Fail-Safe Setting-Up Operation With A SINAMICS G120 Using SLS Without An F-CPU

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Uploaded by

76971495
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 37

Fail-safe setting-up operation with a

SINAMICS G120 using SLS without


an F-CPU
SINAMICS G120 CU240E-2 DP-F, CU240E-2 PN-F,
CU240E-2 F

Application June 2012

Applikationen & Tools


Answers for industry.
Siemens Industry Online Support
This article is taken from the Siemens Industry Online Support. The following link
takes you directly to the download page of this document:
http://support.automation.siemens.com/WW/view/en/62069920

Caution
The functions and solutions described in this article confine themselves to the
realization of the automation task predominantly. Please take into account
furthermore that corresponding protective measures have to be taken up in the
context of Industrial Security when connecting your equipment to other parts of the
plant, the enterprise network or the Internet. Further information can be found
under the Item-ID 50203404.
http://support.automation.siemens.com/WW/view/en/50203404

You can also actively use our Technical Forum from the Siemens Industry Online
Support regarding this subject. Add your questions, suggestions and problems and
discuss them together in our strong forum community:
62069920_Failsafe_JOG_mode_V4-4_DOKU_V10_en.doc
Copyright Siemens AG 2012 All rights reserved

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 2


s Introduction 1

Automation solution 2

Wiring diagrams 3
Engineering and
configuring 4
SINIMICS G120
Fail-safe setting-up operation with Commissioning the
application 5
a SINAMICS G120 using SLS
without an F-CPU 6
Using the application

References 7
Siemens AG 2012 All rights reserved

History 8
Copyright

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 3


Warranty and liability

Warranty and liability


Note The Application Examples are not binding and do not claim to be complete
regarding the circuits shown, equipping and any eventuality. The Application
Examples do not represent customer-specific solutions. They are only intended
to provide support for typical applications. You are responsible for ensuring that
the described products are used correctly. These application examples do not
relieve you of the responsibility to use safe practices in application, installation,
operation and maintenance. When using these Application Examples, you
recognize that we cannot be made liable for any damage/claims beyond the
liability clause described. We reserve the right to make changes to these
Application Examples at any time without prior notice.
If there are any deviations between the recommendations provided in these
application examples and other Siemens publications – e.g. Catalogs – the
contents of the other documents have priority.

We do not accept any liability for the information contained in this document.

Any claims against us – based on whatever legal reason – resulting from the use of
the examples, information, programs, engineering and performance data etc.,
described in this Application Example shall be excluded. Such an exclusion shall
Siemens AG 2012 All rights reserved

not apply in the case of mandatory liability, e.g. under the German Product Liability
Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life,
body or health, guarantee for the quality of a product, fraudulent concealment of a
deficiency or breach of a condition which goes to the root of the contract
(“wesentliche Vertragspflichten”). The damages for a breach of a substantial
contractual obligation are, however, limited to the foreseeable damage, typical for
the type of contract, except in the event of intent or gross negligence or injury to
life, body or health. The above provisions do not imply a change of the burden of
proof to your detriment.
Copyright

Any form of duplication or distribution of these Application Examples or excerpts


hereof is prohibited without the expressed consent of Siemens Industry Sector.

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 4


Table of contents

Table of contents
Warranty and liability ...............................................................................................4
1 Introduction ....................................................................................................6
1.1 Preconditions.....................................................................................6
1.2 Area of validity of this application example.........................................6
1.3 Integrated safety functions.................................................................7
Overview of the automation task ........................................................8
2 Automation solution.......................................................................................9
2.1 Overview of the total solution .............................................................9
Design 9
Demarcation ......................................................................................9
Know-how that is required..................................................................9
2.2 Description of the core functionality..................................................10
Overview and description of the core functionality ............................ 10
Advantages of this solution .............................................................. 10
2.3 Hardware and software components used ....................................... 11
Hardware components..................................................................... 11
Standard software components........................................................ 11
File examples and projects .............................................................. 12
3 Wiring diagrams ...........................................................................................13
Siemens AG 2012 All rights reserved

3.1 24V power supply voltage from the SINAMICS G120 ....................... 14
3.2 External 24V power supply voltage .................................................. 15
3.3 Power Module and motor................................................................. 16
4 Engineering and configuring ....................................................................... 17
4.1 Passwords.......................................................................................17
4.2 Preparation......................................................................................17
4.3 Configuring the basic drive functions................................................ 19
4.4 Parameterizing the safety functions integrated in the drive ............... 24
Copyright

