)
S
( 1 S ) P ag
1 S
.P2
S
and
P 2 I 2 2 R 2 SP ag
Thus
P ag : P 2 :P mech 1 :S :1 S
This equation indicates that, of the total power input to the rotor (i.e. power
crossing the air gap, Pag), a fraction s is dissipated in the resistance of the rotor
circuit (known as rotor copper loss) and the fraction 1-s is converted into mechanical
power. Therefore, for efficient operation of the induction machine, it should operate
at a low slip so that more of the air gap power is converted into mechanical power.
Part of the mechanical power will be lost to overcome the windage and friction. The
remainder of the mechanical power will be available as out put shaft power.
3.6.3. Complete Equivalent Circuit
The stator equivalent circuit, Figure 3.13(a) and the rotor equivalent circuit of Figure
3.13(c) or (d) are at the same line frequency f1 and therefore can be joined
together. However, E1 and E2 may be different if the turns in the stator wining and
the rotor winding are different. If the turns ratio a N1 is considered, the
N2
equivalent circuit of the induction machine is that shown in Figure 3.13(e). Note that
the form of the equivalent circuit is identical to that of a two-winding transformer, as
expected.
15
Introduction to Electrical Machines
I2
I 2' X 2' a 2 X 2
a
(e)
Figure 3.13 Development of the induction machine equivalent circuit
3.6.4. Various equivalent circuit
The equivalent circuit shown in Figure3.13 (e) is not convenient to use for predicting
the performance of the induction machine. As a result, several simplified versions
have been proposed in various textbooks on electric machines. There is no general
agreement on how to treat the shunt branch (i.e., Rc and Xm), particularly the
resistance RC representing the core loss in the machine. Some of the commonly
used versions of the equivalent circuit are discussed here.
3.6.5. Approximate Equivalent Circuit
If the voltage drop across R1 and X1 is small and the terminal voltage V1 does not
appreciably differ from the induced voltage E1, the magnetizing branch (i.e. Rc and
Xm), can be moved to the machine terminals as shown in Figure 3.14 (a).
R2'
S
(a)
This approximation of the equivalent circuit will considerably simplify computation,
because the excitation current (Io) and the load component (I'2) of the machine
current can be directly computed from the terminal voltage V1 by dividing it by the
corresponding impedance.
Note that if the induction machine is connected to a supply of fixed voltage and
frequency the stator core loss is fixed. At no load, the machine will operate close to
synchronous speed. Therefore, the rotor frequency f 2 is very small and hence rotor
core loss is very small. At a lower speed f2 increases and so does the rotor core loss.
The total core losses thus increase as the speed falls. On the other hand, at no load,
frication and windage losses are maximum and as speed falls these losses
decreases. Therefore, if a machine operates from a constant voltage and constant-
frequency source, the sum of core losses and friction and windage losses remains
essentially constant at all operating speeds. These losses can thus be lumped
together and termed the constant rotational losses of the induction machine. If the
core loss is lumped with the windage and frication loss Rc can be removed from the
equivalent circuit, as shown in Figure 3.14(b).
16
Introduction to Electrical Machines
R1 X1 X’2
I1
Io I’2
V1 Xm R2'
S
Pag
(b)
Figure 3.14 Approximate equivalent circuit of Induction motor
3.6.6. IEEE1 Recommended Equivalent Circuit
In the induction machine, because of its air gap, the exciting current Io is high of
the order of 30 to 50 percent of the full-load current. The leakage Reactance X1 is
also high . The IEEE recommends that in such situation, the magnetizing reactance
Xm not be moved to the machine terminals (as is done in Figure 3.14b), but be
retained at its appropriate place, as shown in Figure 3.15. The resistance RC is
however, omitted, and the core loss is lumped with the windage and friction losses.
This equivalent circuit (Figure 3.15) is to be preferred for situation in which the
induced voltage E1 differs appreciably from the terminal voltage V1.
I'2 X '2
R '2
S
R2
S
1
IEEE-Institute of Electrical and Electronics Engineers
17
Introduction to Electrical Machines
X m
V th 1
V1
R 1
2
(X 1 X m ) 2
2
Where
2 2
If R1 ( X 1 X m ) as is usually the case
Xm
Vth V1
X1 X m
Vth K th V1
Xm
Where, K th
X1 X m
The Thevenin impedance is
jX m ( R1 jX 1 )
Z th
R1 j ( X 1 X m )
Rth jX th
2 2
If R1 ( X 1 X m )
2
Xm
R th R 1
X1 X m
K 2 th R 1
and since X1<< Xm
Xth X1
Example 3.3 A 3-phase slip ring induction motor gives a reading of 55V across slip
rings on open circuit when at rest with normal stator voltage applied. The rotor is
star-connected and has impedance of (0.7 + j 5) per phase. Find the rotor current
when the machine is (a) at stand still with the slip rings joined to a star-connected
starter with a phase impedance of (4 + j 3) ohms and (b) running normally with a 5
percent slip.
Solution
(a) At standstill, i.e. S=1
55
Induced emf per phase in rotor winding, E 2 31.8V
3
Resistance per phase in rotor circuit, r2 0.7 4 4.7 4.7
r2 4.7
Power factor cos 2 0.506 ( lagging )
z 2 9.28
(b) Running normally at 5 Percent slip
Induced e.m.f in rotor winding per phase,
E 2 S SE 2 0.05 31.8 1.59 V
Reactance per phase in rotor circuit,
x2 S Sx 2 0.05 5 0.25
Rotor impedance per phase,
z 2 S r22 x22S 0.7 2 0.25 2 0.7433
E2S 1.59
Rotor current per phase, I 2 2.14 A
z 2 S 0.7433
Power factor,
r2 0 .7
cos 2 0.92 ( lagging )
z 2 S 0.7433
Example 3.4 A 3, 15 hp, 460V, 4-pole, 60Hz, 1728 rpm induction motor delivers
full output power to a load connected to its shaft. The windage and friction loss of
the motor is 750 W. Determine the
a) Mechanical power developed.
b) Air gap power
c) Rotor copper loss.
Solution
a) Full-load shft power, P shaft = 15 746 = 11,190 W
Mechanical power developed, Pmech = P shaft + P f&w
= 11,190 + 750 = 11,940 W
120 f 120 60
b) Synchronous speed, N s 1800 rpm
P 4
N s N 1800 1728
Slip, S 0.04
Ns 1800
Pmech 11,940
Air gap power, Pag 12 ,437.5 W
1 S 1 0.04
c) Rotor copper loss, P2 SPag 0.04 12 ,437.5 497.5 W
3.7. PERFORMANCE CHARACTERISTICS
The equivalent circuits derived in the preceding section can be used to predict the
performance characteristics of the induction machine. The important performance,
characteristics in the steady state are the efficiency, power factor, current, starting
torque maximum (or pull-out) torque, and so forth.
