Fail-Safe Setting-Up Operation With A SINAMICS G120 Using SLS Without An F-CPU
Fail-Safe Setting-Up Operation With A SINAMICS G120 Using SLS Without An F-CPU
Caution
The functions and solutions described in this article confine themselves to the
realization of the automation task predominantly. Please take into account
furthermore that corresponding protective measures have to be taken up in the
context of Industrial Security when connecting your equipment to other parts of the
plant, the enterprise network or the Internet. Further information can be found
under the Item-ID 50203404.
http://support.automation.siemens.com/WW/view/en/50203404
You can also actively use our Technical Forum from the Siemens Industry Online
Support regarding this subject. Add your questions, suggestions and problems and
discuss them together in our strong forum community:
62069920_Failsafe_JOG_mode_V4-4_DOKU_V10_en.doc
Copyright Siemens AG 2012 All rights reserved
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
Automation solution 2
Wiring diagrams 3
Engineering and
configuring 4
SINIMICS G120
Fail-safe setting-up operation with Commissioning the
application 5
a SINAMICS G120 using SLS
without an F-CPU 6
Using the application
References 7
Siemens AG 2012 All rights reserved
History 8
Copyright
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
We do not accept any liability for the information contained in this document.
Any claims against us – based on whatever legal reason – resulting from the use of
the examples, information, programs, engineering and performance data etc.,
described in this Application Example shall be excluded. Such an exclusion shall
Siemens AG 2012 All rights reserved
not apply in the case of mandatory liability, e.g. under the German Product Liability
Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life,
body or health, guarantee for the quality of a product, fraudulent concealment of a
deficiency or breach of a condition which goes to the root of the contract
(“wesentliche Vertragspflichten”). The damages for a breach of a substantial
contractual obligation are, however, limited to the foreseeable damage, typical for
the type of contract, except in the event of intent or gross negligence or injury to
life, body or health. The above provisions do not imply a change of the burden of
proof to your detriment.
Copyright
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
Table of contents
Warranty and liability ...............................................................................................4
1 Introduction ....................................................................................................6
1.1 Preconditions.....................................................................................6
1.2 Area of validity of this application example.........................................6
1.3 Integrated safety functions.................................................................7
Overview of the automation task ........................................................8
2 Automation solution.......................................................................................9
2.1 Overview of the total solution .............................................................9
Design 9
Demarcation ......................................................................................9
Know-how that is required..................................................................9
2.2 Description of the core functionality..................................................10
Overview and description of the core functionality ............................ 10
Advantages of this solution .............................................................. 10
2.3 Hardware and software components used ....................................... 11
Hardware components..................................................................... 11
Standard software components........................................................ 11
File examples and projects .............................................................. 12
3 Wiring diagrams ...........................................................................................13
Siemens AG 2012 All rights reserved
3.1 24V power supply voltage from the SINAMICS G120 ....................... 14
3.2 External 24V power supply voltage .................................................. 15
3.3 Power Module and motor................................................................. 16
4 Engineering and configuring ....................................................................... 17
4.1 Passwords.......................................................................................17
4.2 Preparation......................................................................................17
4.3 Configuring the basic drive functions................................................ 19
4.4 Parameterizing the safety functions integrated in the drive ............... 24
Copyright
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
1 Introduction
When machines are operated in the setting-up mode, frequently it is necessary that
the motors are operated with a safety limited speed.
Generally, external devices are required in this case to monitor the motor speed.
The SINAMICS G120 frequency converter with its integrated safety functions,
represents a favorably priced alternative to these external devices.
The fail-safe setting-up mode using the fail-safe digital inputs of the SINAMICS
G120 – with all of the parameter assignments required – is explained in this
application example.
1.1 Preconditions
NOTICE Please carefully note that it is not permissible to use the SS1, SLS, SDI and
SSM safety functions for pulling or continuously regenerative loads.
A "pulling or continuously regenerative load" is involved, if in the no-
voltage state, the motor is accelerated by the load (e.g. lifting
equipment/cranes, winders, wind turbines).
To use fail-safe functions, the closed-loop control must function perfectly.
