User Manual Commander C-08 - GB PDF
User Manual Commander C-08 - GB PDF
Commander C-08
Note:
The manufacturer reserves the right to modify the present manual and equipment at any time without
prior notice.
DE FW SW
0000 000 0000
IP protection: 65
NOTE!
Notify the manufacturer of general identification data printed on the label, before
requesting information about technical specifications and/or the equipment.
3) Remove the board in the bottom from its slot (pos. 3); Battery type Voltage
4) Remove and replace internal battery (pos. 4) with an equal CR2032 3V
one.
1- 8.2 Clean
If necessary, clean with soft cloth.
Do not use any cleaner
1- 12 Installation
Cut a hole for the rectangular box C-08 and No. 6 holes Ø3 mm on the mounting surface, as
indicated on the template (A). Use the screws (1) supplied. If needed buy only screws with the same
characteristics.
Make sure the gasket (2) is mounted correctly and perfectly fits the perimeter of the box C-08 (3).
7
3
2
1
1
1. USB cable;
2. Mounting hole to close the rubber cap using a screw;
3. USB port: normally supplied closed . it can be opened from the keyboard;
4. Closure and rubber protection, IP65.
Only Canbus
and RS485
Option
J6- External Start /stop J11 & J12- CANBUS J13 & J14- RS485
1-Remote start J11 - 1-Shield J13 - 1-Shield
2-Remote stop J11 - 2-Low CANBUS J13 - 2-RX
3-not in use J11 - 3-High CANBUS J13 - 3-TX
4-not in use J11 - 4-Resistance J13 - 4-Resistance
5-not in use
6-not in use J12 – 1-CANBUS Contact NO J14 – 1-RS485 Contact NO
J12 – 2-CANBUS Contact NO J14 – 2-RS485 Contact NO
J12 – 3- Not in use
1- 17 Annexes Warning! before inserting the plugs make sure that the connections
1- 17.1 Wiring strictly comply with the wiring diagram
J3 J4
1-Generator contactor 1-Electric valve
feedback 2-Refuelling pump
2-Mains contactor feedback 3-Start
3-Filter clogged 4-Glow plugs
4-Low oil level 5-Siren
5-Emergency stop 6-Common relays
6-High engine temperature
7-Low fuel level
8-Low oil pressure
Global
alarm
output Only Canbus
and RS485
► Temperature range -30°C +70°C Option
► IP65 protection
►
►
Vdc voltage range 8-35Vdc
Vac voltage range 0-600Vac
Genmac C-08
► Frequency range 45-65Hz
1- 18.1 Automatic
AUT mode - the engine automatically starts in case of
mains failure (out of limits) and stops in the presence
of the same.
1- 18.2 Manual
MAN mode- The engine can be started and stopped
manually by pressing start and stop key buttons; load
switching on mains and generator is managed using
buttons KG and KR.
1- 18.3 Test
TEST Mode- The engine starts immediately to test the
genset for a programmable time. If activated during
AUT mode, in absence of mains C-08 switches the
load on the generator
If activated during MAN mode, the switching can be
controlled only by KG and KR buttons, also if the
mains is faulty. Disabling the test (or after the test
time), the controller returns to the current mode.
1- 18.4 Reset
RESET Mode-The engine will not operate. If the mains
are available it is connected to the load.
If you select Reset mode, the alarms are reset and the
engine stops immediately if it is operating.
If an Alarm is still active it can not be reset.
1- 18.5 Alarms
In case of alarm, the display shows its description. If
more than one alarms is detected, they appear
individually in sequence. For each alarm there is
available a message that can help to identify the
source of the problem. The alarm reset can be made
by pressing the OFF/ RESET button; by this, the alarm
is deleted and the C-08 goes in Reset mode,
preventing accidental generator starting attempts.
If the alarm, after resetting, still remains on the display,
the cause of the alarm is still active and your genset
will stop again unless the problem is solved.
1. In MAN mode you can use the buttons KG and KR to manually close the generator or
mains contactor.