4.5 Acceptance test ...............................................................................30


5 Commissioning the application ................................................................... 32
5.1 Preconditions...................................................................................32
5.2 Preparation......................................................................................32
5.3 Commissioning................................................................................32
6 Using the application ...................................................................................33
6.1 Description ......................................................................................33
6.2 Summary of the input signals........................................................... 35
7 References....................................................................................................36
7.1 References......................................................................................36
7.2 Internet links - data ..........................................................................36
7.3 Selected application examples and FAQs ........................................ 36
8 History ..........................................................................................................37

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 5


1 Introduction

1 Introduction
When machines are operated in the setting-up mode, frequently it is necessary that
the motors are operated with a safety limited speed.
Generally, external devices are required in this case to monitor the motor speed.
The SINAMICS G120 frequency converter with its integrated safety functions,
represents a favorably priced alternative to these external devices.
The fail-safe setting-up mode using the fail-safe digital inputs of the SINAMICS
G120 – with all of the parameter assignments required – is explained in this
application example.

1.1 Preconditions

NOTICE Please carefully note that it is not permissible to use the SS1, SLS, SDI and
SSM safety functions for pulling or continuously regenerative loads.
A "pulling or continuously regenerative load" is involved, if in the no-
voltage state, the motor is accelerated by the load (e.g. lifting
equipment/cranes, winders, wind turbines).
To use fail-safe functions, the closed-loop control must function perfectly.
Siemens AG 2012 All rights reserved

The drive (system converter + motor + driven machine) must be engineered


so that all operating cases of the particular application can be handled.

NOTICE After activating the STO and SS1 safety functions, there is no electrical
isolation between the line supply of the SINAMICS G120 and the motor. If
this is required in your particular application, then you must install an
appropriate line contactor upstream of the SINAMICS G120.
Copyright

1.2 Area of validity of this application example


This application example is valid for the following Control Units with FW V4.4:
CU240E-2 F
CU240E-2 DP-F
CU240E-2 PN-F

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 6


1 Introduction

1.3 Integrated safety functions


When using the CU240E-2 DP-F, CU240E-2 PN-F or CU240E-2 F Control Unit,
you can employ the following safety functions according to IEC 61800-5-2
integrated in the frequency converter:

Table 1-1: Overview of the SINAMICS G120 safety functions

Name Function Description

Safely switching off the torque-generating energy feed to


the motor.
STO Safe Torque Off
Restarting is prevented by the switch-on inhibit function.
(stop function, Category 0 according to EN 60204-1)

Fast and safely monitored drive stopping along the OFF3


ramp.
SS1 Safe Stop 1 After a delay time has expired or the shutdown speed has
been reached, the drive transitions into the STO state.
(stop function, Category 1 according to EN 60204-1)
Siemens AG 2012 All rights reserved

Safe monitoring of the drive speed


Safely Limited
SLS Parameterizable shutdown response when a limit value is
Speed
violated.

Safely displays (monitors) when a speed limit is fallen


SSM Safe Speed Monitor below (n < nx).
SSM is not released for CU240E-2 F.
Copyright

Safe monitoring of the direction of motion (positive and


negative directions).
SDI Safe Direction
Parameterizable shutdown response when traversing in
the direction that has not been enabled.

All of the safety functions are implemented according to:


• EN 954-1 (Cat. 3)
• IEC 61508 (SIL 2)
• ISO 13849-1 (PLd)

Link to the certificate:


http://support.automation.siemens.com/WW/view/en/22339653/134200

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 7


1 Introduction

Overview of the automation task


Fig. 1-1: Concept of the safety functions

The following safety functions are used as a basis for further analysis.
Siemens AG 2012 All rights reserved

Table 1-2: Safety functions of the application example


Safety Description Response
function
Pressing the Emergency Stop Fast stopping of the drive with
SF1 button subsequent pulse cancellation
(SS1).
When protective door 1 is open, it
is not permissible that the drive
Copyright

SF2 Monitoring the drive speed (SLS).


exceeds a velocity/speed
configured by the user.
The extended safety functions integrated in SINAMICS G120 drives should be
controlled via the input terminals of the CU240E-2 DP-F.

