Smart Thermostats: An Experimental Facility To Test Their Capabilities and Savings Potential
Smart Thermostats: An Experimental Facility To Test Their Capabilities and Savings Potential
Article
Smart Thermostats: An Experimental Facility to Test
Their Capabilities and Savings Potential
Sergio Bustamante ID
, Pablo Castro ID
, Alberto Laso, Mario Manana ∗ ID
and Alberto Arroyo
School of Industrial Engineering, University of Cantabria, Av. Los Castros s/n, 39005 Cantabria, Spain;
[email protected] (S.B.); [email protected] (P.C.); [email protected] (A.L.);
[email protected] (A.A.)
* Correspondence: [email protected]
Abstract: The European Commission has explained how heating and cooling in buildings and
industry account for half of the energy consumption of the EU. Several studies explain how to
achieve an energy saving at home, and the use of smart thermostats will help to reduce energy
consumption while increasing the efficiency of households. In this article, a comparative evaluation
was carried out between four smart thermostats that are now on the market, whose characteristics
vary in terms of price, precision of measurements and set temperature, algorithms, etc. A thermal test
chamber was designed and constructed from a refrigerator, a thermal blanket, a Raspberry Pi and
the necessary electronic components for its control and data collection. From the tests carried out in
the thermal chamber, data on the operation of the four thermostats such as the maintenance and the
anticipation of the setpoint temperature, were obtained. It was necessary to run the system enough
times for each thermostat to memorize the housing characteristics, such as its inertia and its thermal
insulation. This would also allow for the generation of a better algorithm to regulate the temperature,
which would create a lower oscillation with respect to the setpoint temperature. The learning of the
thermostats was not demonstrated and for the anticipation mode it was seen that the thermostats
failed to improve or learn in this aspect, as they did not improve the start-up times of the heating
system, with the consequent increase in energy consumption.
1. Introduction
The European Commission [1,2] has explained how heating and cooling in buildings and industry
account for half of the energy consumption of the EU. Heating and hot water in households alone
account for 79% of the total energy use (192.5 Mtoe: million tonnes of oil equivalent). Cooling
represents a fairly small share of the total energy use. A total of 84% of heating and cooling is still
generated from fossil fuels while only 16% is generated from renewable energy.
New opportunities for bigger and smarter control of the main building parameters, such as
ventilation or temperature, are emerging which lead to more comfortable and efficient environments
both in workplaces and homes [3].
Consumers may decide to install a smart thermostat in their homes to achieve savings in the
electric or gas bill [4], but the choice is not always the right one. As will be shown in this article, not all
smart thermostats have a similar operation. In addition, in different smart thermostats, neither the
same comfort or energy savings are obtained.
In this article, a comparative evaluation was carried out between four smart thermostats that are
now on the market, whose characteristics vary in terms of price, precision of measurements and set
temperature, algorithms, etc. These smart thermostats, according to their websites, produce savings of
between 30 and 37% in the energy bill.
In order to carry out the evaluation of smart thermostats, it was deemed appropriate to start from
scratch, since neither a study dealing with the behaviour or learning of smart thermostats, nor a study
evaluating the accuracy of the thermostats had previously been done. It was necessary to carry out the
tests in the most real conditions possible in order to assess their functionalities, their learning curves,
and even their efficiency. To generate these “real” conditions, a thermal test chamber was designed
and constructed from a refrigerator, a thermal blanket, a Raspberry Pi [5] and the necessary electronic
components for its control and data collection. The chamber was managed by the thermostats, so
a system similar to a home was generated, in which its characteristics could be varied, such as its
thermal inertia.
The thermal chamber system was designed in a modular way, so that the elements of both cooling
and heating could be changed, and thus, making small changes in the programming of the electronic
components would create a new thermal chamber with other basic characteristics, such as higher
power or dimensions.
The setpoint temperatures for the tests were obtained from [6,7] and the recommendations of the
manufacturers of the smart thermostats. The periods of the setpoint temperatures were established for
a weekday operation, with some increase in the time of one of them to better observe the operation of
the thermostat. Geolocation features were deactivated because their functionality is already known
and it was not necessary for this evaluation.
