P630 Testing Procedure
P630 Testing Procedure
SUMMARY:
This report is intended to explain procedures for demonstrating the main functions of
the P633 relay using an Omicron test set or similar.
Page 2 of 18
TABLE OF CONTENTS
1. INTRODUCTION
2. EQUIPMENT REQUIRED
3. INITIAL CONFIGURATION
4. PRODUCT CHECKS
8. ON-LOAD TESTS
Page 3 of 18
1. INTRODUCTION
Important :
2. EQUIPMENTS REQUIRED
3. INITIAL CONFIGURATION
3.1. P633 CONNECTIONS
Connector Terminal no.
Voltage X031 1,2
Winding - 1
Current A X031 3,4
Current B 5,6
Current C 7,8
Current N 9,10
Winding-2
Current A X051 1,2
Current B 3,4
Current C 5,6
Current N 7,8
Winding-3
Current A X071 1,2
Current B 3,4
Current C 5,6
Current N 7,8
Power supply X201 25(+),26(-)
Opto input-1 X201 18(+),19(-)
Opto input-2 20(+),21(-)
Opto input-3 22(+),24(-)
Opto input-4 23(+),24(-)
Output relay- X181 (1,2-4,5-NC)(3,2-6,5-NO)
Output relay- (7,8-10,11-NC)(9,8-12,11-NO)
Output relay- (13,14-15,17-NC)(15,14-18,17-NO)
Output relay- (19,20-NC)(21,20-NO)
Output relay- (22,23-NC)(24,23-NO)
Output relay- (25,26-NC)(27,26-NO)
Output relay- X201 (1,2 –NO) (3,4 - NO)
Output relay- (5,6 –NC) (7,6 –NO)
Output relay- (8,9 –NO)
Output relay- (10,11 –NO)
Output relay- (10,12 –NO)
Output relay- (10,13 –NO)
Output relay- (10,14 –NO)
Output relay- (15,16 –NC) (17,16 –NO)
Page 5 of 18
Load default settings into relay from either MiCOM S1 or restart the
relay with COLD START option (Operation/Control and
testing/MAIN/Cold restart – execute). For COLD START; disable MAIN
protection, if it is enabled. After COLD START , “out of service” LED is
steadily lit and “alarm” LED is blinking. To reset alarm, go to
Operation/Control and testing/MT_RC/Reset recording – execute.
By default, the frequency is set to 50 Hz. Change this to 60 Hz, if
required. (Parameters/Function parameters/Global/MAIN/ Nominal freq.
Fnom – 50 Hz or 60 Hz)
4. PRODUCT CHECKS
After auxiliary voltage is applied, check that LED indicators for “Healthy
(H1)” and “Out of service (H2)” light up. After approx. 15 secs the P633
is ready for operation. Check that “MiCOM P633” is displayed in the
first line of the LCD display.
Assignment of LEDs :
1
Oper. Mode K1801 ES manual reset
For single side 3 phase feed, the fault current characteristic crosses the
first knee of the tripping characteristic of the P633 so that the basic
threshold value is always checked for.
The current to which P633 responds for single-side feed is calculated
as follows.
Method :
Pass criteria :
Method :
Pass criteria :
Settings :
Connections:
Arrange to connect current output of the test set to apply two currents,
one for phase-A, winding-A (Ia) and second for phase-A, winding-B (Ib).
Both currents should be in phase opposition.
Method:
Pass Criteria:
Characteristic equation for lower slope ( when 0.5 Idiff> < Ir ™ Ir,m2 )
Id = (m1*Ir) + (Idiff>)*(1-0.5m1) ----------- (iii)
(Please note that “Id” and “Ir” are derived by the relay after amplitude
and vector group matching. Hence, we have to multiply injected
currents by amplitude matching factors for calculation of “Id” and “Ir”.
In our case amplitude matching factor is 1.0 for both windings, hence
no correction required)
Calculate value of “Ir” from the equation (i). Using this value of “Ir”,
calculate theoretical value of “Id” from equation (iii). (A)
Connections:
Method:
Pass Criteria:
Calculate value of “Ir” from the equation (i). Using this value of “Ir”,
calculate theoretical value of “Id” from equation (iii). (A)
Method :
Pass criteria :
Connections :
Page 12 of 18
Test method :
Pass criteria :
Connections :
Method :
Pass criteria :
Method :
Pass criteria :
Method :
Pass criteria :
Assignment of LEDs :
Connections :
Method :
Increase the injected current till relay operation. QUICK CMC can be
used.
Pass criteria :
Method :
Pass criteria :
Settings :
Assignment of LEDs :
Method :
Pass criteria :
Settings :
Method :
Pass criteria :
Settings :
Assignment of OUTPUT relay :
Method :
Pass criteria :
Page 18 of 18
8. ON LOAD TESTS
The purpose of the on-load checks are to:
a. confirm the external wiring to the current and voltage inputs are
correct.
b. ensure the on-load differential current is well below the relay
setting.
c. check the polarity of the line current transformers at each end is
correct.