Secondary of CBCT is connected to Earth Fault Relay. During
normal operating condition as the vector sum of three phase
current i.e. (Īa + Īb + Īc =0) is zero therefore no residual current
MY FAVORITE BOOKS in the primary will be present. Here residual current means zero
sequence current. Therefore there will not be any flux developed
in the CBCT core and hence no current in the secondary circuit
of CBCT.
Privacy
Working Principle of CBCT:
Let Īa, Īb and Īc be the three line currents and Φa, Φb and Φc
be corresponding components of magnetic flux in the core.
Assuming that the CT is operating in the linear region (Read BH
Curve to get idea of linearity), magnetic flux because of
individual phase current will be directly proportional to the phase
current and hence we can write as below,
Φa = kIa
Φb = kIb
Φc = kIc
http://electricalbaba.com/corebalancecurrenttransformer/ 2/6
2/21/2017 Core Balance Current Transformer | Electrical Concepts
Thus the resultant magnetic flux in the CBCT core,
Φr = k(Īa + Īb + Īc) …………………..(1)
But we know from theory of symmetrical components,
Īa + Īb + Īc = 3Ī0 = Īn
Where, Io is zero sequence current and In is neutral current.
Hence we can write as
Φr = kĪn …………………………(2)
Now let us consider two cases:
Case1: During normal condition
Īa + Īb + Īc = 0
Hence from equation (1),
Net resultant flux in the CBCT Core, Φr = 0 which means no
secondary current and therefore the Earth Fault Relay won’t
operate.
Case2: During earth fault, three phase current passing through
the center of Core Balance Current Transformer will not be
balanced rather a zero sequence current will flow. For example
for single line ground fault,
If = 3Ia0 = In
Thus from equation (2),
Net magnetic flux in the CBCT core, Φr will have some finite
value which in turn will induce current in the secondary circuit
due to which earth fault relay will operate. Because of this
reason, a Core Balance Current Transformer or CBCT is also
called Zero Sequence Current Transformer.
http://electricalbaba.com/corebalancecurrenttransformer/ 3/6
2/21/2017 Core Balance Current Transformer | Electrical Concepts
Advantage of Core Balance Current Transformer:
The advantage of using CBCT for earth fault protectionis that
only one CT core is used instead of three core as in
conventional system where the secondary winding of three
cores are connected residually. Thus the magnetizing current
required for the production of a particular secondary current is
reduced by one third which is a great advantage as the
sensitivity of protection is increased.
Also, the number of secondary turn does not need to be related
to the cable rated current because no secondary current flows
under normal operating condition as the currents are balanced.
This allows the number of secondary turns to be chosen to
optimize the effective primary pickup current.
Related Posts:
1. Working Principle of Residual Voltage Transformer
2. Knee Point Voltage of Current Transformer
3. Losses in Electrical Machine – Core Loss and Eddy Current Loss
4. Di鿃erence between Current Transformer & Potential
Transformer
Merry Christmas Wishes 2016 December 20, 2016 at 10:02 pm
http://electricalbaba.com/corebalancecurrenttransformer/ 4/6