2. State-Of-The-Art
A good review of the challenges and opportunities of the new smart home technologies is by
G. Lobaccaro et al. [8], focusing on the wide and flexible ways of adding smart technologies to the
daily routine of households.
One of the most critical points in maintaining comfort and increasing efficiency is the temperature
control. Many efforts in research and industrial development move towards the design and
manufacturing of cheap, friendly and easy-to-use smart thermostats. P. Rau et al. presented a
study of the needs of these thermostats obtained from interviews and surveys of the consumers [9],
noticing that there are still unsolved problems in the hardware and technology on this type of devices
and advising the researchers and designers to focus on the user’s needs. Some other reviews and
detailed studies of modern thermostats can be specified [10,11] which indicate that a lot of work still
has to be done in order to clearly see the benefits of this smart management of temperature.
Several studies [6,12] carried out tests and simulations in which the setpoint temperatures were
varied to explain how to achieve energy savings at home, even integrating algorithms that took into
account the variation of the daily price of electricity. Therefore, the use of smart thermostats will help
to reduce energy consumption while increasing the efficiency of households.
There are also several Smart Thermostat Pilot Programs [13–19] in which a thermostat was
installed in a specific number of homes with a specific heating or cooling system and at the end of the
study the savings achieved by the users were observed. On the one hand, neither the behaviour nor
the learning ability of the thermostats can be obtained from these studies. On the other hand, it cannot
be 100% assured that users have properly used the thermostats during the study, so the results, both
savings and comfort, may not be completely correct.
There is a lack of laboratory-controlled tests, apart from those made by the manufacturers. Also,
the general perception from the user’s answers in the surveys and interviews shows the difficulty of
knowing the real savings coming from the use of smart thermostats [9,11]. These were the original
motivations of this new research.
With this study, the authors try to clarify, to some extent, the capacities and limitations of several
smart thermostats, which are now on the market, quantifying their accuracy and their learning
capability in a controlled facility built for this purpose.
Sustainability 2017, 9, 1462 3 of 18
The geolocation function allows the smart thermostat to turn heating on/off depending on the
distance of users to their home. Although it is a functionality to be taken into account, in this article
this functionality was not used because it was desired that the thermostats worked according to a daily
program and because not all the thermostats possessed it.
Once the components were connected, the operation of the thermal chamber managed by the
Raspberry Pi 3 was divided into three sections. The first one corresponds to the measurements of the
inside temperature by the Pt100 probes. The second one is responsible for turning on/off the heating
and cooling systems of the chamber, and finally, the third section is responsible for obtaining the
working data of the previous sections. The sections listed above are shown in the operating diagram
of Figure 1.
At the top of the operating diagram (as seen in Figure 1), the temperature measurement inside the
chamber is controlled. The transformer supplies the transducer (12 VDC) and the operational amplifier
(±12 VDC). The transducer is responsible for measuring the resistance of the probes depending on the
temperature and transforms it to voltage values between 0 and 10 V at their outputs. The transducer
was calibrated using a Pt100 platinum resistance simulator with resistance values of 108.57, 107.79 and
107.02 Ω which belongs to and was calibrated by the Spanish Metrology Center (CEM). As the analog
to digital converter can only read voltages between 0 and 5 V, it has been necessary to incorporate
the 4-channel operational amplifier, in order to divide the output voltage of the transducer by half.
The digital values obtained by the converter are sent to the Raspberry Pi.
Sustainability 2017, 9, 1462 5 of 18
At the bottom of the operating diagram (as seen in Figure 1), the elements that manage the heating
and cooling system of the chamber are located. The thermostat evaluated in each case is the one that
measures the temperature inside the chamber and, depending on what it measures and the established
setpoint temperature, it closes or opens its internal relay causing a variation in the reading of one of
the inputs (0–1). This variation is registered in the Raspberry Pi which, depending on its value, turns
on the cooling or the heating system through the system relays.
At the same time as the previous action, the Raspberry Pi is responsible for turning on/off the
LED indicators of the window, as well as showing the temperature values inside the chamber through
the LCD.
The other thermostats can also work and be compared, with the difference that they do not tell
the Raspberry Pi what to do with the thermal systems. At the same time, the Raspberry Pi records
and stores the variations of its relays in a file, generates the data and manages the LED indicators
corresponding to each thermostat.
