0% found this document useful (0 votes)
40 views

Test Results: Title: Measurement Fault Calculator

The document contains test results from a fault calculator assessing overcurrent protection parameters. It performed 8 tests of phase and 3-phase faults at various current levels relative to the 51 and 50 protection elements to check tripping times. All tests passed within the expected time ranges.

Uploaded by

imu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views

Test Results: Title: Measurement Fault Calculator

The document contains test results from a fault calculator assessing overcurrent protection parameters. It performed 8 tests of phase and 3-phase faults at various current levels relative to the 51 and 50 protection elements to check tripping times. All tests passed within the expected time ranges.

Uploaded by

imu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Test Results

Title: Measurement
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1.000 A 0.00 ° 50.000 Hz
I L2 1.000 A -120.00 ° 50.000 Hz
I L3 1.000 A 120.00 ° 50.000 Hz
Generator Settings
I L1 1.000A 0.00° +90°
I L3

I L1
180° 0°

I L2
1.0 A -90°
I L2 1.000A -120.00°
I L3 1.000A 120.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0->1 5.047s
Bin. in 2 1->0 n/a
Overload 1->0 n/a

Analog Inputs
VDCin IDCin
0.0001V 0.0000mA
.
Comment
IA=798.9A IB=798.7A IC=798.7A

. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 16-Mar-2019 10:53:57
Title: OC Pickup
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 501.0 mA 0.00 ° 50.000 Hz
I L2 501.0 mA -120.00 ° 50.000 Hz
I L3 501.0 mA 120.00 ° 50.000 Hz
Generator Settings
I L1 0.501A 0.00° +90°

I L3
I L1
180° 0°

I L2

600.0 mA-90°
I L2 0.501A -120.00°
I L3 0.501A 120.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0
Bin. in 2 0
Overload 0

Analog Inputs
VDCin IDCin
0.0000V 0.0001mA
.
Comment
I=501mA
. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 16-Mar-2019 10:56:17
Title: OC Drop-Off
.
Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 478.0 mA 0.00 ° 50.000 Hz
I L2 478.0 mA -120.00 ° 50.000 Hz
I L3 478.0 mA 120.00 ° 50.000 Hz
Generator Settings
I L1 0.478A 0.00° +90°
I L3

I L1
180° 0°

I L2

500.0 mA-90°
I L2 0.478A -120.00°
I L3 0.478A 120.00°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0
Binary Inputs
Name Slope Time
Trip 0
Bin. in 2 0
Overload 0

Analog Inputs
VDCin IDCin
0.0001V 0.0001mA
.
Comment
I=479mA
. .
Synchronized mode (Synchronization to external signal failed)
. . . .
Assessment
Passed 16-Mar-2019 10:57:23

Comment
Summary
3 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

51/50:
Test Object - Overcurrent Parameters
.
General - Values:
TimeTolAbs: 0.04 s VT connection: n/a
TimeTolRel: 5.00 % CT starpoint connection: n/a
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: No

.
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes 51 IEC Normal Inverse 0.50 Iref 0.50 0.95 Non Directional
Yes 50 IEC Definite Time 2.00 Iref 0.10 s 0.95 Non Directional

. .
Test Module
Name: OMICRON Overcurrent Version: 3.20
Test Start: 16-Mar-2019 11:12:54 Test End: 16-Mar-2019 11:13:41
User Name: Manager:
Company:

Test Settings:
.
Fault Model:
Time reference: Fault inception
Load current: 0.000 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 8.000 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: No
Fault voltage LN (for all but two phase faults): n/a
Fault voltage LL (for two phase faults): n/a
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: No
Thermal reset method: n/a
Thermal reset message: n/a
.
Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2 51 2.000 1.000 A n/a 5.015 s 4.448 s 5.689 s
L2-L3 51 2.000 1.000 A n/a 5.015 s 4.448 s 5.689 s
L3-L1 51 2.000 1.000 A n/a 5.015 s 4.448 s 5.689 s
L1-L2-L3 51 2.000 1.000 A n/a 5.015 s 4.448 s 5.689 s
L1-L2 51 3.000 1.500 A n/a 3.151 s 2.865 s 3.472 s
L2-L3 51 3.000 1.500 A n/a 3.151 s 2.865 s 3.472 s
L3-L1 51 3.000 1.500 A n/a 3.151 s 2.865 s 3.472 s
L1-L2-L3 51 3.000 1.500 A n/a 3.151 s 2.865 s 3.472 s
L1-L2 50 1.500 3.000 A n/a 100.0 ms 60.00 ms 140.0 ms
L2-L3 50 1.500 3.000 A n/a 100.0 ms 60.00 ms 140.0 ms
L3-L1 50 1.500 3.000 A n/a 100.0 ms 60.00 ms 140.0 ms
L1-L2-L3 50 1.500 3.000 A n/a 100.0 ms 60.00 ms 140.0 ms
.
Binary Outputs:
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0

Binary Inputs:
Trigger Logic: And
Name Trigger State
Trip 1
Bin. in 2 X
.
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2 51 2.000 1.000 A n/a 5.015 s 5.047 s 655.8 m % No Passed
L2-L3 51 2.000 1.000 A n/a 5.015 s 5.046 s 629.9 m % No Passed
L3-L1 51 2.000 1.000 A n/a 5.015 s 5.047 s 647.8 m % No Passed
L1-L2-L3 51 2.000 1.000 A n/a 5.015 s 5.046 s 625.9 m % No Passed
L1-L2 51 3.000 1.500 A n/a 3.151 s 3.176 s 778.6 m % No Passed
L2-L3 51 3.000 1.500 A n/a 3.151 s 3.173 s 708.8 m % No Passed
L3-L1 51 3.000 1.500 A n/a 3.151 s 3.173 s 686.6 m % No Passed
L1-L2-L3 51 3.000 1.500 A n/a 3.151 s 3.173 s 686.6 m % No Passed
L1-L2 50 1.500 3.000 A n/a 100.0 ms 118.1 ms 18.10 % No Passed
L2-L3 50 1.500 3.000 A n/a 100.0 ms 117.9 ms 17.90 % No Passed
L3-L1 50 1.500 3.000 A n/a 100.0 ms 116.1 ms 16.10 % No Passed
L1-L2-L3 50 1.500 3.000 A n/a 100.0 ms 117.8 ms 17.80 % No Passed
.
Charts for Fault
Types:
Type Angle
L1-L2 n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

0.5 0.7 1.0 2.0 3.0 5.0 7.0 10.0


I/A

.
Charts for Fault
Types:
Type Angle
L2-L3 n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

0.5 0.7 1.0 2.0 3.0 5.0 7.0 10.0


I/A

.
Charts for Fault
Types:
Type Angle
L3-L1 n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

0.5 0.7 1.0 2.0 3.0 5.0 7.0 10.0


I/A

.
Charts for Fault
Types:
Type Angle
L1-L2-L3 n/a
10000.00

1000.00

100.00
t/s

10.00

1.00

0.10

0.5 0.7 1.0 2.0 3.0 5.0 7.0 10.0


I/A

.
State:
12 out of 12 points tested.
12 points passed.
0 points failed.

General Assessment: Test passed!