2. KG allows you to manually close the generator contactor.
3. KR allows you to manually close the mains contactor.
K1 K2 K1 K2 K1 K2 K1 K2
G G G G
A B C D
A. Example: C. Example:
- Mains detected - Mains not detected
- Mains contactor closed - Mains contactor opened
- Generator not detected - Generator not detected
- Generator contactor opened - Generator contactor opened
Condition: Condition:
Normal power supply status by mains. Unpowered load: missing mains and generator is not
started or it is not working
B. Example:
- Mains not detected D. Example:
- Mains contactor opened - Mains not detected
- Generator detected - Mains contactor opened
- Generator contactor closed - Generator detected
Condition: - Generator contactor opened
Status of working generator Condition:
After a blackout, the generator starts up but has not
yet completed the stabilization phase.
B C D E F G
A I
U T S R Q P
A
Q
B
P
C
O
D N
E M
F K
G H I J
D
C
B
B
D
F B C D E
S
C
Q
E
R F
I L M N O P
B E
C
F
C-08
B C
START BY MAINS KW
Function that allows the automatic start and stop of
the generator, according to the maximum and
minimum thresholds programmable on mains
consumption.
If the mains supplies the load and consumption
exceeds the START threshold at least for the start
delay time programmed, C-08 starts the generator
and it will be closed to the load.
In addition to the function name appearing in the "A" form,
will also blackened the indicator (B) on the feature When the value of the consumption of the load is
enabled. To program the settings for the specific function, less than the STOP threshold at least for the stop
use the drive keys to move the cursor on the arrows (C) delay time programmed, the load is reswitched on
next to the desired function, then press "i" to confirm the mains (if available) and the generator is stopped.
If the mains is missing, the load remains on the
generator up to the mains detection.
1) USB Cable
2) n.2 RS232 ports allow direct
connection to multiple devices; c. GSM modem for remote control via PC with
modem or via SMS messages to / from mobile
phones.
d. Converter wired TCP / IP for remote control
from PC via LAN / Ethernet.
a. Others Cable for direct PC connection to e. Connection between No.2 C-08, for
upload and download data and info. communication between generators. Used, for
b. Analog modem connection for remote control example, in systems with generator master and
via PC dial telephone. slave. (Dual system)
d
a
e
c
“TEST setup # 1” and “TEST setup # 2”, each one with its own setting.
The default values are those given in the final pages of this manual and are generally good enought to
ensure good control of the generator plant. Anyway, they can be varied according to the procedure
indicated below.
Press the “menu” button (1);
Pressing the arrow of the drive (3), select "General Setup";
Press the "i" (2) to confirm;
Pressing the arrow of the drive (3), select "Setup Test";
Press the "i" (2) to confirm;
Press the buttons of the drive to select, change and confirm the parameters
6 2
2
6
5
1 - Access the menu;
2 - Confirm your selection;
3 3 - Change the parameters;
4 4 - Change the parameters;
5 - Scroll through the options;
6 - Scroll through the options.
1
6 2
INPUT/OUTPUT
- BATTERY VOLTAGE - EMERGENCY STOP MONITOR SYMBOL
INDICATOR BUTTON ALARM
- RENTAL SERVICE,
HOURS LEFT - CURRENT OVERLOAD - DISPLAY SYMBOL
ALARM
BATTERYCHARGER
ALTERNATOR VOLTAGE - GENERATOR - ENGINE SYMBOL
VOLTAGE ALARM
- EVENT MESSAGE
AVAILABLE IN EVENT - ALTERNATOR
LIST - TIMER ALARM SYMBOL
- GENERATOR SYMBOL
- PROGRAMMED TESTS
GENERIC ALARM - SPECIAL FUNCTIONS
- MAINS SYMBOL SYMBOL
- BATTERY VOLTAGE
- PREVIOUS PAGE ALARM - RENTAL SYMBOL
Menu
IO monitor Warranty
Connectivity Service
Using one of the directional arrows (2, 3, 4 or 5) you can select cyclically the submenu (A, B, C or D) shown in
the screen above; highlighted the preferred one, press the central drive "i" button to confirm (6) the access and
the navigation inside it.
From the various screens inside the submenu, you can select the parameter values moving vertically pressing
up and down drive keys (4 or 5), confirmation to the selection is always by "i" button (6), then changing the
value using the left and right drive keys ( 2 or 3). Then, to confirm the changed value, press again "i" key (6).
The scroll keys (7 and 8), are respectively used to navigate between the previous and the next page of the
currently one showed on the screen.