The final location of the components of the thermal test chamber inside a fuse box is shown in
Figure 2. It was done in this way so that the electronic part of the chamber was more protected and at
the same time accessible.
Figure 3 shows the elements designed to observe in real time some of the data that the system
can obtain. They were located in the window of the fuse box cover so that its visualization was more
accessible, simple and fast, without needing to access the data files.
Sustainability 2017, 9, 1462 6 of 18
The software developed for the operation of the thermal chamber consisted of several scripts
programmed in Python, one of the programming languages used by Raspberry Pi.
The main script was responsible for managing the thermal chamber as a function of the main
thermostat and obtaining the temperature inside. This script was composed of a while loop, in which
each loop read the voltage data pertaining to the Pt100 probes and through the programmed calibration
curves obtained the corrected temperature values. As for the management of the camera, the loop
took into account the states of the thermostats (open/closed), and depending on the state of the main
thermostat, turned on/off the cooling or the heating system. The LEDs located in the window of the
fuse box cover also showed these states through on/off. Finally, this script created a file in which it
wrote in each loop all the data and the states of the thermostats and the systems of refrigeration and
heating that were obtained.
The second most important script was responsible for displaying the temperature data through
the display in the window of the fuse box cover. This script was composed of a while loop, which read
the file generated in the script described above, and extracted the temperature data from the Pt100
probes and displayed them. The rest of the scripts fulfilled secondary functions and were called by the
main scripts.
This software was specifically programmed for this test facility using open sources which makes
it easy to re-adapt to new research interests or thermal environments. Moreover, all the hardware was
built in a modular way with cheap electronic components.
Table 2. Data collection generated from the excel file obtained from the thermal chamber.
Upper Lower
Uncalibrated Uncalibrated
Probe Probe
Day Hour Upper Probe Lower Probe t1 t2 t3 t4 Heat Cold
Temp. Temp.
Temp. (◦ C) Temp. (◦ C)
(◦ C) (◦ C)
22 February 2017 11:07:02 18.230 17.551 16.594 16.380 1 1 1 0 1 0
22 February 2017 11:07:07 18.278 17.647 16.642 16.474 1 1 1 0 1 0
22 February 2017 11:07:12 18.326 17.695 16.689 16.521 1 1 1 0 1 0
22 February 2017 11:07:17 18.374 17.744 16.737 16.568 1 1 1 0 1 0
22 February 2017 11:07:22 18.422 17.840 16.785 16.662 1 1 1 0 1 0
22 February 2017 11:07:28 18.470 17.888 16.833 16.709 1 1 1 0 1 0
22 February 2017 11:07:33 18.470 17.936 16.833 16.756 1 1 1 0 1 0
22 February 2017 11:07:38 18.518 17.985 16.881 16.803 1 1 1 0 1 0
22 February 2017 11:07:43 18.566 18.081 16.929 16.897 1 1 1 0 1 0
22 February 2017 11:07:48 18.614 18.129 16.977 16.944 1 1 1 0 1 0
22 February 2017 11:07:48 18.614 18.129 16.977 16.944 0 1 1 0 0 1
22 February 2017 11:07:53 18.661 18.177 17.025 16.992 0 1 1 0 0 1
Temperature data of the thermostats was obtained in two different ways depending on the
characteristics of each thermostat. One of the thermostats allows downloading the data through its
website but the other thermostats do not have this possibility, so the data collection must be manual;
observing the temperature variation in the thermostat display, on their websites or in their Smartphone
applications.
From the data obtained by the thermal chamber, as seen in the Table 2, and the temperature data
of the thermostats, the graphs of temperature and state of the thermostats versus time were generated
(as seen in Figure 4). The terms “Upper Probe” and “Lower Probe” refer to the two Pt100 probes
installed inside the thermal test chamber. These probes are located above and below the thermostats.
Figure 4. Graph created from the data obtained from the thermal chamber and the data downloaded
from thermostat 1.
Sustainability 2017, 9, 1462 8 of 18
• Comfortable: 19 ◦ C.
• Night: 17 ◦ C.
