User's Guide Smartpack Monitoring-Ctrl-Unit - B - 3
User's Guide Smartpack Monitoring-Ctrl-Unit - B - 3
Information in this document is subject to change without notice and does not represent
a commitment on the part of Eltek Energy.
No part of this document may be reproduced or transmitted in any form or by any means
— electronic or mechanical, including photocopying and recording — for any purpose
without the explicit written permission of Eltek Energy.
Safety Precautions
Published 2005-09-21
Mfm
2 User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09
1 Welcome
Table of Contents
1. Welcome 4
About this Guide ............................................................................................................. 4
System Diagram Flatpack2 Power System ................................................................ 4
5. Technical Specifications 15
6. Functionality Description 16
Alarm Reset .................................................................................................................. 16
Display System Voltages (VoltageInfo)...................................................................... 16
Display Alarm Messages, (Log) (DisplayMessages).................................................. 16
Display Rectifier Information (Rectifier Info)............................................................... 17
Plug-and-Play Rectifier .........................................................................................................17
Mains Phase Assignment versus Rectifier ID ............................................................... 18
Resetting the Number of Rectifiers ............................................................................... 18
About Battery Banks, Strings and Blocks...................................................................... 19
Battery Symmetry Measurements.........................................................................................19
User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09 3
1 Welcome
1. Welcome
Congratulations on your purchase of the powerful Flatpack2 DC power supply system,
which uses the new Smartpack controller a powerful and cost-effective module
developed for monitoring and controlling your DC power system.
Read also the general and site specific documentation that was delivered with your
Flatpack2 DC power system.
Flatpack2
CAN Bus (rectifiers)
LVLD Telecom
equipment
AC mains
supply LVBD
AC Fuses, selector
external Load Fuses
(230VAC or & MCBs
400VAC Symmetry
Alarm & DC
Temp. Sensor distribution
AC Supply DC Supply
(Single- or Battery string #1 Battery (24V, 48V
three-phase) Fuses or 60V)
4 User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09
2 The Smartpack Controller
Key Features
Front panel LCD and buttons for on-site service without PC.
USB- or RS-232 interface for PC connection locally or remote monitoring
and control via modem, Ethernet, web or SNMP.
6 user programmable relay outputs for traditional remote monitoring
6 user programmable inputs for monitoring of other equipment on site
Battery monitoring and testing without site attendance
Temperature compensated charging for increased battery lifetime
Battery lifetime indication
Password protected operator access levels
Alarm/event log with time and date
Windows-based PC communication software
Block Diagram
The microprocessor is the heart of
the system and represents the All customer-specified functions,
intelligence in Smartpack controller. calibration and log data are stored in
The main program and dynamic Smartpack Controller EEPROM chips
data are stored in Flash memory
chips, easily upgraded via the USB Microprocessor EEPROM
FLASH & EEPROM Memory CAN port (2)
or CAN ports 256Kb 512Kb for communication with rectifiers and
DIP switches for other controllers on the CAN bus
configuring the controller’s DIP switch
CAN bus ID number CAN1 Power supply
Power Bus with regulated supply voltages
24 / 48 / 60VDC Input supply for internal and external use
Power supply Step Down
(plug-in PCB)
Flyback rectifier Reg. ±12V
Inputs signals Step Down
(measurements) Reg.+5V
Output signals (control)
for system reference(1), for LVD latching relays (2)
battery current, battery &
load fuse fail (3) CON5
System Connections (internal)
Inputs signals USB 2.0 type B port (1)
(measurements) for battery serial communication interface with
symmetry (4), temperature CON4 USB PCs and computer devices
sense (1) Battery Connections Serial Bus
(internal) Output signals (control)
Inputs signals for Alarm relays (2)
(measurements) for con- CON1
figurable digital inputs (2) Alarm I/O Connections (customer)
(Plug-in PCB)
Inputs signals CON3
(measurements) for battery Battery Connections (customer) (Plug-in PCB)
symmetry (4), temperature
sense (1), battery current
(1), battery fuse fail (1)
CON2 Output signals (control)
Inputs signals Alarm I/O Connections (customer)
(measurements) for con- for Alarm relays (4)
figurable digital inputs (4)
Figure 2 Block diagram of the Smartpack controller showing the module’s main functions
User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09 5
2 The Smartpack Controller
Typical Applications
The Smartpack controller employs CAN bus communication with the Flatpack2 rectifiers
and other bus-connected Smartpack controllers in the system thus enabling flexible
expansion of system functionality and number of measuring points. System components
can be set up and upgraded to meet the demand of any tailor-made power solution.
