0% found this document useful (0 votes)
236 views2 pages

Engineering and Development Corporation of The Philippines: H P H P

The document summarizes the design of purlins for the roof of a proposed 14.2MW powerhouse. It includes input data on dimensions and loads. Normal and tangential loads per meter are calculated from dead, live and wind loads. Load combinations are considered. A trial purlin section of LC 220 X 75 X 25 X 5 mm is analyzed and found to be adequate. Sag rods of 10mm diameter are designed to resist the calculated load of 3018 N.

Uploaded by

mark ignacio
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
236 views2 pages

Engineering and Development Corporation of The Philippines: H P H P

The document summarizes the design of purlins for the roof of a proposed 14.2MW powerhouse. It includes input data on dimensions and loads. Normal and tangential loads per meter are calculated from dead, live and wind loads. Load combinations are considered. A trial purlin section of LC 220 X 75 X 25 X 5 mm is analyzed and found to be adequate. Sag rods of 10mm diameter are designed to resist the calculated load of 3018 N.

Uploaded by

mark ignacio
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PROJECT : DED of Proposed 14.

2MW Addalam HEPP


Engineering and Development DESCRIPTION : Powerhouse_Design of Purlins
Corporation of the Philippines DATE : June 2018
DESIGNED BY : MJRI CHECKED BY : WGB

INPUT DATA
Span length, L = 6.00 m
Roof slope angle, = 15.00 deg
Purlin spacing, S = 0.60 m
Height of roof, h = 15.00 m
Length of rafter, Lr = 7.75 m
Sag Rod tributary width, w = 3.88 m
No. of lines of sag rods, n = 2.0
Wind zone = 1.15
Exposure category = B
Velocity pressure, qh = 3000 Pa
Gust effect factor, G = 0.85
Shape coefficient, Cp (windward) = 0.70
Shape coefficient, Cp (leeward) = -0.50
Steel yield strength, Fy = 170 MPa
Ultimate yield strength, Fu = 400 MPa

DESIGN LOADS
Dead Loads:
Roofing Materials = 500.00 Pa
Purlins & Accessories = 1000.00 Pa
Total, pd = 1500.00 Pa

Live Load: = 1000.00 Pa

Wind Load: (Method 1 - Normal Force Method, NSCP 5th Edition)


Windward = qh*G*cp = 1785.00 Pa
Leeward = qh *G*c p = -1275.00 Pa

Normal Loads Per Linear Meter:


DL: pD*S*cos f = 869.33 N/m
LL: pL*S*cos f = 579.56 N/m
WL: pW*S = 1071.00 N/m (windward)
= -765.00 N/m (leeward)

Tangential Loads Per Linear Meter:


DL: pD*S*sin f = 232.94 N / m
LL: pL*S*sin f = 155.29 N / m

LOADING COMBINATIONS
Case # 1 (DL +LL)
WN = 1448.89 N / m
WT = 388.23 N / m

Case # 2 0.75(DL + LL + WLpres )


WN = 512.92 N / m
WT = 174.71 N / m

Case # 3 0.75(DL + WLsuct)


WN = 1455.25 N / m
WT = 174.71 N / m
Therefore, use for design:
WN = 1455.25 N / m
WT = 388.23 N / m
ANALYSIS AND DESIGN OF PURLINS

A. Normal Moment, M N
WN * L2
MN = = 6548.63 N-m
8
B. Tangential Moment, M T
WT * L2
MT = = 155.29 N-m
n
where: n = 8 (no sag rod)
= 32 (sag rod at midspan)
= 90 (sag rods at one-third point)
= 150 (sag rods at quarter point)

C. Trial Section
L
Req'd Depth = = 200 mm
30
Try this section: LC 220 X 75 X 25 X 5

Section Properties:
Sx = 1E+05 mm3 Ix = 14025000 mm4
3
Sy = 25000 mm Iy = 1331000 mm4

D. Check the Adequacy of Trial Section

fbN = MN = 51.36 MPa


Sx

MT
fbT = = 6.21 MPa
Sy

FbN = 0.66 * Fy = 112.2 MPa

FbT = 0.75 * Fy = 127.50 MPa

Interaction Formula:
fbN fb
+ 1.0
FbN FbT

0.510 < 1.0 Adequate Section!

Use: LC 220 X 75 X 25 X 5

ANALYSIS AND DESIGN OF SAG RODS


WP
ASR =
0.33 Fu
Wp = Lr * WT(DL+LL) * w * Sin q
Wp = 3018 N

ASR = 22.860 mm2

D = 5.395 mm

Use: 10mm Sag Rod!