Siemens AG 2012 All rights reserved
NOTICE After activating the STO and SS1 safety functions, there is no electrical
isolation between the line supply of the SINAMICS G120 and the motor. If
this is required in your particular application, then you must install an
appropriate line contactor upstream of the SINAMICS G120.
Copyright
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
The following safety functions are used as a basis for further analysis.
Siemens AG 2012 All rights reserved
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
2 Automation solution
2.1 Overview of the total solution
Design
This function example is based on the SINAMICS G120 training case (6ZB2480-
0CD00) and a CU240E-2 DP-F (6SL3244-0BB13-1PA1).
Demarcation
This application does not include a description of
the SINAMICS G120 safety functions,
the general drive functions of the SINAMICS G120 or
the hardware interfaces of the CU240E-2 DP-F.
It is assumed that the reader has sufficient knowledge about these subjects.
Information on these topics can be taken from the documents listed under the
references.
Siemens AG 2012 All rights reserved
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
Switches -S1 up to -S3 are provided on a switch box. These are used to select the
safety functions SS1 and SLS.
Switches -S4 up to -S6 are provided in the SINAMICS training case. Using these
switches, the drives are switched on and switched off, the test function for the
safety functions started and any faults acknowledged.
Copyright
When Emergency Stop is actuated, the drive is stopped with the SS1 function
integrated in the drive.
In the automatic mode, the drive rotates with the constant speed. If the setting-up
mode is selected (-S2), and the jog button (-S3) is simultaneously kept pressed,
then the SLS safety function is activated. The drive reduces the speed and safely
monitors this. If the jog button is released (-S3) or is not actuated, then the SS1
function is initiated, the drive brakes along the OFF3 ramp down to a standstill and
then it goes into the subsequent STO state.
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
Hardware components
Table 2-1: SINAMICS G120 training case
Component Type MLFB / ordering data Qty. Manufactu
rer
NOTE The application example was tested with the hardware components listed here. It
goes without saying that alternative components with the same features and
quality can be used. In such a case, it may be necessary to use a different
parameterization and wire-up the components differently.
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
Firmware version
Table 2-4: Firmware used
Component Type
EN/IEC62061
Copyright
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
3 Wiring diagrams
For reasons of simplicity, in this application example, the SINAMICS G120 is
exclusively controlled through the digital inputs, and the setpoint is entered via an
analog input. It goes without saying that the converter can also be controlled via a
fieldbus (PROFIBUS or PROFINET). However, this version is not discussed in this
example. An experienced user will be able to simply make the adaptations
required.
The following wiring diagrams differ regarding the source of the 24 V power supply.
This can be taken directly from the SINAMICS G120 (see Chapter 3.1); however,
an external 24 V power supply can also be used (see Chapter 3.2).
NOTICE The SINAMICS G120 has components at hazardous voltage levels and
controls rotating mechanical equipment, which is also hazardous. If these
warnings are not carefully observed, or if the notes provided in the various
SINAMICS G120 instructions are not followed, then this can result in death,
severe bodily injury or significant material damage.
Siemens AG 2012 All rights reserved
Copyright
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
3 Wiring diagrams
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
3 Wiring diagrams
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
3 Wiring diagrams
You can obtain more information regarding the installation from the SINAMICS G120 Power Module Hardware Installation Manual.
Download under: http://support.automation.siemens.com/WW/view/en/22339653/133300
Fail-safe setting-up operation with a SINAMICS G120 using SLS without an F-CPU
NOTE Most of the screenshots were generated in the "English" language setting. The
displays may slightly differ for other language settings.
4.1 Passwords
In the project, for reasons of simplicity, for the safety configuration of the
SINAMICS components for the drives, a general password of "1" is used.
4.2 Preparation
Table 4-1: Setting interfaces and assigning a PROFIBUS address
No. Action Comment
Copyright
7. Go online.
Note
Only the screen forms in which a
change has to be made are
subsequently described.
Note
Only the screen forms in which a
change has to be made are
subsequently described.
Siemens AG 2012 All rights reserved
15
The potentiometer is interconnected from the analog input to the main setpoint p1070.
16
18. Upload.
Siemens AG 2012 All rights reserved
NOTE In this example, the safety functions in the drive are configured online; this can also
be done offline.
