The document contains the settings for various protection relays for a generator including under voltage, over voltage, under frequency, over frequency, reverse power, over current, short circuit, overload, loss of excitation, over excitation, negative phase sequence current, negative phase sequence voltage, bus bar over voltage, differential relay, and stator earth fault relay settings. It lists the minimum, maximum, and trip set point values as well as enable status and fail class for each protection function and generator.

Uploaded by

iftikhar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
223 views

Generator Under Voltage Setting

The document contains the settings for various protection relays for a generator including under voltage, over voltage, under frequency, over frequency, reverse power, over current, short circuit, overload, loss of excitation, over excitation, negative phase sequence current, negative phase sequence voltage, bus bar over voltage, differential relay, and stator earth fault relay settings. It lists the minimum, maximum, and trip set point values as well as enable status and fail class for each protection function and generator.

Uploaded by

iftikhar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Generator Under Voltage setting (1) values:

Minimum value Maximum value Trip Set point


Set point 40.0% 100.0% 93.0%(10230 V)
Time Delay 0.0 Sec 100 Sec 15 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator Under Voltage setting (2) values:
Minimum value Maximum value Trip Set point
Set point 40.0% 100.0% 90.0%(9900 V)
Time Delay 0.0 Sec 100 Sec 15 sec
Enable Off On On
Fail class Alarm Trip Trip

Generator High Voltage setting (1) values:


Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 106.0%(116600 V)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator High Voltage setting (2) values:
Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 109.0%(11990 V)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip

Generator Under Frequency setting (1) values:


Minimum value Maximum value Trip Set point
Set point 100.0% 80.0% 93.0%(46.5Hz)
Time Delay 0.0 Sec 100 Sec 10 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator Under Frequency setting (2) values:
Minimum value Maximum value Trip Set point
Set point 100.0% 80.0% 90.0%(45.0 Hz)
Time Delay 0.0 Sec 100 Sec 10 sec
Enable Off On On
Fail class Alarm Trip Trip

Generator Over Frequency setting (1) values:


Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 105.0%(52.5Hz)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator Over Frequency setting (2) values:
Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 107.0%(53.5 Hz)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip

Reverse Power setting (1) values:


Minimum value Maximum value Trip Set point
Set point 0.0% 200.0% -3.0 %(780KW)
Time Delay 0.0 Sec 100 Sec 10 sec
Enable Off On On
Fail class Alarm Trip Alarm
Reverse Power setting (2) values:
Minimum value Maximum value Trip Set point
Set point 0.0% 200.0% -5.0 %(1300KW)
Time Delay 0.0 Sec 100 Sec 10 sec
Enable Off On On
Fail class Alarm Trip Trip
Generator over current setting (1) values:
Minimum value Maximum value Trip Set point
Set point 50.0% 200.0% 100.0%
Time Delay 0.0 Sec 3200 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator over current setting (2) values:
Minimum value Maximum value Trip Set point
Set point 50.0% 200.0% 110.0%
Time Delay 0.0 Sec 3200 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip
Generator Short Circuit setting (1) values:
Minimum value Maximum value Trip Set point
Set point 150.0% 350.0% 200.0%
Time Delay 0.0 Sec 3200 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator Short Circuit setting (2) values
Minimum value Maximum value Trip Set point
Set point 150.0% 350.0% 250.0%
Time Delay 0.0 Sec 3200 Sec 1 sec
Enable Off On On
Fail class Alarm Trip Trip
Generator Overload setting (1) values:
Minimum value Maximum value Trip Set point
Set point -200.0% 200.0% 100.0%
Time Delay 0.0 Sec 3200 Sec 10 sec
Enable Off On On
Fail class Alarm Trip Alarm
Generator Overload setting (2) values:
Minimum value Maximum value Trip Set point
Set point -200.0% 200.0% 110.0%
Time Delay 0.0 Sec 3200 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip
Loss of Excitation setting values:
Minimum value Maximum value Trip Set point
Set point 0.0% 150.0% 50.0%
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Over Excitation setting values:
Minimum value Maximum value Trip Set point
Set point 0.0% 100.0% 80.0%
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip
Negative Phase Sequence Current setting values:
Minimum value Maximum value Trip Set point
Set point 0.0% 100.0% 10.0%In (0.28A) I sec
Time Delay 0.2 Sec 100 Sec 0.5 sec
Enable Off On On
Fail class Alarm Trip GB Trip GB
Negative Phase Sequence Voltage setting values:
Minimum value Maximum value Trip Set point
Set point 1.0% 100.0% 5.0%(550V)
Time Delay 0.2 Sec 100 Sec 0.5 sec
Enable Off On On
Fail class Alarm Trip GB Trip GB
Bus Bar over Voltage setting (1) values:
Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 105.0%(11550 V)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Alarm
Bus Bar over Voltage setting (2) values:
Minimum value Maximum value Trip Set point
Set point 100.0% 120.0% 107.0%(11770 V)
Time Delay 0.0 Sec 100 Sec 5 sec
Enable Off On On
Fail class Alarm Trip Trip

Differential relay setting values:

Differential Current Set point:


Minimum setting Maximum setting Trip Set point
4% 40 % 10.2 %(0.53 A)
I sec

Differential Current Time Delay Set point:


Minimum setting Maximum setting Time delay
0 Sec 10 Sec 6.547 Sec

Stator Earth Fault relay setting values:

Stator Earth Fault Set point:


Minimum setting Maximum setting Trip Set point
10 % 110 % 26 %(1.3 A) In

Stator Earth Fault Time Delay Set point:


Minimum setting Maximum setting Time delay
0 Sec 5 Sec 1 Sec