• Eco: 16 ◦ C.
In the second test performed, the behaviour of the thermostats during a whole day was studied.
The maximum and minimum temperatures obtained during the day were evaluated and a comfort
evaluation was carried out.
The heating time was also measured during the tests and a comparison of each thermostat heating
time was made.
The setpoint temperatures used are the same as those of the previous test, and the time periods
that have been established throughout the day are shown in Figure 5. These established periods were
introduced manually, as it was desired that all thermostats should start from an initial daily schedule.
Table 3 shows the data obtained from the test performed. The maximum and minimum
temperatures detected by the sensors of each of the thermostats and the maximum and minimum
temperatures of the Pt100 probes of each case tested are shown.
The last four columns show the difference between the maximum and minimum temperatures
of the Pt100 probes and the thermostats and the difference between the maximum and minimum
temperatures of the Pt100 probes and the setpoint temperature set for each case.
The thermostat with the most accurate temperature sensor was Thermostat 3, which had a
maximum difference between the actual temperature and the temperature measured by its sensor of
0.33 ◦ C above the setpoint temperature, and 0.96 ◦ C below it. Closely following it was Thermostat 4,
where the temperature difference was 1.05 ◦ C in the first case, and 1.15 ◦ C in the second.
The other two thermostats gave higher differences. Thermostat 1 obtained a maximum difference
of 2.08 ◦ C above the setpoint and 1.65 ◦ C below, while Thermostat 2 obtained 3.92 ◦ C above and
0.83 ◦ C below the setpoint.
The thermostat that best set the setpoint temperature was Thermostat 3, followed closely by
Thermostat 4. Thermostat 3 maintained the maximum actual temperature of 1.22 ◦ C above and 0.67 ◦ C
below the setpoint. The results for the Thermostat 4 were very similar when the temperature was above
the setpoint, 1.55 ◦ C, but higher differences were observed when below, with 1.65 ◦ C of temperature
difference.
Thermostats 1 and 2, as in the previous case, move away from thermostats 3 and 4, sometimes
reaching a difference of 3.08 ◦ C in the case of thermostat 1, and of 6.56 ◦ C in the case of Thermostat 2.
Sustainability 2017, 9, 1462 10 of 18
Figure 7. Graphs of temperature and heating system operation during a full day testing.
(a) Thermostat 1 Algorithm 1. (b) Thermostat 1 Algorithm 2. (c) Thermostat 2. (d) Thermostat 3.
(e) Thermostat 4.
Sustainability 2017, 9, 1462 12 of 18
Table 4. Results of actual maximum, minimum and average temperatures of the tests of a full-day
testing of thermostats.
Thermostat 1 Algorithm 1 24.33 14.47 17.34 23.00 15.35 17.77 21.85 17.47 19.52
Thermostat 1 Algorithm 2 25.56 15.79 18.44 23.51 16.03 18.53 23.60 17.92 20.18
Thermostat 2 22.03 14.38 17.16 22.37 15.09 18.31 25.15 14.47 19.71
Thermostat 3 21.07 15.8 18.16 20.78 16.66 17.93 20.92 18.58 19.63
Thermostat 4 23.29 14.90 17.45 22.27 15.88 17.67 21.30 18.08 19.65
Table 5 shows the total and partial operating times of the heating system. It can be observed
how the operating times obtained by Thermostats 1 (Algorithm 2), 3 and 4, were very similar, the first
being Thermostat 1, with a total time of 5h18min, compared to 5h37min and 5h30min obtained by the
other two.
Table 5. Results of partial and total heating system operating times of full-day testing of thermostats.
Table 6 shows the total time and percentage of the day in which the temperature was higher and
lower than the setpoint. Thermostats 1 (Algorithm 2) and 3 were the ones with longer times over the
setpoint temperature.
Table 7 divides the times and percentages of Table 6 into two to indicate how much time and what
percentage of the day the temperature was found in deviations greater or less than 1 ◦ C both above
and below the setpoint temperature. Observing the partial percentage of the deviation greater than
1 ◦ C below setpoint temperature, it is noted that Thermostat 3 had 0% in this section, meaning that it
always maintained the temperature with a deviation less than 1 ◦ C. Thermostats 4 and 1 (Algorithm 2)
were very close, having 0.29% and 0.22% respectively.
