IRI-Pro-V2: Over-Current, Short-Circuit and Earth Fault Relay

The document describes the IRI-Pro-V2 overcurrent, short-circuit, and earth fault relay. It has microcontroller-based protection functions including definite time and inverse time overcurrent protection. It records the last five faults with timestamps and has communication capabilities via a front USB port. The housing is for flush mounting and terminals are provided for current and auxiliary connections.

Uploaded by

spremals
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
0% found this document useful (0 votes)
2K views

IRI-Pro-V2: Over-Current, Short-Circuit and Earth Fault Relay

The document describes the IRI-Pro-V2 overcurrent, short-circuit, and earth fault relay. It has microcontroller-based protection functions including definite time and inverse time overcurrent protection. It records the last five faults with timestamps and has communication capabilities via a front USB port. The housing is for flush mounting and terminals are provided for current and auxiliary connections.

Uploaded by

spremals
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
You are on page 1/ 8

IRI-Pro-V2

Over-Current, Short-Circuit
and Earth Fault Relay
IRI-Pro-V2 : Over-current, Short-Circuit and Earth Fault Relay

Contents

1 Characteristics and Features

2 Design

2.1 Front Panel


2.2 LEDs
2.3 Output Contacts
2.4 Power Supply

3 Fault Recording

4 Reset Delay

5 Housing

6. Communication

7 Terminal Description

8 Trip Test

9 Contact Details

10. Circuit Diagram

11. Technical Data

11.1 Measuring input


11.2 Setting ranges and steps

12. Setting Procedure

13. Dimensional Drawing

14. Order Form

2
IRI-Pro-V2 : Over-current, Short-Circuit and Earth Fault Relay

1. Characteristics and Features 2.4 PPower


ower Supply
 Microcontroller based Numeric Relay.
It has a universal auxiliary supply. The voltage range is
 Digital filtering of the measured values to suppress 24V to 260VAC and 24V to 360VDC. Power supply
the high frequency harmonics and transient connections are not polarized.
dccomponents during short circuit.
 Selectable protective functions between: definite time 3. Fault Recording
over-current relay and inverse time over-current
relay. IRI-PRO records secondary current for last five faults with
real time stamp. It saves following information with CT
 Selectable inverse time characteristics according to current in non-volatile memory in following sequence.
BS142 and IEC 255-4:
Normal inverse 3.0 Type of fault : SC / OL / E/EH
Normal inverse 1.3 Faulty phase / Earth : L1 / L2 / L3 / E
Normal inverse 0.6 (secondary)
Very inverse Value at Fault : L1, L2, L3, Ie Amps
Extremely inverse (True RMS recording guaranteed only if trip time >= 40msec)
 Two stage over-current time protection for phase
current / earth fault current. 4. Reset Delay
 Separately selectable characteristic for Earth fault This parameter [RST-D] introduces a delay in opening of
and phase fault. relay contacts, when the current goes below the dropout
 Continuous self-supervision of software and value for overload and short circuit & earth faults. This
hardware. parameter will not work when manual reset mode is selected.
 Wide operating ranges of the supply voltage [AC/ 5. Housing
DC] 24V-260V AC / 24V-360V DC
The IRI-PRO is supplied in an individual housing for flush-
 Last five faults recording with real time stamping
mounting for installation in a DIN standard of
(Date & time).
73 x 135 mm.
 Relay assignment configurable from HMI.
 Relay reset configurable from HMI. 6. Communication
 Primay current display with CT Ratio. Front USB port is available on IRI_PRO relay to provides a
 Front USB interface for PC/Laptop. local communication with PC. The front end software
provided for relay is fully Windows compatible.
2. Design
The front end software of IRI_PRO relays has following
2.1 FFront
ront PPanel
anel
functions:
The front panel of the protective device IRI-PRO comprises  To edit the parameters of relay
the following operational and indication elements:  To view the running parameters of relay.
 1 LCD-Liquid Crystal Display (16 x 2)  To download the last faults of relay
 Simulation Injection source to test the complete
 Five keypads-for parameter setting
functionality of all protections of relay without using
 8 LEDs for annunciation any three phase injection current source

