0% found this document useful (0 votes)
42 views

Schedule of Loads:: Ground Floor

The document provides a schedule of electrical loads for a building including lighting outlets, convenience outlets, and air conditioning units for each floor. It lists the circuit number, description, number of outlets, voltage, watts, and amps per circuit. The total load for each floor and the grand total load for the building is provided. It also specifies the circuit protection size and wire/conduit size for each circuit.

Uploaded by

Shan Dela Vega
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
42 views

Schedule of Loads:: Ground Floor

The document provides a schedule of electrical loads for a building including lighting outlets, convenience outlets, and air conditioning units for each floor. It lists the circuit number, description, number of outlets, voltage, watts, and amps per circuit. The total load for each floor and the grand total load for the building is provided. It also specifies the circuit protection size and wire/conduit size for each circuit.

Uploaded by

Shan Dela Vega
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

SCHEDULE OF LOADS:

Ground floor:
ckt. No. description no. of outlet volt watts ampere/ckt.
c1 lighting outlet 9 220 900 4.091
c2 lighting outlet 12 220 1200 5.455
c3 lighting outlet 12 220 1200 5.455
c4 lighting outlet 9 220 900 4.091
c5 lighting outlet 15 220 1500 6.818
C1a convenience outlet 11 220 1980 9.000
C2a convenience outlet 18 220 3240 14.727
C3a convenience outlet 16 220 2880 13.091
C4a convenience outlet 10 220 1800 8.182
C12a SPARE
TOTAL: 13,800.00 70.909

Ground floor AC OUTLET


ckt. No. description no. of outlet volt watts ampere/ckt.
c5a Air conditioning unit(5hp) 1 220 3730 21.193
c6a Air conditioning unit(5hp) 1 220 3730 21.193
c7a Air conditioning unit(5hp) 1 220 3730 21.193
c8a Air conditioning unit(5hp) 1 220 3730 21.193
c9a Air conditioning unit(5hp) 1 220 3730 21.193
c10a SPARE
c13a SPARE
c14a SPARE
TOTAL: 18,650.00 105.966

2nd floor:
ckt. No. description no. of outlet volt watts ampere/ckt.
c1 lighting outlet 42 220 4200 19.091
c2 lighting outlet 26 220 2600 11.818
c3 lighting outlet 16 220 1600 7.273
c4 lighting outlet 36 220 3600 16.364
c5 lighting outlet 15 220 1500 6.818
c1b convenience outlet 14 220 2520 11.455
c2b convenience outlet 15 220 2700 12.273
c3b convenience outlet 14 220 2520 11.455
c4b convenience outlet 14 220 2520 11.455
c10b SPARE
c11b SPARE
c12b SPARE
TOTAL: 23,760.00 108.000

2nd floor AC OUTLET


ckt. No. description no. of outlet volt watts ampere/ckt.
c5b Air conditioning unit(5hp) 1 220 3730 21.193
c6b Air conditioning unit(5hp) 1 220 3730 21.193
c7b Air conditioning unit(5hp) 1 220 3730 21.193
c8b Air conditioning unit(5hp) 1 220 3730 21.193
c9b Air conditioning unit(5hp) 1 220 3730 21.193
TOTAL: 18,650.00 105.966

3rd floor:
ckt. No. description no. of outlet volt watts ampere/ckt.
c1 lighting outlet 18 220 1800 8.182
c2 lighting outlet 12 220 1200 5.455
c3 lighting outlet 11 220 1100 5.000
c4 lighting outlet 15 220 1500 6.818
c1c convenience outlet 16 220 2880 13.091
c2c convenience outlet 24 220 4320 19.636
c3c convenience outlet 9 220 1620 7.364
c7c SPARE
c8c SPARE
c9c SPARE
TOTAL: 14,420.00 65.545