This is a good indicator, but, as Table 8 will later show, it is not the best indicator to establish which
thermostat is the best in terms of comfort. Taking into account the time in which the temperature was
found below the setpoint, obviously Thermostats 1 (Algorithm 2) and 3, followed by the Thermostat 4,
were the ones with the best times.
Sustainability 2017, 9, 1462 13 of 18
Table 6. Results of times and total percentages in which the temperature was higher or lower than the
setpoint temperature in the tests of a full day of operation of the thermostats.
14:58:36 9:01:24
Thermostat 1 Algorithm 1
62.40% 37.6%
21:03:00 2:57:00
Thermostat 1 Algorithm 2
87.71% 12.29%
15:23:03 8:36:57
Thermostat 2
62.34% 37.66%
21:20:41 2:39:19
Thermostat 3
88.94% 11.06%
17:05:16 6:54:44
Thermostat 4
71.20% 28.80%
Table 7. Results of times and percentages in which the deviation temperature was above and below
1 ◦ C of the setpoint temperature in the tests of a full day of operation of the thermostats.
In Table 8, the central columns of Table 7 were joined in a single column, showing the time and
percentage of time in which the temperature deviated less than 1 ◦ C both above and below the setpoint
temperature (comfort range).
In this case, the best thermostat was Thermostat 4, which remained in the comfort range 14 h
and 13 min, or 59.29% of the day. The next thermostat was Thermostat 3, with 13h17min (55.35%).
Thermostat 1, with its two algorithms, was in the comfort range less than 50% of the time in both cases.
Algorithm 1 was superior to algorithm 2, with a time of 11h32min versus 9h13min. Thermostat 2,
meanwhile, kept the temperature in this range 33.46% of the day, which made it the worst of the four
thermostats in terms of comfort.
Sustainability 2017, 9, 1462 14 of 18
Table 8. Time and percentage in which the temperature has been found within a range of ±1 ◦ C of
setpoint temperature.
In Figure 8, the Gaussian bells created from the temperature data of the periods with the same
setpoint temperature are observed (a, b, c). Figure 8 also shows the temperature deviations obtained
over a day of operation of each thermostat (d).
The Gaussian bells of Thermostats 3 and 4 are narrower and higher, indicating that the greatest
percentage of their deviation is in a very small range. In the other three tests, the Gaussian bells
of Thermostats 1 (Algorithm 1 and 2) and 2 are lower and wider, so the temperature range of their
deviations is much greater.
Figure 8. Gauss bell of the deviation of the temperature in each one of the cases of setpoint temperature
(16, 17 and 19 ◦ C) (a–c) and temperature deviation with respect to the setpoint temperatures during the
tests of a day of operation (d).
Sustainability 2017, 9, 1462 15 of 18
In Figure 9, the temperature deviation data is shown as histograms of each of the thermostats
tested. Thermostats 1 (Algorithm 2), 3 and 4 had the highest frequencies in the deviations closest to
0 ◦ C, as expected. In the histogram of Thermostat 3, the frequencies of the deviation between 3 and
5 ◦ C increase, due to the anticipation of the ignition of the heating system, as mentioned above.
Figure 9. Histograms of the temperature deviation during the tests performed. (a) Thermostat 1
Algorithm 1. (b) Thermostat 1 Algorithm 2. (c) Thermostat 2. (d) Thermostat 3. (e) Thermostat 4.
Table 9 shows the heating time due to the anticipation mode in the periods prior to 19 ◦ C, which
were the periods in which this mode was activated. As shown, the thermostats with shorter heating
times due to the anticipation mode were Thermostat 1 with its two algorithms and Thermostat 4.
Thermostat 3, as it entered this mode before the others, maintained the heating system for more time,
which led to lower energy efficiency. Thermostat 2, as it does not have this mode, decreased the
comfort of the house.
Table 9. Heating system operating time due to the temperature anticipation mode in each of the periods
prior to 19 ◦ C.
