S S.A.E: Infrastructure & Cities Sector - Smart Grid Division
S S.A.E: Infrastructure & Cities Sector - Smart Grid Division
Introduction
Page 2 2
Infrastructure & Cities Sector – Smart Grid Division
The 7UT6 Family
SIPROTEC 4
7UT6 differential protection relay for transformers,
generators, motors and busbars
7UT612: for two end protection objects (1/3 x 19’’ housing 7XP20)
7UT613: for three end protection objects (1/2 x 19’’ housing 7XP20)
7UT633: for three end protection objects (1/1 x 19’’ housing 7XP20)
7UT635: for five end protection objects (1/1 x 19’’ housing 7XP20)
Page 3 Infrastructure & Cities Sector – Smart Grid Division
Hardware options
7UT613
7UT633
7UT612 7UT613
7UM62 7UT633
1 ½ C.B. application on
Short lines Short lines HV and LV side with
(2 ends) (3 ends) two winding transformer
7UT635
7UT612 7UT613
7UT633
7UT6xx
7UT612
7UM62
IEE input
of the unit
Unit Protection
(Overall Differential) Low-impedance Restricted
Earth Fault Protection
IA
Y
IB A
7UT635
IC B
C
7UT6 3I0“ = IA + IB + IC
87N T 51
G
3~ 3I0‘ = ISP
51N
side 2 side 1 M1
no matching transformers /
M2
L1 L1 no matching connections
L2 L2
L3 L3 numerical vector group
adaptation without zero
sequence current correction
depending of the type of
earthing of the winding.
IL3M2 IL3M1
IL1M3
Surface
mounting
housing
IL2M3
Flush/
cubicle-
mounting IL3M3
housing
7UT613
Basics of Differential
Protection
Page 10 10
Infrastructure & Cities Sector – Smart Grid Division
Basic principles : Kirchhoff’s knot rule
I1
I2
I4
I3
I1 + I2 + I3 + I4 = 0 I=0
Definition:
Currents, which flow into the knot (protected object), are counted positive.
Currents, which flow out of the knot (protected object), are counted negative.
Protection objects:
Line, Transformer, Generator/Motor, Bus bar
Page 11 11
Infrastructure & Cities Sector – Smart Grid Division
Basic principles: current comparison
Ct 1: Ct 2:
IP1 1= - 5%
IP2 = -IP1
2 = +5% IF
Protected
object
IS1= IS2=
0.95·IP1 IDiff = 0.1·IP1
1.05·IP2
I
IS2=
IS1= 1.05·IP2
0.95·IP1
IDiff= IS1+ IS2
IDiff
IDiff = 0.1·IP1
L1
L2
L3
Diff.
Rest. current
Conventional
Differential Protection
Different current values of the CT- sets on the high voltage side (HV)
and on the low voltage side (LV)
Transient currents
Inrush
CT-saturation
I2*L3
I1L1ku 3
I1L1
5·30°
I2*L2
I1L2ku 3
I1L3 I1L2
-I1L1ku 3
I2*L1
SN I NCTlsec
I L1sec
3 U N I NCTlprim
100MVA 1A
I1L1sec 0.7A
3 110kV 750A
I1L1sec= 0.7A , 0°
100MVA 1A
I2L1sec 0.96A
3 20kV 3000A
L3
0.96A 0.7A
29 23
Diff.
IR Wdg. Wdg.
Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling
nominal Load (no fault): 0.70A ·23Wdg = 0.555A ·29Wdg, IR = 0.555· 3 = 0.96A
Page 19 Infrastructure & Cities Sector – Smart Grid Division
Vector group and current value adaptation
~ L3
3I0
IP=
4.55A 5.73A 4300A
Diff. 29 23
IR Wdg. Wdg.
Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling
single pole fault HV -side: 5.73A ·23Wdg = 4.550A ·29Wdg , IR = 4.55A
(1 of 2)
SN = 100 MVA
UN2 = 20 kV UN1 = 110 kV
3000/1A 750/1A
IP2 = 2750A IP1 = 500A
(load current) Side 2 Side 1 (load current)
InO2 = 2887A InO1 = 525A
IDiff = ?
IRest = ?
4. Calculation of the differential and IDiff = |I1* + I2*| IRest = |I1*| + |I2*|
restraint current
Calculation example:
2.5
Trip
Slope 2
2.0 Total
Block
1.5
CT-
error
1.0
Slope 1 Tap-
changer
0.5
IDiff>
Magnet.
0 current
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
I Rest InO
1243A
6 SLOPE 2
45°
5
Trip Block
4
*)
3
2
1241A Add-on
1
SLOPE 1 Stabilization
1221 IDiff>
0 14 I Rest
0 2 4 6 8 10 12 16
1242A 1261A InO
BASE POINT 1 I-ADD ON STAB *) Slope for Add-on Stabilization:
1244A 7UT6 Slope 1 ; 7UT5 ½ Slope 1
BASE POINT 2
flexible adaptation to various transformers, e.g. with tap changer or different Ct’s
high stability against external faults with Ct saturation
IDiff>>: fast tripping for solid short-circuits within one period
Page 26 Infrastructure & Cities Sector – Smart Grid Division
Tripping Characteristic (2 of 2)
Parameters
7UT6: settable
7UT5: 0 (fixed)
7UT6 only
min. setting:
7UT6: 2 ; 7UT5: 5
7UT613 / 63x
Block
45
° Trip
add-on
stabilisatio
n
filter window
1 cycle
iRUSH Cross-block = No (phase separate blocking)
= iDiff Inrush current
in one phase L1-block IDiff, L1 > trip blocking
1P 2P 3P t
I2har
IDiff block Cross-block = Yes (blocking of all phases)
L1-block
Setting
15 %
value L2-block OR IDiff > trip blocking
1 for an adjustable time
L3-block
no block
0
0 t
recognise inrush condition by evaluating the ratio 2nd harmonic I2har to basic wave IDiff.
Time limit for cross-block. Reliable reaction to the inrush condition with cross-block.
Trip of a short circuit after the set time delay.
recognise over excitation [V/Hz] by evaluating the ratio 3rd or 5th harmonic to basic wave
Page 30 Infrastructure & Cities Sector – Smart Grid Division
Tripping Characteristic - Motor Start
Typical for motor start is the starting current and the superimposed dc component with
a large time constant. The two Ct-sets may transform this dc component differently.
The result is a differential current and the risk of an over-function is given.
Detection of motor starting:
Increases the pick-up values for a settable time
I Diff Tripping Characteristic 7UT6 for Motor start
InO
1231 Idiff>>
7
Criterion:
Start-up characteristic
Supervision of 6
restraint current Steady-state
45° Trip
characteristic
5
IRest > I-Restr. Startup
(until 2 I/InO) 4
Increase
than the of pickup
Start-Factor (max. 2) 3
is active for the time:
2
T Start Max
(Duration of dynamical Block
1
increasing of pickup)
1221 Idiff>
0 0 14 I Rest
2 4 6 8 10 12 16
InO
Page 31 Infrastructure & Cities Sector – Smart Grid Division
Tripping Characteristic
0.36
Steady state
characteristi
c
0.12
0.18
Minimum
setting
Add-on
stabilizatio
n
7UT613/63x only
Page 32 Infrastructure & Cities Sector – Smart Grid Division
Page 33 Infrastructure & Cities Sector – Smart Grid Division