The mechanical torque developed Tmech per phase is given by
Introduction to Electrical Machines
R2
Pmech Tmech . mech I 22 . (1 S ) 33331 3.6
S
Where,
2 N
mech 3.6 a
60
The mechanical speed mech is related to the synchronous speed by
mech ( 1 S )syn
Ns 11 3.7
2 ( 1 s )
60
and
120 f
syn x 2 3.8
P .60
From Eqs. (3.6) and (3.7)
2
I R
Tmech . syn 2 2 pag
S
3.9
1
T mech .Pag 3.10
syn
1 2 R2
.I2 3.10a
syn S
1 2 R2
I2 3.11
syn S
From Thevenin equivalent circuit and Eq.1.11
2
1 V th R2
T mech . . 3.12
R S
syn ( R th 2 )2 ( X th X 2 ) 2
S
Note that if the approximate equivalent circuits (Figure 3.13(b) are used to
determine I2 in Eq.(3.12) Vth, Rth and Xth should be replaced by V1, R1 and X1
respectively. The prediction of performance based on the approximate equivalent
circuit may differ by 5 percent from those based on the equivalent circuit of Figure
3.15 or Figure 3.16.
For a three-phase machine Eq.3.12 should be multiplied by three to obtain the total
torque developed by the machine.
20
Introduction to Electrical Machines
2
3 V th R2
T 3 , mech . .
R2 2 S
syn ( R th ) (X th X 2 )2
S
The torque-speed characteristic is shown in Figure 3.17. At low values of slip,
R 2' ' R 2'
(R th ) ( X th X 2 ) and R th
S S
And thus
1 V 2 th
Tmech . .S 3.13
syn R' 2
21
Introduction to Electrical Machines
R '2 1
S T max
R th2 ( X th X 2' ) 2 2
3.15
This expression can be also be derived from the fact that the condition for maximum
torque corresponds to the condition for maximum air gap power (Eq.3.10). This
occurs, by the familiar impedance-matching principle in circuit theory, when the
impedance of R'2/s equals in magnitude the impedance between it and the supply
voltage V1 (Figure 3.16) as shown in Eq.(3.15). The slip Smax at maximum torque
Tmax is
R 2'
ST max
1 3.16
R 2
th ( X th X '
2 )2 2
The maximum torque per phase from Eqs. (1.12) and (1.16) is
2
1 V th
T max . 3.17
2 syn R [ R 2 ( X X ' ) 2 ] 1 2
th th th 2
Equation (3.17) shows that the maximum torque developed by the induction
machine is independent of the rotor circuit resistance. However, from Eq. (3.16) it is
evident that the value of the rotor resistance R2 determines the speed at which this
maximum torque will occur. The torque-speed characteristics for various values of
R2 are shown in Figure.3.19.
22
Introduction to Electrical Machines
R 2'
S T max 3.18
X th X 2'
2
1 V th
T max ' 3.19
2 syn X th X 2
Equation (3.19) indicates that the maximum torque developed by induction machine
is inversely proportional to the sum of the leakage reactances. From Eq. (3.12), the
ratio of the maximum torque developed to the torque developed at any speed is
2
R 2'
R th
S
X th X '
2 2
T max S 3.20
2
T R ' S T max
R
th
S
2
X th X '
2 2
T max
23
Introduction to Electrical Machines
ST th 2
max
From Eqs. (3.18) and (3.21)
2 2
R 2' R'
2
Tmax S ST S
max
2 3.22
T R 2' S T max
2
S
Tmax
2
S
T
max
2
T max 1 S T S
1max
T 2 S S T max
2 2
1 ST S S
max
2 S2 ST max
2 2
1 S S
Tmax
2 S ST max
Hence,
T max S2 S 2
3.23
T max
T 2ST S max
Equation (3.23) shows the relationship between torque at any speed and the
maximum torque in terms of their slip values.
Example 3.5 A 6-pole, 3-phase, 50 Hz, induction motor runs on full load with a slip
of 4 percent. Given the rotor standstill impedance per phase as (0.01 + j 0.05),
calculate the available maximum torque in terms of full load torque. Also determine
the speed at which the maximum torque occurs. .
Solution
Rotor resistance per phase, R2=0.01
Rotor standstill reactance per phase, X2=0.05
Full load slip, S=4%=0.04
Ratio of maximum torque to full load torque
2 2
R2
S 2fl 0.01 0.04 2
X2
0.05
0.0416
2.6
R2 0.01 0 . 016
2 S fl 2 0.04
X2 0.05
24
Introduction to Electrical Machines
R2 0.01
(ii) Slip corresponding to maximum torque, S T max 0.2
X 2 0.05
Speed corresponding to maximum torque,
120 50
N N s ( 1 ST max ) ( 1 0.2 )
6
800 r . p .m .
Example 3.6 A 4-pole, 50 Hz, 3-phase induction motor has a rotor resistance of
0.024 per phase and standstill reactance of 0.6 per phase. Determine the speed
at which the maximum torque is developed.
Solution
Rotor resistance per phase, R2=0.024
Rotor standstill reactance per phase, X2=0.6
Since the torque under running condition is maximum at that value of the slip
which makes rotor reactance per phase equal to the rotor resistance per phase,
R2 0.024
Slip corresponding to maximum torque, ST max 0.04
X2 0.6
Speed corresponding to maximum torque,
N N S 1 ST max
120 50
1 0.04
4
1440 rpm
Example 3.7 The maximum torque of a 3-phase induction motor is twice the full
load torque and starting torque is equal to full load torque. Calculate the full load
speed and the slip at which maximum torque occurs.
Solution Maximum torque, Tmax 2T fl
4 42 4
ST max 2 3 0.268 rejecting higher value
2
Let the full load slip of Sfl. Since the ratio of full load torque to maximum torque
(Eq.3.23) is given by the expression
T fl 2 S T max S fl
Tmax S T2 max S 2fl
1 2 0.268 S fl
Or
2 0.268 2 S 2fl
R 2' '
Z 1 R 1 jX 1 X m // jX 2
S
R 1 jX 1
X m // Z 2'
R 2' '
jX m
jX 2
Z 1 R 1 jX S
1
R 2'
j( X m X 2' )
S
Z1 1
The stator current is
V1
I 1 I o I 2'
Z1
At synchronous speed (i.e., S=0), R2'/s is infinite and so I2' = 0. The stator current
I1 is the exciting current Io. At larger values of slip S2'(=R2'/s +jX2’) is low and
therefore I2'(and hence I1) is large. In fact, the typical starting current (i.e. at S=1)
is five to eight times the rated current. The typical stator current variation with
speed is shown in Figure 3.20.