From Figure 7, Thermostats 1 and 4 started the anticipation mode between 30 and 45 min before
the 19 ◦ C period, while Thermostat 3 started between 1h and 1h45min before. This time did not
decrease during the test which would have improved their efficiency, possibly because it is fixed or it
is the minimum to activate the anticipation mode.
Thus, taking into account energy efficiency, the three thermostats that have the anticipation
mode failed, and it is a point that should be improved by the manufacturers of thermostats. For now,
the activation of the anticipation mode belongs to the end users, who will choose comfort or efficiency
depending on their needs.
5. Conclusions
In this study, four smart thermostats were tested to check their main characteristics. A thermal
test chamber was built to recreate the housing heating and cooling and to plot and record the main
output data.
From the tests carried out in the thermal chamber, data on the operation of the four thermostats,
such as the maintenance and the anticipation of the setpoint temperature, were obtained. It was
necessary to run the system enough times for each thermostat to memorize the housing characteristics,
such as its inertia and its thermal insulation. This would also allow for the generation of a better
algorithm to regulate the temperature, which would create a lower oscillation with respect to the
setpoint temperature.
From the comparative evaluation done, it was clearly seen that Thermostats 3 and 4 were the ones
that obtained the best results in the tests performed. Each of them was slightly better than the other in
some respect, i.e., Thermostat 3 was more accurate when it came to displaying the actual temperature,
while Thermostat 4 kept the temperature in a range much closer to the setpoint temperature.
Thermostat 1, once it learned the characteristics of the housing (in this case, the thermal test
chamber) and started using algorithm 2, obtained very similar results to those of Thermostats 3 and 4.
In last place was Thermostat 2, whose results have always been very far from the ideal ones.
The lack of temperature anticipation and the large recording time intervals (5 min), had seriously
penalized it in the tests performed.
The learning of the thermostats was not demonstrated due to the minimal interaction with the
user since they always worked with established guidelines. As for the anticipation mode, it was
Sustainability 2017, 9, 1462 17 of 18
demonstrated that the thermostats failed to improve or learn in this aspect, as they did not improve
the start-up times of the heating system, with the consequent increase in energy consumption.
Acknowledgments: This work was supported by the Spanish Government under the R+D initiative INNPACTO
with reference IPT-2011-1447-920000, Spanish R+D initiative with reference ENE-2013-42720-R and RETOS
RTC-2015-3795-3. The authors also acknowledge Viesgo for its support.
Author Contributions: All authors contributed equally to this work.
Conflicts of Interest: The authors declare no conflict of interest.
Abbreviations
The following abbreviations are used in this manuscript:
References
1. European Comission. An EU Strategy on Heating and Cooling, 51 Final. Available online: https://ec.europa.
eu/energy/sites/ener/files/documents/1._EN._ACT._part1._v14.pdf (accessed on 9 August 2017).
2. European Comission. EU Reference Scenario 2016—Energy, Transport and GHG Emissions—Trends to
2050. Available online: http://pure.iiasa.ac.at/13656/1/REF2016._report._FINAL-web.pdf (accessed on
9 August 2017).
3. Shahzad, S.S.; Brennan, J.; Theodossopoulos, D.; Hughes, B.; Calautit, J.K. Building-Related Symptoms,
Energy, and Thermal Control in the Workplace: Personal and Open Plan Offices. Sustainability 2016, 8, 331,
doi:10.3390/su8040331.
4. CLEAResult. Opportunities for Home Energy Management Systems (HEMS) in Advancing Residential
Energy Efficiency Programs. Available online: http://www.neep.org/opportunities-home-energy-
management-systems-hems-advancing-residential-energy-efficiency-programs (accessed on 9 August 2017).
5. Raspberry Pi Foundation. Available online: https://www.raspberrypi.org/ (accessed on 22 November 2016).
6. Manning, M.M.; Swinton, M.C.; Szadkowski, F.; Gusdorf, J.; Ruest, K. The effects of thermostat set-back and
set-up on seasonal energy consumption, surface temperatures and recovery times at the CCHT Twin House
Facility. ASHRAE Trans. 2007, 113 Pt 1, 1–12.
7. Energy Star. A Guide to Energy-Efficient Heating and Cooling. Available online: www.energystar.gov/ia/
partners/publications/pubdocs/HeatingCoolingGuide%20FINAL_9-4-09.pdf (accessed on 9 August 2017).