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 8


2 Automation solution

2 Automation solution
2.1 Overview of the total solution
Design
This function example is based on the SINAMICS G120 training case (6ZB2480-
0CD00) and a CU240E-2 DP-F (6SL3244-0BB13-1PA1).

Demarcation
This application does not include a description of
the SINAMICS G120 safety functions,
the general drive functions of the SINAMICS G120 or
the hardware interfaces of the CU240E-2 DP-F.
It is assumed that the reader has sufficient knowledge about these subjects.
Information on these topics can be taken from the documents listed under the
references.
Siemens AG 2012 All rights reserved

Know-how that is required


It is assumed that readers have a basic knowledge about configuring SINAMICS
G120 drives using the STARTER or SIMOTION SCOUT engineering software.
Copyright

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 9


2 Automation solution

2.2 Description of the core functionality


Overview and description of the core functionality
Fig. 2-1: SINAMICS G120 training case
Siemens AG 2012 All rights reserved

Switches -S1 up to -S3 are provided on a switch box. These are used to select the
safety functions SS1 and SLS.
Switches -S4 up to -S6 are provided in the SINAMICS training case. Using these
switches, the drives are switched on and switched off, the test function for the
safety functions started and any faults acknowledged.
Copyright

When Emergency Stop is actuated, the drive is stopped with the SS1 function
integrated in the drive.
In the automatic mode, the drive rotates with the constant speed. If the setting-up
mode is selected (-S2), and the jog button (-S3) is simultaneously kept pressed,
then the SLS safety function is activated. The drive reduces the speed and safely
monitors this. If the jog button is released (-S3) or is not actuated, then the SS1
function is initiated, the drive brakes along the OFF3 ramp down to a standstill and
then it goes into the subsequent STO state.

Advantages of this solution


The solution presented here offers you the following advantages
Simple control of the safety functions integrated in the drive
Simple design based on standard technology
The existing system can be quickly and simply expanded
Space saving and favorably priced solution using integrated safety functions;
no additional hardware is required
Complex safety concepts can be implemented on this basis

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 10


2 Automation solution

2.3 Hardware and software components used


The application was created using the following components:

Hardware components
Table 2-1: SINAMICS G120 training case
Component Type MLFB / ordering data Qty. Manufactu
rer

SINAMICS G120 Control Unit CU240E-2 DP-F 6SL3244-0BB13-1PA1 1 SIEMENS


SINAMICS G120 Power
PM240 6SL3224-0BE13-7UA0 1 SIEMENS
Module
Three-phase induction
Drive 1LA7060-4AB10-Z 1 SIEMENS
motor, 0.12 kW

Table 2-2: Control devices


Component Type MLFB / Qty. Manufacturer
ordering data

-S1 Emergency Stop Emergency Stop mushroom 3SB3000-


1
command device pushbutton 1HA20
Siemens AG 2012 All rights reserved

Switching element 2 NC contacts 3SB3400-0E 1


Emergency Stop backing
Emergency Stop backing plate 3SB3941-0AK 1
plate
-S2 operating mode selector 3SB3000-
Toggle switch 1
switch 2KA11
Switching element 1NO + 1 NC contact 3SB3400-0A 1
Switching element 2 NC contacts 3SB3400-0E 2 SIEMENS

Holder for switching elements Holder for switching elements 3SB3901-0AC 1


Copyright

-S3 jog button 3SB3000-


Pushbutton, black 1
0AA11
Switching element 2 NO contacts 3SB3400-0D 1
Switching element 2 NC contacts 3SB3400-0E 1
Switching element 1 NO contact 3SB3400-0B 1
Holder for switching elements Holder for switching elements 3SB3901-0AC 1
Setpoint potentiometer Potentiometer 4.7 kOhm 1 Others

NOTE The application example was tested with the hardware components listed here. It
goes without saying that alternative components with the same features and
quality can be used. In such a case, it may be necessary to use a different
parameterization and wire-up the components differently.

Standard software components


Table 2-3: Engineering software
Component Type MLFB / ordering data Qty. Manufacturer
6AU1 810-1BA42-
STARTER or SCOUT V4.2.1.0 1 SIEMENS
1XA0

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 11


2 Automation solution

Firmware version
Table 2-4: Firmware used
Component Type

SINAMICS G120 (CU240E-2 DP-F) V4.4

NOTE SIMOTION SCOUT can be used as an alternative to the STARTER software.

