Performance Specification: Hot Side Cold Side

This document specifies the performance of a heat exchanger with the following key details: - It will exchange 58 kW of heat between a hot side with water and a cold side with 40% propylene glycol solution. - The hot side will have an inlet temperature of 26°C and outlet of 16°C. The cold side will have an inlet of 6°C and outlet of 12°C. - It will have a total heat transfer area of 2.76 m2 and an LMTD of 11.89°C. - The unit will be a plate heat exchanger made of 1.4401 stainless steel with 32 plates in a 1M+9L arrangement on
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
233 views2 pages

Performance Specification: Hot Side Cold Side

This document specifies the performance of a heat exchanger with the following key details: - It will exchange 58 kW of heat between a hot side with water and a cold side with 40% propylene glycol solution. - The hot side will have an inlet temperature of 26°C and outlet of 16°C. The cold side will have an inlet of 6°C and outlet of 12°C. - It will have a total heat transfer area of 2.76 m2 and an LMTD of 11.89°C. - The unit will be a plate heat exchanger made of 1.4401 stainless steel with 32 plates in a 1M+9L arrangement on
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

`

Performance Specification
`
Customer: Date: 2018-06-05
Proposal No.:
Email: Run No.: 2335843
Cust. Reference: Item No.:
Technician:
Model: GLP-009-M-4-NX-32 Units Required: 1

Intended End Use: Heat exchanger water/gliycol

Hot Side Cold Side


Fluid Name Water 40% PropGlycol (aq)

OPERATING DATA Inlet Outlet Inlet Outlet


Total Liquid flow m³/h 5,00 5,00 8,92 8,92 m³/h
Operating Temperature °C 26,00 16,00 6,00 12,00 °C
Pressure drop (allowed / calc.) kPa 30,00 / 4,06 30,00 / 15,94 kPa
Total Heat Exchanged kW 58
U-Service W/(m²·°C) 1 765
Total Heat Transfer Area m² 2,76
LMTD °C 11,89
Surface Margin % 20

FLUID PROPERTIES Inlet Outlet Inlet Outlet


Specific Gravity - 1,00 1,00 1,04 1,04
Specific Heat kJ/(kg·°C) 4,18 4,18 3,74 3,75
Thermal Conductivity W/(m·°C) 0,61 0,59 0,42 0,42
Viscosity (avg.) cP 0,87 1,11 7,61 5,76

CONNECTIONS
Position S4 S3 S2 S1
Type THREADED THREADED THREADED THREADED
Size R 1 1/2" R 1 1/2" R 1 1/2" R 1 1/2"
Material 1.4401 1.4401

CONSTRUCTION
Pass Arrangement 1 1
Channel Arrangement 6M+9L 6M+10L
A-Dimension / C-Dimension mm 92,8 / 380
Plate Material (Material/Thickness) 1.4401 / 0.4 mm
Gasket Material (Hot/Cold) NBR(Clip-On) NBR(Clip-On)
No. of Plates 32
Tightening Bolts/Nuts/Finish 8.8 / 8 / FZB
Pressure (design / test) MPa(g) 1,00 / 1,43 1,00 / 1,43
Temperature (min / design) °C -10,00 / 80,00 -10,00 / 80,00
Volume (per Side) l 3,30 3,52
Weight empty / flooded (per unit) kg 101 / 108
Pressure vessel code PED

Remarks:

The performance guarantee, if applicable, is based on the accuracy of the data presented above,
and the customers ability to supply product and operating conditions in conformance with the above.
Tranter International AB ul. Podolska 18 Nysa, 48-303
2018-06-05 Phn: 77 433 05 95 Fax: 77 433 05 95 Email: [email protected] 3.0.0.253
SUPERCHANGER ASSEMBLY
GLP-009-M-4-NX-32

Sizing Number
000000

Dimensions are for reference purposes only and are not to be used for construction.
Property of Tranter International AB and not to be reproduced without their consent nor used in any manner detrimental to the interest of Tranter International AB.

You might also like