4
1 - Access to menu;
8 2 - Change the parameters;
2 3 - Change the parameters;
3 4 - Scroll through the options;
5 - Scroll through the options;
7 6 - Confirm selection
1
7 - Back to the previous screen;
8 - Go to the next screen;
5 6 To exit from menu, press Menu (1) and page back (8)
G
A
B
H
C
I
L
E
G Page forward Indicates to press the corresponding button to go to the next page (in this case
should go to page 2 of 2)
H Icon menu Symbol indicates that we are inside the "General Setup" menu
Indicates the current page number and the total pages available in the menu (in
I Indication pages
this case we are at page 1 of 2 pages available in the "General Setup"menu
L Page back Indicates to press the corresponding button to return to the previous page (in this
case should come back to the main menu
D Connectivity Submenu that allows the setting of communication parameters of the RS232 ports
available
E Help Pages Submenu where you can scroll through all the help pages included in the controller
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
Italian
You select the language in which you must operate the
English
controller. On board are available the following languages:
A Language French English
English, Italian, French, Spanish, Portuguese. And 'possible
Spanish
to request, install any language with any type of character.
Portuguese
D
H
E
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
A Enable automatic test Used to enable or disable the automatic test On-off Off
B Type tests To set the type of test Daily-Weekly-Monthly Weekly
If the type of test is chosen weekly, permits to set the Mond., Tuesd., Wed.,
C Weekly day of testing Thur., Frid., Sat, Sund.
Thur.
day of the week in which the test should be done
If the type of test is chosen monthly, permits to set the
D Monthly test day 1-31 1
day of the month in which the test should be done
E Hour of test starting You set the hours of starting the test 0-23 9
F Minutes of test starting You set the minutes of starting the test 0-59 30
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
A Enable automatic test Used to enable or disable the automatic test On-off Off
B Type tests To set the type of test Daily-Weekly-Monthly Weekly
If the type of test is chosen weekly, permits to set the Mond., Tuesd., Wed.,
C Weekly day of testing Thur., Frid., Sat, Sund.
Thur.
day of the week in which the test should be done
If the type of test is chosen monthly, permits to set the
D Monthly test day 1-31 1
day of the month in which the test should be done
E Hour of test starting You set the hours of starting the test 0-23 9
F Minutes of test starting You set the minutes of starting the test 0-59 30
A
D
E B
F
C
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
Allows you to select one of three special functions. Use the Scr-kwRete-
A Active function none
drive arrow to select this box then change it by “i” button ejp-ejp/t-none
Use arrows to scroll the special function that you want set.
B Arrows
Confirm and enter inside settings by “i” button.
C Padlock Indicates that the function is not active
D SCR Blackened it means that SCR function is activated
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
Is the delay time that elapses from when you close the
A Start by SCR delay 0-59 0
terminal J6-1 to negative and the generator starting.
Is the delay time that elapses from when you close the
B Switching delay for SCR terminal J6-2 to negative and the switching on generator 0-59 0
contactor, also if mains is detected
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
Setup
Alarm relay activation Type of stop value
Alarm description
Global alarm 2
Global alarm 3
1= contact NO
0= contact NC
Retenetive
Only signalo
Stop engine
Delay
disabled
siren
SMS
1 Switching to mains 0
2 Switching to genset 1
3 Starting 0
Alarm: emergency
4 0
arrest (E-STOP)
5 Remote stop active 1
6 Remote start active 1
7 Service 5
8 Battery maintenance 10
Charger alternator
9 10
failure
10 Faulty mains 1
13 1
alarm
14 User alarm 1
16 Start attempts 0
17 Mechanical fault 10
18 Temperature prealarm 2
19 Enigne temperature 2
Engine temperature
20 2
sensor
allarme globale 1
allarme globale 2
allarme globale 3
sempre abilitato
1= contatto NO
0= contatto NC
relè sirena
Retenetive
stop motore
disabilitato
Invio SMS
Delay
avviato)
21 Fuel prealarm 10
22 Fuel level 10
23 Fuel level sensor 10
24 Oil pressure prealarm 2
25 Oil pressure 2
26 Oil pressure sensor 2
27 High battery voltage 15
28 Low battery voltage 15
29 RPM alarm (too fast) 2
31 Autonomy low 10
36 2
sequence
41 5
sequence
F D
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
A Engine running Send a message when the engine has started No-Ok No
