409 M Quick User Guide
409 M Quick User Guide
Use of
409 Retransmission Output snubber circuits across loads as shown above, is
Output Signal recommended.
DC Current 4-20mA/ 0-20mA FRONT PANEL DESCRIPTION
DC Voltage 0 to 10 V , 0 to 5V , 1 to 5V
Symbol Function
Load resistance
For Current o/p <500Ω It is used to come out from the main or sub
For Voltage o/p >2KΩ menu.
Output accuracy ±0.25% of FS
It is used to select the desired parameter in
Alarm Output various operating Mode. After setting the data
Relays 2 Nos. to proper value, by increment or decrement
Type Single Change over (C, NO, NC) key, it is used to enter the value of the
Temperature Indicator With Alarm selected parameter in memory.
Rating 5A @ 230VAC / 30VDC
SPECIFICATIONS It is used as an acknowledgement key for
Latching of alarm in Run mode.
Loop Power Supply
Input Input
Range Range Supply Voltage 24VDC (±10%) @26mA It is used to increment the parameter for
type type
selection. Value of Parameter can be
E -200.0 to 1000.0 ºC 0-2 V TERMINAL CONNECTION
Communication Details incremented by pressing this key. If the key is
J -200.0 to 1200.0ºC 0.4 – 2V Communication pressed continuously for more than 10 counts
K -200.0 to 1350.0ºC ± 10V Interface RS485 (2 Wire) change, the rate of increment will be made
T -200.0 to 400.0ºC 0-10 V faster. This facility is to allow faster data
Protocol Modbus-RTU
change for higher values.
B 450.0 to 1800.0ºC -10-20mV -19999 to 99999 Baud rate 4800,9600, 19200, 38400 bps
R 0.0 to 1750.0ºC ± 75 mV It is used to decrement the parameter for
Physical selection. Value of parameter can be
S 0.0 to 1750.0°C 0-75 mV
Dimension (H x W x D) mm 48 x 96 x 112 decremented by pressing this key. If the key is
Pt 100 -199.9 to 850.0 C O
0-400Ω
Front Bezel (H x W)mm 48 x 96 pressed continuously for more than 10 counts
4-20 mA 0-6000Ω change, the rate of decrement will be made
Panel Cutout mm 92x 46
0-20 mA -19999 to 99999 Depth Behind Panel mm 100 faster. This facility is to allow faster data
PV Write
0-5 V -19999 to 19999 Weight Approx. 260g. change for higher values. User presses during
Facility
1-5 V Enclosure Material ABS Plastic RUN mode for Thermocouple input it shows
*Use external 250ohms, 0.1% for current Input Enclosure Protection IP 20 ambient value.
Table 1.1 Terminal Cable Size 2.5mm2 LOAD CONNECTION
5 digit 0.56 inch RED Display.
Inputs Display process value. Display parameter
Accuracy Environmental Conditions PV
name when user set parameter. Display error
T/C,RTD & Linear + (0.1% of Full Span ± 1 count) TEMPCO message when an error occurs.
Input to PV Display < 100ppm
Resolution ADC: 17 bits,Display :0.1°C/1Count When alarm occurs respective alarm lamp will
Display to RX < 100ppm AL1
Sampling Rate 4 Samples/Sec on.
Humidity 20% to 95% RH
CJC Error ±2.0 °C
(Non-Condensing) When alarm occurs respective alarm lamp will
Sensor Burnout 0.5uA (Approx.) AL2
Ambient temperature 0 to 55°C on.
current
Storage Temperature 0 to 80°C Electrical precautions during use Tx ON when device is transmitting Data (RS-485).
RTD excitation 0.8mA (Approx.) Electrical noise generated by switching of inductive loads
current Power Supply can create momentary disruption, erratic display, latch up, Rx ON when device is receiving Data (RS-485).
Repeatability 0.05% of FS Standard 85-265VAC/ 100-300VDC
Response time < 1000ms Optional 18-36VDC ORDERING CODE
Power consumption <10 VA
Allowable wiring Maximum 15 ohms/wire (Conductor
resistance for resistance between three wires DIGITAL COMMUNIC- RETRANSMIS-
Isolation (Withstanding voltage) MODEL INPUT POWER SUPPLY
RTD should be equal) INPUT* ATION SION O/P
Between primary terminals* and secondary terminals**:
NMRR > 40 dB 409 1 E F 0-5V N None 85-265VAC/ N NONE N None
At least 1500 V AC for 1 minute U1
CMRR >100 dB Between primary terminals* and grounding terminal: 2 J G 0-10V Y Yes 100-300VDC Y RS485 C 4-20mA
Input Impedance 1MΩ(Approx.) for TC,RTD,0-2V, At least 1500 V AC for 1 minute 3 K H 0-2 V U2 18-36VDC D 0-20mA
0.4-2V,0-75mV, ±75mV,0-400Ω Between grounding terminal and secondary terminals**: 4 T I 0.4 – 2V E 1-5V
220 kΩ for 0-10V, ±10V
At least 1500 V AC for 1 minute 5 B R ±75mV F 0-5V
440 kΩ for 0-5V, 1-5V, 0-6000 Ω
Between secondary terminals**:
250Ω for 0-20mA,4-20mA 6 R U 0-75mV G 0-10V
At least 500 V AC for 1 minute
Max Voltage 20VDC 7 S V 0-400Ω
* Primary terminals indicate power terminals and relay * If Digital input is Yes, Retransmission o/p is not possible.
Display & Keys output terminals. 9 PT-100 W 0-6000Ω
PV Display 5-Digit, 7-Segment, 0.56” High, Red ** Secondary terminals indicate analog I/O signal and C 4-20 mA M Serial RS 485# # When Serial input type is selected, RS485 o/p needs to be selected.
Status Individual RED Led for Alarm & Communication O/P.
D 0-20mA S Special
Indication Communication Status Insulation resistance: 20MΩ or more at 500 V DC
E 1-5V
Keys Menu, Enter, Increase, Decrease between power terminals and grounding terminal.