I1
pu
6
5
4
3
2
1
-Ns 0 Ns N
Introduction to Electrical Machines
P1 3 I 12 R 1
Where R1 is the ac resistance (including skin effect) of each phase winding at the
operating temperature and frequency.
Power is also lost as hysteresis and eddy current loss in the magnetic material of the
stator core. The remaining power, Pag , crosses the air gap. Part of it is lost in the
resistance of the rotor circuit. P2 3I 22 R 2
Where, R2 is the ac resistance of the rotor winding. If it is a wound-rotor machine, R2
also includes any external resistance connected to the rotor circuit through slip
rings.
Power is also lost in the rotor core. Because the core losses are dependent on the
frequency f2 of the rotor, these may be negligible at normal operating speeds, where
f2 very low.
27
Introduction to Electrical Machines
Pin 3V1I1Cosθ1
28
Introduction to Electrical Machines
.
Figure 3.23 Efficiency as a function of speed
Example 3.8 A 3, 460V, 1740rpm, 60Hz, 4-pole wound-rotor induction motor has
the following parameters per phase:
R1=0.25 R2’=0.2
X1=X2’=0.5 Xm=30
The rotation losses are 1700 w. with the rotor terminals short-circuited, find
a.) i) Starting current when started direct on full-voltage
ii) Starting torque
b.) i) Full-load slip
ii) Full-load current
iii) Ratio of starting current to full-load current
iv) Full-load power factor
v) Full-load torque
vi) Internal efficiency and the motor efficiency at full-load
c.) i) Slip at which maximum torque is developed
ii) Maximum torque developed
d.) How much external resistance per phase should be connected in the
rotor circuit so that the maximum torque occurs at start?
Solution
460
a) V1 265.6 V / phase
3
i) At start S=1. The input impedance is
r'
jX m 2 jx '2
s
Z1 r1 x 1 '
r2
s
j x m x '2
j300.2 j0.5
0.25 j0.5
0.2 j30.5
1.0866
29
Introduction to Electrical Machines
265.6
I st 245.9 66A
1.0866
2 N s 2 1800
ii) syn 188.5 rad / s
60 60
V1 jX m 266.5 j 30.0
Vth 261.3V
r1 j xm x1 0.25 j 30.5
R2' 0 .2
ii) 6.01
s 0.0333
j306.01 j0.5
Z1 0.25 j0.5
6.01 j30.5
0.25 j0.5 5.598 j1.596
6.212319.7
265.6
I FL 42.754 19.7A
6.212319.7
I st 245.9
iii) 5.75
I FL 42.754
iv) PF= cos(19.7)=0.94 lagging
3 261 . 3 2
T FL 6 . 01
v) 188 . 5 ( 0 . 24 6 . 01 ) 2 ( 0 . 49 0 . 5 ) 2
163 . 11 N . m
30
Introduction to Electrical Machines
0.2 0.2
1
0.1963
0.24 2
0.49 0.5
2
2 1.0187
3 261 .3 2
1
2 188 . 5 0 .24 0 . 24 2 0 .49 0 .5 2 2
431 . 68 N .m
Tmax 431 .68
2.65
TFL 163 .11
d)
' '
R 2 R ext
S T max 1 1
R 2
th ( X th X '
2 )2 2
31
Introduction to Electrical Machines
Z1 r1 x 1 R e jX e
0.25 j0.5 5.598 j1.596
3 2 3
T I1 R e 42.754 2 5.598
syn 188.5
163 N.m
3.8. INDUCTION MOTOR PHASOR DIAGRAM
The rotor m.m.f. F2 lagging behind air-gap flux by a space angle of 90 + 2. The
rotor m.m.f. reacts on the stator and calls for a compensating load component of
stator current I2' such that load component of stator m.m.f. Fl' = rotor m.m.f. F2
' N '2 N k
I2 I2 I2 2 w2
' N1k w1
N1
Here N1' and N2 are the effective number of stator and rotor turns respectively. In
Figure 3.24 load component of m.m.f. F1' I '2 N 1' of the total stator m.m.f. Fl, is
shown opposing rotor m.m.f. F2. Similarly, load-component current I2', of the total
stator current I1, is shown opposite to rotor current I2. In Figure 3.24, per-phase
rotor induced emf E2 lags by a time-phase angle of 90°.
2
32
Introduction to Electrical Machines
drop I1 (rl +jxl) as shown in Figure 3.25 (a). The power factor angle 1 (between V 1
and Il) at the stator terminals is very high, i.e. stator power factor is very poor at
the time of starting a 3-phase induction motor.
At normal operating speed, slip s is small. The rotor voltage equation now
becomes, sE2= I2(r2+ jsx2) and this is illustrated in the phasor diagram of Figure
3.25(b). In this Figure, I 0 I m I fc , where Ifc, is the friction, windage and core-
loss component of stator current. The rest of the phasor diagram is drawn in the
same manner as illustrated in Figure 3.24(a). Figure 3.25(b) reveals that full load
power factor at the stator terminals has considerably improved (0.8 to 0.9
lagging) from its power factor at starting. In the phasor diagrams of Fi gures 3.24
and 3.25, all quantities have per-phase values.
I0
2
sE2=I2Z2
I2
jSI2x2
E1
(b)
Figure 3.25 Induction motor Phasor diagram at (a) standstill and (b) a full-
load slip s.
3.9. MODES OF OPERATION OF A 3-PHASE INDUCTION MACHINES
The three phase induction machine has the following three modes or operating
regions of operations depending upon the values of slips:
a) Motoring Mode : 1<S>0
Under normal operation, rotor revolves in the direction of rotating field produced by
the stator currents. As such, the slip varies from 1 at standstill to zero at
synchronous speed, i.e. 1 < S > 0. The corresponding speed values are zero (S=1)
and synchronous speed (S=0).
b) Generating Mode: S < 0.
For this operating modes, slip is negative, i.e. S<0. An induction motor will operate
in this region only when its stator terminals are connected to constant-frequency
voltage source and its rotor is driven above synchronous speed by prime mover. The
connection of stator terminals to voltage source is essential in order to establish the
rotating air gap field at synchronous speed. In case stator is disconnected from
33
Introduction to Electrical Machines
voltage source and rotor is driven above synchronous speed by the prime mover, no
generating action takes place.
c) Braking Mode: S > 1.
For this mode, slip is greater than 1. a slip more than one can be obtained by
driving the rotor , with a prime mover, opposite to the direction of rotating field. But
such a use in practice is rare. A practical utility of slip more than 1 is obtained by
bringing the rotor to a quick stop by braking action, called plugging. For obtaining
S>1, or for obtaining plugging, any two stator terminal leads are interchanged. With
this the phase sequence is reversed and, therefore, the direction of rotating
magnetic field becomes suddenly opposite to that of the rotor rotation. The
electromagnetic torque T, now acting opposite to rotor rotation, produces the
braking action. Thus the motor can be quickly brought to rest by plugging, but the
stator must be disconnected from the supply before the rotor can start rotate in the
other direction.
