SubStation Structure Design
SubStation Structure Design
50-SDMS-01 Rev. 01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 03-2017G
50-SDMS-01
REV. 01
SPECIFICATIONS
FOR
CURRENT TRANSFORMERS
UP TO 36 KV
CONTENTS
1.0 SCOPE 3
7.0 MARKING 7
8.0 TESTING 8
10.0 GUARANTEE 8
Page 2 of 11
Saudi Electricity Company الشركة السعودية للكھرباء
50-SDMS-01 Rev. 01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 03-2017G
1.0 SCOPE
This specification describes the minimum technical requirements for design, material,
manufacturing, testing and performance of current transformers up to 36 kV for indoor
or outdoor installation in an enclosure and intended to be used for metering and
protection in the distribution system of Saudi Electricity Company (SEC).
Current transformers shall be suitable for operation under the service conditions as per
the latest revision of SEC General Specification: 01-SDMS-01.
External surface of the current transformers shall withstand the effects of direct solar
radiation. The temperature of surfaces exposed to direct solar radiation shall be
regarded as 75˚C, plus the effect of any internal heating.
Page 3 of 11
Saudi Electricity Company الشركة السعودية للكھرباء
50-SDMS-01 Rev. 01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 03-2017G
Current transformers shall be suitable for operation in SEC distribution system with
parameters outlined in the latest revision of SEC General Specification: 01-SDMS-01.
Current transformers shall be made from high quality materials. The encapsulating
material shall be self extinguishing and heat resistant with excellent mechanical
strength.
Low voltage current transformers shall be of single ratio. Medium voltage current
transformers can be either single or Multi ratio.
Current transformer shall be provided with mounting accessories for cables and bus
bars. These accessories shall be stainless steel. Mounting arrangement on wall/floor
shall be excluded. Double secondary terminals shall be provided for short circuiting
the secondary winding before opening the measuring circuit.
Table-1
Rated insulation levels for current transformer primary windings
Page 4 of 11
Saudi Electricity Company الشركة السعودية للكھرباء
50-SDMS-01 Rev. 01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 03-2017G
6.4 Burden
The accuracy class for metering CTs shall be 0.5 for the rated burden at the rated
current and extended current. The accuracy class for protective current transformers
shall be 5P10 and 10P10.
The minimum requirement for the extended rating at 55˚C shall be 120% of primary
current. The extended rating at 55˚C shall be clearly marked on the nameplate.
The rated short time thermal current (Ith) shall be equal to or higher than that of
associated equipment as applicable with a minimum duration of one second.
The rated dynamic current (Idyn) shall not be less than 2.5 times Ith.
6.10.2 Current transformers shall be window type and suitable for horizontal and vertical
mounting on cables and/or bus bars.
Page 5 of 11
Saudi Electricity Company الشركة السعودية للكھرباء
50-SDMS-01 Rev. 01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 03-2017G
6.10.3 Current transformers with primary current up to 400 Amps shall be suitable for rigidly
fixing on the surface of fiberglass meter boxes. and be provided without terminal
covers and a suitable exposed length of wires shall be provided.
6.10.4 Current transformers with primary current of 500 Amps and above shall be suitable
for bus bar fixing with no terminal covers and a suitable exposed length of wires
provided.
6.10.5 The window size of LV current transformers shall be suitable for the sizes of cables
and busbars as per Table-2.
Table-2
Dimensions of CTs and bus bar/cable sizes
Maximum Dimension
C T Ratio Color Code Busbar Cable
Height Width Depth
200/5 Amps Red 1x30 mm 110 mm 80 mm 55 mm
250/5 Amps Orange 1x30 mm 110 mm 80 mm 55 mm
300/5 Amps Yellow 1x30 mm 110 mm 80 mm 55 mm
400/5 Amps Green 1x30 mm 110 mm 80 mm 55 mm
500/5 Amps Blue 1x10x100 mm 110 mm 80 mm 55 mm
600/5 Amps Indigo 1x10x100 mm
800/5 Amps Violet 1x10x100 mm
1500/5 Amps Brown 1x10x100 mm
3000/5 Amps Black 2x10x100 mm
4000/5 Amps Grey 3x10x100 mm
6.10.6 The secondary wires for all low voltage CTs shall be high temperature insulated
copper 2.5 Sq.mm, brought out directly from the CT with a suitable exposed length,
with no terminals or terminal covers.
