This document provides instructions for setting up a PLC and HMI to enable downloading G-code files to a 20PM controller via RS485 communication. Key steps include configuring the PLC for Modbus RTU communication at 115200 bps, enabling PEP protection for register O100, and selecting the "Delta PM RTU" protocol in the HMI controller. Supported HMI models are listed. The G-code download element allows selecting and downloading supported NC or FGC file formats to station numbers 1 through 255 using the configured COM port.

Uploaded by

Thiago Garcia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
107 views

20PM G-Code Download Function Instruction PLC Setting

This document provides instructions for setting up a PLC and HMI to enable downloading G-code files to a 20PM controller via RS485 communication. Key steps include configuring the PLC for Modbus RTU communication at 115200 bps, enabling PEP protection for register O100, and selecting the "Delta PM RTU" protocol in the HMI controller. Supported HMI models are listed. The G-code download element allows selecting and downloading supported NC or FGC file formats to station numbers 1 through 255 using the configured COM port.

Uploaded by

Thiago Garcia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

20PM G-Code Download Function Instruction

PLC Setting
1 In this document, HMI and PLC all use COM2 RS485 for communication.
2 G-Code download function only support RTU mode, so you need to change PLC
communication setting first.
2.1 Open PMSoft
2.2 Set 20PM COM2 to Modbus RTU, 115200, 8, N, 1 as follow command.

Notice:When using RTU mode, communication data length must be 8, don’t use 7.
2.3 Enable PEP protection for O100.

 
2.4 Download program to 20PM and enable ”Apply PEP setting”。

2.5 Re-power 20PM after download.

HMI 設定
1. 20PM G-Code download function only supports DOP-B07PS415 and DOP-B07PS515 at this
time.
2. HMI controller must select ”Delta PM RTU”.

3. Choose G-Code folder in Element Bank


4. There are 2 elements in the G-Code folder, follow are explanation of elements.

(1) G-Code file manager


This element only provide preview and select file function. The button in the red square doesn’t
work now.
(2) G-Code download
After select the G-code file, use this element to execute G-code download process.

Supported station number range is 1~255;

COM must set same as the Delta PM RTU setting in the Communication setting.

(3) G-Code supported format


Support nc and fgc format now.