C Curve PDF
C Curve PDF
Minutes
20
Minutes
designed to protect very sensitive 10
branch circuits such as semiconduc- 10
6
4 6
tors. Magnetic Trip Point—2 to 3 4
Tripping time
times circuit breaker rating. Thermal 2
Tripping time
2
Trip Point—1.13 to 1.45 circuit break- 1
1
er rating. 40
40
20
Tripping characteristic: B, -6 20
10
Type B characteristic designed for 10
6
European residential circuit protec- 4 6
4
tion. This characteristic can also be 2
Seconds
Seconds
used for protection of computers and 1
electronic equipment. Magnetic Trip 1
0,6
0,4 0,6
Point—3 to 5 times circuit breaker 0,4
rating. Thermal Trip Point—1.13 to 0,2
0,2
1.45 circuit breaker rating. 0,1
0,1
0,06
Tripping characteristic: C, -7 0,04 0,06
0,04
Type C characteristic is for general 0,02
0,02
13 device protection in control circuits 0,01
and all other supplementary circuit 1 1,5 2 3 4 5 6 8 10 15 20 30 0,01
1 1,5 2 3 4 5 6 8 10 15 20 30
protection systems. Magnetic Trip Multiple of rated current
Multiple of rated current
Point—5 to 10 times circuit breaker
rating. Thermal Trip Point—1.13 to
Components
Minutes
Tripping time
2 2
1 1
40 40
20 20
10 10
6 6
4 4
Seconds
Seconds
2 2
1 1
0,6 0,6
0,4 0,4
0,2 0,2
0,1 0,1
0,06 0,06
0,04 0,04
0,02 0,02
0,01 0,01
1 1,5 2 3 4 5 6 8 10 15 20 30 1 1,5 2 3 4 5 6 8 10 15 20 30
Multiple of rated current Multiple of rated current
772
Siemens Industrial Control Products
5SX Miniature Circuit Breakers Technical
Technical Data
5SX2.. 5SX5.. 5SX6..
Approvals UL 1077 Recognized
File E116386 — —
CSA File LR93659
EN 60 898, DIN VDE 0641 TEIL 11, IEC B98
Housing Grey Molded plastic, RAL 7035, Black Handle
Terminals:
(1) 14–5 AWG/16 mm2 16 mm2 Max. (1) 1/0 AWG/50 mm2
—Load Side
—Line Side (1) 14–4 AWG/25 mm2 25 mm2 Max. (1) 1/0 AWG/50 mm2
Mounting Snap-on to 35 mm DIN Mounting Rail
Mechanical Endurance 20,000 Operations
Rated AC Voltage 50/60Hz:
250/440V 250/415V 250/440V
IEC
—UL 1077 1 Pole 120/227 Volt AC 50/60Hz — —
2 Pole 120/240/480 Volt AC 50/60Hz — —
3 Pole 120/240/480 Volt AC 50/60Hz — —
Rated DC Voltage Per Pole 55V — 60V
IEC 1 Pole — 220V —
2 Pole — 440V —
3 Pole — — —
UL1077 1 Pole 65VDC — —
2 Pole 125VDC — —
Auxiliary Contacts Rating for 5SX9 UL 360VA Steady State, 3600VA Inrush, 480V AC, Maximum
IEC AC15: 6A, 230V AC; DC14: 1A, 220V DC
Rated Interrupting Capacity 6kA 4.5kA 6kA
—UL 1077 120/240 Volt AC 14kA — —
240 Volt AC 7.5kA — —
277 Volt AC 5kA — —
480 Volt AC 5kA — —
Permitted Ambient Temp. Range 25C to 45C 25C to 45C 25C to 45C 13
Shock Resistance 30g —half-sine shock load 6 ms 30 g—half-sine shock load 6 ms
Vibration Resistance 6g 6g
Components
Note: Circuit Protection device catalog Example: Device on left is a 1-pole
Industrial
numbers are not directly refer- breaker with a marking of C32. C indi-
enced on the product. cates trip curve characteristic C. The 32
Identification of the proper device can indicates an amp rating of 32; therefore,
be determined as follows: this device is a 5SX2132-7.
1) Note the number of poles 1, 2 or 3.
2) Note the breaker type, characteristic
and amp rating.
5SX21
g 9.81 m/s2
773
Siemens Industrial Control Products