File examples and projects


Table 2-5: Delivery condition of the application example
Component Note
62069920_Failsafe_JOG_mode_V4-4_CODE_v10.zip Zipped project
62069920_Failsafe_JOG_mode_V4-4_DOKU_V10_en.pdf This document
ISO_13849-1_SET_project_to_FAQ_62069920.set SET project according to
ISO 13849-1
IEC62061_SET_project_to_FAQ_62069920.set SET project according to
Siemens AG 2012 All rights reserved

EN/IEC62061
Copyright

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 12


3 Wiring diagrams

3 Wiring diagrams
For reasons of simplicity, in this application example, the SINAMICS G120 is
exclusively controlled through the digital inputs, and the setpoint is entered via an
analog input. It goes without saying that the converter can also be controlled via a
fieldbus (PROFIBUS or PROFINET). However, this version is not discussed in this
example. An experienced user will be able to simply make the adaptations
required.
The following wiring diagrams differ regarding the source of the 24 V power supply.
This can be taken directly from the SINAMICS G120 (see Chapter 3.1); however,
an external 24 V power supply can also be used (see Chapter 3.2).

NOTICE The SINAMICS G120 has components at hazardous voltage levels and
controls rotating mechanical equipment, which is also hazardous. If these
warnings are not carefully observed, or if the notes provided in the various
SINAMICS G120 instructions are not followed, then this can result in death,
severe bodily injury or significant material damage.
Siemens AG 2012 All rights reserved
Copyright

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 13


Copyright Siemens AG 2012 All rights reserved

3 Wiring diagrams

3.1 24V power supply voltage from the SINAMICS G120


Fig. 3-1: Power supply voltage from the SINAMICS G120

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 14


Copyright Siemens AG 2012 All rights reserved

3 Wiring diagrams

3.2 External 24V power supply voltage


Fig. 3-2: External power supply

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 15


Copyright Siemens AG 2012 All rights reserved

3 Wiring diagrams

3.3 Power Module and motor


Fig. 3-2: PM and motor

You can obtain more information regarding the installation from the SINAMICS G120 Power Module Hardware Installation Manual.
Download under: http://support.automation.siemens.com/WW/view/en/22339653/133300

Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU

Version 1, Item-ID: 62069920 16


4 Engineering and configuring

4 Engineering and configuring


An explanation is given in this chapter as to how the individual components must
be parameterized. The STARTER or SIMOTION SCOUT engineering software is
used for the SINAMICS G120.
Step-by-step information is subsequently provided as to how the associated
software project was generated for this particular application example.

NOTE Most of the screenshots were generated in the "English" language setting. The
displays may slightly differ for other language settings.

4.1 Passwords
In the project, for reasons of simplicity, for the safety configuration of the
SINAMICS components for the drives, a general password of "1" is used.

NOTE This password should not be used in a real application!


Siemens AG 2012 All rights reserved

4.2 Preparation
Table 4-1: Setting interfaces and assigning a PROFIBUS address
No. Action Comment
Copyright

In order to go online with


SINAMICS, open STARTER or
1. SIMOTION SCOUT.
Then click on "Options" "Set
PG/PC Interface".

Version 1 09.07.2012 17/37


4 Engineering and configuring

No. Action Comment

The interface is now selected,


which is used to go online.
2. In this case, it is
"CP5711(PROFIBUS)"
Now click on "Properties".
Siemens AG 2012 All rights reserved
Copyright

Profibus address "0" is now


assigned for the PG.
3. The transmission rate is also set
here.
OK

4. The PROFIBUS address of the SINAMICS G120 is defined later.

Version 1 09.07.2012 18/37


4 Engineering and configuring

4.3 Configuring the basic drive functions


Initially, the hardware in the drive system must be commissioned and the required
motion functions created.

Table 4-2: Configuring the basic functions


No. Action Comment

Open STARTER or SIMOTION


SCOUT and create a new
1.
project. To do this, under
"Project" click on "New".

Then select a name for the


2. project and if required, change
the storage location.
Siemens AG 2012 All rights reserved
Copyright

Then click on "Insert single drive


3.
unit".