Page 6 of 11
Saudi Electricity Company الشركة السعودية للكھرباء
50-SDMS-01 Rev. 01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 03-2017G
Voltage Ratios
600-300 / 5-5
400-200 / 5-5
17.5 kV
300-150 / 5-5
150-75 / 5-5
400-200 / 5-5
200-100 / 5-5
36 kV 80-60 / 5-5
60-30 / 5-5
20-10 / 5-5
7.0 MARKING
7.1 The terminals shall be marked clearly and indelibly either on their surface or in their
immediate vicinity. They shall be marked as P1/P2 and S1/S2 for primary and
secondary respectively.
7.2 The nameplate shall carry the following information in accordance with IEC 61869.
7.2.1 Manufacturer's name and reference number
7.2.2 Serial number and a type designation
7.2.3 Rated primary and secondary currents
7.2.4 Rated frequency
7.2.5 Rated output and corresponding accuracy class
7.2.6 Current Transformers having an extended current rating shall have this
rating at 55˚C indicated immediately following the class designation, for
example, 10 VA class 0.5 ext. 200% 55˚C
Page 7 of 11
Saudi Electricity Company الشركة السعودية للكھرباء
50-SDMS-01 Rev. 01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 03-2017G
7.3 In addition to all the requirements for the marking of metering current transformers
in IEC 61869-2, the transformer ratio shall be boldly marked on the body, in figures
at least 20 mm high.
8.0 TESTING
8.1 Certified copies of type tests carried out in an independent SEC approved laboratory in
accordance with IEC 61869-2, shall be submitted with the tender/inquiry.
8.2 Routine test certificates for each current transformer by serial number shall be
submitted to SEC prior to the delivery.
SEC reserve the rights to test the current transformers in their own laboratory, the
testing shall be carried out according to IEC 61869-2 and shall be done by selecting
random sample, as 10% of any batch delivered to the SEC stores. The batch shall be
assumed as rejected if more than three (3) current transformers found faulty in the
sample.
In case of acceptance, SEC can decide to test the whole batch and the supplier has to
replace the failed current transformers or any other defective current transformer in the
same batch found later.
In case of rejection, the supplier shall have two choices. The first is to replace the
whole batch, the second is to let SEC do the test for the whole quantity, and the
supplier shall bear the cost of the test and replace the failed current transformers.
Page 8 of 11
Saudi Electricity Company الشركة السعودية للكھرباء
50-SDMS-01 Rev. 01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 03-2017G
9.2 Each box of individual current transformer shall be marked with the information as
mentioned in clause 7.2.
10.0 GUARANTEE
10.1 The vendor shall guarantee the current transformers against all defects arising out of
faulty design or workmanship, or defective materials for a period of one (1) year from
the date of commissioning, or two (2) years from the date of delivery. SEC certificates
for the date of commissioning shall be accepted.
10.2 If no exceptions to this specification are taken and no list of deviations is submitted, it
shall be deemed that, in every respect, the current transformers offered shall conform
to this specification. SEC interpretation of this specification shall be accepted.
The attached Technical Data Schedule shall be completed and submitted with the bid
along with type tests and supporting catalogues.
Page 9 of 11
Saudi Electricity Company الشركة السعودية للكھرباء
50-SDMS-01 Rev. 01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 03-2017G
Page 10 of 11
Saudi Electricity Company الشركة السعودية للكھرباء
50-SDMS-01 Rev. 01
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 03-2017G
Date
Page 11 of 11