All the three regions of operation (braking, S=2.0 to S=1.0; motor regions, S=1.0
to S=0 and generator region, S=0 to S=-1) are illustrated in Figure 3.26.
Figure 3.26 torque-slip curve of an induction machine showing its braking, motor
and generator regions
3.10. OPERATING CHARACTERISTICS OF INDUCTION MOTORS
Steady-state operating characteristics of an induction motor show graphically the
variation of speed, power factor, stator current and efficiency as the shaft power
output is varied from no-load to full load. For a given induction motor, the operating
characteristics are governed by its rotor resistance, air-gap length and shape of both
stator and rotor slots. The objective of this article is to describe the nature of the
steady-state operating characteristics of induction motors and to examine the
factors that govern them. Figure 3.27 illustrates typical operating characteristics of
an induction motor. The shape of these curves is now explained below.
34
Introduction to Electrical Machines
35
Introduction to Electrical Machines
At no load, stator current Io is shown in Figure 3.28. The function of the third, i.e.
load, component of Io at no load is to supply friction and windage (F.W.) loss. (For a
transformer at no load, this third component is zero). The rotor power developed at
no load, is, therefore, equal to F.W. loss. As this loss is quite small, rotor current
and therefore load component is very small.
V1
'
1' I 2
1
I '2
I0
O
I2
I2 E2
E1
36
Introduction to Electrical Machines
increasing loads follows a semi-circle and this leads to the induction motor circle
diagram.
e.) Air gap:
In induction motors, for constant supply voltage, the air-gap flux remains sub-
stantially constant. If the air-gap length is increased, then constant flux requires
more magnetizing current. This reduces the no-load power factor as well as the full-
load power factor of the induction motor. Therefore, in order that an induction motor
operates at a better power factor, the air-gap length is kept as small as is
mechanically possible. Small air-gap clearance in induction motors necessitates a
heavier shaft and high-grade bearings than are required for other types of rotating
machines of the same rating and speed.
Open slots in an induction motor has the effect of increasing the air-gap length
(1.10 to 1.20 times the actual air-gap length) as a result of which more magnetizing
current is required and the operating power factor of the motor is worsened. But an
induction motor with open slots has less leakage reactance and, therefore, more Tst,
more Tmax etc. Likewise induction motors with semi-closed slots or closed slots
requires less magnetizing current and, therefore, better operating power factor, but
its Tst, Tmax etc are reduced. In view of this, at the design stage, a compromise has
to be made between Tst, Tmax and the operating power factor of the induction
motors.
3.11. DETERMINATION OF EQUIVALENT CIRCUIT PARAMETERS
The equivalent circuit parameters of poly phase induction motors can be determined
from no load test, blocked-rotor test and stator winding dc resistance. The object of
this article is to describe the methods of determining the parameters from these
tests.
3.11.1. No-load test (or running light test)
The induction motor is made to run at no load at rated voltage and frequency. Per
phase values of applied stator voltage Vnl, input current Inl and input power Pnl are
recorded.
r2
The no-load slip S is very small, therefore in Figure 3.15 of IEEE recommended
s
equivalent circuit, is very large as compared to Xm. In view of this, the resultant of
r2
parallel branches jXm and jx 2 is almost equal to jXm as illustrated in Figure
s
3.30 (a). Thus the no-load reactance Xnl seen from the stator terminals is equal to x1
+ Xm, i.e.
Xnl = x1 + Xm = X1 3.26
37
Introduction to Electrical Machines
Vn 1
Z n1
I n1
And stator no-load resistance:
Pn1
Rn1 2
I n1
2 2
X n1 Z nl Rn1
The rotational losses Prot (friction, windage loss and core loss) are usually
assumed constant and can be obtained from the relation.
(a)
3.11.2. Blocked-rotor test
Blocked-rotor test, similar to the short-circuit test on a transformer, is performed on
the induction motor to calculate its leakage impedance.
For performing this test, the rotor shaft is blocked by external means, i.e. the rotor
shaft is held stationary by belt-pulley arrangement or by hand. Now balanced poly
phase voltages at rated frequency are applied to the stator terminals through a poly
phase variac. This applied voltage is adjusted till rated current flows in the stator
winding. Per phase values of applied voltage Vbr, input current (=rated current) Ibr
and the input power Pbr are recorded. Current Ibr may be affected by rotor position;
in view of this the rotor should be held in a position that gives Ibr equal to the mean
of maximum and minimum current value.
Measure the dc resistance per phase of the stator winding soon after this test and
multiply it by 1.1 to 1.3 in order to obtain the per phase effective stator resistance
r1.
The equivalent circuit under blocked-rotor test is as shown in Figure.3.30 (b).
38
Introduction to Electrical Machines
R2
S
(b)
Figure 3.30 Induction motor equivalent circuits for (a) no-load test and (b) blocked-
rotor test
From the instrument readings during blocked-rotor test, the parameters can be
obtained as under:
The blocked-rotor impedance
Vbr
Z br
I br
and the blocked-rotor resistance,
P
Rbr br
2
I br
Blocked-rotor reactance
X br Z br 2 Rbr 2
An examination of Figure 3.30 (b) reveals that the blocked-rotor impedance seen
from the stator terminals is given by
jX m ( r2 jx 2 )
Z br Rbr jX br r1 jx1
r2 j( x 2 X m )
jX m ( r2 jx2 ) r2 j ( x2 xm )
r1 jx1 .
r2 j ( x 2 xm ) r2 j ( x2 xm )
2
jX m [ r2 jr2 x 2 jr2 ( x2 X m ) x2 ( x 2 X m ]
r1 jx1 2
r2 ( x2 X m )2
2
jX m [ r2 x 2 X 2 jr2 X m ]
or Rbr jX br r1 jx1 2
r2 X 22
3.27
Where X2 = x2 +Xm, is the rotor self-reactance.