B Contactor active group Send a message when you close the contactor group No-Ok No
C Mains contactor active Send a message when mains contactor is closed No-Ok No
D Not automatic Send a message when C-08 is not in automatic mode No-Ok No
E Mains ok Send a message when the mains are ok No-Ok No
F Call Numbers Show the numbers set (up to 5) that the controller must
send messages to
B
All locked by
password: All locked by
Warranty password:
Engine setup Service setup
Alternatore setup Rental setup
Mains setup Connectivity
Speciali function
S R U T
B
O
C
P
D
Q
E
V
F
W
G
X
H
I
N
M L K J
RANGE OF DEFAULT
POS. NAME DESCRIPTION VALUES VALUES
DEFAULT
POS. NAME DESCRIPTION RANGE OF VALUES
VALUES
A
THIS MENU IS PROTECTED BY PASSWORD
A O N M L
B
I
H
D
E G
D
G
E
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
Permits to detect engine running status by the
A Digital pressure signal On-off off
digital oil pressure sensor
Permits to detect engine running status by the
B Oil pressure threshold 0
analog oil pressure value
Permits setting the voltage of D+ the
C D+ threshold batterycharger alternator, over which the engine 0-9999 10
is considered started (starter disconnect)
You set the frequency value measured on a
permanent magnet alternator type Saprisa, or a
Threshold w / pickup
D pickup or a”W” tachometric sensor, over which 0-9999 0
Saprisa
the engine is considered started (starter
disconnect)
You set the voltage value measured of the power
Generator voltage
E alternator, over which the engine is considered 0-100 20
threshold
started (starter disconnect)
You set the frequency value measured of the
Generator frequency
F power alternator, over which the engine is 0-100 20
threshold
considered started (starter disconnect)
It shows you the nominal voltage and frequency
values set in “Alternator menu”, used as V=400
G Nominal V and F
reference when you set parameters in points E F=50
and F
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
Engine ON detection
A Minimum length of the starting 0-20 3
time
You set the number of start attempts; when
B Number of attempts 1-10 5
expired, the “starting failure” alarm is activated
It is the maximum duration time of each starting
C Duration attempt attempt. When the engine is detected running, 1-10 5
the crancking output is de-activated
It is the time between a failed starting attempt
D Retry Delay 1-10 5
and the next one
It is the time delay from the engine running
detection to the enable of the alarms; this time
E Delay alarms engine allows the generator to reach the nominal 0-1000 8
operating conditions (over speed is always
enabled)
It is the duration time of the acoustic advisor in
F Siren time 0-1000 30
case of alarm
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
It is the nominal speed of the engine, used also
A RPM Nominal 0-10000 1500
as reference to set the limits on points B and C
You set the minimum value beyond which the
B Rpm limit slow 0-10000 80
alarm for low engine rpm
You set the minimum value beyond which the
C Rpm limit fast 0-20000 120
alarm for high engine rpm
It 's the relationship between the frequency of the
tachometric signal (W, Pickup or Saprisa) and the
D RPM Constant number of revolutions of the engine. Is acquired 0-100 30
automatically by the "RPM autodetect" function in
the "engine tools" page
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
It sets the stop system (terminal J4-1)
Electrovalve: type of stop called “energize to
run”, normally used with electric fuel valve
Electrovalve;
A Stop mode connection. Electrovalve;
Electromagnet
Electromagnet: type of stop called “energize to
stop”, normally used with electrosolenoid
connection.
You set the maximum time of the stop phase,
after which the engine must still be seen
B Stop phase time stopped. It also coincides with the maximum time 0-99 8
of supplying of the electromagnet, to avoid
problems due to permanent power supply.
It sets the cooling time after which the engine is
stopped: after the generator contactor opening,
C Cooling time 0-255 30
the engine continues to run for the set time, to
cool down without load
Permits to change the function on terminal J4-2.
If set to ON, this output works as “energize to
Electromagnet output stop” for the time at point “B”.
D On-Off On
enable If set to OFF, this output works as “fuel refilling
pump command”. For more details see “Fuel
Setup” menu setting
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
You set the maximum glow plugs time before
A Preheating time 0-99 3
starting.
If ON, during preheating is also supplied the fuel
Preheating with
B electrovalve output. If OFF, during the preheating On-off Off
electrovalve
the fuel electrovalve output is not supplied.
