Common causes of premature battery failure include elevated temperatures, repeated cycling from full charge to discharge, and overcharging or undercharging. These factors can shorten a battery's lifespan by accelerating corrosion and plate degradation through excessive heat, gassing, or sulfate buildup. Additionally, overdischarge can cause hydration damage through lead dissolution and plating, while vibration, ripple current, improper storage, and misapplication may also negatively impact a battery's performance and lifetime.

Uploaded by

avandetq15
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
341 views

Common Causes of Battery Failures

Common causes of premature battery failure include elevated temperatures, repeated cycling from full charge to discharge, and overcharging or undercharging. These factors can shorten a battery's lifespan by accelerating corrosion and plate degradation through excessive heat, gassing, or sulfate buildup. Additionally, overdischarge can cause hydration damage through lead dissolution and plating, while vibration, ripple current, improper storage, and misapplication may also negatively impact a battery's performance and lifetime.

Uploaded by

avandetq15
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Common Causes of Battery Failures

All batteries have a limited life span. However the life span can be considerably
shortened by certain factors which tend to cause premature battery failure. The factors
discussed below are some of the most common causes of battery failure. Given the
roles batteries play and will continue to play in our everyday life, a thorough
understanding of these factors will enable engineers and technicians involved in the
maintenance of batteries prevent the occurrence of some of these factors in order to
prolong battery life.

The factors discussed below are mostly applicable to VRLA (Valve Regulated Lead Acid)
batteries which have almost completely replaced conventional lead acid batteries with
refillable liquid sulphuric acid electrolyte. VRLA batteries are designed to be
maintenance free and the hydrogen that is emitted is recombined internally so that the
electrolyte (essentially a paste) does not need replacing over the life of the battery, a
valve is installed to release any excess pressure that may build up if the battery were
failing. A key drawback of VRLA batteries is the short service life which was procured
at the expense of low maintenance.

Elevated Temperatures
Anticipated battery life is specified by the manufacturer for batteries installed in an
environment at or near the reference temperature of 25°C (77°F). Above this
temperature, battery life is reduced. The chief aging mechanism is accelerated
corrosion of the positive plates, grid structure, and strap, which increases exponentially
as a function of temperature. Elevated temperatures reduce battery life. An increase
of 8.3°C (15°F) can reduce lead-acid battery life by 50% or more.

Repeated Cycling
Repeated cycling from fully charge to fully discharge and back may cause loss of active
materials from the positive plates. This reduces battery capacity and its useful life.

Overcharging
Overcharging by the battery charging system causes excessive gassing and high internal
heat. Too much gassing can lead to the removal of active material from the plates. Too
much heat can also oxidize the positive plate material and warp the plates.

Undercharging
A faulty charging system will not maintain the battery at full charge. Severe
undercharging allows sulfate on the plates to become hard and impossible to remove
by normal charging. The undercharged battery may fail to deliver the required power
needed for its application.

Over discharge
Over discharge leads to hydration. Hydration occurs in a lead-acid battery that is over
discharged and not promptly recharged. Hydration results when the lead and lead
compounds of the plates dissolve in the water of a discharged cell and form lead
hydrate, which is deposited on the separators. When the cell is recharged, multiple
internal short circuits occur between the positive and negative plates. Once hydration
is evident, the cell is permanently damaged. Hydration is not visible in VRLA cells
because the containers are opaque

Vibration
A battery must be mounted securely. Vibrations can loosen connection, crack the case
and damage internal components.

DC Ripple Current
Excessive DC ripple current might contribute to battery aging. VRLA batteries are
extremely susceptible to ripple current since it can lead to cell heating and will
accelerate the degradation of cells which are at risk from thermal runaway.

Improper Storage
Storing wet cells beyond the manufacturer’s recommended duration promotes
sulfation, and decreases cell capacity and life.

Misapplications
Batteries are commonly designed for a specific use. If the battery is not designed for a
given application, it might not meet its life or performance expectations.