2.2 LEDs Note : For USB comunication, no power is required


to energie the relay
relay..
On the front panel there are 8 LEDs. Their functions are
indicated by the appropriate inscriptions. On fault I>, I>>,
7. Terminal Description
Ie> & Ie>> LEDs with appropriate phase lamps L1/ L2 /
L3 give the fault indication. Flashing of the green LED
There are two terminal blocks A & B. Block A is for current
marked ON gives the indication of healthiness of relay in
connection while Block B is for Auxiliary & trip contact
terms of watchdog.
connection as per below table.
2.3. Output Contacts
A1 A2 A3 A4 A5 A6 A7 A8
Relay 3 is fixed for CB tripping, common for all type of
faults. Relay1and Relay2 are user configurable for A
annunciations like OL / SC /E /EH /Self supervision. Reset
function of all output contacts is individually programmable B
[Auto Reset / Manual Reset] from HMI. RESET DELAY is B1 B2 B3 B4 B5 B6 B7 B8 B9

available with all output contacts but get disable in Manual


Reset mode.

3
IRI-Pro-V2 : Over-current, Short-Circuit and Earth Fault Relay

Terminal No Description 10. Circuit Diagram

A
A1 L1 Current Transformer Phase
IRI-PRO-3I-EI/3O-EO
A2 L1 Current Transformer Neutral
A3 L2 Current Transformer Phase L1
B7 B8
B9

L2

A4 L2 Current Transformer Neutral L3

A5 L3 Current Transformer Phase Auxilary


A1 L1.1 Supply
S1 B1

A6 L3 Current Transformer Neutral


P1 RELAY -1
B2
P2 A2 L1
S2 L1.2

A7 Earth CT1
B3
S1 A3 L2.1 RELAY- 2

P1
B4
L2
P2 S2 A4 L2.2

A8 Earth CT2 S1 A5 L3.1


CB TRIP RELAY
B5

B6
P1

B
L3
P2 S2 L3.2
A6

A7
N2

B1 Relay-1 NO
Ie
A8 N1
IRI Pro 3O-EO/3I-EI

B2 Relay-1 COMM
B3 Relay-2 NO
B4 Relay-2 COMM
IRI-PRO-I
B5 Relay-3 NO
B6 Relay-3 COMM
B7 B8

B7 Auxiliary Supply Line (Non polar)


B9
L1
L2
L3

B8 Auxiliary Supply Line (Non polar) N

Auxilary
B9 Earth P1
S1 A1 L1.1 Supply
RELAY -1
B1

P2 S2 A2 L1.2 L1 B2

B3
A3
RELAY- 2
B4

8. Trip Test A4

CB TRIP RELAY
B5

A5 B6

This feature allows the user to check contact operation. A6

TRIP test can be used while commissioning the relay to see A7

the operation of contacts of IRI-PRO. It is selectable from A8

front LCD menu and becomes active only when currents IRI Pro I

are below all pickup levels and trip levels. Selecting trip
test, gives the momentary operation of all three available
contacts in IRI-PRO one by one with LED flashing indications.

9. Contact Details IRI-PRO-EO


Number of relays : 3 [Relay 1,2,3]
Relay 1,2,3
Type of Contact [Relay 1,2,3] : (SPST-NO, type A ) B7 B8
B9
L1

Assignment of Contact : Relay3 common for trip on L2


L3
I > and I >> , IE > and N

IE >> Auxilary
A1 Supply B1
RELAY -1
Relay 1 & 2are configurable A2 B2

for O/L,S/ C ,E,EH, Self A3


RELAY- 2
B3

supervision ] A4
B4

B5
CB TRIP RELAY
Max. breaking capacity : 1250 VA / 150 W resistive A5 B6

500 VA / 90 W inductive A6

Max. breaking voltage : 400 V AC, 125 V DC


S1 A7 N2

Max. continuous current : 8A


P1
Ie
P2 S2 A8
N1

Max. making current (16 ms) : 20 A IRI Pro EO

4
IRI-Pro-V2 : Over-current, Short-Circuit and Earth Fault Relay

11. Technical Data

11.1 Measuring input

Rated data : Rated current IN 1A or 5A


Rated frequency FN 50Hz
Power consumption in current circuit : At IN = 1A 0.2 VA
At IN = 5A 0.1 VA
Thermal withstand capability in current circuit : for 1 s 100 x IN
for 10 s 20 x IN
continuously 4 x IN
Dropout ratio : > 96 %
Returning time : 30 ms
Minimum operating time : 30 ms

11.2 Setting ranges and steps

Parameter Display Setting range Step

I> I> 0.20 – 2.5 x IN 0.05 x IN


t> 0.1 –150 s 0.01 s
ti > 0.01 – 1.500 0.005
I >> I >> 0.5 – 25 x IN 0.5x IN
t >> 0.03 – 20 s 0.01 s