Data is only written into the window in which parameter changes are required.
Copyright
In this particular example, the following safety functions are used: SS1 and SLS
deselected.
- SS1 is interconnected with F-DI
6
0
- SLS is interconnected with F-DI
1
All other safety functions are
deactivated by "[255] Statically
incat".
Copyright
10
Siemens AG 2012 All rights reserved
Copyright
Note
- STOP A corresponds to an
STO
- STOP B corresponds to an
SS1
15 Go offline.
17 Go online.
been changed, an acceptance test must be carried out. The acceptance test must
be appropriately documented. The acceptance reports must be appropriately
stored and archived.
The acceptance test must be carried out after parameterization has been
completed and a power-on reset.
Information about the acceptance test, acceptance report and an example of a
corresponding acceptance report are provided in the "SINAMICS G120 Safety
Integrated Function Manual" in Chapter 4.9 "Acceptance test – completing
Copyright
commissioning".
From STARTER V4.2 and higher, a feature will be available that will allow you to
generate an acceptance documentation/acceptance report with all of the relevant
parameters. The procedure to generate this acceptance documentation is
described in the subsequent Table 4-4.
1. Go online.
3. "G120_CU240E_2_DP_F" is
used with the template
"ATP_G120_
Extended_sensorless_V4.4".
Copyright
5.1 Preconditions
Preconditions for operation:
o All of the components are connected as described in Chapter 3 Wiring
diagrams.
o The line supply voltage is connected to the SINAMICS G120.
5.2 Preparation
(see Chapter 4.2 Preparation)
Siemens AG 2012 All rights reserved
5.3 Commissioning
Table 5-1: Commissioning the application example
No. Action Comment
Copyright
Switches -S1 up to -S3 are provided on a switch box. These are used to select the
safety functions SS1 and SLS.
Switches -S4 up to -S6 are provided on the SINAMICS training case. Using these
switches, the drives are switched-on and switched off, the test function for the
safety functions started and any faults acknowledged.
Copyright
6.1 Description
Switching-on/switching-off
Emergency Stop button -S1 must be released in order to operate the drive. Drive 1
(OFF1) is switched-on using switch -S4.
Automatic mode
In the automatic mode, the drive speed can be entered in the range from 0 – 1500
rpm using the potentiometer.
Setting-up mode
Safety function SS1 is activated when activating the setting-up mode using the
operating mode selector switch -S2 .
SS1 is deactivated and SLS is activated after pressing the jog button -S3 . With a
delay time parameterized in the SINAMICS G120, the drive speed is
consequentially reduced to 160 rpm and is safely monitored using SLS. The speed
of 160 rpm is obtained from the following parameters:
SLS speed limit p9531[0] * setpoint speed limit p9533 / 100.
In this example:
200 rpm * 80% / 100 = 160 rpm
Emergency Stop
SS1 can be activated at any time by pressing the Emergency Stop command
device -S1 .
Acknowledgement
SINAMICS alarms that are present can be acknowledged using -S6. The test stop
of the safety functions, which is to be cyclically executed, is also activated using
Siemens AG 2012 All rights reserved
-S6.
Copyright
AI 0 -S5 Analog rotary switch Enter the main setpoint for the speed
Emergency Stop
F-DI 0 -S1 Activating SS1
button
actuated
The drive safely limits its speed to 160 rpm and safely
Actuated Actuated Actuated
monitors the speed.
7 References
7.1 References
This list is in no way complete and only reflects a selection of suitable literature.
Table 7-1: References
Subject area Title
/1/ SINAMICS G120 Safety Integrated Function Manual, Edition 01/2011
http://support.automation.siemens.com/WW/view/de/50736819
/2/ SINAMICS G120 Operating Instructions, Edition 01/2011
http://support.automation.siemens.com/WW/view/de/50815575
/3/ SINAMICS G120 List Manual, Edition 01/2011
http://support.automation.siemens.com/WW/view/de/49946755
8 History
Table 8-1: History
Version Date Change
V1.0 06/2012 First edition with SINAMICS Version 4.4
Siemens AG 2012 All rights reserved
Copyright