Comparison of the imaginary components of both sides of Eq. (3.27) gives
39
Introduction to Electrical Machines
X m [ r22 x 2 X 2 ]
X br x1
r 22 X 22
r22
Xm x2
X 2
x1
r22
X2
X2
2
Since X 2 r2 , therefore r2 may be neglected. With this
X2
X m x2 X m x2
X br x1 x1
X2 X m x2
x2
x1
x
1 2
Xm
Usually the magnetizing reactance Xm >> rotor leakage reactance x2, therefore
x2
is negligible small and this gives
Xm
Xbr = x1 +x2 3.28
There is no practical method of separating x1 and x2. For wound rotor machines x1 is
assumed equal to x2 i.e. x1 = x2= ½Xbr
For squirrel cage induction machines, total leakage reactance Xbr (=x1 +x2) can be
distributed between stator and rotor as per the following table:
Table 3.1: Empirical distribution of leakage reactance Xbr
Fraction of Xbr
Class of motor X1 X2
Class A (normal Tst , high Ist and low slip) 0.5 0.5
Class B (normal Tst, low Ist and low slip) 0.4 0.6
Class C (high Tst , low Ist and high slip) 0.3 0.7
Class D (high Tst , low Ist and high slip) 0.5 0.5
Once x1 is known, then from Eq. (3.26), the stator magnetizing reactance is given
by
Xm= Xnl –x1
Now taking the real components of both sides of Eq. (3.27) blocked-rotor resistance
Rbr as seen from the stator terminals is
X2
R br r1 r2 2 m 2
r2 X 2
For machines of normal design, X2>> r2 therefore, r2 in the denominator can be
neglected as compared to X2
40
Introduction to Electrical Machines
2
X
R br r2 r2 m
X2
Per phase rotor resistance
2
X
r2 ( R br r1 ) 2 3.29
Xm
Thus Xm from Eq. (3.26) r2 from Eq. (3.29), r1 form dc resistance per phase of stator
winding and x1, x2 from Eq. (3.28) and Table 3.1 can be determined from three
tests. The equivalent circuit can now be used for computing the motor performance.
Note: For large motors (above 20KW or so), if induction motor characteristics are
required near s =1 (e.g. for starting torque etc.); then since rotor frequency f2 is
equal to the line frequency, the blocked- rotor test should be carried out at line
frequency and with currents equal to those encountered at the time of starting.
In case induction motor characteristics are required near synchronous speed (e.g.
during normal operation), then rotor frequency is equal to sf1, therefore, the
blocked-rotor test should be carried out at reduced frequency and with normal
currents.
3.11.3. Separation of friction and windage loss from the no-load test
The power input to the induction motor at no-load has to supply the stator copper
loss, core loss and friction and windage loss.
The dc resistance of the stator winding is measured and its per phase effective value
r1 is calculated from the relation.
r1 = (1.1 to 1.3) (dc resistance of one phase)
For computing the friction and windage loss, the applied voltage to the unloaded
induction motor is varied from 1.25 times the rated voltage to about 20% of the
rated voltage. The input power, current and voltage are recorded so that a graph
can be plotted. The speed, with reduction in voltage, will fall only slightly so that the
friction and windage loss remains substantially constant
From each of the input-power readings, the corresponding stator ohmic loss is
subtracted to obtain the core loss and friction and windage loss, i.e.
Prot m( Pnl I nl2 r1 )
Where, Pnl is the per phase power input,
Inl is the per phase stator current and
r1 is the effective per phase stator resistance.
The plot of the rotational loss P rot with variable stator voltage is shown in Figure
3.31. The intercept of the extraplotted Prot curve with the ordinate gives the friction
and windage loss, because the core loss is zero for zero applied voltage.
41
Introduction to Electrical Machines
42
Introduction to Electrical Machines
1
x1 x 2 X br 2.158
2
X m X nl x1 86 .51 2.158 84.352
And
X 2 X m x 2 84.352 2.158 86 .51
From eq.(3.29), per phase rotor resistance is given by
2
X
r2 ( R br r1 ) 2
Xm
2
86.51
1.102 0.6 1.2 0.402
84.352
Thus the parameters of the induction motor equivalent circuit are:
r1= 0.72; r2= 0.402; x1=x2=2.158; and Xm=84.352
3.12. SPEED CONTROL OF INDUCTION MOTORS
The synchronous speed Ns of an ac motor is related to supply frequency f and poles
P by the equation.
120 f
Ns
p
As regards induction motor, the rotor is given by
N (1 s ) N s
Where S is the slip
It is found from the above two equations that the basic methods of speed control of
an induction motor are:
a) by changing the number of poles and
b) by varying the line (input) frequency.
By the above two methods, the synchronous speed of an induction motor can only
be changed. These methods are applicable only to cage induction motors
The slip can be changed by the following methods.
c) by varying the input voltage
d) by varying the rotor resistance
The methods(c-d) are applicable to slip-ring (wound rotor) induction motors,
whereas only the method (c) can be applied to machines with cage rotor.
a) by changing the number of poles (Pole changing methods)
Four-pole to eight –pole connections
In pole changing induction motors, the stator winding of each phase is divided into
two equal groups of coils. These coil groups are connected in series and parallel with
the current direction being reversed only in one group, to create two different
numbers of poles (even) in the ratio 2.1 respectively. When the connection is
changed from series to parallel or vice versa, the current in one group of coils is also
reversed at the same time. This technique, termed the consequent pole method, is
applied to all three windings (phases). This type of induction motor has always the
squirrel cage rotor, which can adapt to any number of stator poles.
Figure 3.32(a) shows schematically only four coils of one phase of the windings
connected in series, along with the direction of current in them, producing eight
43
Introduction to Electrical Machines
poles in the stator. If the current in coils 2 and 4 is reversed and the connection is
changed to parallel with two coils (1 and 3, and 2 and 4) connected in series for
each path, four poles are formed in the stator (Figure 3.32(b)). It may be noted that
the direction of current in coils 1 and 3 remains the same. Only one type of
connection is shown.
44
Introduction to Electrical Machines
In any pole changing (P-pole/2P-pole) induction motor, there are two equal parts as
stated above. The changeover for constant torque operation takes place as shown in
Figure 3.33.
Low
speed High
(2P) speed
(P)
Ns
Ns N
2
PY 3 (VI cos Y )
2. For parallel-star connection (Figure 3.33(b))
PY Y 2 3 (VI cos Y Y )
It is assumed that the power factor remains unchanged and the motor losses are
negligible. With the changeover of stator winding from series star to parallel star,
the power drawn from the supply is doubled. Simultaneously, the speed is also
doubled. So the motor torque remains constant. Constant torque operation is more
common.
Constant horsepower operation: (/YY)
The power drawn from the supply is given by:
45
Introduction to Electrical Machines
P 3 VICos
2. For parallel-star connection (Figure (3.34(b))
Ns Ns
2
E 4.44 m f T ph K w
46
Introduction to Electrical Machines
The induced emf E is nearly equal to the applied voltage V (neglecting drop in stator
impedance). Then, we can write
V
f
4.44 m T ph K V Hz
When the frequency is reduced, the applied voltage also must be reduced
proportionally so as to maintain constant flux, otherwise the core will get saturated
resulting in excessive iron losses and magnetizing current. The maximum torque
also remains constant under this condition. However, the voltage is not varied
proportionally in the lower frequency range to account for the voltage drop in the
winding resistance. This type of control (constant V/f) is used for speed control
below base frequency (line frequency of 50Hz).