8. Lobaccaro, G.; Carlucci, S.; Löfström, E. A Review of Systems and Technologies for Smart Homes and Smart
Grids. Energies 2016, 9, 348, doi:10.3390/en9050348.
9. Rau, P.-L.P.; Gong, Y.; Huang, H.-J.; Wen, J. A Systematic Study for Smart Residential Thermostats: User
Needs for the Input, Output, and Intelligence Level. Buildings 2016, 6, 19, doi:10.3390/buildings6020019.
10. Sönmez, D.; Dinçer, K. A Review of Modern Residential Thermostats for Home Automation to Provide
Energy Efficiency. In Proceedings of the 2016 4th International Istanbul Smart Grid Congress and Fair (ICSG),
Istanbul, Turkey, 20–21 April 2016; pp. 1–4, doi:10.1109/SGCF.2016.7492430.
11. Yang, R.; Newman, M.W. Learning from a learning thermostat: Lessons for intelligent systems for the home.
In Proceedings of the 2013 ACM International Joint Conference on Pervasive and Ubiquitous Computing,
Zurich, Switzerland, 8–12 September 2013; doi:10.1145/2493432.2493489.
12. Zhang, D.; Zeng, P.; Zhang, Y.; Li, S. An Integrative Study of Home Energy Management for Residential
Energy Consumers. In Proceedings of the 5th Annual IEEE International Conference on Cyber Technology
in Automation, Control and Intelligent Systems, Shenyang, China, 8–12 June 2015.
Sustainability 2017, 9, 1462 18 of 18
13. Aarish, C.; Perussi, M.; Rietz, A.; Korn, D. Evaluation of the 2013–2014 Programmable and Smart Thermostat
Program. Available online: http://www.cadmusgroup.com/wp-content/uploads/2015/06/Cadmus.
_Vectren._Nest._Report._Jan2015.pdf?submissionGuid=c8eda45b-2759-4a31-90e3-d2ecdb9001de (accessed
on 9 August 2017).
14. Aarish, C.; Rietz, A.; Perussi, M.; Higgins, K.; Horvath, Z.; Reynolds, A. Evaluation of 2013–2014 Smart
Thermostat Pilots: Home Energy Monitoring, Automatic Temperature Control, Demand Response. Available
online: http://www.cadmusgroup.com/wp-content/uploads/2016/05/Cadmus._ATC._HEM._Report.
_FINAL._revised._Sep._2015.pdf (accessed on 9 August 2017).
15. Apex Analytics LLC. Nest Thermostat Heat Pump Control—Pilot Evaluation Findings. Available online:
https://nest.com/downloads/press/documents/energy-trust-of-oregon-pilot-evaluation-whitepaper.
pdf (accessed on 9 August 2017).
16. Apex Analytics, LLC. Smart Thermostat Pilot Evaluation. Available online: http://assets.energytrust.org/
api/assets/reports/Smart._Thermostat._Pilot._Evaluation-Final._wSR.pdf (accessed on 9 August 2017).
17. Aarish, C.; Rietz, A.; Perussi, M.; Higgins, K.; Horvath, Z.; Reynolds, A. Wi-Fi Programmable
Controllable Thermostat Pilot Program Evaluation. Available online: http://ma-eeac.org/wordpress/
wp-content/uploads/Wi-Fi-Programmable-Controllable-Thermostat-Pilot-Program-Evaluation._Part-
of-the-Massachusetts-2011-Residential-Retrofit-Low-Income-Program-Area-Study.pdf (accessed on
9 August 2017).
18. Aarish, C.; Jones, C. Smart Thermostats and the Triple Bottom Line: People, Planet, and Profits.
In Proceedings of the ACEEE Summer Study on Energy Efficiency in Buildings, Pacific Grove, CA, USA,
21–26 August 2016.
19. CLEAResult. Smart thermostats, CLEAResult for Commonwealth Edison. Available online:
http://ilsagfiles.org/SAG._files/Meeting._Materials/2015/6-23-15._Meeting/CLEAResult._Smart.
_Thermostat._WhitePaper._20150505.pdf (accessed on 9 August 2017).