Version 1 09.07.2012 19/37


4 Engineering and configuring

No. Action Comment

The adjacent window is then


displayed. The Control Unit is
selected here. A CU240E-2 DP-
4. F is used in this example.
The PROFIBUS address of the
Control Unit (in this case,
address "4") is also defined.
Siemens AG 2012 All rights reserved

The Control Unit is transferred


into the project.
5.
Now click on "Configure drive
unit".
Copyright

The Power Module is defined


6. here. In this example, a PM240
is used.

7. Go online.

Version 1 09.07.2012 20/37


4 Engineering and configuring

No. Action Comment

Open the "Configuration" window


8. as several settings are still
required.
Siemens AG 2012 All rights reserved

9. Then click on "Wizard".

The Control Unit is configured


here.
In this screen form, the
presettings of the inputs and
Copyright

outputs "20.) 3-wire


10. (rel/on/reverse)" is setup.

Note
Only the screen forms in which a
change has to be made are
subsequently described.

Version 1 09.07.2012 21/37


4 Engineering and configuring

No. Action Comment

The motor type is selected in this


screen form.
A "1LA7 standard induction
motor" is used in this example. If,
for the motor data, you set the
radio button to "Enter from order
11. no. List2, then the drive can be
selected from the list.

Note
Only the screen forms in which a
change has to be made are
subsequently described.
Siemens AG 2012 All rights reserved

For the motor data identification,


click on "[1]Identify motor data at
12.
standstill and with motor
rotating".
Copyright

Here, the "OFF3 ramp-down


13. time" is set to a value of 0.5
seconds.

Version 1 09.07.2012 22/37


4 Engineering and configuring

No. Action Comment

Then, under Control Unit, click


14
on "Inputs/outputs".
Siemens AG 2012 All rights reserved

The digital inputs and outputs are interconnected as follows:


DI5 = p840[0]
DI12 = p2103[0]
Copyright

15

Version 1 09.07.2012 23/37


4 Engineering and configuring

No. Action Comment

The potentiometer is interconnected from the analog input to the main setpoint p1070.

16

17 Copy RAM to ROM.

18. Upload.
Siemens AG 2012 All rights reserved

4.4 Parameterizing the safety functions integrated in the


drive

NOTE In this example, the safety functions in the drive are configured online; this can also
be done offline.
Data is only written into the window in which parameter changes are required.
Copyright

In this particular example, the following safety functions are used: SS1 and SLS

Table 4-3: Parameterizing the safety functions integrated in the drive


No. Action Comment
Go online with STARTER or
1.
SIMOTION SCOUT.

Version 1 09.07.2012 24/37


4 Engineering and configuring

No. Action Comment

Configuring the drive


2. Open the "Safety Integrated"
window under the "Functions"
item for the drives.
Siemens AG 2012 All rights reserved

Configuring the drive


3 In order to change the settings in
the safety screen form, click on
"Change settings".
Copyright

Configuring the drive


In the example, the following is
configured:
Select control with "Motion
Monitoring via terminals" and
4
"Safety without encoder"
Set "Safety functions" to
"Enable".
Then click on "Safety inputs /
outputs".

Version 1 09.07.2012 25/37


4 Engineering and configuring

No. Action Comment

Configuring the drive


5
Here, click on "Drive".

Configuring the drive


The individual safety functions
are now either interconnected
with fail-safe inputs, or
Siemens AG 2012 All rights reserved

deselected.
- SS1 is interconnected with F-DI
6
0
- SLS is interconnected with F-DI
1
All other safety functions are
deactivated by "[255] Statically
incat".
Copyright

Configuring the drive


7 Now open the “Configuration”
window.

Version 1 09.07.2012 26/37


4 Engineering and configuring

No. Action Comment

Configuring both drives


The selection "Test stop
selection" is interconnected with
8
parameter r722.12.
Then open the "Mechanics
parameterization" screen form.

Configuring the drive


The transmission ratio between
the motor and load must be set
here.
If a gearbox is not being used,
then under "Number of load
revolutions" a 1 should be
9 entered and under "Number of
motor revolutions", 1 * pole pair
number r313[0].
Siemens AG 2012 All rights reserved

"Number of motor revolutions" =


numerator, gearbox * pole pair
number r313[0].
Here, the ratio is 1 : 2, as a
gearbox is not being used.
Copyright

Version 1 09.07.2012 27/37


4 Engineering and configuring

No. Action Comment


Configuring the drive
Under the item "Safe stop functions", "Monitoring time" is set to the OFF3 ramp-down time
(here, 0.5s).