As the voltage increase above rated value, when the input frequency goes above
base frequency, only constant (rated) voltage with variable frequency (frequency
control) is used for speed control. Under this condition, both flux and maximum
torque decrease as the frequency is increased.
Advantages of constant volt/Hz operations are the following:
a) Smooth speed control,
b) Small input current and improved power factor at low frequency start, and
c) Higher starting torque for low cage resistance
Maximum Torque
Neglecting the stator winding resistance, the maximum torque is
3V 2
Tmax
2syn X1 X '2
So, the maximum torque remains constant as stated earlier for constant volt/Hz
ratio for frequencies below base frequency, except for very low values of frequency
(Figure 3.35). This is taken as constant torque control with constant flux or
volt/Hz ratio.
For input frequency above base frequency, only constant (input) voltage with
variable frequency is applied as stated earlier. In this case the maximum torque
changes to
2
3 V
T max
2 syn X 1 X 2
'
supply frequency
Where,
base frequency
With α >1 as frequency is higher than base frequency, both maximum torque and
flux, as given by volt/Hz ratio, decrease as frequency increases (as shown in Figure
3.34). This is taken as constant power control with variable flux.
47
Introduction to Electrical Machines
TL N 2
48
Introduction to Electrical Machines
3
Figure 3.37 the torque- speed characteristics for four external resistances
The major disadvantage of the rotor resistance control method is that the efficiency
is low at reduced speed because of higher slips. However, this control method is
often employed because of its simplicity. In applicationwhere low-speed operation is
only a small proportion of the work, low efficiency is acceptable. A typical application
of the rotor, resistance control method is the hoist drive of a shop crane. This
method also can be used in fan or pump drives, where speed variation over a small
range near the top speed is required.
3.13. STARTING OF IM
Most induction motors-Large and Small-are rugged enough that they could be
started across the line without incurring any damage to the motor windings,
although about five to eight times the rated current flows through the stator at
rated voltage at standstill. However, in large induction motors, large starting current
are objectionable in two respects:
First, the mains supplying the induction motor may not be of a sufficiently
large capacity.
Second, because of large starting current, the voltage drops in the lines may
be excessive, resulting in reduced voltage across the motor.
Because the torque varies approximately as the square of the voltage, the starting
torque may become small at the reduced line voltage that the motor might not even
start on load. Thus we formulate the basic requirement for starting:
The line current should be limited by the capacity of the mains, but only to the
extent that the motor can develop sufficient torque to start (on load , if necessary)
A number of methods is available of for starting both cage-rotor and wound-
rotor motors:
49
Introduction to Electrical Machines
starting torque, on account of the fact that motor torque is proportional to the
square of the applied voltage. Despite this, reduced-voltage starting is the most
popular method of starting three-phase squirrel-cage induction motors and consists
of stator resistor (or reactor) starting, auto-transformer starting and star-delta
starting. The various methods are now described in what follows.
a. Direct-on-line (across-the-line) starting.
As the name suggests, this method involves the direct switching of polyphase stator
on to the supply mains. The motor takes low-power factor starting current of 5 to 8
times its full-load current, depending upon its size and design. Such large currents
of short duration don't harm the rugged squirrel cage motor, but the high currents
may cause objectionable voltage drop in the power supply lines feeding the
induction motor. These large voltage drops cause undesirable dip in the supply line
voltage; consequently the operation of other equipments connected to the same
supply line is effected considerably. A common example is the momentary dimming
of lamp and tube-lights in the home at the instant a refrigerator motor starts. If the
supply system is of sufficient power capacity and the low-power factor starting-cur-
rent surges don't cause objectionable voltage dips in the supply line voltage, then
the direct-on-line starting should be preferred.
The relation between starting torque Tst and full-load torque Tfl is now obtained. Let
Ist and Ifl be the per-phase stator currents drawn from the supply mains
corresponding to starting and full-load conditions respectively. From Torque
equation
1 2 R2
T mech .I2
syn S
R2
I 22st 2
Tst
1 I 2st S 3.30
Tfl R I fl
I 22fl 2 2 fl
S fl
Eq. (3.30) is valid in case rotor resistance remains constant. Actually, rotor
resistance varies with the frequency of rotor current; at starting rotor frequency is
50 Hz and at full load it is only a few hertz.
Here I2st and I2fl are the per-phase rotor currents at starting and full-load conditions
respectively.
If no-load current is neglected, then
I st I 2st
or
I fl I 2 fl
2
Tst I st
From equation (1.30), S fl
Tfl I fl
50
Introduction to Electrical Machines
If V1 is the per phase stator voltage and ZSC is the standstill per phase leakage
impedance referred to stator, then per phase short-circuit current at standstill (or at
starting) is,
V1
I sc
Z sc
Where,
Z sc R 1 R 2 jX1 X 2
Note that here shunt branch of the induction motor equivalent circuit is neglected.
Therefore, for direct switching,
V1
I st I sc
Z sc
Equation (3.30) can, therefore, be written as
2
Tst I sc
Sfl 3.31
Tfl I fl
b. Stator resistor (or reactor) starting
In this method, a resistor or a reactor is inserted in between motor terminals and
the supply mains, as illustrated in Figure 3.38.
1
xV
3V1 3xV1
V1
xV1
Figure 3.38 Reactor (or resistor) starting of squirrel cage induction motor
At the time of starting, some voltage drop occurs across the starting resistor or
reactor and, therefore, only a fraction x (less than 1) of the supply voltage appears
across the stator terminals. This reduces the per-phase starting current Ist drawn by
the motor from the supply mains. As the motor speeds up, the reactor is cut out in
steps and finally short-circuited when the motor speed is near to its operating
speed. Since per phase voltage is reduced to xV1, see Figure 3.38 , the per-phase
starting current Ist is given by
xV1
I st xI SC 3.32
Z SC
2
Tst I st
As before S fl
T fl I fl
51
Introduction to Electrical Machines
2
Tst I
Or x 2 sc Sfl 3.33
Tfl Ifl
2
In an induction motor, torque (voltage)
2
Starting torque with reactor or resistor starting xV1
x 2 3.34
Starting torque with direct starting V
1
Series reactor is more costly than the series resistor, but the former has lower
energy loss and is more effective in reducing the voltage, because the induction-
motor power factor at starting is quite low.
c. Autotransformer starting
A fraction of xV1 of the supply voltage V1 is applied to the stator terminals at the
time of starting, by means of an autotransformer as shown in Figure 3.39.
xV1
x I sc 3.35
Z1
If no-load current of autotransformer is neglected, then per phase output VA of an
autotransformer must be equal to its per phase input VA. That is
I st x 2 .I sc 3.36
52
Introduction to Electrical Machines
Eq. (3.35) shows that the motor starting current per phase is reduced only to x
times the direct switching current Isc ; but the per phase starting current from the
supply mains is reduced to x2 times the direct switching Isc .