Figure 3 Front access USB port, and DIP switches for ID configuration on the side.
The Smartpack controller’s outputs and inputs for monitoring and controlling the
system, the batteries, alarm relays and status of external equipment are located on
the controller’s rear panel.
6 User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09
2 The Smartpack Controller
System CON5
15 pins D-Sub (female) 10 +
Battery CON4
Connections 15 pins D-Sub (male)
FUNCTION SIGNAL PIN-OUT 3 + Batt. Symmetry 1
Batt. Symmetry 5
Batt Sym 5 − 1 1 −
Temp Sense 2 − 2 6 + Batt. Symmetry 6
Batt Sym 5 + 3 5 −
Temp Sense 2 + 4 Interface 11 + Batt. Symmetry 7
1 5 Batt Sym 6 − 5 Cable 3 10 −
Batt Sym 6 + 6 15 + Batt. Symmetry 8
Batt Current 2 + 7 13 −
11 15 Batt Current 2 − 8 4 + Temp. Sense 2
NC 9 2 −
(Blue) Batt Sym 7 − 10 7 + Batt Current 2
Batt Sym 7 + 11 15-pins 8 −
Batt Fuse Fail 2 − 12 D-Sub 14 + Batt Fuse Fail 2
Batt Sym 8 − 13 female 12 −
Batt Fuse Fail 2 + 14
Batt Sym 8 + 15 (Internal
Smartpack controller Connections)
In
Figure 5 Overview of internal system and battery connections
User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09 7
2 The Smartpack Controller
i l
1 9 Config. Input 2A − 3 5 COM
Config. Input 2B + 4 Alarm Circuit 1
7 NC
Relay Output 1 COM 5 9 NO
T
Relay Output 1 NO 6 10-pins 8 COM
2 10 plug Alarm Circuit 2
Relay Output 1 NC 7 10 NC
(Green) Relay Output 2 COM 8 female
Relay Output 2 NO 9 (Customer
Relay Output 2 NC 10
Connections)
Smartpack controller
In Out
Notice: the signals available at the
Ext. Alarm I/O CON2 interface terminals may vary. Read
Connections 26 pins your system’s specific documents.
FUNCTION SIGNAL PIN-OUT
Config. Input 5B + 1 21 +
Config. Input 5A − 2 Input Circuit 3
20 −
Config. Input 6B + 3 19 +
Config. Input 6A − 4 Input Circuit 4
System Specific Interface Terminals
NC 5 10 −
1 + Input Circuit 5
Relay Output 3 NC 6
Relay Output 4 NC 7 2 −
19 26 3 + Input Circuit 6
Relay Output 5 NC 8 Interface
Relay Output 6 9 4 −
NC Cable 2 15 NO
Config. Input 4A − 10
1 9 NC 11 23 COM
Alarm Circuit 3
(Green) NC 12 6 NC
16 NO
NC 13 COM
NC 14 24 Alarm Circuit 4
Relay Output 3 NO 15 26-pins 7 NC
Relay Output 4 NO 16 D-Sub 17 NO
male 25 COM
Relay Output 5 NO 17 Alarm Circuit 5
Relay Output 6 NO 18 8 NC
18 NO
Config. Input 4B + 19 COM
Config. Input 3A − 20 26 Alarm Circuit 6
Config. Input 3B + 21 9 NC
NC 22 (Customer
Relay Output 3 COM 23 Connections)
Relay Output 4 COM 24
Relay Output 5 COM 25 In Out
Relay Output 6 COM 26
Smartpack controller
Figure 6 Overview of customer connections alarm relay & digital input signals
8 User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09
2 The Smartpack Controller
When Flatpack2 rectifiers are hot-plugged in the power shelves the first time, the
Smartpack controller automatically assigns the rectifiers with the next available ID
number (software-assignment), and automatically increases the number of
communicating rectifiers on the CAN bus.
