Ahu 6 Alternate Arrangement

The document provides design conditions and airflow rates for an air handling unit (AHU 6) with a total airflow of 45,000 m3/h and 11,000 m3/h of fresh air. It summarizes the summer and winter cycles, including return air temperatures and humidity, fresh air inputs, enthalpy wheel operation, cooling and heating coil capacities, and mixed air outputs.

Uploaded by

naresh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
281 views4 pages

Ahu 6 Alternate Arrangement

The document provides design conditions and airflow rates for an air handling unit (AHU 6) with a total airflow of 45,000 m3/h and 11,000 m3/h of fresh air. It summarizes the summer and winter cycles, including return air temperatures and humidity, fresh air inputs, enthalpy wheel operation, cooling and heating coil capacities, and mixed air outputs.

Uploaded by

naresh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Project Clean Room Preliminary Calculation AHU 6 …. Total 45000 m3/h …..

Fresh Air … 11000 m3/h

Design Conditions Summer Winter


SET POINT
DB º C 42 -7
RH % 45 90
CHILLED WATER 6 …..12 22 º C …… 45 % RH
HOT WATER 70…..50

Summer Cycle
Return Air
Return Air Extract Air 22°C/45 %RH
22°C/45 %RH 33 °C/51.5% RH 34000 m3 /h
11000 m3 /h 11570 m3 /h

Coil Off Coil Off


Fresh Air 11°C/98 RH 22 °C/48.6 Mixed Air
42°C/45 % RH 9700 m3 /h RH 22.8°C/45.8 %RH
11000 m3 /h Pretreated Air 10072 m3 /h 44074 m3 /h
30 °C/52.2 RH
10425 m3 /h

Enthalpy Wheel 60% Sensible & Total Efficiency Cooling Coil Heating Coil Mixing Box
Total Recovery 123 KW Total Capacity Kw 114 Total Capacity 37 Kw
Sensible Recovery 40.8 KW Sensible Capacity Kw 64 Water Flow 0.44 kg/s
Latent Recovery 123.0 KW Latent Capacity Kw 50
Mois. Trans. 114.77 ( Out of Process ) Water Flow 4.5 kg/s
ADP 10.3 , CCF =0.96 SHR =0.56
Winter Cycle
Return Air
Return Air Extract Air 22°C/45 %RH
22°C/45 %RH 4.6 °C/78.3% RH 34000 m3 /h
11000 m3 /h 10281 m3 /h

Coil Off
Fresh Air 22 °C/29.6 Mixed Air
-7°C/90 % RH RH 22°C/40.9 %RH
11000 m3 /h Pretreated Air 12265 m3 /h 46267 m3 /h
8.5 °C/70.5 RH
11703 m3 /h

Enthalpy Wheel 60% Sensible & Total Efficiency Cooling Coil Heating Coil Mixing Box
Total Recovery 94 KW Not Used Total Capacity 54 Kw
Sensible Recovery 63.7 KW Water Flow 0.66 kg/s
Latent Recovery 30.1 KW
Mois. Trans. 43.63 ( in to process )
Return Air
22°C/45 %RH
34000 m3 /h

Mixed Air
22.8°C/45.8 %RH
Mixed Air 44074 m3 /h
22.8°C/45.8 %RH
44074 m3 /h

Mixing Box Humidifier


Not Used
Return Air
22°C/45 %RH
34000 m3 /h

Supply Air
22°C/45 %RH
46267 m3 /h
Mixed Air
22°C/40.9 %RH
46267 m3 /h

Mixing Box Humidifier


26. 4 kw
Steam 38 kg/hr