Now
Tst xI sc 2
.S fl
Tfl I 2fl
I sc 2
x2 .Sfl 3.37
I fl2
Per phase staring current, Ist, from the supply mains can be calculated in Eq. (3.37)
with the help of Eq. (3.36). Substitution of the value of Isc in terms of Ist gives
2
Tst 1 I
x 2 2 st .S fl
T fl x I
fl
2
I
x 2 st .S fl 3.38
I
fl
The ratio of the starting to full-load torque in terms of both Ist and Isc can be
obtained from Eq. (3.37) as follows.
Tst x 2 I sc I sc
.S fl
T fl I 2fl
I st I sc
S fl 3.39
I 2fl
Per phase motor starting current in terms of Ist, from Eq. 3.35, is given by
1
x I sc x I st
x2
1 3.40
I st
x
For an induction motor, torque (voltage) 2
2
Tst with an autotransformer xV1
x 2 3.41
Tst with direct switching V1
53
Introduction to Electrical Machines
It is from above that with an autotransformer, the starting current Ist from the
mains and the starting torque Tst are reduced to x2 times their corresponding values
with DOL starting, see Eqs (3.36) and (3.41).
d. Star-Delta Method
A Star-Delta method starting may also be employed to provide reduced voltage of
start. In this method, the normal connection of the stator windings is delta while
running (Figure 3.40).
Figure 3.40 pertaining to the star-delta starting of a 3-phase cage induction motor
If these windings are connected in star at start, the phase voltage is reduced,
resulting in less current of starting. As the motor approaches its full-speed, the
windings will be connected in delta.
Thus, the line current under each of these connection are:
Vph VL
IY with the windings connected in Star ;
Z ph 3 Z ph
VL
I 3 with the windings connected in Deta
Z ph
So that the ratio of the current is
I V Z
Y L ph 1
I 3Z 3V 3
ph L
Showing that the current drawn from the line under a star connection is only one-
third ( 1 ) of that under delta connection. On the other hand, the ratio of the
3
current in the stator windings is
V ph
I ph Y Z ph 1
I ph 3 Vph 3
Z ph
2
VL
Also
Tst with Star Delta Starter 3 1
2
Tst with direct switching in Delta VL 3
54
Introduction to Electrical Machines
This shows the star-delta starter also reduce the starting torque to one-third of that
produced by direct switching in delta.
Example 3.10 A squirrel induction motor has a full-load slip of 0.05. The
motor starting current at rated voltage is 6 times its full-load current. Find the
tapping on the auto-transformer starter which should give full-load at start. Also find
the line current at starting in terms of full-load current.
Solution
Here , motor starting or short-circuit current Isc is 6Ifl.
2
Tst I
x 2 sc .S fl
T fl I fl
1 x 2 6 2 0.05
1
x 0.745
Or 1.8
or 74.5% tappings
The starting line current is
I st x 2 I sc 0.7452 6 I fl
3.33 I fl
Example 3.11 A small 3-phase induction motor has a short-circuit current 5
times of full load current and full load slip 5%. Determine the starting torque and
starting current if starting resistance starter is used to reduce the impressed voltage
to 60% of normal voltage.
Solution
Starting current,
Ist 0.6ISC 0.6 5I fl 3I fl
Starting torque,
2
I
Tst Tfl st Sfl Tfl 3 0.05 0.45Tfl i.e. 45% of full load torque.
2
Ifl
At the time of start, the entire external resistance is added in the rotor circuit. As
the rotor speeds up, the external resistance is decreased in steps so that motor
torque tends to remain maximum during the accelerating period. Finally, under
normal operation, the external resistance is fully cut off and the slip rings are short-
circuited so that motor now develops full-load torque at low value of slip for which it
is designed.
Calculation of Resistance of elements (or sections)
Consider one phase of the rotor of a wound-rotor induction motor, with resistance r2
and standstill leakage reactance x2. Let R1, R2 ,R3 …….Rn be resistance of the n
resistance elements (or sections) and R1’ , R2’, R3’,….Rn’, Rn+1’ be the total
resistance in each phase of the rotor circuit on 1st ,2nd ,3rd ,…,nth and (n+1)th stud
respectively as shown in Figure 3.40(a) , such that
R1= R1 + R2 + R3 +R4 +………+ Rn-1+Rn + r2
R2 = R2 + R3 +R4 +………+ Rn-1+Rn + r2
R3’ = R3 +R4 +………+ Rn-1+Rn + r2
:
:
Rn+1= r2.
(a)
(b)
56
Introduction to Electrical Machines
Figure 3.41 (a) pertaining to the design of starter for wound-rotor IM; (b) Variation
of input current with time
Note that Figure 3.41(a) illustrates n-elements starter, n-section starter, (n+1) stud
starter or n-step starter. For calculation of the section resistances, the following
assumptions are made:
i. During starting time , a constant load torque is assumed
ii. The stator leakage impedance and its no-load current are neglected
iii. Stator current is taken to fluctuate between fixed limits I1max (maximum
value) and I1min (minimum value) as shown in Figure 3.41(b).
At the time of start, the movable handle is at stud 1 and the rotor circuit resistance
is R1’. When the supply is switched on to the stator, the input current shoots to I1max
and its value is given by
V1
I 1 max 3.42
2
R 1'
x 2
S1
Note that at the time of start, slip S1 = 1
On first stud, R1’ remains in the circuit until the motor has started and the current
has fallen from I1max to I1min . At the same time the slip falls from S1 to S2
V1
I 1 min 3.43
2
R1'
x 2
S2
As soon as I1min is reached at stud 1, resistance R1 is cut out by moving the handle
from stud 1 to stud 2. During the notching process (the process of moving the
handle from one stud to the next), the speed is assumed to remain constant, i.e. the
slip remains as S2 but current at stud 2 becomes I1max as illustrated in Figure
3.41(b).
V1
I 1max 3.44
2
R'2
x 2
S2
At stud 2, the speed rises so that the slip becomes S3 and current decreases to I1min,
V1
I 1 min 3.45
2
R'2
x 2
S3
During the next notching process, i.e., at the third stud when R2 is cut out,
V1
I 1 max 3.46
2
R3'
x 2
S3
and
57
Introduction to Electrical Machines
V1
I1 min . 3.47
2
R '3
x2
S4
and so on
58
Introduction to Electrical Machines
S2 S3 S4
S1 S2 S3
S S S
...... n n 1 fl
Sn 1 Sn Sn
R '2 R '3 R '4
R 1' R '2 R '3
R 'n 1 R 'n
.......