10
Siemens AG 2012 All rights reserved
Copyright

Configuring the drive


Under the item "Safely limited
speed", "Set velocity limitation" is
set to 80%. As a consequence,
when selecting SLS, the motor
speed is automatically limited to
80% of the SLS speed, in this
particular case 200 rpm.
11 STOP B is selected as fault
response.

Note
- STOP A corresponds to an
STO
- STOP B corresponds to an
SS1

Version 1 09.07.2012 28/37


4 Engineering and configuring

No. Action Comment

Configuring the drive


The parameters must now be
copied.
12
To do this, click on "Copy
parameters".
Then click on "Activate settings".
Siemens AG 2012 All rights reserved

Configuring the drive


You will now be prompted to
Copyright

13 enter a new password.


For example, set the password
to "1".

Configuring the drive


The drive device parameters are
14
now copied to the ROM.
Acknowledge with "Yes".

15 Go offline.

Then switch off the Control Unit


16 POWER OFF/ON
and switch on again.

17 Go online.

Version 1 09.07.2012 29/37


4 Engineering and configuring

No. Action Comment


Load the configuration into the
18
PG.

19 Save the project.

This message indicates that a


test stop is required for the
safety functions in the drive.
This involves a warning, i.e. the
drive can be switched-on and
20 operated.
In this example, the test stop can
be initiated using switch -S6.
STO is triggered when selecting
the test stop.

4.5 Acceptance test


In order to verify the safety-related parameters, when the machine is
commissioned for the first time and when the safety-relevant parameters have
Siemens AG 2012 All rights reserved

been changed, an acceptance test must be carried out. The acceptance test must
be appropriately documented. The acceptance reports must be appropriately
stored and archived.
The acceptance test must be carried out after parameterization has been
completed and a power-on reset.
Information about the acceptance test, acceptance report and an example of a
corresponding acceptance report are provided in the "SINAMICS G120 Safety
Integrated Function Manual" in Chapter 4.9 "Acceptance test – completing
Copyright

commissioning".
From STARTER V4.2 and higher, a feature will be available that will allow you to
generate an acceptance documentation/acceptance report with all of the relevant
parameters. The procedure to generate this acceptance documentation is
described in the subsequent Table 4-4.

Table 4-4: Generating acceptance documentation using STARTER


No. Action Comment

1. Go online.

Version 1 09.07.2012 30/37


4 Engineering and configuring

No. Action Comment

Under the folder


"Documentation", click on
2.
"Create acceptance
documentation".

Select the corresponding Control


Unit and template. In this
particular example,
Siemens AG 2012 All rights reserved

3. "G120_CU240E_2_DP_F" is
used with the template
"ATP_G120_
Extended_sensorless_V4.4".
Copyright

Version 1 09.07.2012 31/37


5 Commissioning the application

5 Commissioning the application


Configuring the application example was described step-by-step up until now. The
following steps must be observed for the case that the project example is to be
directly loaded into the hardware.
To start, SINAMICS G120 should be restored to the factory setting.

5.1 Preconditions
Preconditions for operation:
o All of the components are connected as described in Chapter 3 Wiring
diagrams.
o The line supply voltage is connected to the SINAMICS G120.

5.2 Preparation
(see Chapter 4.2 Preparation)
Siemens AG 2012 All rights reserved

5.3 Commissioning
Table 5-1: Commissioning the application example
No. Action Comment
Copyright

Loading the SINAMICS G120


configuration
1. The configuration can be directly
loaded into the SINAMICS G120.
To do this, first go online and
then download the configuration.

After this, a backup must be


initiated from RAM to ROM for
2.
the SINAMICS, and the system
restarted (power-on reset).

Version 1 09.07.2012 32/37


6 Using the application

6 Using the application


Overview Fig. 6-1: Operator control elements for the application example
Siemens AG 2012 All rights reserved

Switches -S1 up to -S3 are provided on a switch box. These are used to select the
safety functions SS1 and SLS.
Switches -S4 up to -S6 are provided on the SINAMICS training case. Using these
switches, the drives are switched-on and switched off, the test function for the
safety functions started and any faults acknowledged.
Copyright

6.1 Description
Switching-on/switching-off
Emergency Stop button -S1 must be released in order to operate the drive. Drive 1
(OFF1) is switched-on using switch -S4.

