0909 Gs R Xu 12001 - A2 - Control Panel Loop Wiring Drawing

This document is a control panel loop wiring diagram for the Thang Long & Dong Do Field Development project. It was issued for acceptance with minor comments from the client. The client asked for clarification that ICSS interface signals are not driven by an interposing relay. They also requested that the MODBUS connection to ICSS be shown on the diagram and that spare terminals be provided in the panel to terminate a spare multipair cable. The supplier addressed these comments in the response sheet.

Uploaded by

chuminh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
260 views

0909 Gs R Xu 12001 - A2 - Control Panel Loop Wiring Drawing

This document is a control panel loop wiring diagram for the Thang Long & Dong Do Field Development project. It was issued for acceptance with minor comments from the client. The client asked for clarification that ICSS interface signals are not driven by an interposing relay. They also requested that the MODBUS connection to ICSS be shown on the diagram and that spare terminals be provided in the panel to terminate a spare multipair cable. The supplier addressed these comments in the response sheet.

Uploaded by

chuminh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 58

Thang Long & Dong Do Field Development

Tick Box Code Status Legend


Seller authorised to proceed. Document to
1 Accepted be revised and resubmitted as “Certified
Final - As Built”.
Seller authorised to proceed as noted.
Accepted With
2 Document to be revised and resubmitted
Comments
for acceptance within the prescribed time.
Seller not to proceed. Document to be
3 Not Accepted
revised and resubmitted for acceptance.

Reference/Information Document used for reference or


4
Only information. Review not necessary.

ACCEPTANCE DOES NOT RELIEVE THE SELLER OF RESPONSIBILITY FOR DOCUMENT


ACCURACY, COMPLIANCE WITH THE APPLICABLE CODES, STANDARDS AND PURCHASE
ORDER REQUIREMENTS
GPS SDRL Code: C18

A2 12.06.2013 ISSUE FOR ACCEPTANCE MP JM LH


A1 07.11.2012 ISSUE FOR ACCEPTANCE NS LH MSN
Rev. Date Reason for issue Prep. Checked Accepted

Global Process Systems Pte. Ltd.


5 Temasek Boulevard
#10-03 Suntec Tower Five
Singapore 038985

Doc. title according to SMDR:

CONTROL PANEL LOOP WIRING DRAWING


System number according to Norsok: SFI code: PTSC doc. number:
TLDD-2004-5DG-M-F01-001
Project document number Pages
Project number Orig. code Disc. code Doc. type Sequential number
0909 - GS - R - XU - 12001 1 of 28
GPS/ LAMSON LP/MP COMPRESSOR PACKAGE

Type of Document: Diagram Pages: 2 of 28

Control Panel Loop Wiring Drawing

Issued for Acceptance A2 12.06.2013 MP JM LH

Issued for Acceptance A1 07.11.2012 NS LH MSN

Made Chk'd GPS LAMSON


Reason for Issue Rev Issue Date App’d by
by by App’d App’d
Contract/PO No.: GPS Document No.: Vendor:
S656-GPS- 0909-GS-R-XU-12001
CONT-ME-00004
Supplier Document No. :
ROS-37P12-DIA-7004
Rotation Offshore System

UCP LOOP WIRING DRAWING


220VAC DISTRIBUTION
24VDC DISTRIBUTION FOR IO MODULES AND INSTRUMENTS
24VDC DISTRIBUTION FOR IO MODULES AND INSTRUMENTS
BANYU URIP PROJECT
RESPONSE SHEET

Description of Document: CONTROL PANEL LOOP DIAGRAM


0909-GS-R-XU-12001

S No Client Comments ROS Response Remark


Final Resolution
Please clarify, ICSS interface signals are driven by
1. ICSS signals are not driven by interposing relay.
interposing relay, if yes the relay shall be SIL-2.

2. Show the MODBUS connection to ICSS In corporated as per the comments

Panel shall have spare terminals to terminate the


3. Spare Terminals will be provided in the panel.
spare multipair cable.

Page 1 of 1
Thang Long & Dong Do Field Development

Tick Box Code Status Legend


Seller authorised to proceed. Document to
1 Accepted be revised and resubmitted as “Certified
Final - As Built”.
Seller authorised to proceed as noted.
Accepted With
2 Document to be revised and resubmitted
Comments
for acceptance within the prescribed time.
Seller not to proceed. Document to be
3 Not Accepted
revised and resubmitted for acceptance.

Reference/Information Document used for reference or


4
Only information. Review not necessary.

ACCEPTANCE DOES NOT RELIEVE THE SELLER OF RESPONSIBILITY FOR DOCUMENT


ACCURACY, COMPLIANCE WITH THE APPLICABLE CODES, STANDARDS AND PURCHASE
ORDER REQUIREMENTS
GPS SDRL Code: C18

A2 12.06.2013 ISSUE FOR ACCEPTANCE MP JM LH


A1 07.11.2012 ISSUE FOR ACCEPTANCE NS LH MSN
Rev. Date Reason for issue Prep. Checked Accepted

Global Process Systems Pte. Ltd.


5 Temasek Boulevard
#10-03 Suntec Tower Five
Singapore 038985

Doc. title according to SMDR:

CONTROL PANEL LOOP WIRING DRAWING


System number according to Norsok: SFI code: PTSC doc. number:
TLDD-2004-5DG-M-F01-001
Project document number Pages
Project number Orig. code Disc. code Doc. type Sequential number
0909 - GS - R - XU - 12001 1 of 28
GPS/ LAMSON LP/MP COMPRESSOR PACKAGE

Type of Document: Diagram Pages: 2 of 28

Control Panel Loop Wiring Drawing

Issued for Acceptance A2 12.06.2013 MP JM LH

Issued for Acceptance A1 07.11.2012 NS LH MSN

Made Chk'd GPS LAMSON


Reason for Issue Rev Issue Date App’d by
by by App’d App’d
Contract/PO No.: GPS Document No.: Vendor:
S656-GPS- 0909-GS-R-XU-12001
CONT-ME-00004
Supplier Document No. :
ROS-37P12-DIA-7004
Rotation Offshore System

UCP LOOP WIRING DRAWING


220VAC DISTRIBUTION
24VDC DISTRIBUTION FOR IO MODULES AND INSTRUMENTS
24VDC DISTRIBUTION FOR IO MODULES AND INSTRUMENTS
BANYU URIP PROJECT
RESPONSE SHEET

Description of Document: CONTROL PANEL LOOP DIAGRAM


0909-GS-R-XU-12001

S No Client Comments ROS Response Remark


Final Resolution
Please clarify, ICSS interface signals are driven by
1. ICSS signals are not driven by interposing relay.
interposing relay, if yes the relay shall be SIL-2.

2. Show the MODBUS connection to ICSS In corporated as per the comments

Panel shall have spare terminals to terminate the


3. Spare Terminals will be provided in the panel.
spare multipair cable.

Page 1 of 1