R 'n 2 R 'n 1
R 'n 1 r
2 (say ) 3.50
R 'n R 'n
Since the slip S1=1, the total resistance in rotor circuit on the first step (or first
stud) from Eq. (3.48), is
S1 r
R1' r2 2 3.51
S fl S fl
From Eq. 3.50,
59
Introduction to Electrical Machines
R 4 3R 1
R n n 1R1 3.55
The slip Sfl provided I1max=Ifl. In case I1max is different from Ifl, slip Sfl should be
calculated accordingly and then from Eq. (3.53), α can be obtained. Once R1’is
determined by using Eq.(3.51), first the resistance element R1 is obtained by using
Eq.(3.54) and then R2, R3, R4……. Can be calculated from Eq. (3.55).
Example 3.13 Calculate the values of resistance elements of a 4-step starter
for a 3-phase, 400-V, wound-rotor induction motor. The full-load slip is 3% and the
maximum starting current is limited to its full-load value. Rotor resistance per phase
is 0.015-Ω.
Solution
For a 4-step starter, there are 4-sections i.e. n=4.
Here, Sfl=3%=0.03
1 1
( S fl ) n 0.03 4 0.416
The total resistance of rotor circuit at the moment of starting
r2 0.015
R1' 0.5
S fl 0.03
The resistances of various elements are:
R1=R1’(1-)= 0.5(1-0.416)=0.292
R2=R1=0.416 x 0.292 = 0.121
R3=2R1=R2=0.416 x 0.121 = 0.051
R4=3R1=2R2=R3=0.416 x 0.051 = 0.021
Checking :
R’1=R1+R2+R3+R4+r2 =0.292+0.121+0.051+0.021+0.015= 0.5
3.14. APPLICATIONS OF POLYPHASE INDUCTION MOTORS
For loads requiring low starting torques and substantially constant speeds,
squirrel-cage induction motor is the best choice, because of its ruggedness,
simplicity, low cost and reduced maintenance charges. Squirrel cage motor may
be designed with low rotor resistance or with high rotor resistance. As stated
before, a high rotor resistance gives better starting conditions but poor running
performance. On the other hand, a cage motor with low rotor resistance gives
poor starting conditions but better running performance. In view of this, the
rotor-circuit resistance should be chosen judiciously at the design stage so that
there is a compromise between its starting conditions and running performance.
Squirrel cage motors with relatively low rotor resistance (full-load slip 3 to 5%)
are used for fans, centrifugal pumps, most machinery tools, wood-working tools
etc. Cage motors with relatively high rotor resistance (full-load slip 3 to 7%)
are used for compressors, crushers, reciprocating pumps. Squirrel cage motors
with still higher values of rotor-circuit resistance (full-load slip 7 to 16%) are
used for intermittent loads like punching presses, shears, hoists, elevators etc.
A wound-rotor induction motor is used for loads requiring severe starting
conditions or for loads requiring speed control. A wound rotor induction motor is
60
Introduction to Electrical Machines
more expensive than a squirrel cage motor and also it requires more
maintenance because of the brushes and slip rings. A wound-rotor motor, also
called slip-ring motor, may be used for hoists, cranes, elevators, compressors
etc.
The relative advantages of cage motor over a wound-rotor motor of the same
power rating are given below.
i) A cage rotor requires considerably less conductor material than a wound
rotor, consequently I2 R loss in cage rotor is less. Therefore, cage motor is
a little more efficient than a wound-rotor motor.
ii) Wound-motor construction requires slip rings, brushes, short-circuiting
devices etc. As a result of it, a wound-rotor motor is costlier than a cage
induction motor.
iii) A squirrel-cage rotor has very small length of overhang; therefore, it has
low rotor overhang leakage flux. This has the effect of resulting in low
leakage reactance x2 for a cage rotor than for a wound rotor.
Consequently, the diameter of circle diagram for a cage motor is greater
than for a wound-rotor motor. This shows that a cage motor has more
pull-out torque, greater maximum power output and better operating
power factor as compared to a wound-rotor induction motor.
iv) Cage motor is more rugged and requires no slip rings, brushes etc.
therefore, its maintenance charges are low.
v) Cage rotor can be cooled better because of its bare end-rings.
The disadvantages of cage motor as compared to a wound rotor motor are its
small starting torque for very large starting current and its poor starting power
factor. In addition to it, the total energy lost during starting of cage motor is
much more than with the wound-rotor motor and this fact is very important
where frequent starting of large number of motors is required.
61
Introduction to Electrical Machines
62
Introduction to Electrical Machines
63
Introduction to Electrical Machines
3.15. A 3-phase , 400 V, 50Hz star-connected induction motor gave the following
test results:
No load: 400 V, 7.5A, 0.135 power factor
Blocked rotor: 150 V, 35A, 0.44 power
factor
The ratio of standstill leakage reactance of stator and rotor is estimated as 2.
If the motor is running at a speed of 900rpm, determine
a) Net mechanical power output
b) The net torque and
c) Efficiency of the motor
Assume stator to rotor copper losses to be equal.
Ans. P sh=8648.98 W; Tsh=86.033 N.m;= 86.23%
3.16. Design the 5-sections of a 6-stud starter for a 3-phase slip-ring induction
motor. The full-load slip is 2% and the maximum starting current is limited to
twice the full-load current. Rotor resistance per phase is 0.03-Ω.
Ans. 0.356 Ω; 0.187 Ω; 0.098 Ω; 0.052 Ω;0.027 Ω
3.17. A squirrel induction motor has a full-load slip of 0.05. The motor starting
current at rated voltage is 6 times its full-load current. Find the tapping on the
auto-transformer starter which should give full-load at start. Also find the line
current at starting in terms of full-load current. Ans. 74.5%; 3.33 Ifl
3.18. A 3-phase squirrel cage induction motor has a short-circuit current of 5 times
the full-load current. Its full-load slip is 5%. Calculate the starting torque as
percentage of full-load torque if the motor is started by
a) Direct-on-line starter
b) Start-delta and
c) Auto-transformer starter, limiting the motor starting current to twice
the motor full-load current.
d) What is the percentage auto-transformer tapping under (c) case?
Ans. a) 1.25%; b) 0.417; c) 0.20; d)
40%
3.19. Calculate the values of resistance elements of a 4-step starter for a 3-phase,
400-V, wound-rotor induction motor. The full-load slip is 3% and the maximum
starting current is limited to its full-load value. Rotor resistance per phase is
0.015-Ω.
Ans. 0.291 Ω; 0.121 Ω; 0.051 Ω; 0.021 Ω
64