IE> Ie > 0.05 -2.5 x IN 0.05x IN


tE > 0.03 - 150s 0.01s
tiE 0.01 – 1.500 0.005
IE >> IE >> 0.5 – 15x IN 0.05 x IN
tIE >> 0.02 – 20 s 0.01s
Reset Delay RST-D 0 – 20sec 0.1sec
CT Ratio CT Ratio 1-2500 1
Trip Time ± 5% or + 20msec for VINV,NINV3.0/1.3, ± 3 % or ± 20 ms for DEFT
Tolerances (whichever is higher)
±7.5% or + 30msec (whichever is higher) for EINV , NINV0.6
Accuracy as per IEC-255-4 in band of (I/Is > 2 to I/Is<20) and Is>0.1In
Pickup Tolerances ± 5% from set value

0.14 I : Injected Current


Normal Inverse 3.0 t = ti [s]
(I / IS) 0.02
–1 Is : Pickup Set Level
ti : TMS for Inverse Characteristic
0.061 t : Definite delay in DEFT characteristic
Normal Inverse 1.3 t = ti [s]
(I / IS) 0.02 – 1

0.028
Normal Inverse 0.6 t = ti [s]
(I / IS) 0.02 – 1

13.5
Very Inverse t = ti [s]
(I / IS) – 1
!!! !!!
80
Extremely Inverse t = ti [s] O/L, S/C, E and EH protections are
(I / IS) 2 - 1 available with DISABLE option in HMI.

5
IRI-Pro-V2 : Over-current, Short-Circuit and Earth Fault Relay

12 Setting Procedure

Menu Frames

Menu 1 Menu 5 : OL - RELAY : RLY1


Default Page Ir Iy Ib Ie XX .XX A (RMS)
(ENTER Key on SC - RELAY : -----
(Running Parameters) Relay Assignment)
E - RELAY : ----
#EDIT/VIEW MENU# EH - RELAY : -----
<PROTECTION> SUPERVISION - RELAY :
<LAST FAULT1> BACK
Menu 2
(Pressing Enter Key) <LAST FAULT2>
Menu 6: RELAY 1 : AUTO
<LAST FAULT3>
(ENTER Key on RELAY 2 : AUTO
<LAST FAULT4> Relay Reset)
BACK
<LAST FAULT5>
<RELAY ASSIGN>
<TRIP TEST> #TRIP#
<EDIT RTC> Menu 7 [F] Ir XX.XXA (Fault Current)
(Presing Enter
<CHANG PASSWORD> [F] Iy XX.XXA (Fault Current)
Key on FAULT
1,2,3,4,5 selection ) [F] Ib XX.XXA (Fault Current)
#EDIT#
<CT -RATIO> [F] Ie XX.XXA (Fault Current)
<CHAR - P> Trip OL : L1, L2, L3, E
Menu 3 : <CHAR - E>
I> Trip SC : L1, L2, L3, E
(Pressing Enter
Key on PROTECTION ti> + [ Date / Time Stamp)
selection ) t>
I>> BACK
t>>
Ie>
tie>
te>
Ie>>
te>>
RST- Delay

# CHAR P/E#
Menu 4 : DEFT
(Pressing Enter EINV
Key on CHAR-P/E
selection ) VINV
NINV0.6
NINV1.3
NINV3.0
BACK

ti : Time multiplier setting only for Inverse time characteristic


t: Timer setting only for definite time characteristic

6
IRI-Pro-V2 : Over-current, Short-Circuit and Earth Fault Relay

13. Dimensional Drawing


Front View
146

136.5

72
68
Side View

72

148
134
36.5

TOP View
136.5

146

Cut out Dimensions


Installation Depth : 175mm
All dimensions in : mm

7
www.cselectric.co.in

IRI-PRO-V2

14. Order Form

IRI-PRO-V2 Protection Phase Rated Earth Rated

1 E/F with High set - EO -


3/OC + 1 E/F Without High set - 3O-EO -
3/OC +1 E/F with High set - 3I-EI -
1 O/C + High set - I1-
Rated Current(O/C Element) IN
1-Amp -1
5-Amp -5
Rated Current for Earth
1-Amp -1
5-Amp -5

C&S Electric Limited


(Protection & Control Division)
44, Okhla Industrial Estate, New Delhi -110 020
Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413 E-mail: [email protected]

Corporate Office : 222, Okhla Industrial Estate, New Delhi -110 020
Tel . : +91 11 3088 7520 -29, Fax : +91 11 2684 7154, 2682 9063