When a previously installed rectifier is hot-plugged in the power shelf again, it retains its
previous ID and serial number.
To ensure a correct bus communication and avoid data reflection, you must always
terminate the CAN bus with two 120Ω resistors at both ends of the line, see Figure 7.
Figure 7 CAN bus terminated with a 120Ω resistor on both line ends (60Ω bus impedance)
The example in Figure 8 shows two networked Flatpack2 DC power systems. The CAN
bus must then be terminated with only two 120Ω resistors, one at each end of the line.
End-of-Line
Resistor 1 2 120Ω
120Ω
01 02 n n+1 n+2 m
Flatpack2 Flatpack2
DC Power System 1 DC Power System 2 End-of-Line
Resistor
Figure 8 Two Flatpack2 DC power systems CAN bus connected with CAT5 twisted-pair cables.
Only two 120Ω resistors are to be terminated on both line ends (60Ω total bus impedance)
User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09 9
3 Installation of Smartpack Controller
Safety precautions
Get acquantied with the satety precaution on page 2, before installing or handling
the equipment.
10 User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09
4 Front Panel Operation
LED indicators
The Smartpack controller has the following LED indications:
• “Power” (green) indicates that the power supply is ON or OFF
• Alarm (red) indicates an alarm situation (major alarm)
• Warning (yellow) indicates an abnormal situation (minor alarm)
LCD Display
The graphic display is an important part of the power supply system’s user interface. The
display is in Status Mode (displays the system’s status) or in Menu Mode (displays the
menu structure).
Depending on the display’s mode, the upper line shows the output voltage or menu
options, while the lower line displays battery and load current, alarms, or information
about which key to press. See also chapter “Modes of Operation”, on page 12.
Front Keys
You can control the whole Flatpack2 DC power system via a network of software menus
accessed with the controller’s front keys.
o Press on the key to change from Status Mode to Menu Mode.
o Press the or keys to scroll up or down and navigate to find menu options
(function or parameter).
o Press then the key to select the function.
User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09 11
4 Front Panel Operation
Modes of Operation
The controller’s display is either in Status Mode or in Menu Mode.
Status Mode
When the front keys are not in operation, the display is in Status Mode. The following
information is then scrolled through the display:
Menu Mode
When the front keys are in operation, the controller’s display switches to Menu Mode and
the following information is scrolled through the display:
• The upper line shows the name of the active menu or sub-menu
• The lower line indicates which key to press
Notice that if no keys are pressed within 30 seconds, the display will automatically switch
from Menu Mode and to back to Status Mode.
12 User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09
4 Front Panel Operation
User Options
1
When you “enter” Menu Mode, you access the User Options.
1
The “Vx” references, if any, on the right hand of the option, are not shown in the
display. They only indicate in which software version (x) the option was first implement.
User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09 13
4 Front Panel Operation
Service Options
When you enter Menu Mode, you access the User Options. You may then scroll down to
the password protected Service Options. 2
2
The “Vx” references, if any, on the right hand of the option, are not shown in the
display. They only indicate in which software version (x) the option was first implement.
14 User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09
5 Technical Specifications
5. Technical Specifications
System
Mains Failure (individual phases)
Digital Inputs (programmable names)
Features Load Disconnect (voltage or timer)
System Load Fuse
Output Voltage Measurement Load Current
Total Load Current Measurement
Load/Battery Disconnect Battery
Alarm Level Settings (major / minor) High Battery voltage
Low Battery voltage
Alarm Log (up to 1000 events)
High Battery temperature
Real Time Clock with Battery Backup
Low Battery temperature
Site Text/ID Battery Capacity
Test of Relay Outputs Battery Disconnect
Voltage Level setup Battery Fuse
Symmetry Failure
Battery Battery quality indication
Battery Current Measurement Battery discharge current
Battery Temperature Measurement (optional)
Rectifier
Battery Testing (acc. to discharge table or set time
Rectifier Failure
limit)
Critical Rectifier Failure (> 1, programmable)
Battery Test Information (10 latest tests) Rectifier Capacity w. programmable level
Setup of Battery Data Rectifier Current Limit
Battery shunt setup Rectifier Over voltage Protection
Battery quality indication Rectifier Current
Battery Boost Charging
Battery Cable Voltage Drop Compensation
Temperature Compensated Charging
Protection against Temperature Probe Failure
Rectifier Specifications
Available information about each rectifier, e.g. serial
Input Voltage 24/48/60 VDC
number, version, internal temperature
Individual Rectifier Current Measurement Dimensions 109 x 44 (1U) x 140mm (wxhxd)
Individual Rectifier Input Voltage (4.3 x 1.7 x 5.5”)
User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09 15
6 Functionality Description
6. Functionality Description
In this chapter you can find helpful and more detailed descriptions of expressions,
technical terms, functions, etc. used in Flatpack2 DC power supply systems.