Operating mode selector switch


You can toggle between the automatic mode and setting-up mode using operating
mode selector switch -S2 .

Automatic mode
In the automatic mode, the drive speed can be entered in the range from 0 – 1500
rpm using the potentiometer.

Version 1 09.07.2012 33/37


6 Using the application

Setting-up mode
Safety function SS1 is activated when activating the setting-up mode using the
operating mode selector switch -S2 .
SS1 is deactivated and SLS is activated after pressing the jog button -S3 . With a
delay time parameterized in the SINAMICS G120, the drive speed is
consequentially reduced to 160 rpm and is safely monitored using SLS. The speed
of 160 rpm is obtained from the following parameters:
SLS speed limit p9531[0] * setpoint speed limit p9533 / 100.
In this example:
200 rpm * 80% / 100 = 160 rpm

Emergency Stop
SS1 can be activated at any time by pressing the Emergency Stop command
device -S1 .

Acknowledgement
SINAMICS alarms that are present can be acknowledged using -S6. The test stop
of the safety functions, which is to be cyclically executed, is also activated using
Siemens AG 2012 All rights reserved

-S6.
Copyright

Version 1 09.07.2012 34/37


6 Using the application

6.2 Summary of the input signals


Table 6-1: SINAMICS inputs
Digital input Switch Component Description
Activating SLS when the protective door
DI 4 -S3 Jog button
is open

DI 5 -S4 Drive Switching-on/switching-off

AI 0 -S5 Analog rotary switch Enter the main setpoint for the speed

AI 1 -S6 Analog rotary switch Initiate test stop, acknowledge alarms

Table 6-2: Fail-safe inputs at the F-DI module


Digital input Switch Component Description

Emergency Stop
F-DI 0 -S1 Activating SS1
button

Operating mode Toggling between the automatic and


F-DI 1 -S2
selector switch setting-up mode
Siemens AG 2012 All rights reserved

Table 6-3: Operator control


-S2 -S3 -S4 Description
Not Not Not
Drive is switched on
actuated actuated actuated
Not Not
Actuated Drive is in the automatic mode
actuated actuated
Not
Actuated Actuated Safety function SS1 is initiated.
Copyright

actuated
The drive safely limits its speed to 160 rpm and safely
Actuated Actuated Actuated
monitors the speed.

Version 1 09.07.2012 35/37


7 References

7 References
7.1 References
This list is in no way complete and only reflects a selection of suitable literature.
Table 7-1: References
Subject area Title
/1/ SINAMICS G120 Safety Integrated Function Manual, Edition 01/2011
http://support.automation.siemens.com/WW/view/de/50736819
/2/ SINAMICS G120 Operating Instructions, Edition 01/2011
http://support.automation.siemens.com/WW/view/de/50815575
/3/ SINAMICS G120 List Manual, Edition 01/2011
http://support.automation.siemens.com/WW/view/de/49946755

7.2 Internet links - data


This list in no way complete and only reflects a selection of suitable information.
Table 7-2: Internet links, reference
Siemens AG 2012 All rights reserved

Subject area Title


\1\ Reference to the http://support.automation.siemens.com/WW/view/de/62069920
article
\2\ Siemens Industry http://support.automation.siemens.com
Online Support
\3\ SINAMICS G120 http://support.automation.siemens.com/WW/view/de/22339653/13330
documentation 0
Copyright

7.3 Selected application examples and FAQs


Table 7-3: Application examples and FAQs
Application examples Link
/1/ SINAMICS G120; controlling the http://support.automation.siemens.co
safety functions via F-DI m/WW/view/de/24230051
/2/ SINAMICS G120; controlling the http://support.automation.siemens.co
safety functions via PROFIBUS m/WW/view/de/24093625
with PROFIsafe
/3/ SINAMICS G120; controlling the http://support.automation.siemens.co
safety functions via PROFINET m/WW/view/de/29585944
with PROFIsafe

Version 1 09.07.2012 36/37


8 History

8 History
Table 8-1: History
Version Date Change
V1.0 06/2012 First edition with SINAMICS Version 4.4
Siemens AG 2012 All rights reserved
Copyright

Version 1 09.07.2012 37/37