CT Class
CT Class
EN002
Iron core current transformers (CT) are accurate in amplitude and phase when used
near their nominal values. At very low and at very high currents they are far from ideal.
For overcurrent and differential protection, the actual performance of CTs at high
currents must be checked to ensure correct function of the protection relay.
CT model
Composite error εC
Composite error εC is the difference between the ideal secondary current and the
actual secondary current under steady-state conditions. It includes amplitude and
phase errors and also the effects of any possible harmonics in the exciting current.
T
1
T ∫0
( K N i S − i P ) 2 dt
εC = ⋅ 100% (eq. 1)
IP
T = Cycle time
KN = Rated transformation ratio INPrimary/INsecondary
iS = instantaneous secondary current
iP = instantaneous primary current
IP = Rms value of primary current
Note:
All current based protection functions of VAMP relays, except arc protection, thermal
protection and 2nd harmonic blocking functions, are using the base frequency
component of the measured current. The IEC formulae include an RMS value of the
current. That is why the composite error defined by IEC 60044-1 is not ideal for VAMP
relays. However the difference is not big enough to prevent rough estimation.
1/7
Standard accuracy classes
At rated frequency and with rated burden connected, the amplitude error and phase
error and composite error of a CT shall not exceed the values given in the following
table.
Marking: The accuracy class of a CT is written after the rated power. E.g. 10 VA 5P10,
15 VA 10P10, 30 VA 5P20
Figure 2. This figure of equation 3 shows that it is essential to know the winding resistance
RCT of the CT if the load is much less than the nominal. A 10 VA 5P10 CT with 25% load
gives actual ALF values from 15..30 when the winding resistance varies from 0.5 Ω to 0.05
Ω.
2/7
The actual accuracy limit factor kA depends on the actual burden. (Figure 2)
Si + S N
k A = k ALF (eq. 3)
Si + S A
If the current is an asymmetric short circuit current like in Figure 3 the needed accuracy
limit factor should be multiplied by coefficient kDC:
k DC = 1 + ωτ (eq. 4)
15
Current (kA)
10
-5
-10
0 0.02 0.04 0.06 0.08 0.1
Time (s)
3/7
Table 1. Safety factor c for accuracy limit factor. Using slightly smaller safety factor than
indicated in the table will increase the setting inaccuracy.
RCT + R N
k A = k ALF (eq. 6)
RCT + RW + RL
ck I I 2
S N > DC k NTra (RCT + RW + RL ) − RCT I NCT sec (eq. 8)
k ALF I NCT
Example 1
Transformer:
16 MVA YNd11 Zk = 10%
110 kV / 21 kV (84 A / 440 A)
CTs on HV side:
100/1 5P20 15 VA
Winding resistance RCT = 0.3 Ω (RCT depends on the CT type, INCT and power rating. Let's
say that the selected CT type, 100 A and an initial guess of 15 VA, yields to 0.3 Ω.)
Safety factor c = 4. (Table1. Transformer differential, earthed Y.)
CTs on LV side:
500/1 5P20 15 VA
Winding resistance RCT = 0.4 Ω (RCT depends on the CT type, INCT and power rating. Let's
say that the selected CT type, 500 A and an initial guess of 15 VA, yields to 0.4 Ω.)
Safety factor c = 3. (Table 1. Transformer differential, ∆.)
4/7
RL = 0.05 Ω Typical burden of a VAMP relay 1 A current input.
RWHV = 0.138 Ω Wiring impedance of high voltage side.
(2x16 m Cu, 4 mm2)
RWLV = 0.086 Ω Wiring impedance of low voltage side.
(2x10 m Cu, 4 mm2)
f = 50 Hz Frequency
τ = 50 ms DC time constant
Equation 4 gives:
kDC = 1 + 2π50 x 0.05 = 16.7
The nominal primary current should be enough for the maximum short circuit current
according equation:
Ik
I CTpri ≥ (eq. 9)
100
The needed minimum value for the actual accuracy limit factor kA (equation 3.)
depends on the highest setting value, the applied delay type definite/inverse and the
needed fault current grading for selectivity. A reasonable actual accuracy limit factor
for most cases should be according equation 9.
5/7
Example 2
Network:
Ik = 30 kA Maximum short circuit current
RL = 0.008 Ω Typical burden of a VAMP relay 5 A current input.
RW = 0.09 Ω Secondary wiring impedance
CT:
1000/5 10P10 30 VA (10P10 ⇒ 10% error @ 10x1000 A)
RCT = 0.4 Ω Secondary winding resistance
Equation 4 gives:
kDC = 1 + 2π50 x 0.05 = 16.7
This is an impractical big CT. We must either use a CT with 1 A nominal secondary or
ignore the DC-component. The latter choice may increase trip time at heavy faults.
The corresponding distance will be half of the wire length, because there are two wires
from the CT to the relay.
6/7
Example 3
Let us calculate the maximum possible distance between CT and protection relay with
in the following case.
CT = 500/5 10P10
kAFL = 10 Accuracy limit factor at rated current and rated
burden according CT specification.
INCTsec = 5A Nominal secondary current of the CT
SN = 15 VA Rated burden of the CT
RL = 0.008 Ω Burden of a VAMP relay 5 A current input.
RCT = 0.6 Ω Secondary winding resistance
c = 1.4 Safety factor. See Table 1.
ISET = 8xIN Overcurrent setting
Wire = 2.5 mm2 Cu Cross-sectional area and material
δCu = 17.2 nΩm Unit resistance of copper
kDC = 1 This ignores any decaying DC component
Keywords : Current transformer, Current selection, Current requirements, Current accuracy class, Current
accuracy limit, Current power rating, Current wiring
VAMP Ltd Visiting Address: Tel: +358 20 753 3200 ISO 9001:2000
P.O.Box 810 Vaasa Airport Park Fax: +358 20 753 3205 certified company
FI-65101 VAASA Yrittäjänkatu 15 Email: [email protected]
Finland Vaasa, Finland http://www.vamp.fi
We reserve the rights to product alterations without prior notice.
Copyright © Vamp Ltd. All trademarks are the property of their respective holders.
7/7