Alarm Reset
You can reset all active alarms by selecting “UserOption>AlarmReset”, via the
Smartpack controller’s front keys. The controller will immediately report alarm conditions
that are still active.
The Flatpack2 DC power system can be configured with automatic or manual alarm reset.
When Automatic Alarm Reset is enabled (default) and the alarm condition no longer
exists the Smartpack controller will deactivate the alarm lamps and relays to indicate
that normal operation is established.
When Manual Alarm Reset is enabled and the alarm condition no longer exists the
operator must reset the alarm manually.
Following voltages may be displayed selecting the VoltageInfo sub options (level 3):
Option Description
NomVolt Nominal output voltage
BoostVolt Battery boost-charging voltage
LowBatt1 Voltage limit for Low Battery Alarm 1
LowBatt2 Voltage limit for Low Battery Alarm 2
HighBatt1 Voltage limit for High Battery Alarm 1
HighBatt2 Voltage limit for High Battery Alarm 2
LVD 1 Voltage limit for Low Voltage Disconnect unit 1
The Smartpack controller’s alarm log may store up to 1000 chronological events. Each
log entry contains event text, event action, time and date. When the log is full, the oldest
value is overwritten. The log is stored in EEPROM.
16 User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09
6 Functionality Description
Following information may be displayed selecting the Rectifier Info sub options (level 3):
Option Description
NoOfRects. Number of rectifiers installed in the system.
RectCurrent Rectifier current
RectSerialNumber Rectifier ID and serial number
Rect.PrimaryVolt Rectifier input voltage
Rectifier Status Rectifier status
Rectifier Temp Rectifier temperature
While the controller is accessing information from a specific rectifier, the green LED on
the rectifier’s front panel flashes.
The Smartpack controller sends out status messages every 200ms to all the Flatpack2
rectifiers connected to the CAN bus, such as:
o The Smartpack controller’s status
o Current Limit Reference
o Measured Output Voltage
o Reference Output Voltage
o Over-voltage Protection Reference
o Etc.
Plug-and-Play Rectifier
When a rectifier is hot plugged in a power shelf for the first time, the Smartpack
controller assigns the next available ID number to the rectifier, starting with “01”. This ID
number (or CAN bus address) and the rectifier’s serial number are stored in both
modules.
To achieve a more controlled ID assignment, you should always insert & hot-plug new
Flatpack2 rectifiers in the power shelves, one module at a time, starting with shelf
position 1, 2, 3 and so on. The sequence is indifferent after positions 9. Read chapter
“Mains Phase Assignment versus Rectifier ID”, page 18.
The power shelf position numbers vary with the type of AC mains and the type of power
shelves installed in your system. Refer to your system’s quick start guide and specific
documentation for more information.
User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09 17
6 Functionality Description
3
4AC Power Shelves (Single AC feed: 4 AC inputs per shelf, each feeding 1 rectifier).
4
2AC Power Shelves (Dual AC feed: 2 AC inputs per shelf, each feeding 2 rectifiers).
18 User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09
6 Functionality Description
- + - + - + - +
+ (0V)
+ (0V)
- + - +
symmetry inputs, enabling symmetry measurement of:
o 2 battery strings (block meas. method)
o 4 battery strings (double mid-point meas. method)
Two measurement points per string, o 8 battery strings (mid-point meas. method)
from the middle to the outer terminals
Figure 12 Example of terminal connection points for Symmetry Block, Mid-point and
Double Mid-point measurement methods
User’s Guide Smartpack Monitoring & Ctrl Unit, Art. 350003.013, v2.1-2005-09 19