3rd floor AC OUTLET


ckt. No. description no. of outlet volt watts ampere/ckt.
c4c Air conditioning unit(5hp) 1 220 3730 21.193
c5c Air conditioning unit(5hp) 1 220 3730 21.193
c6c Air conditioning unit(5hp) 1 220 3730 21.193
TOTAL: 11,190.00 63.580
GRAND TOTAL LOADS: 100,470.00 519.966
protection/ckt. size of wire/conduits
15 AT 3.5mm² THHN (STRANDED) /20mm∅
15AT 3.5mm² THHN (STRANDED) /20mm∅
15AT 3.5mm² THHN (STRANDED) /20mm∅
15AT 3.5mm² THHN (STRANDED) /20mm∅
15AT 5.5mm² THHN (STRANDED) /20mm∅
30AT 5.5mm² THHN (STRANDED) /20mm∅
20AT 5.5mm² THHN (STRANDED) /20mm∅
20AT 5.5mm² THHN (STRANDED) /20mm∅
30AT 5.5mm² THHN (STRANDED) /20mm∅
3.5mm² THHN (STRANDED) /20mm∅
100AT 30mm² THHN (STRANDED) /25mm∅

protection/ckt. size of wire/conduits


60AT 5.5mm² THHN (STRANDED) /20mm∅
60AT 5.5mm² THHN (STRANDED) /20mm∅
60AT 5.5mm² THHN (STRANDED) /20mm∅
60AT 5.5mm² THHN (STRANDED) /20mm∅
60AT 5.5mm² THHN (STRANDED) /20mm∅
5.5mm² THHN (STRANDED) /20mm∅
5.5mm² THHN (STRANDED) /20mm∅
5.5mm² THHN (STRANDED) /20mm∅
300AT 50mm² THHN (STRANDED) /25mm∅

protection/ckt. size of wire/conduits


20AT 5.5mm² THHN (STRANDED) /20mm∅
15AT 5.5mm² THHN (STRANDED) /20mm∅
15AT 5.5mm² THHN (STRANDED) /20mm∅
20AT 5.5mm² THHN (STRANDED) /20mm∅
15AT 5.5mm² THHN (STRANDED) /20mm∅
20AT 5.5mm² THHN (STRANDED) /20mm∅
30AT 5.5mm² THHN (STRANDED) /20mm∅
20AT 5.5mm² THHN (STRANDED) /20mm∅
20AT 5.5mm² THHN (STRANDED) /20mm∅
3.5mm² THHN (STRANDED) /20mm∅
3.5mm² THHN (STRANDED) /20mm∅
3.5mm² THHN (STRANDED) /20mm∅
150AT 50mm² THHN (STRANDED) /25mm∅

protection/ckt. size of wire/conduits


60AT 5.5mm² THHN (STRANDED) /20mm∅
60AT 5.5mm² THHN (STRANDED) /20mm∅
60AT 5.5mm² THHN (STRANDED) /20mm∅
60AT 5.5mm² THHN (STRANDED) /20mm∅
60AT 5.5mm² THHN (STRANDED) /20mm∅
350AT 50mm² THHN (STRANDED) /25mm∅

protection/ckt. size of wire/conduits


15AT 3.5mm² THHN (STRANDED) /20mm∅
15AT 3.5mm² THHN (STRANDED) /20mm∅
15AT 3.5mm² THHN (STRANDED) /20mm∅
15AT 3.5mm² THHN (STRANDED) /20mm∅
20AT 5.5mm² THHN (STRANDED) /20mm∅
30AT 5.5mm² THHN (STRANDED) /20mm∅
20AT 5.5mm² THHN (STRANDED) /20mm∅
3.5mm² THHN (STRANDED) /20mm∅
3.5mm² THHN (STRANDED) /20mm∅
3.5mm² THHN (STRANDED) /20mm∅
90AT 22mm² THHN (STRANDED) /25mm∅

protection/ckt. size of wire/conduits


60AT 5.5mm² THHN (STRANDED) /20mm∅
60AT 5.5mm² THHN (STRANDED) /20mm∅
60AT 5.5mm² THHN (STRANDED) /20mm∅
175AT 22mm² THHN (STRANDED) /25mm∅