You can set the value of the engine temperature
above which are not supplied the glow-plugs
C Skip preheating -999 a 999 70
before the starting, because the engine is already
considered "warm"
You can select the type of glow plugs:
Only Before start: the glow plug output is active Only before
only before each starting attempt. start / lso
Also during the start: the glow plugs output is during the Only before
D Preheat type
active before and during each starting attempt. start / also start
Also during attempts: the glow plugs output is during
active before starting, during the starting and also attempts
during the pause between attempts.
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
It sets the minimum battery voltage; if the battery
A Low battery level value measured is less than this value, the “low 0-500 8
battery alarm” is showed
It sets the maximum battery voltage; if the battery
B High battery level value measured is higher than this value, the 0-500 17
“High battery alarm” is showed
If you confirm with "i" button this option, the
counter about hours left to the next batteries
C Counter reset maintenance (E) resets and it returns to baseline Ok
programmed value (D). It can be used after
performing maintenance on the batteries.
You set the hours at which the manufacturer
recommends checking the battery fluid. After
D Set battery life hours 0-65535 14999
expiration, the display will show a warning
message for checking
It shows the hours left to next batteries
E Battery hours left
maintenance
It remember you some safety operations during
F Warnings
the batteries maintenance
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
You select the brand of transmitter that are
Vdo-veglia-
A Analog tool type referred to the relevant tables which was included Vdo
datcon
on the operating curve
B Unit of measure You select the measure unit Litres-Gallons Litres
You set the capacity of the tank. Necessary for
C Tank capacity 0-2000 100
the management of the 'autonomy'
You can set the average hourly consumption of
D Consumption the engine declared by the manufacturer. It is 0,1-1000 8.0
necessary for the management of the 'autonomy'
Value below which the display shows an alarm
E Fuel Limit 0-100 10
message that normally shuts down the generator.
Value below which the display shows a warning
F Fuel Pre-alarm message that normally does not stop the 0-100 20
generator.
Value below which the display shows an alarm
message about the low generator autonomy. C08
G Autonomy alarm limit use the fuel level measured compared to the 0-100 2
“Tank capacity” (C) and to the “Consuption” (D)
to calculates it.
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
This parameter allows you to activate (On) or
A Refueling enable deactivate (Off) the output (J4-2) designed to On-off Off
control a pump for the automatic refilling of fuel.
It sets the fuel level below which the automatic
B Start refueling level 30
fuel refilling starts
It sets the fuel level that, when reached, the
C Stop refueling level 100
automatic fuel refilling stops
It 's a time delay on the refilling starting detection
D Start refueling delay (point B) to avoid false signals due to the 0-59 10
possible movement of fuel sensor in the tank
You set a time limit after which the filling pump
E Stop refueling timer output is stopped, although the stop level (C) was 0-59 5
not reached.
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
You select the brand of transmitter that are
Vdo-veglia-
A Analog tool type referred to the relevant tables which was included Vdo
datcon
on the operating curve
B Unit of measure You select the measure unit Bar-psi Bar
Value below which the display shows an alarm
C Oil pressure limit 1-400 2.0
message that normally shuts down the generator.
Value below which the display shows a warning
D Oil pressure prealarm message that normally does not stop the 1-400 3.0
generator.
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
You select the brand of transmitter that are
Vdo-veglia-
A Analog tool type referred to the relevant tables which was included Vdo
datcon
on the operating curve
B Unit of measure You select the measure unit °C / °F °C
Value above which the display shows an alarm
C Max Temperature limit 40-999 100
message that normally shuts down the generator.
Value above which the display shows a warning
D Temperature prealarm message that normally does not stop the 40-999 90
generator.
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
Engine warranty hours
A It shows the hours left to warranty expiration 1999
left
B Initial warranty You can set the hours of warranty 0-65535 1999
If you confirm with "i" button this option, the
counter about hours left to warranty expiration (A)
C Counter reset Ok
resets and it returns to baseline programmed
value (B).
If ON, you enable the automatic counting of the
guarantee, which starts after detecting at least 48
D Counter enable On-off Off
consecutive hours of active connections. If Off,
the warranty counter is not active.
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
Displays the operating hours counted for the
A Work Hours 0
generator
Confirm with "i" this option, the hours saved are
B Counter reset Ok
reset
C Hours left to service Show hours left before next service 999
D Set service hours Sets working hours before next service 0-65535 999
If you confirm with "i" button this option, the
counter about hours left to next service (C) resets
E Service counter reset and it returns to baseline programmed value (D). Ok
It can be used after performing service on the
generator.
If you confirm with "i" this option, the event list is
F Clear event log Ok
deleted
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
A Rental Time Left View time left to the end of the rental
B Set rental hours You can set the hours of rental 0-23 1
C Set rental minutes You can set the minutes of rental 0-59 30
If you confirm with "i" button this option, the
D Counter reset counter about rental left time (A) resets and it ok
returns to baseline programmed values (B, C).
If ON, you enable the rental counting. If Off, the
E Countdown enable On-off off
rental counting is not active
RANGE OF DEFAULT
POS. NAME DESCRIPTION VALUES VALUES
Generator nominal
A Allows you to set the rated voltage 0-600 400
voltage
You can set the low threshold voltage;if the
Generator low voltage voltage measured is less than this value, the
B 0-100 85
limit generator is considered faulty and C-08 shows
the “low generator voltage alarm”
You can set the high threshold voltage;if the
Generator high voltage voltage measured is higher than this value, the
C 100-200 115
limit generator is considered faulty and C-08 shows
the “high generator voltage alarm”
Generator nominal
D Allows you to set the rated frequency 50-60 50
frequency
You can set the low threshold frequency;if the
Generator low frequency frequency measured is less than this value, the
E 0-100 90
limit generator is considered faulty and C-08 shows
the “low generator frequency alarm”
You can set the high threshold frequency;if the
Generator high frequency frequency measured is higher than this value, the
F 100-200 110
limit generator is considered faulty and C-08 shows
the “high generator frequency alarm”
You can set a delay time for closing the
generator contactor.This time starts from when
G Switch to generator delay 0-100 1
the C-08 opens the mains contactor (software
interlock function)
RANGE OF DEFAULT
POS. NAME DESCRIPTION VALUES VALUES
It is the delay time beyond which if the voltage is
Generator within limits within limits set in (BCEFparameters of previous
A 0-65535 20
delay table), the generator is considered stable and its
contactor is closed
You set the nominal operating current of the
B Nominal current 0-9999 100
generator
You set the maximum overload admitted on the
C Current overload value generator. If exceeded, an alarm message is 0-1000 200
showed
You set the value that permits to consider a short
D Short circuit current circuit on the generator. If exceeded, related 0-1000 300
alarm message is showed
It sets the ratio of Current Transformers to read
E CT ratio regulation the current valued (sample: for CT 100/5A, you 0-10000 30
must set it at 20, because 100 : 5 = 20)
single-
F System Type You can set the type of system phase/three- three-phase
phase
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
A Mains nominal voltage Allows you to set the rated voltage 0-600 400
You can set the low threshold voltage;if the
voltage measured is less than this value, the
B Mains low voltage limit 0-100 85
mains is considered faulty and C-08 starts the
generator
You can set the high threshold voltage;if the
voltage measured is higher than this value, the
C Mains high voltage limit 100-200 115
mains is considered faulty and C-08 starts the
generator
D Mains nominal frequency Allows you to set the rated frequency 50-60 50
You can set the low threshold frequency;if the
frequency measured is less than this value, the
E Mains low frequency limit 0-100 90
mains is considered faulty and C-08 starts the
generator
You can set the high threshold frequency;if the
Mains high frequency frequency measured is higher than this value, the
F 100-200 110
limit mains is considered faulty and C-08 starts the
generator
You can set a delay time for closing the mains
contactor.This time starts from when the C-08
G Switch to mains delay 0-100 1
opens the generator contactor (software interlock
function)
RANGE OF DEFAULT
POS. NAME DESCRIPTION
VALUES VALUES
It 's the delay time beyond which if the mains
return within the limits set in (B, C, E, F,
A Mains within limits delay parameters of previous table) is considered 0-600 20
stable and mains contactor is closed, then begins
the stop phase of the generator.
It 's the delay time beyond which the mains is
considered faulty, compared with the limits
B Faulty mains delay specified in (B, C, E, F, parameters of previous 0-600 5
table). This parameter is used to filter any
temporary instability of the mains
single-
C System type You can set the type of system phase/three- three-phase
phase